Li 2004
Li 2004
Abstract
Analytical solutions have been derived for the first time for temperature
fluctuations along a hot wire when it is exposed to turbulent velocity
fluctuations of different frequencies and wave numbers. The solutions are
used to analyse the dynamic response of the hot wire alone first. The results
show that attenuation to the velocity fluctuations exists at high frequencies
and depends on the relative end-conduction heat loss from the hot wire to its
supports. A simplified circuit for a hot-wire anemometer is then used to
analyse the frequency response of the combined hot wire and its anemometer.
It is found that even though the frequency response of the anemometer (as
that determined from a square wave test) can be very high, the cut-off
frequency of the combined system is low, depending on the hot-wire length
to diameter ratio, Reynolds numbers, overheat ratio and the hot-wire
material used. A preliminary investigation of the spatial resolution of the hot
wire to the velocity fluctuations at different wave numbers is also presented.
Keywords: hot wire, dynamic response, turbulence measurements
temperature distribution along the hot-wire filament, Betchov five orders of magnitude less for the hot-film wall shear stress
(1949), Corrsin (1963), Champagne et al (1967), Hinze (1975), probes. They also found that fD increases with the mean
Freymuth (1979), Perry (1982) and Li et al (2004), to mention velocity flowing across the hot wires and the overheat ratio
a few. In these analyses, the solution of the mean temperature that the hot wires were operated at.
along the hot wire was generally given. The solution was then Morris and Foss (2003) analysed the frequency response
used to investigate the effect of the hot-wire length to diameter of a constant temperature hot-wire anemometer system nu-
ratio on the uniformity of the temperature distribution. In merically. In their analysis, the temperature distribution along
order to have a reasonably uniform temperature profile along the hot wire was solved for a particular hot wire at a speci-
the wire (away from its two ends), it is generally accepted that fied Reynolds number. In order to minimize the influence of
2l/d needs to be larger than 200. the anemometer on the hot wire itself, the cut-off frequency of
The dynamic response of the hot wire has been the anemometer was assumed to be very high. Their results
analysed by Freymuth (1979), Hinze (1975) and Perry (1982) of hot-wire attenuation on turbulent velocity at high frequency
analytically. In Freymuth (1979), the hot-wire filament confirmed the results of Freymuth (1979), which were based
was assumed to be infinitely long. Perry (1982) analysed on intuitive arguments. They also drew a similar conclusion
the dynamic response of the hot wire by considering the to Freymuth (1979) that changing the overheat ratio of the hot
perturbation in velocity, temperature and electrical current wire will not affect this attenuation. This is in contrast to the
separately. Hinze (1975) analysed the dynamic response of the findings from Khoo’s group.
hot wire by using the perturbations in the electrical resistance Borgos (1980), in his review on the electrical testing
of a hot wire, and the perturbation in hot-wire temperature was of the cut-off frequency from the anemometers, listed the
connected to its resistance. In Hinze (1975), the profile of the following limitations from such a test: (1) flow effects
temperature fluctuation was assumed to be similar to that of caused by unsteady boundary layers; (2) spatial resolution;
the mean temperature in order to determine the contribution (3) nonlinearity of the system with large velocity fluctuations;
of the heat conduction to the electrical resistance fluctuation. (4) the effect of thick coatings that are sometimes used over
thermal sensors and (5) only indirect information about the
Freymuth (1977a, 1977b) was the first to study the
effect of heat conduction. The limitations (2) and (5) can
dynamic response of the hot-wire system, which includes
be investigated by solving the differential equation of small
the hot wire itself and the anemometer for operating the
temperature fluctuations (less than 10%) for a simplified hot-
hot wire at constant temperature. In this pioneering
wire system.
work, Freymuth (1977a, 1977b) solved the combined energy
In this paper, theoretical solutions for the temperature
balanced equations of the hot wire and coupled to the
fluctuations along a hot wire are derived for given turbulent
electrical circuit. In considering the energy balance for
velocity fluctuations. To the best of our knowledge, this is the
thin wires, Freymuth (1977a) assumed that the temperature
first time that such solutions are given. The solutions are used
profile along the wire is uniform. From the solutions to these to study the hot-wire attenuation of velocity fluctuations at high
coupled equations, Freymuth (1977a, 1977b, 1978) suggested frequencies. The results confirm the conclusions of Freymuth
a method for determining the cut-off frequency of the hot-wire (1979) on this attenuation. By using the theoretical solution,
anemometer by using a small square or sine-wave voltage the effect on this attenuation from hot wires of different length
perturbation. to diameter ratios, Reynolds numbers, hot-wire materials and
In turbulence measurements, the hot-wire anemometer overheat ratios is investigated systematically. In contrast, the
is normally tuned to achieve a uniform frequency response results of Morris and Foss (2003) were for a particular hot wire
over the range of interest. The cut-off frequency is in general (a 1 mm active region of 5 µm tungsten filament with 50 µm
determined, using the method suggested by Freymuth (1977a), copper plated support stubs) at a single length to diameter ratio
by a square or sine wave test, which introduces a small (200) and a single mean flow velocity (7.5 m s−1).
