Item

Description Of Item Unit Nos Nos Length Breadth Depth Quantity Remarks
No
1.76 Providing and fixing seamless ceiling with gypboard of 12.5 PART-A CIVIL WORKS
mm thick, fixed to the underside of the suspended grid
formed of GI perimeter channel of size 20 x 27 x 30 mm (MF
6A) fixed along the wall by using wood screws and metal
expansion rawl plugs. The GI intermediate channel of size 45 x
15 x 0.90 mm (MF7) shall be fixed to the suspended strap
hangar/GI ceiling angle at intervals not more than 1220mm.
The suspended GI ceiling angle/strap hangar is to be
connected with GI soffit cleat of size 37 x 27 x 25 x 1.6 mm
and it should be fixed on the roof slab/beam, by using metal
expansion fasteners(Wt. Type) of 12.5 mm dia. to a length of
35 mm with 6 mm dia bolt/sctew at top ends. The GI ceiling
section of size 80 x 26 x 0.5 mm (MF 5) is to be provided
across the intermediate channel at intervals not more than
457 mm centres at bottom and the same shall be fixed by Sqm
GI connection clips 2.64 mm dia at the intersection points.
The ends of ceiling section (MF5) channel by adopting an
overlap length of minimum 150 mm , shall be connected with
intermediate channel perimeter " channel in insertion The
gypboard shall be fixed to the under side of the suspended
grid by using 25mm long dry wall screws. The joints shall be
finished with joint paper tape by using jointing compound of
India Gypboard Ltd., and applying over it 3 layers of the filler
compound to provide a smooth surface. The ceiling surface
shall be painted with two coats of approved first quality
plastic emulsion over a coat of primer etc., complete. The rate
shall include making cutouts for tube lights, spot lights, duct
doors, for specified size, grills etc., for which no extra will be
paid [Link] shall include providing additional
RA 03 & Part
FIRST FLOOR
PANTRY 1.00 2.600 2.170 5.64
DEDUCTION -1.00 1.800 0.600 -1.08
VERTICALS 0.00
LONG SIDES 2.00 1.800 0.200 0.72
SHORT SIDES 2.00 0.600 0.200 0.24
CABIN 0.00
NORTH 1.00 4.240 0.640 2.71
EAST 1.00 2.400 0.600 1.44
WEST 1.00 2.400 0.650 1.56
SOUTH 1.00 4.240 0.340 1.44
VERTICALS 0.00
WEST /EAST 2.00 2.400 0.200 0.96
NORTH / SOUTH 2.00 3.050 0.200 1.22
HALL 0.00
EAST O/O 1.00 24.400 0.630 15.37
SOUTH I/I 1.00 5.320 0.400 2.13
EAST O/O 1.00 2.930 0.400 1.17
SOUTH I/I 1.00 4.240 0.280 1.19
WEST O/O 1.00 23.300 0.650 15.15
NORTH I/I 1.00 3.680 0.700 2.58
WEST O/O 1.00 4.220 0.460 1.94
NORTH I/I 1.00 6.050 0.640 3.87
VERTICALS 0.00
EAST 1.00 23.400 0.200 4.68
SOUTH 1.00 5.720 0.200 1.14
EAST 1.00 2.410 0.200 0.48
SOUTH 1.00 4.250 0.200 0.85

1 of 2
Item
Description Of Item Unit Nos Nos Length Breadth Depth Quantity Remarks
No
WEST PART-A CIVIL 1.00
WORKS 22.350 0.200 4.47
NORTH 1.00 4.150 0.200 0.83
WEST 1.00 3.600 0.200 0.72
NORTH 1.00 6.060 0.200 1.21
GROUND FLOOR 0.00
NEW LAB CEILINGS 0.00
NORTH SIDE 1.00 11.580 0.775 8.97
SOUTH SIDE 1.00 11.580 0.775 8.97
WEST SIDE 1.00 7.300 0.670 4.89
EAST SIDE 1.00 7.300 0.670 4.89
VERTICALS 0.00
NORTH SIDE 1.00 10.300 0.200 2.06
WEST SIDE 1.00 7.300 0.200 1.46
SOUTH SIDE 1.00 10.300 0.200 2.06
EASTSIDE 1.00 7.300 0.200 1.46

TOTAL QTY MEASURED UPTO DATE 107.41


TOTAL QTY MEASURED UPTO PREVIOUS BILL 0.00
BALANCE QTY FOR PAYMENT 107.41