UM SE5001A v1.1
UM SE5001A v1.1
SE5001A
Serial Device Server
User’s Manual
v. 1.1
April 2017
Important Announcement
The information contained in this document is the property of Atop Technologies, Inc. and is supplied for the sole
purpose of operation and maintenance of Atop Technologies, Inc. products. No part of this publication is to be used
for any other purposes, and it is not to be reproduced, copied, disclosed, transmitted, stored in a retrieval system, or
translated into any human or computer language, in any form, by any means, in whole or in part, without the prior
explicit written consent of Atop Technologies, Inc., offenders will be liable for damages. All rights, including rights
created by patent grant or registration of a utility model or design, are reserved.
Disclaimer
We have checked the contents of this manual for agreement with the hardware and software described. Since
deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual is
reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for improvement
are welcome. All other product names referenced herein are registered trademarks of their respective companies.
Published by
Atop Technologies, Inc.
2F, No. 146, Sec. 1, Tung-Hsing Rd.
Taiwan, R.O.C.
Tel: 886-3-5508137
Fax: 886-3-5508131
www.atop-tech.com
www.atoponline.com
Copyright © 2017 Atop Technologies, Inc. All rights reserved. Technical data is subject to change. All other product
names referenced herein are registered trademarks of their respective companies. This document is intended to
provide customers with brief descriptions on the product and to assist customers to get started. For detail
information and operations of the product, please refer to the manual in the CD attached.
User Manual Version 1.1
SE5001A Serial Device Server
1 Introduction ....................................................................................................... 4
1.1 SE5001A Series Comparison ........................................................................................ 4
1.2 Packaging ..................................................................................................................... 5
1.3 Application Connectivity ................................................................................................ 6
5 Diagnostics ......................................................................................................64
5.1 Using Standard Ping Command .................................................................................. 64
5.2 Using Device Management Configuration Utility .......................................................... 65
Appendix ....................................................................................................................66
Specifications .................................................................................................................... 66
Upgrade Procedures ......................................................................................................... 67
Error Messages................................................................................................................. 69
Emergency Firmware Recovery ........................................................................................ 70
2
User Manual Version 1.1
SE5001A Serial Device Server
Preface
Purpose of the Manual
This manual supports you during the installation and configuring of the SE5001A Ethernet Serial Server only, as well
as it explains some technical options available with the mentioned product. As such, it contains some advanced
network management knowledge, instructions, examples, guidelines and general theories designed to help users
manage this device and its corresponding software; a background in general theory is a must when reading it.
Please refer to the Glossary for technical terms and abbreviations (if any).
Warranty Period
We provide a 5 year limited warranty for SE5001A Ethernet Serial Server.
FCC WARNING
Class A for Serial Device Server (Model SE5001A)
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15
of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment uses, generates and radiates radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference
to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expenses.
A shielded-type power cord is required in order to meet FCC emission limits and also to prevent interference to the
nearby radio and television reception. It is essential that only the supplied power cord be used.
Use only shielded cables to connect other devices to this equipment by RS-232 or RS-485 ports.
Be cautioned that changes or modifications not expressly approved by the party responsible for compliance could
void ones’ authority to operate the equipment.
3
User Manual Version 1.1
SE5001A Serial Device Server
1 Introduction
The SE5001A Ethernet Serial device server acts as a gateway between Ethernet (TCP/UDP) and
RS-232/RS-422/RS-485 communications. The information transmitted by SE5001A is transparent to both host
computers (Ethernet) and serial devices (RS-232/RS-422/RS-485). Data coming from the Ethernet is sent to the
designated RS-232/RS-422/RS-485 port and data received from RS-232/RS-422/RS-485 port is sent to the
Ethernet transparently allowing bidirectional communication.
In the computer-aided manufacturing or industrial automation areas, SE5001A is used by field devices to directly
connect to an Ethernet network. The user can then use a network application or use Virtual COM software to
simulate a virtual com port in the PC to fetch serial data from SE5001A remotely over Ethernet.
With SE5001A, it is possible to communicate with a remote serial device in the LAN or even in the Internet, which
dramatically increases reach in distance and scalability.