perturbation to the electrical resistance in one of the two The hot wire is then connected to a constant temperature
arms of a Wheatstone bridge. However, during turbulence anemometer with simplified circuit, and the frequency
measurements, the fluctuations in the output voltage can only response of the combined system is investigated. It is found
be caused by the velocity fluctuations over the hot wire and that, similar to Khoo et al (1999), the cut-off frequency of the
the resistance fluctuations can only be a consequence of this system is mainly controlled by the hot wires rather than
velocity variation. Thus, the question should always be asked the anemometer itself, provided that the cut-off frequency of
as to how much could one be confident about the cut-off the latter is reasonably high. It is also found that the overheat
frequency determined by such a square/sine wave test. Khoo ratio, the Reynolds number and the length to diameter ratio
et al (1998, 1999), Chew et al (1998) and Teo et al (2001) of the hot wire can all influence the cut-off frequency of the
have studied the dynamic response of a hot-wire anemometer system. The spatial resolution of the hot wire for turbulent
for near-wall hot-wire/film probes experimentally. By using fluctuation along the wire is also studied preliminarily. It
a specially designed rotating disc to produce a known velocity is found that spatial resolution is not uniform across the
fluctuation at various frequencies, they were able to determine whole frequency range for a given wave number and length to
the frequency response of the marginally elevated and flush- diameter ratio.
mounted hot wires. They found that the cut-off frequency fD
of the hot-wire system, determined using velocity perturbation, 2. Equation for temperature along the hot wire
is much less than the cut-off frequency fS determined using
square or sine wave methods. Their results show that fD is By considering the heat generation, heat convection, heat
one order of magnitude less than fS for hot wires and up to conduction and heat accumulation in a hot-wire filament, it
1836
Dynamic response of constant temperature hot-wire system
can be shown that the equation for instantaneous temperature Here overbar means steady conditions. For a hot wire 2l long
along a hot wire of constant diameter is given by (Perry 1982) with large supports, such as the hot-wire prongs, the boundary
conditions of the mean temperature are
∂θ ∂ 2θ
τ = 2 + (Q − ξ )θ + Z. (1)
∂t ∂η θ =0 at η = ±1
Here ∂θ (4)
=0 at η = 0.
θw − θa x ∂η
θ= η=
θa l These boundary conditions are symmetrical at η = 0, and the
4I 2 R0x α l 2 4I 2 R0x l 2 solution to equation (3) with boundary conditions (4) is
Q= Z=
πkw d πkw θa d
Z cosh(Y η)
kf l 2 l2 θ= 1 − (5)
ξ = 4Nu τ = ρw Cw . Y2 cosh(Y )
kw d kw
Here we have assumed that the centre of the hot wire is at where
x = 0, the ends of the hot wire are at x = ±l where the hot
wire connects to the prongs and the electrical resistance of the Y = ξ − Q.
hot wire depends on its temperature according to
Solution (5) is the same as that given by Corrsin (1963)
Rx = R0x (1 + α(θw − θa )) by using the same boundary conditions as in (4). The
l (2) dimensionless group Y is the Biot number of the hot wire.
Rw = 2 Rx dx. The mean temperature of the hot wire can be determined from
−l
(5) as
In equation (1), we use the Nusselt number recommended by
Fand (1965) Zθa tanh(Y )
θm = θa + 1 − . (6)
Nu = 0.35 + 0.56Rew 0.52 Pr0.3 . Y2 Y
Here Rew is the Reynolds number based on the hot-wire The overheat ratio of the hot wire is defined as
diameter and Pr is the Prandtl number. According to Holman Rw − R0
(1992), the above relationship is valid for 0.1 < Rew < a=
R0
10 000, which would cover the Reynolds number range in
most of the turbulent measurements so far. It should be noted where R0 = 2lR0x . The mean temperature in (6) is related to
that the above Nusselt number of convective heat transfer for the overheat ratio a as
flow across a cylinder is for steady flows at different mean a
velocities. In analysing the dynamic response of the hot wire, θm = θa + .
