START-S12-M Technical manual
Foreword Index
This manual provides all the specific information Par. Desricption Pag.
you need to familiarize yourself with and correctly 1 Scheme of the control unit / wiring diagram 6
operate your unit. Read it very carefully when you 1.1 Description of the electrical connections 7
purchase the instrument and consult it whenever 2 Use and functions of the control panel 8
you have doubts regarding use and before perfor- 2.1 State of the control unit
ming any maintenance operations. Nologo has the 2.2 Settings and parameters
right to modify the product without previous notice. 2.3 Example how to use the MENU 9
and information
2.4 Set up a password for programming 10
Environmental protection
2.5 Cancel of the operation 11
measures 2.6 Display the number of cycles
and the speed of the motor
Information regarding the environment 2.7 Desactivation of the cycle when the control
for customers within the European panel wil be turned on
Union. European Directive EC 2002/96 3 Installation of the control unit 12
requires that units bearing this symbol 3.1 Connection of the TENSION and MOTOR
on the unit and/or on the packaging be 3.2 Connection of the lamp 230 Vac or 12 Vac
disposed of separately from undifferenti- 3.3 Pre-fl ashing time
ated urban wastes. 3.4 Connection of the ANTENNA 13
The symbol indicates that the product must not be 3.5 STOP connection
disposed of with the normal household wastes. 3.6 Connection of the 8k2 safety edge or N.C.
The owner is responsible for disposing of this prod- 3.7 Connection of the Open and Close limit switch
uct and other electrical and electronic equipment 3.8 The connection of partial opening or START 14
through specific waste collection facilities indicated
3.9 Connection of the PHOTO-BEAMS with cable
by the government or local public agencies. Correct
3.10 CONNECTION of the safety
disposal and recycling help prevent any potentially or UNFOLDING FUNCTION
negative impact on the environment and human 3.11 Connection of the PHOTO-BEAMS 15
health. To receive more detailed information re-
3.12 Connection of the photo-beam
garding disposal of your unit, we recommend that (activated when closing) with TEST
you contact the competent public agencies, the 3.13 Deactivation of the PHOTOCELL A
waste collection. 3.14 SLOW DOWN SWITCH 16
3.15 Connection of the brake and internal brake
4 ACTIVATE the single OUTPUTS 17
5 Functions 18
5.1 Logic of functions
5.2 Working time 19
5.3 Set SPEED and ACCELERATION 20
Small legend
5.4 SCHEME relation between SPEED 21
and FREQUENCY of the motor
LSO or FCA Open limit switch
6 INTERLOCK Function 22
LSC or FCC Close limit switch 7 RESET of the control unit and restore of 23
START Control to drive the gate factory default settings
PEDESTRIAN in sliding units: control partial opening 7.1 Restore factory settings
Vac (alternate current) corrente alternata 7.2 WARNING of the SETTING PARAMETERS 24
Vdc (discrete current) corrente continua 7.3 SAVE SET UP and CHECK of the parameters
NC normally closed 8 LIST of the FUNCTIONS 26
NA o NO normally open 9 Problems 29
Isolated contact isolated from power supply 10 Note 30
11 Declaration of CE conformity 31
-2-
START-S12-M Technical manual
Safety precautions
We remind that the installations of gates and automatic doors must be executed from qualified personnels
according to the norms. Before installing check the strength and mechanic part of the gate or door, check
that the mechanical stops are suitable to stop immediatelly the cycle of the gate or door even in case of faulty
limit switches or during the manual cycle. For your security we recommend to install a STOP switch when
activated it stops immediatelly the gate. The switch has a N.C. opening in case is activated (as shown in par.
no. 3.7)
Dangerous
Damage
This is a warning and if it is not
For safety reasons, protect your
respec it can provoque material
face during the connection
damage
FILTER-S12
Option for CE Norms
-3-
START-S12-M Technical manual
Type of installation
The control board START-S12-M can be used for Industrial rapid doors and for sliding automation with
threephase motors (delta connection) up to 3 hp with ventilation systems.
fOTO A
Check the software version and compatibility with the operating manual
When the control unit is turn on, you can see 4 numbers in the display. This is the software number. We
suggest to check this number with the version on the manual. (see pic).
CODE
1602 START-S12-m
Vers. firmware 1602
-4-
START-S12-M Technical manual
1 2 3 4 5
6 7
FUSE 1
10 A
8 9 10 11
24 25 26 27
mF1
mF2
mF3
FR1
FR2
12 13 14 15 16 17 18 19 20 21 22 23
28 29 30
P1 P2 P3 Set the control unit mF1-2-3 Three-phases output for 230Vac motors delta connection
DIP not used FR1-2 Output for brake motor
JP1 Connector for temperature sensor LED WARNINg Indicates that the capacitors are still charged, be-
F1 fuses protection motor and power: 10A fore taking the central wait until the LED turns off.
