Fume Hood Manual Final 20150909
Fume Hood Manual Final 20150909
ISSUED DATE:
September 9, 2015
PREPARED BY:
Page 2 of 33
Introduction
A fume hood is an enclosed working chamber fitted with an exhaust ventilation system. It is
one component of an exposure control system that is designed to contain, dilute and disperse
gases, mists, vapours, and particulate matter to the external environment. It is also an integral
part of the building air handling system. The fume hood is the primary engineering control
device in most laboratories for protecting workers and students from exposure to hazardous
chemicals. It is therefore imperative that it function properly at all times during its operation.
A fume hood structure is basically a cabinet, with an open side (or sides) for access to the
interior of the hood. A transparent, movable sash, allows the user to restrict or enlarge the
fume hood opening. The hood is connected, via ductwork, to an exhaust fan, usually located
on the roof of the building in which the hood is located. The exhaust fan draws air from the
room in which the hood is in through the hood opening and out through the ductwork.
This manual is intended to provide University of Windsor workers and students a greater
understanding of fume hood selection, design, installation, operation and maintenance to
ensure a consistent approach to the operation, testing and maintenance of fume hoods in
laboratories at the University of Windsor.
This manual applies to all work that requires servicing and repairing of a fume hood, entering
or removing duct work, entering the fan housing, changing filters, shutting off fans or any
other maintenance that requires entering the inside of the exhaust system.
Special precautions are usually not required when servicing equipment that is outside of the
fume hood cabinet and/or outside of the potentially contaminated air stream. For example,
belts and pulleys may be serviced, vibration isolators may be adjusted and lamps may be
replaced on many chemical fume hoods without entering the interior of the hood or exhaust
duct.
Disclaimer
This manual addresses fume hood safety operational and maintenance issues. It must be
reviewed by the Fume Hood User to ensure that their operations conform to the
recommended procedures, as well as any federal, provincial or local laws and/or regulations.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 3 of 33
1. Biology
2. Centre for Automotive and Research Education (CARE)
3. Ed Lumley Centre of Engineering Innovation (CEI)
4. Education
5. Essex Hall - Chemistry
6. Essex Hall - Physics
7. Great Lakes Institute for Environmental Research (GLIER)
8. Human Kinetics
9. Lebel
10. Memorial Hall
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 4 of 33
A fume hood that has been properly designed, manufactured, installed, and operated will
deliver a safe working environment to laboratory personnel.
Selection Guide
This selection guide was developed in accordance with the Canadian Standards Association
(C.S.A) Standard Z316.5 (Fume Hoods and Associated Exhaust Systems).
An assessment by Facility Services and the users should be made of the anticipated
processes before a fume hood is selected to ensure that users are adequately protected and
the fume hood may be expected to perform reliably. These may include but are not limited to
the following: chemical resistance and reactivity; chemical toxicity; radioactive contamination;
thermal stress; adsorption and absorption of hazardous substances; explosions; fire; services
required (water, gas, and vacuum); mechanical stress, (vibration); and workplace
environment.
Manufactures Information
The fume hood shall meet the minimum design criterial outlined in CSA Z316.5-04 and meet
or exceed performance standards specified by ANSI/ASHRAE 110-1995. The following
information should be obtained from the manufacturer prior to purchase.
Page 5 of 33
When ready with your selection, fill in the Fume Hood Selection Form (Appendix 3 CCC-2010-12)
and submit to the Chemical Control Centre. The Chemical Control Centre and Facility
Services will review and assist in the ordering and purchasing process and will ensure the
new fume hood is added to the University of Windsor Fume Hood inventory records.
Installation
Fume hoods shall be installed according to the manufacturer’s instructions. The following
information shall be recorded and kept on file by Facility Services when the fume hood
exhaust system is installed:
1. “As built” drawings showing the complete installation
2. Identification of the materials of construction
3. Operating and maintenance instructions
4. Make, Model, Serial Number and Associated Exhaust Fan Location
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 6 of 33
Commissioning
After the installation, the Chemical Control Centre, Facility Services and the Contractor shall
be notified to commission the fume hood. Commissioning shall include, but not be limited to,
determinations of the following:
1. Electrical safety
2. Adequate lighting
3. Noise level (less than 55 dBA)
4. Functioning of components and services
5. Field performance test results as specified in Clause 9.4 CSA Z316.5-04.
In order for the manual to be effective, a ll workers and students who work with o r
s u p e r v i s e t h o s e w o r k i n g w i t h fume hoods or perform fume hood maintenance
shall understand and follow these responsibilities and guidelines.
