HKIE Structural Exam 2022 Design Questions
HKIE Structural Exam 2022 Design Questions
Question Paper
Seat number:
Page 1
Question 1 Data Centre over Vehicular Tunnel
Client’s Requirements
1. A ten-storey data centre is to be constructed over a twin vehicular tunnel with a building
footprint of 55m x 84m. See Figure Q1a.
3. The overall width of the tunnel is 22m. A protection zone of 3m is required around the
tunnel. See Figure Q1b.
4. No structures are permitted in the protection zone, and any changes in stresses in any
directions to the tunnel should be limited to 20kPa.
5. For data equipment, a clear column spacing (between inner face of columns) shall be in
the multiples of 1.2m with a minimum column spacing of 12m, except a column free
space is required between the cores in the E-W direction with a clear span of 28.80m for
the flexibility to accommodate more advanced equipment in the future for data floors
1/F to 5/F inclusive.
6. Four lift/stair wells, with an internal dimension of 5m x 9.6m with opening facing the
data floor, are required to be provided for access at the perimeter of the building, which
should also be used for the provisions of all supporting utilities/facilities, in order to
maximize the open space of the data hall.
7. The ground floor is located at 5mPD. The building has an overall height restriction,
including plants of 82.5mPD. See Figure Q1b.
8. The floor to floor between the ground and the first floor is 8.5m, while that between the
other data floors is 6.5m.
9. A clear floor to ceiling height for the basement is 4.8m, while that for the ground and
data floor is 6.0m and 4.5m respectively.
Page 2
10. The following should be allowed for in the design of the building:
11. The plants will be located on the roof which is accessible, structures can be provided if
required, subject to height restriction.
Imposed Loads
12. The following imposed loadings should be adopted in the design. Other not specified
below should be in accordance with the Hong Kong Code of Practice for Dead and
Imposed Loads 2011.
• Superimposed Dead Load – Basement (1.5kPa), Ground Floor (5.0kPa) and Typical
Floor (3.0kPa), Roof (5.0kPa)
• Superimposed Live Load - Basement (15.0kPa), Ground Floor (10.0kPa) and Typical
Floor (20.0kPa) Roof (15.0kPa)
13. The Wind load should be in accordance with the Hong Kong Wind Code (2004 or 2019).
14. A deflection limit control of Span/360 shall be maintained for the Live Load, whilst the
limit can be relaxed to Span/240 for the total loads.
Page 3
Site Conditions
Section A
a. Prepare a design appraisal with appropriate sketches including two distinct and viable
solutions for the proposed data centre including two viable foundation systems.
Clearly indicate the functional framing, fire proofing, load transfer and stability aspects
of each scheme. Identify the solution you recommend and give reasons for your choice.
(30 marks)
b. Explain how the building structure will resist wind load including detailed description of
the structural wind frame(s), design assumptions and how the floor deflections are to be
checked and controlled.
(10 marks)
Section B
c. Prepare sufficient design calculations to establish the form and size of all the principal
structural elements including the foundations.
(20 marks)
Page 4
d. Prepare general detailed structural framing plans (typical floor, ground floor and
basement/foundation) to show the dimensions, layout, movement joints (if any),
disposition of the structural elements and critical structural details (including major
beam penetrations, if any) for estimating purposes.
(20 marks)
e. Prepare sufficient details of the critical elements / connections such as columns, beams,
column/beam, column/slab connections etc. reflecting the chosen design solution.
(10 marks)
f. Prepare a detailed project programme for the design and construction of the project
including a method statement for controlling the tunnel movements during
construction.
(10 marks)
Page 5
FIGURE Q1a
FIGURE Q1b
Page 6
Figure Q1
Question 2 Conversion of Factory Building to Office with Roof Top
Extension
Client’s Requirements
3. A new stair and lift core is to be constructed in the area bounded by grids B-C and grids
3-4. The existing stair and lift core, and the structures between grids D-E and grids 1-5 is
to be demolished from ground level up after the completion of the new extension and
the lift and stair core.
