• System state monitoring: class 0.
2
• Energy metering: class 0.5S, up to 16 tariffs
• Remote communication via Modbus
• Assisted commissioning
• Configuration without power supply
SINEAX DM5S
Premium class
heavy-current transducer
Technical data
Inputs via screw terminals 6mm2 Ambient conditions, general information
Nominal current: adjustable 1...5 A Operating temperature: –10 up to 22 up to 24 up to +55°C
Maximum: 7.5 A (sinusoidal) Storage temperature: –25 up to +70 °C
Consumption: ≤ I2 x 0.01 Ω per phase Temperature influence: 0.5 x measurement uncertainty per 10 K
Overload capability: 10 A continuous Long term drift: 0.2 x measurement uncertainty per year
100 A, 10 x 1 s, interval 100 s Others: Usage group II (EN 60 688)
Relative humidity: < 95% no condensation
Nominal voltage: 57.7…400 VLN, 100...693 VLL
Altitude: ≤ 2000m max.
Maximum: 480 VLN, 832 VLL (sinusoidal)
Device to be used indoor only!
Consumption: ≤ U2 / 1.54 MΩ per phase
Impedance: 1.54 MΩ per phase Mechanical attributes
Overload capability: 480 VLN, 832 VLL continuous Dimensions (H x B x D): 110 x 70 x 70mm
600 VLN, 1040 VLL, 10 x 10 s, interval 10 s Orientation: Any
800 VLN, 1386 VLL, 10 x 1 s, interval 10 s Housing material: Polycarbonat
Nominal frequency: 45… 50 / 60 …65 Hz Weight: 500 g
Measurement TRMS: up to 31st harmonic Flammability class: V-0 acc. UL94, self-extinguishing,
non dripping, free of halogen
Systems Single phase
Split phase (2 phase system) Order code
3-wire, balanced load SINEAX DM5S, programmable, up to 4 analog outputs, Modbus/RTU, meters
3-wire, unbalanced load, phase shift No-go
3-wire, unbalanced load Blocking with
Features, selection code blocking
DM5S-
3-wire, unbalanced load, Aron connection
code
4-wire, balanced load
4-wire, unbalanced load 1 Basic device
4-wire, unbalanced load, Open-Y Without display, for rail mounting 0
2
2 Application
Power supply via screw terminals 6mm
Nominal voltage: 100…230 V AC ±15%, 50...400 Hz Universal version for all applications (3U,3I) 1
24...230 V DC ±15% Single phase, 3/4-wire balanced load (3U,1I) 2
Consumption: ≤ 8 VA Single phase or 4-wire balanced load (1U,1I) 3
3 Nominal frequency range
Analog outputs via plug-in terminals 2.5mm2, galvanically isolated
Linearization: Linear or kinked 45…50/60…65 Hz 1
Range: ± 20 mA (24 mA max.), bipolar 4 Power supply
Uncertainty: ± 0.1% (included in basic accuracy) Nominal voltage 24...230V DC, 100...230V AC 1
Response time (50Hz): ≤ 165 ms (for averaging time 4 cycles) 5 Bus connection
Burden: ≤ 500 Ω (max. 10 V / 20 mA)
Burden influence: ≤ 0.1% without A 0
Residual ripple: ≤ 0.2% RS-485 (Modbus/RTU protocol) 1
6 Outputs
Modbus/RTU via plug-in terminals 2.5mm2 without A 0
Physics: RS-485, max. 1200 m (4000 ft)
1 analog output, bipolar ±20mA 1
Baud rate: 2.4 up to 115.2 kBaud
Number of participants: ≤ 32 2 analog outputs, bipolar ±20mA 2
3 analog outputs, bipolar ±20mA 3
Configuration interface USB 4 analog outputs, bipolar ±20mA 4
Physics: USB, max. 3m 7 Test certificate
Connection: Socket USB-B
Device class: Human interface device (HID) Without test certificate 0
Test certificate in German D
Measurement uncertainty Test certificate in English E
Reference conditions: Ambient 23°C ±1K, sinusoidal, 8 Configuration
(acc. IEC/EN 60688) Measurement over 8 cycles, PF=1,
Frequency 50...60 Hz, burden 250 Ω Basic configuration 0
Voltage, current: ± 0.12% FSU / FSI 1) 2)
Power: ± 0.2% (FSU x FSI) 2)
Power factor: ± 0.1° 2)
Frequency: ± 0.01 Hz
Active energy: Class 0.5S, EN 62 053-22
Reactive energy: Class 2, EN 62 053-23
1)
FSU / FSI – Configured maximum value of voltage / current inputs
2)
Additional uncertainty if neutral wire not connected (3-wire connections)
• Voltage, power: 0.1% of measurement value; Load factor: 0.1°
Printed in Switzerland • Subject to change
• Energy: Voltage influence x 2, angle uncertainty x 2 Camille Bauer AG
Aargauerstrasse 7
Safety
CH-5610 Wohlen / Switzerland
SM-1032-000-01-EN-05.13
Current inputs are galvanically isolated from each other.
Protection class: II (protective insulation, voltage inputs via
Phone: +41 56 618 21 11
protective impedance)
Pollution degree: 2 Fax: +41 56 618 21 21
Protection rating: IP30 (housing), IP20 (terminals)
Overvoltage category: CAT III up to 600V
[email protected] www.camillebauer.com