F2 fused protection terminal boards (4, 5): 1.6A
F3 fuses for power supply for accessories and safeties: 200mA
The red led in the input LSO-LSC-STOP-PhOTO-UNFOLDINg EDgE are always lit on
The green led in the inputs OPEN-CLOSE-START are normally lit on
LSO LSC STOP PhOTO UNFOLDINg OPEN CLOSE START
WARNINg: If the inputs are desactivated from display with S13, S14, S15, S16, S17 red leds are SWITChED OFF
-5-
START-S12-M Technical manual
wiring
diagram
fIlTER RINg
CABlE MOTOR
OUTPUT
1 TURN ElECTRICAl
gROUND BAR
ShIElDED
CABlE
ENgINE
MOTOR
TERMINAl
MOTOR BOARD
-6-
START-S12-M Technical manual
Earth 1 Earth
230 Vac (N) 2 230 Vac 50Hz, power supply, neutral
230 Vac (L) 3 230 Vac 50Hz, power supply, phase
-7-
START-S12-M Technical manual
P.Fcc t23c
In this case the door is with closing limit switch and
that the heat temperature is 23°C.
- t-
Set up T
Set up of the Time
programming
- S- Set up S
Logic of the control unit
- L-
Set up L
Set up of the programm
(Speed, power...)
- r- Set up R
Activation of the outputs
Displays information
- E-
about the control unit
Set up E
Back to the standard functions
gO BACk SELf-RESET
+ To go back to the previous If the control unit is not used for more
group press P2 and P3 than one minute, the control unit go out
P2 P3
from the programming saving
programs and all changes.
-8-
START-S12-M Technical manual
You can read the information through a display: you can read if it is working properly, the manoeuvre counter
and the sink temperature. Some information can be shown only on the R function (see Chapter no.4)
- t- SYmBOlS
P1
Access to
the MENU
Press and Keep pressed Release
release
P2
- L- 1st Press
- S-
DOWN
2nd Press
- r- 3rd Press
P1 confirm
In the function R if you press P1, you can choose the group function: first select P2 and P3 and then confirm
with P1. Now you can go to the function R07, R08, R09 and R10
DOWN r 07 P1
Show the tension
in the capacitors
P1
r 08
P2
Show temperature
of the IgBT
P1 P1
r 09
Show the resistive
value in the
Safety edge input
P1 (terminal board no.20) P1
P3
r 10
UP Show the
cycle counters
(point indicated the
P1 thousands) P1
-9-
START-S12-M Technical manual
To save all changes it is possible to select a password of 4 numbers. To activate this function make as follow:
• PASSWORD ACTIVATION:
Press P1, P2 and P3 in the function S32 and then confirm with P1.
- t- P2
- S-
P1
Access to the menu 2nd press
P1 confirm
In the function S if you press P1, you can choose the group function: first select P2, now you can go to the
function S32 and then confirm with P1.
S 01
• INSERT PASSWORD
Choose the first number with the buttons P2 and P3 then
confirm with P1. The same procedure applies to the other
digits.
0---
P2 finished entering the 4 digit. Press P1 to confirm. To can-
cel press P1, within 10 seconds. Otherwise, the next ac-
cess will be required the security code.
S 32
P1 - OK
! Pay attention in case you forget
the password it is not possible to
enter in control board as well.
S 33
If you select the fucntion no. S33 you can cancel the password.
Wait 10 seconds to confi rm the operation.
P1 - OK
-10-
START-S12-M Technical manual
When you confirm the operation you can read the following message to cancel the operation. If you press P1
in 10 seconds, this operation will be cancelled.
344.2
If you read these number, it
means that the installation
has made 344200 cycles.
2.7 Desactivation of the cycle when the control panel wil be turned on
When the tension has been interrupted and you turn on the control board again it will make a new cycle. To
exclude this operation make as follow:
-11-
START-S12-M Technical manual
S12
230 Vac flAShINg
4 5 6 7 1 - Activated (standard)
0 - Deactivated
S 05
lAMP IN PAUSE
It is shown the connection of a 12 Vac lamp with or
1 - Activated
without flashing card. 0 - Deactivated (standard)
t 07
PRE -flAS hIN g TIME WhEN
ThE DOOR IS ClOSED
from 0 to 10 s
Standard value 0.5 s
t 08
PRE-flAShINg TIME
WhEN ThE DOOR IS OPEN
from 0 to 10 s
Standard value 2 s
-12-
START-S12-M Technical manual
20 21 22 23
S 15
STOP
1 - Activated
0 - Deactivated
S 22
SAFETY EDGE
1 - Activated (Standard)
0 - Deactivated
S 38
SAFETY EDGE contact
0 - NC contact
1 - 8K2 contact (Standard)
The picture shows the connection of both limit switches but you can connect it separately. You can use only
LSO or only LSC.
