Project : HMU Date : 10/28/2024
Owner : MoH Pharmaceutical & Medical Equipment WH Column : C2
Location : VTE, Lao PDR Floor :
Column-Tied Design
Constant :
Yeild Stress, fy (ksc) = 3,000
Allowable Stress of Steel, fs (ksc) = 1,200 B = 0.2 m.
Comp. Stress of Concrete, fc' (ksc) = 240
DRAWING
T = 0.2 m.
Input : x
Column Width, Bx (m) = 0.20
Column Long, Ty (m) = 0.20
Column Length, L (m) = 2.89
y
Column Load, Pcol (Tons) = 1.17
Main Bars Design: Main Bars : 4 - DB12 mm.
Ratio L/B = 14.44 Stirrup : RB9 mm. @ 0.192 m.
Type of Column = Short Col.
Reduction Factor : R = 1.00
Pcon=R(0.85*Ag*0.25*fc') (Tons) = 20.40
Psteel = Pcol-Pcon (Tons) = -
As (cm2) = -
4 6 8 10 12
As (cm2) % As (cm2) % As (cm2) % As (cm2) % As (cm2) %
RB12 4.52 1.13% 6.79 1.70% 9.05 2.26% 11.31 2.83% 13.57 3.39%
DB12 4.52 1.13% 6.79 1.70% 9.05 2.26% 11.31 2.83% 13.57 3.39%
RB15 7.07 1.77% 10.60 2.65% 14.14 3.54% 17.67 4.42% 21.21 5.30%
DB16 8.04 2.01% 12.06 3.02% 16.08 4.02% 20.11 5.03% 24.13 6.03%
RB19 11.34 2.84% 17.01 4.25% 22.68 5.67% 28.35 7.09% 34.02 8.51%
DB20 12.57 3.14% 18.85 4.71% 25.13 6.28% 31.42 7.86% 37.70 9.43%
DB25 19.63 4.91% 29.45 7.36% 39.27 9.82% 49.09 12.27% 58.90 14.73%
DB28 24.63 6.16% 36.95 9.24% 49.26 12.32% 61.58 15.40% 73.89 18.47%
DB32 32.17 8.04% 48.25 12.06% 64.34 16.09% 80.42 20.11% 96.51 24.13%