α
the flow considered is unsteady. So far a correlation between
Reynolds numbers and the Nusselt number for unsteady This shows that, for a given hot wire, the mean temperature
inflows across a cylinder is not available. As a referee of the hot wire is determined by the overheat ratio. Using
pointed out, strictly, one has to solve the coupled flow and (6), the mean electrical current through the hot wire can be
heat conduction equations in order to determine properly the determined. Once the electrical current is known, Z and
thermal response of the hot wire with contributions from both Y can be determined from their definitions, and the mean
the conduction and convection components. The recent work temperature profiles along the hot wire can be established.
of Lange et al (1999) solved such a problem for hot wires in free The profiles are the same as those plotted in Freymuth (1979).
stream and close to the wall numerically with prescribed steady In general, the profiles are uniform near the centre of the
inflow velocity at given Reynolds number. The numerical hot wire for reasonably large Biot numbers. However, for
code may also be used for solving the heat convection for flow small Biot numbers, the mean temperature profiles are close
across a cylinder with prescribed unsteady inflow velocity. An to parabolic shapes. When measuring turbulent velocity using
investigation in this direction would be most welcome. In this a hot wire, a uniform temperature distribution is desirable.
paper, we assume that the above given relationship between This is because the temperature distribution along the hot wire
the Reynolds numbers and the Nusselt number can be applied is a balance between the heat generation and the heat losses
to the unsteady incoming velocity. from convection and end conduction. A calibration of the
hot wire is to relate the heat generation (through the electrical
3. The mean temperature distribution at steady current flow along the hot wire) to the heat losses due to
conditions convection. Because the heat losses of a hot wire are from
both convection and end conduction, one way to increase the
Under steady conditions, equation (1) becomes hot-wire sensitivity is by using longer wires so that the losses
due to end conduction are only a small fraction of the total loss.
∂ 2θ An empirical value in practice is 2l/d 200 (Champagne
+ (Q − ξ )θ + Z = 0. (3)
∂η2 et al 1967).
1837
J D Li
1
4. The solution for the temperature fluctuation 1
C2 = e−Ys sinh[Ys (1 − η)]M(η) dη
2Ys sinh(2Ys ) 0
For a hot wire, the temperature along the wire can fluctuate 1
when the velocity passing it and/or the current through it −eYs
sinh[Ys (1 − η)]M(−η) dη .
changes. For small perturbations, the equation for the hot- 0
wire temperature fluctuations can be written as When M(η) is symmetrical, C1 = C2 .
∂θ ∂ 2θ The electrical resistance fluctuation rw of the hot wire is
τ = + (Q − ξ )θ + (Q − ξ )θ + Z (7) connected to the integration of the temperature fluctuations
∂t ∂η2
along the wire, and can be expressed as
where the prime means fluctuations, θ = θw /θa and τ is the l 1
time constant of the hot wire. In (7), we have assumed that rw = R0x α θw dx = R0x lαθa θ dη. (11)
the ambient temperature θa is constant since we are concerned −l −1
here with only the turbulent velocity measurements using hot Using (10) and the constants C1 and C2 , it can be shown that
wires. Using the definition for Q, Z and ξ , equation (7) can be 1
r̃w 1
reorganized as = αθa θ̃ dη
R0 2 −1
∂θ ∂ 2θ
τ = + (Q − ξ )θ + 2(Z + Q θ)i + χ θu. (8) αθa 1 cosh(Ys η)
∂t ∂η2 = − 1 M(η) dη. (12)
2Ys2 −1 cosh(Ys )
Here i is the current fluctuation, u is the velocity fluctuation,
and using the expression for Nu, it can shown that Because the function cosh(Ys η) is symmetrical at η = 0,
this result shows that only the symmetrical part of M(η) can
U dNu 0.29Rew 0.52 make a contribution to the electrical resistance fluctuations of
χ =− ξ ≈− ξ.
Nu du 0.35 + 0.56Rew 0.52 the hot wire. The current fluctuation i is a function of t while the
In equation (8), the fluctuation of ξ due to the temperature velocity fluctuation u can be a function of both t and x. Because
fluctuations (through the variation in kinematic viscosity ν and of this, ĩ will be a function of s only and symmetrical with
thermal conductivity kf of air) has been neglected. Estimation respect to η = 0 while ũ will be a function of both s and η.
has been made of its magnitude. It is found that in general the
error from neglecting the term is about 1% of the second r.h.s. 5. Dynamic response of the hot wire
term in equation (8).