4. The proposed use of the new building with the minimum clear headroom, finishes &
E&M services zone and fire resistance rating is listed as follows:
Page 7
6. For the new extension above 9/F, the column to column spacing should not be more than
7.5m centre to centre.
7. The flat roof at 9/F outside of office as indicated on plan is for green landscape lawn with
planter soil 400mm thick and 200mm thick waterproofing and insulation layer.
Imposed Loads
8. The imposed loads shall be in accordance with the latest version of the Code of Practice
for Dead and Imposed Loads in Hong Kong, unless specified.
Wind Loads
9. The existing building was designed based on the Code of Practice on Wind Effects in Hong
Kong 1983.
10. According to APP117 of Practice Notes for AP/RSE (PNAP), the structural adequacy of an
existing building or part thereof, as may be affected by proposed A&A works may, subject
to the following requirements, be checked according to the then prevailing Building
Regulations and codes of practice to which they were designed:
(a) Wind Calculations
In the case of A&A works involving:
i. partial or total removal of existing major wind resisting walls or frames, which
would result in a reduction in their stiffness by 5% or more, or
ii. the extension of building dimensions which would result in an increase of 10%
or more of the wind exposure areas of a building, the structural adequacy of
the building due to wind should be checked based on the current wind code
(Code of Practice on Wind Effects in Hong Kong 2004 or 2019)
Site Conditions
11. The site is located at Kwai Chung New Territories and with flat ground level at +6.5mPD.
12. On the two sides of the site and separating by a lane of 3 m width, there are two 8
storeyed factory buildings with caisson foundation. The front and rear of the site are
streets of 6m width.
Page 8
13. Ground conditions:
From -8mPD – -20mPD Completely decomposed granite, SPT N-value > 200
15. Design for staircases, cladding, window systems, façade, protective barrier, and roof top
signboard is not required. However, the loading effect of these structures should be
considered.
16. Detailed layout and design of the non-structural elements inside the service core.
Section A
a. Prepare two distinct and viable solutions for the proposed conversion works including
viable schemes for lateral and gravity loads stability and provide your key consideration.
Clearly indicate the functional framing, load transfer and stability aspects of each scheme
to meet all client’s requirements. Identify the solution you recommend and give reasons
for your choice.
(30 marks)
b. Give a brief assessment on the effects of the proposed alterations and additions works
and suggest strengthening solution if necessary for the following.
1) The existing caisson foundation.
2) The existing beam-column frame after demolishing the structures between
grids D-E and grids 1-5 (portion B).
(10 marks)
Page 9
Section B
c. Prepare sufficient design calculations to establish the form and size of all the principal
structural elements for superstructure above 8/F, including transfer (if any) and critical
structures.
(10 marks)
d. Prepare dimensional framing plans and sections for superstructure above 8/F, to
show the general arrangement of the structural elements including transfer (if any) and
critical structures.
(25 marks)
e. Prepare the structural details for the principal structural elements at above 8/F
including transfer (if any) and critical structures for estimating purposes.
(10 marks)
f. Prepare a detailed method statement for the demolition of the existing structures.
(10 marks)
Page 10
Page 11
Page 12
FIGURE Q2-E
Page 13
FIGURE Q2-F
Page 14
Question 3 Office Building with Open Sky Garden
Client’s Requirements
1. An office building with open sky garden is to be constructed within the developed area of
Hong Kong. See Figure Q3.
2. This office building includes an upper block tower and a lower block tower of plan
dimension 28m x 28m and 37m x 37m respectively. An open skygarden is located at roof
of lower block tower with minimum headroom of 12 to 16m.
3. The proposed use of the office building with the minimum headroom requirements and
fire resistance rating is listed as follows:
Page 15
4. The restrictions on the location of vertical structural elements are as follows:
5. The main roof structure above upper tower shall not be inverted.
6. No intermediate horizontal supports or ties are permitted at the exposed columns at sky
garden level.