Supervisor
A supervisor is a person who has charge of a workplace or authority over a worker. Examples
of a supervisor may include but are not limited to the Dean, Department Head, Professor,
Manager, Team Leader, and Senior Staff Member. The supervisor is responsible to ensure all
lab personnel are instructed and trained on the proper operations of the fume hood and have
taken the Fume Hood Training, and recordsof this training shall be kept. In addition the
supervisor shall:
Perform routine inspections of the fume hood.
Ensure fume hoods are not being used improperly. Example: alarms silenced, cluttered,
used for storage.
Inform lab personnel if the fume hood is not working and instruct personnel to discontinue
use of the fume hood and label fume hood with notification.
Take appropriate assessment and corrective measures where fume hood performance is
uncertain. This may include lockout of the fume hood to render it safe.
Arrange for repair or air flow adjustments through the work order process with Facility
Services by contacting dispatch at extension 2850 or [email protected]
When work must be done inside of the fume hood, the supervisor shall ensure the sash is
shut, hazardous materials are closed, secured and if necessary removed from the fume
hood, and free from active experiments prior to and for the duration of the repair.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 7 of 33
2. Is the fume hood face velocity in the acceptable range (80 -120 fpm)?
Check the airflow alarm for the alarm light or buzzer noise. Check to see that the audible alarm has
not been disabled.
If a visual display is not installed on the alarm, check for airflow with a paper strip hung from the
bottom of the hood sash. Do not rely on noise from the fume hood to indicate proper operation
(blower motor noise may persist even if a fan belt breaks).
3. Is work in the fume hood being conducted six inches back from the sash?
Setting work back six inches from the plane of the sash reduces influence of drafts from people,
doors, air supply diffusers, etc.,
Page 8 of 33
Facility Services
Facility Services is involved in the acquisition, installation, commissioning and maintenance of
fume hoods on campus. Facility Service personnel shall:
Ensure all fume hoods ordered through projects meet the regulatory requirements
outlined in Z316.5-04 and this manual.
Ensure installation of fume hood is done in compliance with the manufactures instructions.
Ensure a commissioning report is conducted and provided to the University in accordance
with the regulations and this manual.
Notify and forward all commissioning, decommissioning reports to the Chemical Control
Centre to be reflected in the University of Windsor fume hood inventory system.
As maintenance staff performs maintenance on fume hoods and filters, Facility Services
shall:
Upon receiving a work order request, Facility Services will conduct a fume hood system
evaluation and communicate with the Supervisor an appropriate time line for evaluation
and repair.
Facility Services shall send out a Service of Interruption Notice to all parties prior to the
date of work.
Perform all required repairs to ensure the fume hood is performing in the acceptable
range and all components are operational to ensure the fume hood provide a safe and
reliable service.
Contact the appropriate personnel to complete repairs as required.
Notify applicable department, Supervisor and the Chemical Control Centre of completed
repair.
Perform annual inspections as outlined in CSA Z316.5-04 and Appendix 1 of this Manual.
Page 9 of 33
Page 10 of 33
This section describes the operating performance criteria (primarily sash height and airflow
face velocity) and physical condition criteria that has been established for fume hoods. In
addition, several other factors may affect the operating performance of a fume hoods
such as the location of the hood in the lab, make-up air, weather conditions outside, etc.
It is important to remember that face velocity is not the only factor contributing to hood
performance. Work practices and make-up air also affect performance.
Fume hood face velocity will be measured by University of Windsor Chemical Control (CCC)
personnel annually. If it is suspected that a fume hood is not operating properly,
immediately notify your Supervisor.
When the annual face velocity measurement is complete, the certification sticker (located on
the face of every fume hood) must be updated.