By taking the Laplace transform of (8), we obtained To determine the frequency response and the spatial resolution
2 of a single hot wire, let us assume that, for a particular non-
d θ̃
− [τ s + (ξ − Q)]θ̃ = −2(Z + Q θ)ĩ − χ θ ũ. (9) dimensional wave number β = kl,
dη2
Here ∼ means the Laplace transform and s is the Laplace ũ = ũ1 (s) cos(βη). (13)
variable. For a given s, equation (9) is a second-order ordinary Then it can be shown, after much algebra, that
differential equation (ODE) with variable coefficients. The
r̃w = P ĩ + Aũ1 (14)
general solution of (9) (Kreyszig 1993) can be written as
where
eYs η η −Ys η
θ̃ = C1 eYs η + C2 e−Ys η + e M(η) dη r̃w ĩ ũ1
2Ys 0 r̃w = , ĩ = , ũ1 =
R0 I U
e−Ys η η Ys η
− e M(η) dη. (10)
2Ys 0
2Q tanh(Ys )
Here C1 and C2 are constants to be determined by using the P =− − 1
Ys2 Ys
boundary conditions for θ , and
2
2Q tanh(Ys ) tanh(Y ) τs
Ys = τ s + (ξ − Q) + − + (15)
τs Ys3 Y3 Ys2 Y 2
M(η) = −2(Z + Q θ)ĩ − χ θ ũ.
χQ β
The boundary conditions for θ are such that (because we A= sin(β) − 2 (Y tanh(Y ) cos(β)
βYs2 Y 2 Y + β2
have assumed that the ambient temperature is constant and the
β
temperature for the supports of the hot wire is the same as that + β sin(β)) − 2 (Ys tanh(Ys ) cos(β)
of the ambient) Ys + β 2
β
θ̃ (η = −1, s) = θ̃ (η = 1, s) = 0. + β sin(β)) + ((Ys − Y )(tanh(Ys )
2[(Ys − Y )2 + β 2 ]
Using these conditions, the constants C1 and C2 in (10) − tanh(Y )) cos(β) + β(1 − tanh(Ys ) tanh(Y )) sin(β))
can be determined as β
1 + ((Ys + Y )(tanh(Ys )
1 2[(Ys + Y )2 + β 2 ]
C1 = e−Ys sinh[Ys (1 − η)]M(−η) dη
2Ys sinh(2Ys ) 0
1 + tanh(Y )) cos(β) + β(1 + tanh(Ys ) tanh(Y )) sin(β)) .
− eYs sinh[Ys (1 − η)]M(η) dη
0 (16)
1838
Dynamic response of constant temperature hot-wire system
0.9
the velocity fluctuations at high frequencies for this particular
hot wire and Reynolds number. In terms of energy, this is
0.8 only 85%. This attenuation starts at fairly low frequency
fl = ωl /2π ≈ 160 Hz and finishes at f ≈ 160 kHz.
0.7
Unfortunately, this covers the frequency range in most of the
turbulence measurements today.
In calibrating the hot wires, both static and dynamic
0.6
calibration methods exist. The static calibration method
ω1 100ω1 1000ω1
calibrates the hot wire at different mean velocities (f = 0).
0.5 Figure 1 shows that this will not be able to capture the plateau
100 101 102 103 104 105 106 107 108
ω at the high frequencies. Also, this attenuation cannot be
corrected by using the existing ‘dynamic calibration’ method
Figure 1. The dynamics response (or attenuation) of the hot wire
only.
(Perry 1982) either. In the existing dynamic calibration,
the shaking frequencies of the calibrator at different mean
velocities would in general be at about 1 Hz, far too low a
When β → 0,
frequency to capture the plateau at the high frequencies shown
χ Q tanh(Ys ) tanh(Y ) τs in figure 1. Given the very large frequency range where the
A → A1 = − + . (17)
τs Ys3 Y3 Ys2 Y 2 transition in attenuation occurs, it would be very difficult to
If we consider the hot wire at constant temperature all the time, come up with a scheme to calibrate the hot wire so that this
the electrical resistance fluctuation rw would be zero as that transition and the plateau at the high frequency can be captured.
assumed by Freymuth (1979). Later, we will show that this It seems that the only feasible solution would be to calibrate
cannot be true for the commonly used hot-wire anemometers. the hot wire using the existing methods and correct the hot-
For the time being, let us accept this assumption. Then the wire results using its frequency response such as that shown
dynamic response of the hot wire to the velocity fluctuations in figure 1.