7. For cantilever structure (if any), maximum cantilever span to be less than 4.0m from
centre to centre.
Imposed Loads
8. The imposed loads shall be in accordance with the latest version of the Hong Kong Code
of Practice for Dead and Imposed Loads.
9. Superimposed dead load of 20 kPa should be allowed for the Sky Garden at 10/F.
Wind Loads
10. The wind loads shall be in accordance with the Code of Practice on Wind Effects in Hong
Kong 2004 or 2019.
Site Conditions
11. Adjacent to the eastern boundary of the site is a 5-storey religious building with shallow
footing foundation.
Page 16
12. Ground conditions:
From +6mPD to +2mPD Lose Fill, SPT average N-value = 10 [Category 4(d)]Note 1
Note 1: Categories of soil/rock refer to Table 2.1 of Code of Practice for Foundation 2017.
14. Detailed layout and design of the structure inside the service core.
Section A
a. Prepare a design appraisal with appropriate sketches including two distinct and viable
solutions for the proposed office building including two viable foundation schemes.
Indicate clearly the functional framing, load transfer and stability aspects of each scheme
to meet all client’s requirements. Identify the solution you recommend and give
reasons for your choice.
(30 marks)
b. Explain how the structure will resist wind load including detailed description of the
structural wind loads and design assumptions. Prepare a detailed wind load calculation
and stability checking for the proposed office building.
(10 marks)
Page 17
Section B
c. Prepare design calculations to establish the form and size of all principal structural
elements for superstructure from G/F to R/F including transfer structures, slender
columns and critical structures (if any).
(15 marks)
d. Prepare full dimensional framing plans for G/F, typical floors of lower and upper office
block, and all levels with transfer and critical structures (if any).
(20 marks)
e. Prepare structural details for the principal structural elements from G/F to R/F including
transfer and critical structures (if any), for cost estimation purpose.
(10 marks)
Page 18
MEZZANINE FLOOR PLAN
G/F PLAN
Figure Q3
Page 19
SKY GARDEN FLOOR PLAN
Figure Q3
Page 21
Page 22
SECTION A-A Figure Q3
Question 4 Highway Bridge
Client’s Requirements
1. A dual single lane existing bridge as shown in Figure Q4 has reached its capacity and needs
to be enhanced to cater for traffic flow across the two sides of the river and it is proposed
to build a new bridge alongside with the existing. The existing alignment of the bridge is
to be at a high point in the middle to allow for navigation channel. (see existing elevation
as shown).
3. The cross section of the new bridge is to have a two lanes carriageway with 1.0m of
marginal strip on the near side and 0.5m on the off side. No columns are permitted in
the navigation channel and 5.0m to the left and right of the existing column in elevation
and no movement joint is to be allow within the span of the new bridge.
4. The existing navigation channel is to remain in service as much as possible during the
construction of the new bridge. The channel may be closed between 10:00pm on
Saturday evening to 06:00am on the following Sunday morning.
6. Closure of one lane of highway for construction is allowed each night between mid night
and 06:00am.
Design Requirements
7. The structural design shall be in accordance with the latest version of the Structures
Design Manual for Highways and Railways published by the Highways Department of the
HKSAR Government.
Page 23
Imposed Loads
Wind Loads
9. The wind loads shall be in accordance with the requirements in the latest version of the
Structures Design Manual for Highways and Railways.
Site Conditions
10. The site is located at open area with Degree 3 of exposure to wind.
20m – 35m Very dense soil, SPT N-value >50{Category 4(d)} Note 1
35m and below Moderately decomposed granite with total core recovery >85%
{Category 1(c)} Note 1
Note 1: Categories of soil/rock refer to Table 2.1 of Code of Practice for Foundation 2017
12. Design against ship impact and calculations for railings and abutment for the proposed
bridge.