Note - Face velocity may be lower than 80 fpm or higher than 120 fpm if designed by
manufacture to perform outside of this range. These fume hoods will be clearly identified on
the fumehood by a notice from the CCC.
Higher face velocities do not offer more protection. They can result in decreased protection
due to turbulence w i t h i n t h e f u m e h o o d causing the release of contaminants from
the hood to the worker.
Page 11 of 33
Ceiling diffusers should not be located immediately in front of the hood face. Deflecting
supply air from the quadrant of the diffuser blowing at the hood face should result in
better hood performance.
Wall grilles or registers are not recommended by ACGIH (American Conference of
Governmental Industrial Hygienists) for new facilities. However, in existing facilities,
the wall grilles should have double deflection louvers set for maximum deflection.
Plumbing Services
Isolating valves s h o u l d b e located within the end panels, controlled by handles
projecting through the side-posts of the fume hood. These or any other controls
installed on the side posts should be located to avoid any interference with the smooth entry
of air into the fume hood. Acid neutralization tanks shall be installed on all fume hood sink
drains as applicable.
Fixtures
Fixtures / valves for water, air, gas or nitrogen, exposed within the hood are to have a
chemical resistant metallic bronze finish, and portions exposed on the exterior of the fume
hood are to be chrome-plated. De-ionized and Reverse Osmosis water faucets should
be polyvinyl corrosion-resistant finish with polyoxymethylene lining, and stainless steel
valves. Faucets must be aligned with the cup sink to prevent overspray and wetting of
interior hood surfaces. Colour coding and identification of service fixtures shall be according
to the standard of the laboratory facility.
Cup Sinks
Cup sinks shall be raised 6 mm above the recessed work surface to prevent spills from
entering the plumbing system, drains lines shall be 38 mm with integral debris catch.
Access to Services
Cut-outs for plumbing and electrical services and fitments are provided with the fume hood
and all unused openings in exterior panels for service connections shall be complete with
cap plugs of the same material as exterior panels.
Service connections shall be accessible from the outside of the fume hood, using
removable panels. Isolating valves must be provided on the building side of the services.
Where two or more hoods are installed side by side, interior service panels may be used.
They shall be of the same material as the interior panels, have beveled edges and
molded PVC gasket, and shall be secured by non-corrosive fasteners set flush with the
face of the panel.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 12 of 33
Fume hoods must be tested for minimum control functions and face velocity as follows:
• After new installation.
• After any repair or modifications are made to the fume hood or exhaust system.
• At least once per year.
Face velocity testing will be carried out by the CCC annually and also by request of the
Department Head/Research Supervisor. Every three years the face velocity measurement
will be carried out by an external contractor.
Detailed procedure for average face velocity testing is specified in the Chemical Fume Hood
Testing Procedure (CCC-2010-14), see Appendix 2.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 13 of 33
When conducting maintenance work on fume hoods, all work must be carried out according
to current regulations. The work on fume hoods refers to all preventative or corrective
maintenance work on all exhaust systems during which a person could be exposed.
This procedure applies to all pe rsonne l who perform maintenance and may require
entering or removing duct work, changing filters, shutting off fans or any other maintenance
that requires entering the inside of the exhaust system.
Fume hood maintenance can involve daily, periodic, and/or annual inspections and details
are specified in CSA Z316.5-04. When performing fume hood maintenance, proper pre-
maintenance procedures shall be taken. When coordinating a shutdown of the system, all
Supervisors affected by the shutdown must receive notification prior to the beginning of
maintenance.
Note: It is not necessary to shut down the exhaust system when replacing lamps, cleaning
behind the fume hood baffles, or replacing the airflow sensors.
For each hood type there are specific guidelines on proper maintenance and personal
protective equipment (PPE).
Maintenance Staff shall not handle laboratory equipment. It must be assumed that the
internal duct surface, fume hood lining and all internal exhaust components are potentially
contaminated with chemical residue. Ask the Supervisor if any unique hazardous materials
such as perchloric acid or radioactivity were ever used in the hood. If so, contact the
Chemical Control Centre.
The following personal protective equipment (PPE) shall be worn when conducting
maintenance on a Fume Hood:
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 14 of 33
All maintenance personnel working on fume hoods shall wash their hands with soap and
water (even if gloves were worn) at the completion of their work. In general, good personal
hygiene such as washing your hands after working in any lab is highly recommended.
