Plant-Tech Arabia Co.Ltd.

Inspection Tracking Plan (ITP)


Client Name SIPCHEM ITS No PTA-ITP-SP-02 Revision No 0 Date 14/Oct/24

Project Code Responsible Prepared By Reviewed By Accepted By

Drawing #. Designee SIPCHEM INSPECTION TEAM

Equipment # /Package # Name

Descrption Signature

A=Approval, H=Hold Pont, I=Information, M=Monitor, R=Document Review, S=Surveillance, W=Witness, Indicates revision

VERIFYING DOCUMENTS INSPECTION ACTIVITIES BY


EXAMINATION & INSPECTION TECHNICAL DOCUMENTS
Sl#
ACTIVITIES (if applicable)
SIPCHEM SIPCHEM
SIPCHEM
ACCEPTANCE CRITERIA RECORD / REFERENCE PLANT TECH QC OPERATION / INSPECTION REMARKS
MAINTENANCE
PROCESS TEAM

DOCUMENTS REVIEW

1 Review & Approval of Inspection & Test Plan. Approved Drawings Approved drawings Shop Drawings R NA NA R/A

2 Approval of method statement As per Scope of Work R R/A NA R/A

3 Design and Drawings Approved Drawings Approved drawings Shop Drawings R NA NA R

4 Material Approval Design Specification Approved Material submiitals MTC/Data sheet H R NA R

5 Lifting Plans As per Sipchem procedure Rigging Plan H R/A NA R

MATERIAL RECEIVING (REMOVAL OF FIELD INSTRUMENTS)

Removal & Disconnection of Temperature


6 Approved drawings Approved drawings Scope of work H NA NA H
Transmitter & Temperature Element

Removal of Pressure Gauges & Temperature


7 Approved drawings Approved drawings Scope of work H NA NA H
Gauges

Removal & Disconnection of Pressure


8 Approved drawings Approved drawings Scope of work H NA NA H
Transmitters

Page 1 821659066.xlsx
A=Approval, H=Hold Pont, I=Information, M=Monitor, R=Document Review, S=Surveillance, W=Witness, Indicates revision

VERIFYING DOCUMENTS INSPECTION ACTIVITIES BY


EXAMINATION & INSPECTION TECHNICAL DOCUMENTS
Sl#
ACTIVITIES (if applicable)
SIPCHEM SIPCHEM
SIPCHEM
ACCEPTANCE CRITERIA RECORD / REFERENCE PLANT TECH QC OPERATION / INSPECTION REMARKS
MAINTENANCE
PROCESS TEAM

9 Removal & Disconnection of Control Valve Approved drawings Approved drawings Scope of work H NA NA H

10 Removal & Disconnection of On-Off Valve Approved drawings Approved drawings Scope of work H NA NA H

Removal & Disconnection of Flowmeter


11 Approved drawings Approved drawings Scope of work H NA NA H
Coriolis

Proper Tagging and Identification Shall be


12 Approved drawings Approved drawings Approved drawings H NA NA H
placed in the Field

Approved Procedure /
Visual Inspection of all Removed field
13 Manufacturer Approved drawings Project specs / Standards H NA NA H
Instruments for any damage
Recommendations.

Approved Procedure /
14 Handling, Tagging, Storage & Preservation Manufacturer Approved MRIR Project specs / Standards H NA NA R/A
Recommendations.

RE-INSTALLATION OF FIELD INSTRUMENTS

Installation & Re-connection of Temperature Approved Drawings, Visual check


15 RFI & Checklist Scope of work H M W H
Transmitter & Temperature Element satisfactory

Installation of Pressure Gauges & Temperature Approved Drawings, Visual check


16 RFI & Checklist Scope of work H M W H
Gauges satisfactory

Installation & Re-connection of Pressure Approved Drawings, Visual check


17 RFI & Checklist Scope of work H M W H
Transmitters satisfactory

Approved Drawings, Visual check


18 Installation & Re-connection of Control Valve RFI & Checklist Scope of work H M W H
satisfactory

Approved Drawings, Visual check


19 Installation & Re-connection of On-Off Valve RFI & Checklist Scope of work H M W H
satisfactory

Installation & Re-connection of Flowmeter Approved Drawings, Visual check


20 RFI & Checklist Scope of work H M W H
Coriolis satisfactory

Page 2 821659066.xlsx
A=Approval, H=Hold Pont, I=Information, M=Monitor, R=Document Review, S=Surveillance, W=Witness, Indicates revision

VERIFYING DOCUMENTS INSPECTION ACTIVITIES BY


EXAMINATION & INSPECTION TECHNICAL DOCUMENTS
Sl#
ACTIVITIES (if applicable)
SIPCHEM SIPCHEM
SIPCHEM
ACCEPTANCE CRITERIA RECORD / REFERENCE PLANT TECH QC OPERATION / INSPECTION REMARKS
MAINTENANCE
PROCESS TEAM

Approved Drawings, Visual check


21 Install appropriate steel tags on all instruments. RFI & Checklist Scope of work H M W H
satisfactory

Install all required accessories for installation


including Instrument mounting stanchions,
impulse tubes and connections for process hook- Approved Drawings, Visual check
22 RFI & Checklist Scope of work H M W H
ups and conduit connections with associated satisfactory
accessories as mentioned in the instrument
installation detail drawings.

Approved Drawings, Visual check


23 Instrument tubing RFI & Checklist Scope of work H M W H
satisfactory

Conduct a pressure test for all new and Approved Drawings, Visual check
24 RFI & Checklist Scope of work H M W H
modified instrument tubing/ piping satisfactory

PRE-COMMISSIONING

Function Test / Loop Check of Temperature Method statement / Project


25 Approved Drawing / P&ID. Test Package. H W W NA
Transmitter Specifications

Function Test / Loop Check of Pressure Method statement / Project


26 Approved Drawing / P&ID. Test Package. H W W NA
Transmitter Specifications

Method statement / Project


27 Stroke check / Function Test for Control Valve Approved Drawing / P&ID. Test Package. H W W NA
Specifications

Page 3 821659066.xlsx
A=Approval, H=Hold Pont, I=Information, M=Monitor, R=Document Review, S=Surveillance, W=Witness, Indicates revision

VERIFYING DOCUMENTS INSPECTION ACTIVITIES BY


EXAMINATION & INSPECTION TECHNICAL DOCUMENTS
Sl#
ACTIVITIES (if applicable)
SIPCHEM SIPCHEM
SIPCHEM
ACCEPTANCE CRITERIA RECORD / REFERENCE PLANT TECH QC OPERATION / INSPECTION REMARKS
MAINTENANCE
PROCESS TEAM

Method statement / Project


28 Function Test of On-Off Valve Approved Drawing / P&ID. Test Package. H W W NA
Specifications

Method statement / Project


29 Function Test of Flow meter Coriolis Approved Drawing / P&ID. Test Package. H W W NA
Specifications

Compiling of QA/QC records & ALL INSPECTION REPORTS / SCOPE OF WORK.ALL


30 Inspection reports H NA NA H
ITP close out CHECKLIST INSPECTION DOCUMENTS

Remarks:

Page 4 821659066.xlsx