Section A
a. Prepare a design appraisal with appropriate sketches indicating two distinct and viable
solutions for the spans of the proposed highway bridge including two viable foundation
schemes. Indicate clearly the functional framing, load transfer and stability aspects of
each scheme to meet all client’s requirements. Identify the solution you recommend and
give reasons for your choice.
(30 marks)
Page 24
b. Explain how the structure will resist wind load including detailed description of the wind
loads and design assumptions. Prepare detailed wind load calculations for the proposed
highway bridge.
(10 marks)
Section B
c. Prepare sufficient design calculations to establish the form and size of all the principal
structural elements including the foundation.
(20 marks)
d. Prepare foundation plans and details, framing plans, sections and elevations to show the
dimensions, layout and disposition of the structural elements and critical details for cost
estimating purposes.
(20 marks)
e. Prepare a detailed method statement covering essential activities for the construction of
the superstructure and sub structures of the bridge including foundation works.
(10 marks)
Page 25
EXISTING CAP EXISTING CAP CL Bearing
CL Bearing CL Viaduct
CL Existing Pier CL Existing Pier existing
existing abutment
No column zone EXISTING BRIDGE abutment
4.0
C
L Bearing CL Bearing
PROPOSED BRIDGE
proposed abutment proposed
navigation channel
abutment
PLAN
No column zone
38.0 55.0 38.0
CL Bearing CL Exisiting Pier C
L Viaduct CL Exisiting Pier CL Bearing
Existing Abutment R50.0 Existing Abutment
0.3 +18.56 mPD
+15.35 mPD 4.9 % gradient 4.9 % gradient
+15.35 mPD
+0 mPD
LONGITUDINAL ELEVATION
for EXISTING BRIDGE
1.0 0.5
Marginal CL Viaduct Marginal
0.5 Strip 3.65 3.65 Strip 0.5
Carriageway Carriageway
barrier barrier
surfacing
2.5% fall road level 2.5% fall
0.1 min
Client’s Requirements
1. A new covered grand stand is proposed to be built at a coastal area with ground level at
+6mPD as shown in Figure Q5a.
3. The minimum clear headroom of the roof is 20m measured from the ground level.
6. Occasional above ground structural elements for overall stability of structure can be built
outside the footprint of the grand stand with a 5m zone at the rear and 10m zones on
both shorter sides as shown in Figure Q5b.
7. For completely unobstructed view towards the football pitch, columns will not be allowed
along the front edge of the grand stand or within the seating or corridor areas.
8. The minimum column spacing along the length of the grand stand shall be 20m from
centre to centre.
9. No foundation (including pile caps) shall be constructed within 1.5m below the ground
level and built outside the site boundary.
10. At least 25% area of the roof should be glazed for natural lighting.
Imposed Loads
Wind Loads
13. The wind loads shall be in accordance with the Code of Practice on Wind Effects in Hong
Kong 2004 or 2019.
Page 27
Site Conditions
Section A
a. Prepare a design appraisal with appropriate sketches indicating two distinct and viable
solutions for the proposed grand stand including two viable foundation schemes.
Clearly indicate the function framing, load transfer and stability aspects of each scheme
to meet all client’s requirements. Identify the solution you recommend and give
reasons for your choice.
(30 marks)
b. Explain how the structure will resist wind loads including detailed description of the wind
loads and design assumptions. Prepare detailed wind load calculations for the proposed
grand stand.
(10 marks)
Section B
c. Prepare sufficient design calculations to establish the form and size of all the principal
structural elements including the foundation. In calculation of wind loads,
considerations on torsional forces and cross-wind base moment and dynamic effect are
not required.
(20 marks)
d. Prepare framing plans, sections and elevations to show the dimensions, layout and
disposition of the structural elements and critical details and foundation plan for cost
estimation purpose.
(20 marks)
Page 28
e. Prepare a detailed method statement covering essential activities for the safe
construction of the grand stand including foundation works.
(10 marks)
Page 29
Figure Q5a
Figure Q5b
Page 30
Figure Q5
Figure Q5c
Page 31
End of Question Paper
Figure Q5