After maintenance work is completed, PPE shall be disposed of in accordance with Health &
Safety requirements.
1. The Supervisor of the user group must be contacted by Facility Services and informed
that maintenance will be performed on their fume hood through a Service of Interruption
Notice.
2. The user group must stop all use of the fume hood, ensure the fume hood is free from
all active experiments, ensure all containers are capped and in proper storage
containers and remove equipment as required.
3. If work is required on the interior of the hood, ask the laboratory personnel to move
any chemicals a n d e q u i p m e n t in the hood and ensure all spills have been
cleaned up/decontaminated.
Note: Acid digestions using acids other than perchloric should be performed in fume hoods designed
to withstand the corrosive and damaging effects of repeated manipulations using acid.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 15 of 33
Exhaust Fans
Facility Services shall;
1. Verify if fan is a dedicated fan or serves multiple fume hoods.
2. Confirm if fan is operational.
3. Inspect fan mountings, flexible connectors, pulleys and impeller and adjust/replace as
necessary.
4. Check fan, motor, drive and bearings for correct running and repair /adjust as
necessary
5. Inspect fan discharge flue for stability/slippage and repair/adjust as necessary.
Ductwork
Facility Services shall;
1. Inspect all ductwork for cracks and repair as necessary.
2. Inspect ductwork for additional attachments of tubing or miscellaneous ductwork that
may have been added.
3. Check fire dampers for correct operation
4. Check volume control dampers for correct setting.
5. Check supply air inlets and measure velocity/volume on all grilles/diffusers and compare
inlet/extract volumes for correct operation.
Room
Supervisors shall examine the surroundings of the fume hood with respect to furniture
or large equipment installed after the original installation or previous check which do not
comply with the requirements. Rectify as necessary.
These velocity alarms provide continuous monitoring of the air flow through the fume hood
complete with a visual and audible alarm in the event of abnormal air flow conditions.
Monitors provide adjustable alarm set points and a test button to confirm satisfactory
operation.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 16 of 33
Supervisors post an “Attention – Do Not Use This Fume Hood” notice on the fume hood
to be shut down. It is important that this notice be posted in the lower, center area of the
sash so it is easily visible to lab occupants. Refer to Appendix 4 for the Do Not Use This
Fume Hood Templates to be placed on the Fume Hood.
Where practical the sash of the fume hood must also be locked out ( s e e l o c k o u t / t a g
o u t p r o c e d u r e ) so lab occupants will not be able to inadvertently use the hood. Please
be sure to check with lab occupants before locking out a f u m e hood so any
research materials or experiments can be removed.
Upon completion of work on exhaust components, contact CCC to verify and document face
velocity results, T h e C C C w i l l remove the “Do Not Use This Fume Hood” notice. For
work that does not affect the face velocity the supervisor can remove the notice.
Note: The new verification date may not affect the annual inspection date.
Implementing lockout
Lock out of the fume hood is required anytime the operation of the fume hood is in question
and the function may result in a risk to the user and/or maintenance staff. Lockout is required
for mechanical service and maintenance operations if the procedures to be performed could
involve worker and/or student exposure to hazardous materials, energized electrical parts, to
machinery that could unexpectedly start up, or to a stored energy source on the equipment or
machinery. There may be times when full lock out is not required, this will be determined in
consultation with the supervisor, health & safety, facility services and/or service provider.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 17 of 33
Personal locks
Every Supervisor that is required to lock out machinery or equipment needs a lock and keeps
the key to that lock. This lock ensures personal lockout protection. Each department, Health
& Safety and Facility Services have their own locks to lock out the fume hoods.
Lockout
Once a Supervisor has determined that lockout of a fume hood is required, follow the
procedures below. Every individual who is responsible to lock out a fume hood must know
these steps.
1. Identify the fume hood that needs to be locked out.
2. Shut down all operations within the fume hood (Fume hood users may be required to
assist in this step). Supervisors shall ensure all Fume hoods in laboratories are cleared
of active experiments, open chemicals, reagents or waste containers. All chemicals,
reagents and waste that cannot be removed must be sealed and/or capped.