is
ĩ A 6. Attenuation of the hot wire to velocity
=− . (18)
ũ1 P fluctuations (β = 0)
Freymuth (1979) considered the dynamic response of the hot
wire for velocity fluctuations with time only, this corresponds To investigate the effect of the hot-wire length and other
to β = 0 in (18) and the dynamic response of the hot wire parameters on the attenuation at zero wave number β = 0,
becomes (note that P is a function of s only) the ratio of the plateau at high frequencies to that at low
frequencies needs to be determined. Using (19), this is defined
ĩ A1
=− . (19) as
ũ1 P
A1 /P |ω→∞
Figure 1 shows the dynamic response of the hot wire according ε1 = (20)
A1 /P |ω→0
to equation (19) for a 5 µm platinum wire with 2l/d = 200,
a = 0.5 and Rew = 3.2 (This corresponds to a mean velocity with
of U ≈ 14 m s−1). Here the dynamic response is defined as A1 χ (1 − tanh(Y )/Y )
the magnitude ratio between the electrical current fluctuations =
P 2Y 2 + 2Q(1 − tanh(Y )/Y )
i and the velocity fluctuation u . The results in the figure ω→∞
1839
J D Li
1 1
0.95 0.95
Platinum wire
a = 0.5
ε1
0.9
ε1
0.9
Tungsten wire
a = 0.01
0.85 0.85
0.8 0.8
101 10 2 10 3 101 102 103
I/d I/d
Figure 2. The dependence of attenuation on hot-wire length to Figure 4. Hot-wire attenuation of platinum and tungsten wires.
diameter ratio.
1 1
0.98
0.95
Dynamic Response
0.96
Platinum wire
ε1
0.9
0.94
0.85 0.92
Tungsten wire
0.9
0.8 100 101 102 103 104 105 106 107 108
100 10 1
10 2
10 3 ω
Re
Figure 5. Dynamic response of platinum and tungsten hot wires.
Figure 3. The dependence of hot-wire attenuation on Reynolds
number.
The figure shows that the attenuation decreases as the Reynolds
As the length to diameter ratio increases, the heat losses from number increases. This is because, as the Reynolds number
the end conduction become relatively less than those from increases, the convective heat losses increase. This again
convection, and so does the attenuation. results in relatively smaller conductive heat losses.
Figure 2 also compares the attenuation at the overheat
Figure 4 shows the attenuation of the platinum and
ratios a = 0.5 and 0.01 for the given hot wire. It can be seen
tungsten wires at different l/d with Rew = 3.2 and a = 0.5.
that the overheat ratio does have some effect on the attenuation,
The figure shows that the tungsten wire gives more attenuation
especially at small l/d. The figure shows that a higher overheat
than the platinum wire. This is because tungsten has a thermal
ratio will result in less attenuation.
The results for a = 0.01 have been compared with the conductivity kw = 174 W K−1 m−1, which is higher than
results from Freymuth (1979) at a ≈ 0. When plotted as ε 1 kw = 71.6 W K−1 m−1 for platinum. Because of this, the
versus Y (the Biot number), no distinction can be made between relative heat losses from end conduction for the tungsten
the two results. Thus the present theoretical results at a ≈ 0 wire will be higher than those for the platinum wire at a
agree with the results of Freymuth (1979), which were based given Reynolds number. However, the thermal diffusivity
on intuitive arguments for very small overheat ratios. Morris of tungsten is higher than that of platinum. This means that
and Foss (2003) found that their results at a = 1.7 agree with the frequency at which the tungsten wire starts to attenuate the
the results of Freymuth (1979) at a ≈ 0. The present results velocity fluctuations will be higher than that for the platinum
in figure 2 show that the attenuations at a ≈ 0 and a > 0 are wire for the same 2l/d. Figure 5 shows the dynamic response
different, especially at smaller 2l/d. of the platinum and tungsten wires. The figure shows that the
Figure 3 shows the effect of Reynolds number on the frequency at which the tungsten hot wire starts to attenuate is
attenuation for platinum wire with 2l/d = 200 and a = 0.5. indeed higher than that of the platinum wire.
1840
Dynamic response of constant temperature hot-wire system
1841
J D Li
Bode Diagram
50
Magnitude (dB)
0
–50
–360
100 101 102 103 104 105 106 107
Frequency (rad/sec)
GBP=10000000
5 Lb=1.0032LbRb/Rw
Amplitude
–5
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Time (sec) x 10–5
–2
1
Imaginary Axis
–3
Hot wire and CTHWA
0 –4 combined
System: B
Pole: –5.17e+005 – 1.34e+0061 –5
Damping: 0.522
–1 Overshoot(%): 14.6
Frequency (rad/sec): 1.57e+006 –6
–7
–2
–8
–3 –9
–10
–4 101 102 103 104 105 106
–9 –8 –7 –6 –5 –4 –3 –2 –1 0 f (Hz)
Real Axis 6
x 10
Figure 9. Frequency response of a hot wire and its anemometer.
