Model: ACEGAFXR0551ML Date of Selection: 04/04/2024 / [Link]
Software Version: 4.06 Application Name: Voltas Chiller Selection Program
Customer : Engineer Name : admin
Project : SCREW CHILLER ISP/SSP :
Consultant : Location :
AIR COOLED EFFICIENT SCREW R134A Package Technical Specifications
Manufacturer: : VOLTAS LIMITED, INDIA Chiller Series: : ENERGY EFFICENT AC
Actual Capacity: : 56.2 Tons FLOODED CHILLER
Chiller Package Model: : ACEGAFXR0551ML Refrigerant:- : R-134a
Nominal Capacity: : 56.2 Tons
Additional Features required if any: Refer Annexure
Unit Operation Condition Evaporator
Fluid WATER
Fluid Inlet Temp °C 12.00
Fluid Outlet Temp °C 7.00
Fouling Factor M² °K/kW 0.0180
Ambient Temp °C 35.0
Altitude mtr 0.00
Chiller Performance Data at full load condition Evaporator
Fluid Flow Rate L/s 9.45
Fluid Pressure Drop Kpa 44.8
Capacity Tons 56.2 kW/Ton 1.063
Unit Power Consumption KW 59.7 COP (kW/kW) 3.310
Unit Operating Current Amp 103.88 EER (Btu/W-h) 11.290
Tolerance on above parameters as per AHRI Standard
Special Note :-
Part Load Performance at AHRI condition: Reducing Ambient Temperature(IPLV)
% LOAD AMBIENT CAPACITY INPUT IKW/TR FLOWRATE PRESSURE INLET OUTLET
TEMP. ( °C) (TR) POWER (KW) ( L/s) DROP ( Kpa) TEMP. ( °C) TEMP. ( °C)
100 35.0 56.20 59.70 1.0630 9.45 44.8 12.00 7.00
75 27.0 42.10 34.70 0.8240 9.45 44.8 10.75 7.00
50 19.0 28.10 23.00 0.8170 9.45 44.8 9.50 7.00
25 13.0 14.00 12.30 0.8780 9.45 44.8 8.25 7.00
[Link] (kW/Ton) = 0.8287 (COP) = 3.310 [Link] (COP) ((kW/kW)) = 4.244
Certified in accordance with the AHRI Air-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the
AHRI Directory at [Link]
Page 1 of 4
Model: ACEGAFXR0551ML Date of Selection: 04/04/2024 / [Link]
Software Version: 4.06 Application Name: Voltas Chiller Selection Program
Part Load Performance at AHRI condition: Reducing Ambient Temperature(NPLV)
% LOAD AMBIENT CAPACITY INPUT IKW/TR FLOWRATE PRESSURE INLET OUTLET
TEMP. ( °C) (TR) POWER (KW) ( L/s) DROP ( Kpa) TEMP. ( °C) TEMP. ( °C)
100 35.0 56.20 59.70 1.0630 9.45 44.8 12.00 7.00
75 27.0 42.10 34.70 0.8240 9.45 44.8 10.75 7.00
50 19.0 28.10 23.00 0.8170 9.45 44.8 9.50 7.00
25 13.0 14.00 12.30 0.8780 9.45 44.8 8.25 7.00
[Link] (kW/Ton) = 0.8287 (COP) = 3.310 [Link] (COP) ((kW/kW)) = 4.244
Certified in accordance with the AHRI Air-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the
AHRI Directory at [Link]
Chiller Package General Information
Voltage - Phase - Frequency (V-X-Hz) : 400V+/- 10% - 3Ph - 50Hz +/- 3%
Control Voltage (Volts) : 210-240 V
Minimum % capacity reduction :
Chiller Package Size (L x W x H, mm) : 3900 X 2236 X 2570
Approx Refrigerant Charge (kgs.) : 85
BMS Link : With MODBUS or BACNET Protocol
Start Mode : Star-Delta Standard
Shipping Weight (kgs.) : 3420
Operating Weight (kgs.) : 3550
Page 2 of 4
Model: ACEGAFXR0551ML Date of Selection: 04/04/2024 / [Link]
Software Version: 4.06 Application Name: Voltas Chiller Selection Program
Compressor Details
Type : Semi Hermetic Screw
Model : VLAF-03
RPM : 2950
Quantity Per Unit : 1
Oil Type : HBR-B08
Oil Charge (Lit), per Comp : 16
Unit Starting Current at 400V (Amps) : 285
Max. allowable operating current : 120
(Amps) at 400V, per Compressor
Evaporator and Condenser Details
Evaporator Condenser
Type Shell and Tube - Flooded
Model EF6AJ1R-2p 9AV35
Quantity Per Unit no. 1 4
No Of Passes no. 2 0
Water Connection Size NB 100
Additional Features
Part No: ACEGAFXR0551ML
Page 3 of 4
Model: ACEGAFXR0551ML Date of Selection: 04/04/2024 / [Link]
Software Version: 4.06 Application Name: Voltas Chiller Selection Program
Note: 1. Product development is a continuous process in Voltas, hence specifications and technical data subject to
alterations without notice.
2. Extended Capacity Models are available on request
Page 4 of 4