3. Store chemicals and reagents in appropriate storage containers and ensure that the act
of shutting off equipment does not cause a hazard to other workers.
4. Apply a personal lock to the fume hood, and ensure that all parts and attachments are
secured against inadvertent movement.
5. Test the lockout to make sure it’s effective and to verify that the Fume hood has been
effectively locked out.
6. A tag shall be placed on the lock to identify the following information:
Area responsible for lock out
Date of Lock Out
Reason for Lock Out
Contact Information – Name, Phone, E-mail
Remove Locks.
1. A personal lock must only be removed by the individual who installed it, or if this is not
possible, the matter must be referred to the supervisor or department in charge, who may
take responsibility for its removal.
2. Removal by a Supervisor or manager in charge must only take place after making every
reasonable effort to contact the worker who installed the lock, and ensure that the
machinery or equipment can be operated safely.
3. A worker must be notified at the start of his or her next shift if the worker’s personal
lock(s) has been removed.
The procedures outlined in this manual will be followed when completing the repairs.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 18 of 33
Properly functioning fume hoods help achieve this goal with respect to the hazards of
chemical vapours and other harmful airborne substances. It is important to remember that
a fume hood is not a storage area. Keeping equipment and chemicals unnecessarily in
the hood may cause airflow blockage.
Note – all fume hoods users must take Fume Hood Training prior to operating any
fume hood.
Train and educate users on fume hood use and specific hazards and work methods
that help reduce contaminant exposure.
Have a general awareness of the operation of your fume hood and be aware of
any differences in visual or audible cues that may imply a change in function.
Substitute toxic chemicals with less hazardous materials whenever possible.
Keep fume hood exhaust fans on at all times.
Perform all work six inches inside the fume hood.
Never place your head inside the fume hood.
Keep the f um e hood sash closed as much as possible at all times to ensure the
optimum face velocity and to minimize energy usage.
Keep lab doors and windows closed to ensure negative room pressure to the corridor
and proper air flow into the fume hood.
Do not store chemicals in the fume hood.
Keep the slots of the baffle free of obstruction.
Do not use the fume hood exhaust as a waste disposal mechanism (e.g., for
evaporation of chemicals).
Avoid rapid movements in front of the f u m e hood including opening and closing the
fume hood sash rapidly and swift arm and body movements in front of or inside the
hood. These actions may increase turbulence and reduce the effectiveness of fume
hood containment.
Do not override or disable mechanical stops on the sash
Fume hood exhaust fans may shut down due to unexpected failure or for periodic fan
maintenance. Scheduled exhaust fan outages will be coordinated and communicated by
Maintenance. When exhaust fans shut down unexpectedly or when face velocities are low,
all fume hood operations must be shut down, experiments terminated and all chemical
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 19 of 33
containers capped.
Fume Hood Use
Always walk by fume hoods slowly at least three feet behind the operator at the fume
hood. Air currents produced by a rapidly walking person can draw vapours and gasses
out of the fume hood and expose the operator.
Never walk by fume hoods rapidly or too closely behind the user at the fume hood.
When removing objects and arms from fume hood, always move slowly in a direction
parallel with airflow. Airflow will help to clean fumes and gasses off of arms and
objects when arms are parallel with airflow direction.
When removing objects and arm from fume hood, never use a scooping or side-to-
side motion.
Movement across the fume hood will defeat the inward airflow and may cause fumes
and vapours to be drawn out.
Keep doors and windows closed. Open windows and laboratory doors that are propped
open cause disruptive air currents that can compromise fume hood performance and
place operators at risk. Laboratory heating, cooling and ventilation systems are
designed to operate with laboratory doors and windows closed.
Page 20 of 33
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 21 of 33
Page 22 of 33
Experiment Setup
During setup and teardown only, the sash may be raised beyond the established working
position.
During setup time, there must be no hazardous vapours or gasses present in the fume
hood since the fume hood will provide NO PROTECTION.
Wait at least two minutes after all hazard generating activity has ceased before opening
the sash above working position.
