0% found this document useful (0 votes)
94 views2 pages

2" Control Valve for Water Systems

Uploaded by

maneltechneaux
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
94 views2 pages

2" Control Valve for Water Systems

Uploaded by

maneltechneaux
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

WS2CI

WATER
SPECIALIST
CONTROL
VALVE

Certified to NSF/ANSI/CAN 61 and NSF/ANSI/CAN 372.

• 2” Top mount control valve suited for commercial/industrial applications


• Epoxy coated lead free brass valve body
• Economical stainless steel optional meter assembly
• Service flow rate of 435 lpm (26.1 m3/h) (115 gpm),
backwash 303 lpm (18.2 m3/h) (80 gpm)
• Solid state microprocessor with easy access front panel settings
• Front panel display for time of day, days until next regeneration,
volume remaining and current flow rate. Optional 2" Meter
• Four methods to initiate regeneration; meter immediate, meter delayed,
time clock delayed or pressure differential
• Program in ppm, French degrees, German degrees, or cubic meters
• Fully programmable regeneration cycle sequence (maximum 9)
• Programmable regeneration cycle times
• Days override feature; 1-28 days available
• Coin Cell Lithium battery back-up with an 24 hour carry over
• Level VI 15-volt output DC power supply provides safe and easy installation
• Pre or Post treated water regenerant refill
• 24 Hour Clock
• Reliable and proven DC drive
• One piece expanding seal spacer stack assembly
• Linearly reciprocating piston operation
Water Specialist 2” CI Control Specifications
Inlet/Outlet (1)............................................................................................ 2” Female BSPT or NPT
Cycles ....................................................................................................... Up to 9
Valve Material............................................................................................ Lead free brass
Regeneration............................................................................................. Downflow

CONTROL VALVE FLOW RATES


Service @ 1 bar/15 psi drop......................................................... 435 lpm (26.1 m3/h) (115 gpm)
Backwash @ 1.7 bar/25 psi drop................................................. 303 lpm (18.2 m3/h) (80 gpm)
Cv Service..................................................................................... 29.7
Cv Backwash................................................................................ 16.0
OPERATING PRESSURES
Minimum/Maximum...................................................................... 1.4 - 8.6 bar (20 psi - 125 psi)

OPERATING TEMPERATURES
Minimum/Maximum...................................................................... 4º - 43º C (40º - 110º F)

METER SPECIFICATIONS
Accuracy....................................................................................... ± 5%
Flow Rate Range........................................................................... 5.7 - 568 lpm (1.5 - 150 gpm)
Volume Range............................................................................... 0.02 - 5,700 m3
Totalizer......................................................................................... 1 - 99,999 m3
(264 - 26,417,000 gallons)

DIMENSIONS & WEIGHT


Distributor Pilot
Valve bodies with 2" Female BSPT Inlet & Outlet................ 50mm OD
Valve bodies with 2" Female NPT Inlet & Outlet.................. 1.90” OD (1.5" NPS)
Drain Line Connection.................................................................. 1.5” Female NPT
Brine Line Adapters Included....................................................... 1” Male NPT elbow,
¾” x 1” solvent weld elbow and
1
⁄2" OD Poly Tube Compression
Mounting Base.............................................................................. 4” - 8 UN
Height From Top Of Tank.............................................................. 216 mm (8.5”)
Shipping Weight With Meter........................................................ 13 Kg (29 lbs.)

ELECTRICAL SPECIFICATIONS POWER SUPPLY


U.S. International
Supply Voltage.................................................................... 100VAC to 120VAC.... 200VAC to 240VAC
Supply Frequency............................................................... 50/60 Hz..................... 50/60 Hz
Output Voltage.................................................................... 15VDC........................ 15VDC
Output Current.................................................................... 500 mA....................... 500 mA

TANK APPLICATIONS
Water Softener.............................................................................. 12” - 48” diameter
Water Filter (2)............................................................................... 12” - 36” diameter
CYCLES OF OPERATION
Choose up to nine regeneration cycles, in any order, with a wide range of available values:
Cycle Range of values
Backwash...................................................................................... 1 - 120 minutes
Rinse.............................................................................................. 1 - 120 minutes
Pause (service).............................................................................. 1 - 480 minutes
Brine (co-current).......................................................................... 1 - 180 minutes
Refill (softener).............................................................................. 0.1 - 99.0 minutes
Refill (filter).................................................................................... 0.1 - 99.0 minutes

Options: Backwash Filter, Weather Cover


Compatible with the following typical concentrations of regenerants or chemicals: Sodium chloride, potassium
chloride, potassium permanganate, sodium bisulfite, chlorine and chloramines
1. See Distributor Pilot
2. Filter tank size calculated @ 407 lpm per m2 of bed area /10 gpm of backwash per square foot of bed area

Form No. 2828 • 9/23/2021