4
User Manual Version 1.1
SE5001A Serial Device Server
1.2 Packaging
Optional Accessories
Name Part Number Description
DK-25 30200000000022G DIN-Rail Kit
ADP-DB9(F)-TB5 59906231G Female DB9 to Female 3.81mm TB5 Converter
Y-Type (BT1-10V) power adaptor, 100-240VAC input, 1.25A @ 12VDC
US315-12(US-Y) 50500151120009G
output, US plug
Y-Type (BT1-10V) power adaptor, 100-240VAC input, 1.25A @ 12VDC
USE315-12(EU-Y) 50500151120019G
output, EU plug
5
User Manual Version 1.1
SE5001A Serial Device Server
TCP Server Mode:SE5001A can be configured as a TCP server in a TCP/IP Network to listen for an incoming
TCP client connection to a serial device. After the connection is established between the serial device server and
the host computer, data can be transmitted in both directions. This also applies to Virtual COM running in the server
mode.
6
User Manual Version 1.1
SE5001A Serial Device Server
7
User Manual Version 1.1
SE5001A Serial Device Server
UDP Mode
UDP is a faster but connectionless network protocol. It does not guarantee the delivery of network datagrams.
SE5001A can be configured to transfer data using unicast or multicast UDP from the serial device to one or multiple
host computers. Data can be transmitted between serial device and host computer in both directions.
8
User Manual Version 1.1
SE5001A Serial Device Server
Tunneling Mode
In the case that the serial device needs to communicate with each other without a host computer, two SE5001As
can be paired together (pair connection) to communicate over TCP or UDP transparently. The serial device would
be unaware of the change in the communication medium.
9
User Manual Version 1.1
SE5001A Serial Device Server
2 Getting Started
2.1 Panel Layout
10
User Manual Version 1.1
SE5001A Serial Device Server
Pin# RS-232 Full Duplex 2-Wire RS-485 Half Duplex RS-422/4-Wire RS-485 Full Duplex
Pin# RS-232 2-Wire RS-485 Half Duplex RS-422/4-Wire RS-485 Full Duplex
1 RxD NC T+
2 CTS NC T-
3 TxD DATA+ R+
4 RTS Data- R-
5 SG (Signal Ground) SG (Signal Ground) SG (Signal Ground)
11
User Manual Version 1.1
SE5001A Serial Device Server
2. RJ45 Connector.
One can choose either 568A or 568B definition. If one wants to make a crossover cable, one should use 568A and
568B definition respectively in each terminal of a UTP cable.
Note: Note: Reverse polarity protection is available in SE5001A, so VIN+ and VIN- could be reversed.
12
User Manual Version 1.1
SE5001A Serial Device Server
2.3 Buzzer
“ ^ “: Beep twice
“ = “: Beep off
Message Description
^===^===^===^===^===^===^... (1sec) Watchdog problem, return service is required
^^^^^^^^^^^^^^^^^^^^^^^... Memory problem, return service is required
^==^========^^ (5sec) Startup OK but AP firmware is disabled
^==^========^^^ (5sec) Startup OK and AP firmware is enabled
Table 1. Buzzer Message
2.4 LED
Name Color Status Description
PWR Green On Device is powered on
Off Power is not connected
RUN Green On AP firmware is disabled
Blinking AP firmware is running
Off Kernel firmware is damaged
LAN Green On Ethernet is connected
Blinking Data is transmitting
Off Ethernet is disconnected
COM Green Blinking Data is transmitting
(Tx/Rx) Off Data is not transmitting
13
User Manual Version 1.1
SE5001A Serial Device Server
3 Software Setup
SE5001A Ethernet Serial device server is shipped with default settings shown in the following table:
14
User Manual Version 1.1
SE5001A Serial Device Server
SE5001A could be configured by Serial Manager, for more information, refer to Serial Manager’s manual.
You can use a Telnet utility to change configuration settings of SE5001A by following steps:
->Telnet to SE5001A using command “telnet IP_address”. (For example:”telnet 10.0.50.100” in MS-DOS
command prompt window). After telnet into SE5001A, system will prompt for a password, the default password is
“default”. (Figure 3.1)
Note: Press the default button of SE5001A to reset the password to the default value.