During setup and teardown of experiments, the fume hood alarm will most likely sound
due to insufficient airflow. During this time only, it is acceptable to mute the alarm by
pressing the “Test” or “Enter” button. Alarms vary by manufacturer; contact the
Supervisor if in doubt.
Sash Use
There are two types of sliding sashes on the front of fume hoods in common use:
The Vertical Sash is the most common and moves vertically only.
The Combination Sash consists of horizontally sliding panels in a vertically rising
frame.
Page 23 of 33
Apparatus Location
Always locate apparatus at least 6 inches behind the sash plane. If this is not done,
vapours and gasses released near the hood face may not be captured and contained.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 24 of 33
Always support large object on blocks. Airspace beneath these objects reduces airflow
disruption and vapour buildup in front of the object. Ensure adequate air flow within the
fume hood; consult with supervisor if in doubt.
Baffles
Keep opening around the baffles in the rear and top of the fume hood clear of
obstructions such as laboratory wipes.
Do not adjust the baffles in any way. Only qualified personal should adjust baffle or
duct dampers.
Airflow may be affected, and workers could be exposed if baffles are improperly
adjusted.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 25 of 33
Electrical Safety
Never tamper with cords or use ungrounded electrical items.
Electrical SHOCK may result.
Never use electrical items when flammable gasses or vapours are present in the hood.
FIRE or EXPLOSION may result
Decommissioning
Chemical fume hoods will not be re-located or decommissioned without prior notification
being given to the CCC and Facility Services.
Decommissioning shall be done with accordance of CSA Standard Z316.5-04(14) and the
fume hood must be rendered unusable and safe by following these guidelines:
1. Remove all services (power, water, vacuum, gas, nitrogen, etc.) - cap lines if possible.
2. Turn off exhaust fan (typically via disconnect or fan shut off switch).
3. Use lockout system to prevent sash from opening during decommissioning.
4. Cover sash opening with plywood and screw in place.
Once the fume hood has been removed from service, the CCC must be notified to remove
the fume hood from the active inventory and the data base updated.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 26 of 33
Definitions
Fume Hood
In the context of this guideline, “fume hood” means “a boxlike structure enclosing a source of potential air
contamination, with one open or partially open side, into which air is moved for the purpose of containing
and exhausting air contaminants, generally used for bench-scale operations but not necessarily involving the
use of a bench or table.”—ANSI/ASHRAE 110
Air jambs
The air jambs are vertical sills or side posts at the front of the hood. These are tapered to promote smooth
air flow into the hood.
Baffles
Moveable partitions used to create slotted openings along the back of the Fume Hood body.
Containment
Is the fume hood’s ability to capture gases and vapours for effective exhaust.
Exhaust Volume
Is the volume of air that is exhausted from the fume hood. It is calculated by multiplying the face velocity
(ft/min) by the face area (ft²) and is expressed in cubic feet per minute (ft³/min or cfm).
Face Velocity
The average air speed entering the open sash. It can be measured by various measuring devices or calculated
by dividing the exhaust volume (cfm) by the face area (ft²) and is expressed in feet per minute (ft/min or fpm).
Face velocity is a measurement of the average velocity at which air is drawn through the face of the fume hood.
Face velocities too high or too low can be detrimental to the performance of the fume hood. The acceptable
range of the average face velocity may vary between 80-100 feet per minute (fpm) depending on hood type
and hazard. Currently, all fume hoods are certified for work with hazardous chemicals if the air velocity is
between 80 and 120 fpm. At velocities greater than 120 fpm face velocity, studies have demonstrated that the
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 27 of 33
creation of turbulence causes contaminants to flow out of the hood and into the user’s breathing zone.
Plenum
A low-velocity chamber used to distribute static pressure (from the fan in the system) throughout its interior.
Radioisotopes Hood
A hood designed for safe and convenient handling of low-level radioactive matter.
Sash
Is the fume hood’s moveable door which is usually made of laminated glass. Vertically raising, horizontal sliding,
or combinations of both are the most common sash types.
Static Pressure
is pressure drop in an HVAC system resulting from duct bends and restrictions from various components such
as a fume hood. It is expressed in inches of water gauge (in. WG).