S 13
LSO
12 13 14 15 16 17 18 19 20 21 22 23
1 - Activated
0 - Deactivated
S 14
LSC
1 - Activated
!
0 - Deactivated
OPEN CLOSE
N.C. N.C.
-13-
START-S12-M Technical manual
12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Partial
OPENINg
It is possible to connect a timer in the terminal board no. 19 and 21 to program the opening time of the gates.
The contact of the timer should be normally open (N.O.) and it should be closed for all the time the gate is
open. If the conncection of opening command is available in the terminal board no 19, connect it in parallel.
!
Output + 12Vdc 60mA -28-
Output - 12Vdc 60mA -29-
PHOTO A when closing -30-
S 17
12 13 14 15 16 17 18 19 20 21 22 23 8 9 10 11 Input UNFOLDING
1 - Activated
0 - Deactivated
!
12 Vac
RX TX
If the input is not used,
set S17 at 0
NC Contact
-14-
START-S12-M Technical manual
TX
RX
12 Vac
NC Contact
TX
In case the photo-beam are not working pro-
RX perlym the control unit will lit on for 5 seconds
and the gate is not moving.
NC Contact
S 09 S 06
TEST in PHOTO OUTPUT TEST in the INPUT
1 - Activated safeties
0 - Deactivated 1 - Activated
0 - Deactivated
S 03
Photocell A deactivated If you set S03 it deactivates the PHOTO A after in-
1 - Activated tervention of slow down LS. If S03 is 1 the time of
0 - Deactivated function T11 is not considered
-15-
START-S12-M Technical manual
24 25 26 27
Common
Switch
OPEN CLOSE
S 20 S 21
Switch input when opening Switch input when CLOSING
1 - Activated (Standard) 1 - Activated (Standard)
0 - Deactivated 0 - Deactivated
Pay attention when you connect the brake and pay attention of the polarity. Program with S19 according to
the type of brake:
S 19
POLARITY OUTPUT OF THE BRAKE
0 - brake deactivate with tension (Standard)
1 - brake activate with tension
You can activate the INTERNAL BRAKE (S37), activating this function, the internal brake is activated for 2
seconds after engine shutdown.
S 37
INTERNALE BRAKE
1 - light decelaration 5 - no aceleration, no brake
2-
3- 6 - light braking
4 - high deceleration 7-
8-
9 - high braking
-16-
START-S12-M Technical manual
- t- - L- P2 - 1st press
- S-
P1 P2
Access to the functions
P2 - 2nd press
SYmBOlS
Press and
release
Keep pressed Release
- r- P2 - 3td press
In the function R if you press P1, you can choose the subfunction group fun-
ction: first select P2 and P3 and then confirm with P1. Now you can go to the
P1 confirm
function R01, R02, R03 ...
r 01
OPEN
with set up
DOWN acceleration
P1 P1
r 02
CLOSE
P2 with set up
P1 acceleration P1
r 03 P1
OPENINg
with slow down
P1
r 04 P1
CLOSINg
with slow down
P1
P3 UP
r 05 P1
Activate the LIghT
P1
r 06 P1
ACTIVATE
the TEST output
P1
r 11 P1
ACTIVATE
the BRAkE output
P1
-17-
START-S12-M Technical manual
5 Functions
S 01 1 Signal Reverse
By each START command inverts: OPEN-CLOSE
It recloses automatically
2 Automatic
The START command can open or recharge the pause
time. It recloses automatically
3 Bistable function
By each START command it follows: open-stop-close-
stop-open... It doesn’t recloses automatically
Stable function with
4 automatic reclosing
after pause time
By each START command it opens-stops-closes-
stops-opens... It recloses automatically after pause time
5 Signal reverse
+ Dead-man function
Same as function S01 - 1
OPEN and CLOSE with “Dead-man function“ function
6 Collective use
+ Dead-man function
Same as function S01 - 2
OPEN and CLOSE with “Dead-man function“ function
7 Bistable function
+ Dead-man function
Same as function S01 - 3
OPEN and CLOSE with “Dead-man function“ function
Bistable function with
Reclosing when
S 02 1 turning on
(Standard value 0)
Complete open and close. ONLY when the tension has
been interrupted when the gate is open.