Figure 8. Zero and pole diagram for a CTHWA.
1842
Dynamic response of constant temperature hot-wire system
3 3
Hot wire only
2 CTHWA only 2
CTHWA only
1 1
0 0
Frequency Response (dB)
–2 –2
–3 –3
Hot wire only
–4 –4
Hot wire and CTHWA
–5 –5 combined with a = 0.5
Hot wire with 0.6
–6 increasing a = 0.3 0.7
–6
0.5 0.8
0.7 0.9
–7 0.9 –7 1.0
–8 –8
–9 –9
–10 –10
101 102 103 104 105 106 101 102 103 104 105
f (Hz) f (Hz)
Figure 10. The effect of overheat ratio on the frequency response of Figure 11. The effect of overheat ratio on the frequency response of
the hot wire system with GBP = 107 and a perfectly balanced bridge. the hot-wire system with GBP = 106 and an imbalanced bridge.
3
wires in free stream. Both the present results and those of Khoo
2
et al (1999) show that the frequency response determined using
the square/sine wave test in turbulence measurements could 1
off frequency is due to less attenuation at higher overheating Figure 12. The effect of 2l/d on the frequency response of the
ratio as mentioned before (figure 2). This finding is different hot-wire system.
from those of Freymuth (1979) and Morris and Foss (2003),
and agrees with the experimental results of Khoo et al (1999). Figure 11 also shows the frequency response of the hot-
Figure 11 shows the frequency response of a CTHWA wire system at different overheat ratios. The parameters used
with GBP1 = GBP2 = 106 for the two amplifiers. This for the 5 µm platinum wires are: 2l/d = 200 and U =
CTHWA is close to the anemometers using amplifiers of the 10.0 m s−1. It can be seen from the figure that the frequency
old generation (Perry 1982). The resistors Ra and Rc are the response of the hot-wire system increases with increasing
same as those used in figure 7, and are the values recommended overheat ratio. At a = 0.5, the cut-off frequency is about
in Perry (1982). It is found that the best frequency response 13 kHz and at a = 0.9 this is increased to 37 kHz. However,
of the hot-wire system can be achieved by using a slightly figure 11 shows that at a = 0.9, the system is close to marginal
unbalanced bridge with Rb = 9.9Rw . When using perfect stability. We think that this close to loss of stability at high
bridge balance, it is found that the frequency response of the overheat ratios is because the cut-off frequency of the CTHWA
hot-wire system becomes unstable at high overheat ratios (say is too low, and the time constants for the hot wire and that of
a > 0.6). This imbalance of the bridge is achieved in practice the CTHWA are too close to each other. It is recommended
by adjusting the offset voltage Eb and Perry (1982) suggested that amplifiers of the new generation (with GBP > 106) should
that R o = Rw Rc − Ra Rb is in general of the order of 100 2 always be used.
(p 62). The present results confirm his suggestion. To Figure 12 shows the frequency response of the hot wire
achieve an optimal frequency response for the CTHWA, the and its anemometer for platinum wires of different 2l/d. The
inductance Lb was re-tuned to 1.033Lw Rb /Rw . The cut-off parameters for the CTHWA are the same as those used for
frequency for the CTHWA at a = 0.5 is about 48 kHz for the figure 9. The overheat ratio a = 0.9 is fixed. The figure shows
parameters given. This is about double the 25 kHz normally that the cut-off frequency increases from 18 kHz to 101 kHz
achieved in practice, considering that only idealized electronic when 2l/d increases from 100 to 800. This increase in
components are used here. cut-off frequency as 2l/d increases is due to the decrease
1843
J D Li
3 3
CTHWA only 2
2
0 0
Frequency Response (dB)
–2 –2
–3 Platinum wire
–3 Hot wire system with 2l/d = 200
increasing mean velocity Ti/Ni wire
–4 U = 1.0 m/s –4
increasing
3.0 2l/d = 50
–5 10.0 –5 100
30.0 200
–6 100.0 –6
–7 –7
–8 –8
–9 –9
–10 –10
101 102 103 104 105 106 101 102 103 104 105 106
f (Hz) f (Hz)
Figure 13. The effect of Reynolds number on the frequency Figure 14. The effect of hot-wire materials on the frequency
response of the hot-wire system. response of the hot-wire system. The results for the Ti/Ni wires at
different 2l/d are also shown.
