GAS BURNER
SERIE P 2 stages from 406 up to 1744 kW
Burners for gas, double stage, aluminium frame, fan at high pressurisation,
combustion head with adjustment at high efficiency and high flame stability.
Available in the versions Methane (natural gas) or G.P.L. (to specify at the
order) on demand specific versions for town gas, coal gas or biogas.
Disposition rationalized of the components with accessibility facilitated for
the operations of setting and maintenance.
Gas train complete of working valve double stage with flow adjustment,
safety valve, gas pressure switch, filter stabiliser of gas pressure, completely
assembled, electrically linked and tested.
TECHNICAL DATA
MODEL GAS P70/2 CE GAS P100/2 CE GAS P150/2 CE
Mcal/h 116/350-650 172/500-1000 240/700-1500
Thermal power min 1° st./min 2° st.-max 2° st.*
kW 135/406-754 200/581-1162 279/814-1744
G20 flow (NATURAL GAS) min 1° st./min 2° st.-max 2°st.* Nm ³/h 13.5/41-76 20/58.4-117 28/81.7-175.2
G31 flow (LPG) min 1° st./min 2° st.-max 2° st.* Nm ³/h 5.2/15.7-29.3 7.8/22.6-45.2 10.8/31.6-67.8
Fuel Natural gas (second family) - LPG (third family)
Combustible category |2R’|2H’|2L’|2E’|2E+’|2Er’|2ELL’|2E(R)B|38/P’|3+’|3P’|38’|3R
Intermitted working operation (min. 1 stop every 24 hours) two stages
Environmental conditions operation/storage -15..+40°C/-20...+70°C, rel. humidity max 80%
Max temperature combustion air °C 60 60 60
Minimum pressure gas train D1”1/2 FS50 NATURAL GAS/LPG ** mbar 21/27 42/36 -
Minimum pressure gas train D2” FS50 NATURAL GAS/LPG ** mbar 17/25 33/31 63/43
Minimum pressure gas train DN65 FS65 NATURAL GAS/LPG ** mbar - 22/28 36/33
Minimum pressure gas train DN80 FS80 NATURAL GAS/LPG ** mbar - - 27/31
Maximum pressure at the entry of the valves ([Link]) mbar 200 200 200
Nominal electric power kW 1.4 2.7 3.4
Motor fan kW 1.1 2.2 3
Nominal absorption power A 2.5 5.2 6
Nominal absorption auxiliary A 0.6 0.5 0.6
Electrical supply 3 ~400V,1/N ~230V-50Hz
Degree of electric protection IP40 IP40 IP40
Noisiness*** min-max dBA 72-78 81-82 83-84
Weight burner**** kg 47 65 79
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 mt (sea level)
** Minimal feeding-gas pressure of the gas train to get the maximum power of the burner considering counter-pressure in combustion chamber of value 0 (zero)
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 mt of distance (UNI EN ISO 3746 law)
**** For burner with long head add 3 kg weight
20110613
Le illustrazioni e i dati riportati sono indicativi. F.B.R. Bruciatori S.r.l. si riserva il diritto di apportare, senza obbligo di preavviso, tutte le modifiche opportune, per l’evoluzione dei propri prodotti.
The illustrations and data here shown are indicative. F.B.R. Bruciatori S.r.l. reserves the right to bring, without any obligation of warning, any changes that would be appropriate to the continuing development of their products.
F. B . R . B R U C I AT O R I - M A D E I N I TA LY - C O M PA N Y Q U A L I T Y C E R T I F I E D I S O 9 0 0 1
GAS BURNER
SERIE P 2 stages from 406 up to 1744 kW
FIRING RATES: Thermal power - Pressure in combustion chamber
Pression in the combustion
chamber [mbar]
Thermal power
DIMENSIONS (mm)
F2 = overall dimension with the burner out in position of maintenance
* Recommended diameter of hole on the boiler
MODEL N N O O O Gas
A B C D E F1 F2 G H I L M TC TL S R1 R2 R3 R4 RD train
min max min * max weight
GAS P 70/2 CE - D1”1/2-FS50 300 188 308 175 168 660 1100 327 171 144 10 M12 310 368 185 185 250 250 385 18 260 380 532 576 1 1/2” 23 kg
GAS P 70/2 CE - D2”-FS50 300 188 308 175 168 660 1100 327 171 144 10 M12 310 368 185 185 250 250 385 18 260 380 536 576 2” 23 kg
GAS P 100/2 CE - D1”1/2-FS50 300 238 372 185 184 660 1160 438 173 0 0 M12 340 368 195 195 250 250 385 18 260 380 532 591 1 1/2” 23 kg
GAS P 100/2 CE - D2”-FS50 300 238 372 185 184 660 1160 438 173 0 0 M12 340 368 195 195 250 250 385 18 260 380 536 591 2” 23 kg
GAS P 100/2 CE - DN65 300 238 372 185 184 660 1160 438 173 0 0 M12 340 368 195 195 250 250 385 18 260 380 540 630 DN65 50 kg
GAS P 150/2 CE - D2” 320 238 372 209 193 800 1380 438 213 183 40 M14 340 368 220 220 250 280 400 23 284 380 552 600 2” 25 kg
GAS P 150/2 CE - DN65 320 238 372 209 193 800 1380 438 213 183 40 M14 340 368 220 220 250 280 400 23 228 340 495 585 DN65 50 kg
GAS P 150/2 CE - DN80 320 238 372 209 193 800 1380 438 213 183 40 M14 340 368 220 220 250 280 400 23 228 420 590 605 DN80 60 kg
20110613
Le illustrazioni e i dati riportati sono indicativi. F.B.R. Bruciatori S.r.l. si riserva il diritto di apportare, senza obbligo di preavviso, tutte le modifiche opportune, per l’evoluzione dei propri prodotti.
The illustrations and data here shown are indicative. F.B.R. Bruciatori S.r.l. reserves the right to bring, without any obligation of warning, any changes that would be appropriate to the continuing development of their products.
F. B . R . B R U C I AT O R I - M A D E I N I TA LY - C O M PA N Y Q U A L I T Y C E R T I F I E D I S O 9 0 0 1