S 04 1 It detects the passage The access will be detected from the photo-beams, if
(Standard value 0) S07 is 0 the pause time is 2sec.
It reverse in case
S 07 1 of access
(Standard value 1)
Put S04 in 1. When the gate is opening, the control unit
inverts the direction and close.
S 08 2 Obstacle Detection
(Standard value 2)
3 - Function as REVERSE and then STOP
4 - Automatic adjustment of motor torque, function L09 choose
the right function according to the motor installed
(not for sliding gates or safety devices).
-18-
START-S12-M Technical manual
T 01
T 12
T 03
T 02
T 04
T 11
t=0s
SET STANDARD
DESCRIPTION
UP - seconds -
T 01 Set up the fully opening time of the door/gate value from 0,1 s 4,0
T 02 Set up the opening time of partial opening value from 0,1 s 3,0
T 03 Set up the start position of OPEN decelerating time value from 0,1 s 2,0
T 04 Set up START position of the CLOSING deceleration time value from 0,1 s 1,0
Set up start position of deactivation of the photocelle.
T 11 value from 0,1 s 0,5
It is not considered if S03 is set in 1
Deactivation Time of the input SAFETY EDGE (term.S16) from starting
of LSO. This function is useful in case of anti-folding to avoid the unroll
T 12 1,0
of the curtain which can temporary cover the photocell and the door
will start opening again.
-19-
START-S12-M Technical manual
Are now given the parameters that allow you to set SPEED, ACCELERATION and ABSORPTION:
-20-
START-S12-M Technical manual
1 12 105 64.50
5 14.50 110 67.00
10 17.00 115 69.50
15 19.50 120 72.00
20 22.00 125 74.50
25 24.50 130 77.00
30 27.00 135 79.50
35 29.50 140 82.00
40 32.00 145 84.50
45 34.50 150 87.00
50 37.00 155 89.50
55 39.50 160 92.00
60 42.00 165 94.50
65 44.50 170 97.00
70 47.50 175 99.50
75 49.50 180 102.00
80 52.00 185 104.50
85 54.50 190 107.00
90 57.00 195 109.50
95 59.50 200 112.00
100 62.00
-21-
START-S12-M Technical manual
6 INTERLOCK Function
WARNINg: The TEST function and the PARTIAL OPENINg are not available in this function!!!
To activate the INTERLOCK function use function S35 and connect the 2 control units.
CONTROL BOARD A
When one con-
trol uniti is wor-
king, you can
see in the di-
S 35
splay FBUSS, INTERLOCK fUNCTION
and it cannot ac- 1 - Activated
cept other com- 0 - Deactivated
mands.
CONTROl
BOARD A
8 9 10 11
CONTROl
BOARD B
24 25 26 27
CONTROL BOARD B
CONTROl
BOARD B
8 9 10 11
CONTROl
BOARD A
24 25 26 27
-22-
START-S12-M Technical manual
The control panel allows users to restore parameters to their standard values (see par. 8) also allows you set
up the default factory settings of rapid doors (4.5 m - 3.5 m - 2.5 m) and sliding gates.
P1
- t- P2
- S-
Access to the functions 2nd press
S 01
P1 confirm
P2
S 18 P110
Wait 10 seconds, otherwise, if you press
P1 in 10 seconds, this operation will be
!
cancelled.
P1 - OK
WARNINg:
This operation
cancel all settings
-23-
START-S12-M Technical manual
The first paramenters are indicated for high speed doors, depending on the height of the door. The paramen-
ter no.4 is for industrial sliding gates.
S 27 S 28 S 29
Set up P1 Set up P1 Set up P1
STANDARD 1 STANDARD 2 STANDARD 3
STANDARD 1 - 2 - 3 (These parameters are the same for all 3 set up)
Set up Val. Set up Val. Set up Val.
L01 20 (13 Hz) L05 8 L09 11 [A]
L02 20 (13 Hz) L06 8 L10 15 [A]
L03 80 (50 Hz) L07 8 L11 50
L04 40 (25 Hz) L08 8
-24-
START-S12-M Technical manual
fOTO A2
T06 10,0 L06 4
T07 2,0 L07 4
for sliding gates T08 2,0 L08 4
T09 120,0 L09 3,0 [A]
T10 5,0 L10 5,0 [A]
T11 0,0 L11 70
T12 0,0
T13 1
T14 10
T15 0
T16 0
STARTS12 has 2 memory slots saving all manually set up and you can check it again. See how to check the
set up with functions S23, S24, S25, S26. Once all parameters are set up, it is possible to change.