1844
Dynamic response of constant temperature hot-wire system
concluded that the less the attenuation of the turbulent velocity 0.9
fluctuations at high frequencies by the hot wire, the higher the
cut-off frequency of the hot-wire system will be. 0.8
Spatial Resolution β = 0
conductive heat loss relative to the total heat loss can increase
0.6
the cut-off frequency of the hot-wire system. This conclusion
can also be used to explain the findings of Khoo et al (1998, 0.5
1999) that for the air flow generated from a rotating disc, at sin2(β)/β2 Decreasing 2l/d = 800
0.4 400
the same mean velocity, the cut-off frequency of the hot wire 200
100
increases as it is moved close to the wall. As the hot wire is 0.3
moved close to the wall, the heat loss is increased for a hot
0.2
wire experiencing the same mean velocity as that found by
Khoo et al (1997) and Lange et al (1998) for air flowing over a 0.1
0
lost from the hot-wire filament to the surrounding air than that –1
to the hot-wire prongs through end conduction. Because of –2
Hot wire and
this, the relative end conduction heat loss becomes less as the –3 CTHWA β = 0
hot wire is moved close to the wall, a false ‘high’ velocity –4
is measured and the hot wire shows an ‘improved’ frequency –5
Hot wire only
response. –6 β = π/2
On the other hand, for air is flowing over a well-insulated –7 Hot wire and
wall, the heat loss to the surrounding air will be reduced –8 CTHWA β = π/2
between the hot wire and the wall as the hot wire is placed close –9
to it. This is because the temperature gradient between the hot –10
102 103 104 105 106 107
wire and the wall is less than that between it and the free stream ω (rad/sec)
(see figure 13 of Lange et al (1999)). This will result in less
heat loss directly from the hot-wire filament to the surrounding Figure 16. The frequency response of the hot wire at two different
air in comparison with a hot wire placed in free stream at the wave numbers.
same mean velocity. Because of this, a hot wire placed close
to a well-insulated wall will measure a false ‘low’ air velocity. along the hot wire, β = 0, and the hot wire cannot in general
Of course, in practice, it is very difficult to have a wall made resolve the spatial variation of the turbulence structures when
of materials having smaller thermal conductivity than that of the hot wire is longer than the structure’s length scale. This is
air, as pointed out by Lange et al (1999). This explains their the spatial resolution problem of the hot wire.
‘unexpected and contradictory’ numerical results that a false Figure 15 shows the spatial resolution of the hot wire at
‘low’ velocity will be measured near a well-insulated wall in different wave numbers β for different 2l/d at ω = 0. The
turbulent airflows. The present results show that, for a hot wire figure shows that as β increases, the spatial resolution of the hot
in airflow near a well-insulated wall, not only will the measured wire decreases dramatically, as would be expected. Figure 15
velocity be falsely low, but also the cut-off frequency will be shows that the spatial resolution is improved as the 2l/d
reduced. However, for turbulence measurements in the near decreases. The spatial resolution approaches
wall regions of water or oil channels (Alfredsson et al 1988), sin2 (β) sin2 (kl)
=
because of the high thermal conductivities of water and oil, the β 2 (kl)2
measured turbulence quantities will be closer to the true values as 2l/d → ∞. This is the function used by Wyngaard (1968)
(Khoo et al 1997) than those measured in airflows. in his analysis of the spatial resolution of three-dimensional
turbulence. Spatial resolution of this form is obtained by
8. Frequency response of the hot wire at wave assuming uniform mean temperature along the hot wire, which
numbers other than zero (β /= 0) can only be achieved at 2l/d → ∞.
Figure 16 shows the frequency response of the hot wire
So far we have been considering the frequency response of a with its anemometer at β = 0 and β = π/2. The parameters
single wire and it has been assumed that the velocity fluctuation used for the hot wire and its anemometer are the same as
is uniform along the wire (β = 0). When the fluctuation varies those used for figure 7. It can be seen from the figure that, for
1845
J D Li
1846
Dynamic response of constant temperature hot-wire system
be adopted. In this case, for statistically stationary turbulent Freymuth P 1978 Theory of frequency optimisation for hot-film
flows, the frequency of the measured voltage can be connected anemometers J. Phys. E: Sci. Instrum. 11 177–9
Freymuth P 1979 Engineering estimation of heat conduction loss in
to the length scale in the streamwise direction by using Taylor’s
constant temperature thermal sensors TSI Q. 3 (3)
hypothesis. Wyngaard (1968) assumed that the turbulence is Hinze J O 1975 Turbulence 2nd edn (New York: McGraw Hill)
isotropic and using the three-dimensional spectra given by Pao Holman J P 1992 Heat Transfer 7th edn (New York: McGraw Hill)
(1965) as that of the fully resolved. In turbulent wall shear Khoo B C, Chew Y T and Li G L 1997 Effects of spatial resolution
flows, the turbulence will in general be non-isotropic, and thus on turbulence measurements in the very near-wall viscous
sublayer region Exp. Fluids 22 327–35
only qualitative conclusions can be drawn by using the spectra
Khoo B C, Chew Y T, Lim C P and Teo C J 1998 Dynamic response
for isotropic turbulence. Work along this line is currently of hot-wire anemometer: Part I. A marginally-elevated
under investigation. hot-wire probe for near wall velocity measurements Meas. Sci.