Page 28 of 33
ANSI*/ASHRAE**
Standard 110-1995, Method of Testing Performance of Laboratory Fume Hoods
_______________
* American National Standards Institute
** American Society of Heating, Refrigerating and Air-Conditioning Engineers Inc.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 29 of 33
Scheduled Maintenance
Emergency and scheduled maintenance of fume hoods is the responsibility of University of Windsor Facility
Services and all other inquiries regarding these matters should be directed to Facility Services Dispatch at ext.
2850 or [email protected]. Annual Face velocity testing is the responsibility of the Chemical Control Centre.
Monthly Maintenance
All ground-fault circuit interrupters shall be tested monthly by Facility Services
Task Responsibility
1 Inspect the sash mechanism for corrosion and damage; Facility Services
2 Inspect the fans, motors, drives, and bearings for correct operation Facility Services
and wear;
4 Operate the wash down system( if there is one) and observe the Facility Services
performance to ensure thorough washing;
5 Test the controls of the services to the fume hood for proper Facility Services
operation;(e.g. water, gas, air, vacuum)
6 Check the stability and condition of the discharge stack including Facility Services
guy wires
7 Check the laboratory make-up air balance and adjust as necessary Facility Services
8 Inspect the interior of the ductwork through the inspection ports or other Facility Services
methods.
9 Check the operation of any balancing damper; Facility Services
10 Inspection of the sink drains (if there is one) for corrosion; leakage and Facility Services
blockage;
11 Check acid neutralization tanks (if there is one) and replace Facility Services
material as required;
12 Repair defects and lubricate as necessary; Facility Services
13 Measuring the hood face velocity; Chemical Control Centre
14 Verification of the calibration of the airflow monitor; CCC/Third Party
15 Testing the carbon filters (if any) for loading, contamination and leakage
Third party
and replacing if necessary
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 30 of 33
1. The face velocity measurement test is to be conducted annually to check the performance of fume
hoods.
2. Lab ventilating systems, both supply and exhaust, including fume hood exhaust shall be in full
normal operation.
3. The door to the laboratory should be closed to maintain the negative pressure of the lab with
respect to the corridor.
4. All fume hoods are tested with the sash opening of 45 cm (18-inches) and 15 cm (6-inch).
5. All other hoods in the same room are in the 45 cm sash opening position.
6. When adjustments are made to hood sashes, supply and exhaust air in the room will be allowed to
stabilize before testing is done.
7. A calibrated air velocity meter is used to measure the hood face velocity in feet per minute (FPM) or
meter per second (m/sec).
Testing Procedure
1. Position the sash so that the fume hood opening is 45 cm (18- inches).
2. Divide the fume hood opening into equal imaginary grids with sides measuring no more than 30 cm
x 30 cm (12-inches) - total 6 grids.
3. Position the tip of the velocity meter probe in the Centre of each of six squares and measure the
velocity of the air (each grid velocity should be the average of at least 10 measurements made over
at least 10 seconds)
4. Record the measurements on the form “LABORATORY CHEMICAL FUME HOOD INSPECTION”
(CCC-2010-13)
5. Continue taking reading until all grids are completed.
6. Average the readings to determine the average face velocity.
7. Position the sash at 15 cm (6 –inches) height.
8. Divide the fume hood opening into 3 equal grids.
9. Follow steps 3, 4, 5, 6 for measuring and recording data.
All hoods should have a sticker designating the 45 cm sash height. Keep the sash at this level to ensure optimal
face velocity.
Always use eye protection and insulated gloves when conducting this test.
Page 31 of 33
Testing Procedure
The tracer gas testing to determine direction of airflow pattern and leakage can be time consuming and
expensive and is used mainly for newly installed hoods or in some other specific situations for rigorous
evaluation of hood performance by the manufacturer.
1. The average face velocity with the sash opening of 18” must be a minimum 80 FPM
2. The average face velocity with the sash opening of 18” cannot be greater than 120 FPM
3. Smoke cannot come out of the hood.
Date: September 9, 2015
FUME HOOD MANUAL Approved by: VP, Human Resources
Page 32 of 33
Contact Information for Faculty & Staff Responsible for Hood Operation
Name Title
Staff Contact Title
Department Account #
Campus Address
Phone # Email
Page 33 of 33