Thanks of the 2 memory slots, it is possible to save and check 2 differents set up.
S 23 S 24
Press P1 Press P1
Save all set up Save all set up
MEMORY 1 MEMORY 2
S 25 S 26
Press P1 Press P1
Charge set up of Charge set up of
MEMORY 1 MEMORY 2
-25-
START-S12-M Technical manual
-26-
START-S12-M Technical manual
1 - Fast reverse
2 - Collective use
3 - Bistable function
4 - Bistable function with automatic reclosing
5 - Fast reversing and “Dead’s man“ function
6 - Collective use and “Dead’s man function
7 - Bistable funciton and “Dead’s man“ function
8 - Bistable function with automatic reclosing
and “Dead’s man“ function
S 22 Activate the input for SAFETY EDGE (terminal 20-21) 0 Deactivated - 1 Activated 1
-27-
START-S12-M Technical manual
SET
DESCRIPTION VALUES ACCEPTED STANDARD MEMO
UP
S 23 Copy set up of memory 1
1= light acceleration
4 = heavy acceleration
Integrated electric brake
S 37 5=neither acceleration nor braking 0
(activated for 2 seconds after motor stopping)
6= light braking
9= heavy braking
S 38 Safety edge - contact terminal board no.20-21 0: N.C. contact - 1: 8K2 contact 1
SET UP DESCRIPTION
R 01 Activate Opening until P1 has been released with acceleration set up
R 02 Activate CLOSING until P1 has been released with acceleration set up
R 03 Activate the OPENING until P1 has been released with slow down acceleration
R 04 Activate CLOSING until P1 has been released with slow down set up
R 05 Activate LIGHT/SIGNAL LIGHTH until P1 has been released
R 06 Activate TEST output until P1 has been released
R 07 Display the tension of the capacitors until P1 has been released
R 08 Display temperature of the IGBT until P1 has been released
R 09 Display the resistive value in the SAFETY EDGE input (terminal board no.20) until P1 has been released
R 10 Display the number of cycles number of cycles until P1 has been released (point indicated the thousands)
R 11 Activate the brake output
-28-
START-S12-M Technical manual
9 Problems
Here are listed some functions issue indicated in the display. You can see the causes and the procedure to
solve the issue.
Problem Description Solution
Er02
The overcurrent level of programm L10
OVERCURRENT in the MOTOR has been exceeded. If necessary incre-
ase the value.
Er03 Tension in the capacitors too low The tension in the capacitors is too
low. Check the network tension.
Er04
The control unit has an absorption of
Absorption at 1.5 A more than 1,5A even if the motor is not
when the motor is not working working. Check the accessories and
the motor.
Er07 Er17
Er27 Er67 Signal error of the encoder Check the encoder connections
Er77
Er57
The barriers doesn’t detect the cycle
of the door when the motor is powe- Check the curtains
ring.
-29-
START-S12-M Technical manual
.................................................................................................
10 Note
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
-30-
START-S12-M Technical manual
11 Declaration of CE conformity
(according to EC Directive 2006/42, Attachment II, part 1, ses. A)
Company: EB TECHNOLOGY SRL
The undersigned Ernestino Bandera, Address: Corso Sempione 172/5
Administrator 21052 Busto Arsizio VA Italy
Product’s name: START-S12-M
DECLARES THAT: Centrale Inverter 230Vac
THE PRODUCT COMPLIES with what is outlined in the European Community directive:
Reference: Attachment II, part 1, ses. A (EC Declaration of Conformity issued by the manufacturer).
THE PRODUCT COMPLIES with what is outlined in the European Community directives:
Reference to harmonized standards: ETSI EN 300 220-3 ETSI EN 301 489-1 ETSI EN 301 489-3
The directive 2006/42/CE remind that it is not allowed the function of the product until the machine, for which
the product is included, is not indentify and declared conformed to the 2006/42/CE directive.
-31-
START-S12-M Technical manual
Il sottoscritto, rappresentante il seguente The undersigned, representative of the fol- Le soussigné, représentant du constructeur
costruttore, dichiara che l’apparecchio de- lowing manifacturer, hereby certifies that the suivant certifie que les appareils ci-dessus
nominato equipment known as référencés
Der Unterzeichner bescheinigt, dass das El abajo firmante, representante el fabricante O abaixo-assinado, represendo o seguinte
Produkt siguiente, declara que el equipo denominado construtor declara que o aparelho denomi-
nado
-32-