Technol. 9 751–63
Khoo B C, Chew Y T and Teo C J 2003 A model for the frequency
References response of a near-wall hot wire: velocity perturbation and
sine-wave voltage perturbation tests Exp. Therm. Fluid Sci. 27
Alfredsson P H, Johansson A V, Haritonidis J H and Eckelmann H 167–75
1988 The fluctuating wall shear stress and the velocity field in Khoo B C, Chew Y T, Teo C J and Lim C P 1999 Dynamic response
the viscous sublayer Phys. Fluids 31 1026–33 of hot-wire anemometer: Part III. Voltage-perturbation versus
Beljaars A C M 1976 Dynamic behavior of the constant temperature velocity testing for near wall hot-wire/film probes Meas. Sci.
anemometer due to thermal inertia of the wire Appl. Sci. Res. Technol. 19 152–69
32 509–18 Kreyszig E 1993 Advanced Engineering Mathematics 7th edn
Betchov R 1949 Theorie non-lineaire de l’anemometre a fil chaud (New York: Wiley)
Proc. K. Ned. Akad. Wet. 52 195–207 Lange C F, Dust F and Breuer M 1999 Wall effects on heat losses
Borgos J A 1980 A review of electrical testing of hot-wire and from hot-wires Int. J. Heat Fluid Flow 20 34–47
hot-film anemometers TSI Q. 3 (3) Li J D 2001 An investigation on the length to diameter ratio of
Bremhorst K and Gilmore G B 1978 Influence of end conduction on hot wire filament in turbulence measurements 14th
the sensitivity to stream temperature fluctuations of a hot-wire Australasian Fluid Mechanics Conf. (Adelaide University,
anemometer Int. J. Heat Mass Transfer 21 145–54 10–14 Dec. 2001)
Bruun H H 1995 Hot-Wire Anemometry: Principles and Signal Li J D, McKeon B J, Jiang W, Morrison J F and Smits A J 2004 The
Analysis (Oxford: Oxford University Press) response of hot wires in high Reynolds-number turbulent pipe
Champagne F H, Sleicher C A and Wehrmann O H 1967 Turbulence flow Meas. Sci. Technol. 15 789–98
measurements with inclined hot wires: Part 1. Heat transfer Ligrani P M and Bradshaw P 1987 Spatial resolution and
experiments with inclined hot wire J. Fluid Mech. 28 153–75 measurement of turbulence in the viscous sublayer Exp. Fluids
Chew Y T, Khoo B C, Lim C P and Teo C J 1998 Dynamic response 5 407–17
of hot-wire anemometer: Part II. A flush-mounted hot-wire and Morris S C and Foss J F 2003 Transient thermal response of a
hot-film probes for wall shear stress measurements Meas. Sci. hot-wire anemometer Meas. Sci. Technol. 14 251–9
Technol. 9 764–78 Pao Y H 1965 Structure of turbulent velocity and scalar field at large
Corrsin S 1963 Turbulence: experimental methods Handbuch der wavenumber Phys. Fluids 8 1063–108
Physik vol 9, part 2 (Berlin: Springer) pp 523–90 Perry A E 1982 Hot Wire Anemometry (New York: Oxford
Fand R M 1965 Heat transfer by forced convection from a cylinder University Press)
to water in cross flow Int. J. Heat Mass Transfer 8 995 Teo C J, Khoo B C and Chew Y T 2001 Dynamic response of
Freymuth P 1977a Frequency response and electronic testing for hot-wire anemometer: Part IV. Sine-wave voltage perturbation
constant-temperature hot-wire anemometers J. Phys. E: Sci. testing for near-wall hot-wire/film probes and the presence of
Instrum. 10 705–10 low-high frequency response characteristics Meas. Sci.
Freymuth P 1977b Further investigation of nonlinear theory for Technol. 12 37–51
constant-temperature hot-wire anemometers J. Phys. E: Sci. Wyngaard J C 1968 Measurement of small scale turbulence
Instrum. 10 710–3 structure with hot wires J. Phys. E: Sci. Instrum. 1 1105–8
1847