15
User Manual Version 1.1
SE5001A Serial Device Server
1. After verifying the password, the following terminal screen appears (Figure 3.2).
Note
1. If SE5001A does not receive any commands within 1 minute, Telnet connection will terminate automatically.
2. After “0. Exit” is selected; the console will ask the user to save the configurations.
3. Changes to networking parameters will take effect only SE5001A is restarted.
->Select “1” from “Input choice and enter (0~4):” to enter “Overview” (Figure 3.3):
16
User Manual Version 1.1
SE5001A Serial Device Server
3.2.2. Networking
Select “2” from “Input choice and enter (0~4):” to enter Networking page as following (Figure 3.4):
17
User Manual Version 1.1
SE5001A Serial Device Server
This page includes the option to configure different COM1 parameters, including link mode, serial port settings,
serial buffer, packet delimiter, and advanced control commands.
18
User Manual Version 1.1
SE5001A Serial Device Server
Type 1 (Link Mode) from “Input choice and enter (1~4):” of COM1
To Enable IP filter:
Input y in the “Do one want to enable IP filter(y/n)?” to enable IP Filter. Otherwise input n.
Input idle time in “Please input idle time to send TCP alive packet(x*10sec):”(ex. Input 2 to change the
sending TCP keep alive packet period to 20 sec)
Note:
1. IP filtering function is disabled if setting FILTER_IP to “0.0.0.0”.
2. IP filter is disabled by default
3. If IP filter is enabled, only source IP assigned can connect to SE5001A’s COM.
4. If the multi-connection firmware is installed, SE5001A will prompt for “Multi_Port”, meaning multiple
19
User Manual Version 1.1
SE5001A Serial Device Server
connection
Select TCP connection behavior: 1 for connect always, 2 for connect on serial data
If 2 is selected, console will prompt for additional configurations.
Input idle time to disconnect in the “Please input idle time to disconnect(0sec , 1~255):” (Input 0
to disable; Input 2 to disconnect TCP connection after 2 seconds of serial Inactivity)
Input error retrying time in “Please input waiting time for error retrying(0 minute,1~255):” (Input 0
to disable; Input 2 to try to connect to a TCP Server every 2 minutes)
Input idle time in “Please input idle time to send TCP alive packet(x*10sec):”(Input 2 to the send TCP
keep alive packet every 20 seconds)
20
User Manual Version 1.1
SE5001A Serial Device Server
Input SE5001A’s local listening port in the “Please input local port:”
Input remote device’s listening port in the “Please input Destination port:”
21
User Manual Version 1.1
SE5001A Serial Device Server
22
User Manual Version 1.1
SE5001A Serial Device Server
23
User Manual Version 1.1
SE5001A Serial Device Server
Type 2 from “Input choice and enter (1~4):” of COM1, the following screen appears. It is possible to give the COM
port alias name, set the baud rate and parity, determine number of data bit and stop bit, and the type of flow control
to use here (Figure 3.12).
24
User Manual Version 1.1
SE5001A Serial Device Server
Type 3 from “Input choice and enter (1~4):” of COM1, by default COM port serial buffer is enabled meaning that
once a TCP connection is established, old serial data received from serial device before the connection will be
emptied. If this option is disabled, SE5001A will keep old serial data when the connection is broken (Figure 3.13).
25
User Manual Version 1.1
SE5001A Serial Device Server
Another kind is character delimiter. If the character delimiter is set to 0x0d, this means SE5001A will send out all the
serial data in buffer in one packet over Ethernet only if it reads 0x0d. The following figure shows how to configure
character delimiter:
(Figure 3.15)
26
User Manual Version 1.1
SE5001A Serial Device Server
Type 1 from “Input choice and enter (0~2):” to back up the settings from the EEPROM to the Flash.
SE5001A would then show “EEPROM Backup (Yes)”.
Type 2 from “Input choice and enter (0~2):” to erase the settings stored in the Flash. SE5001A would
then show “EEPROM Backup (No)”.
27
User Manual Version 1.1
SE5001A Serial Device Server
It is also possible to modify various settings through the web server interface. To do so, please follow the steps
below.
3.3.1. Log in to the System
1. After opening the web browser, ex. Microsoft IE, Firefox or any other web browser, enter the IP address of
SE5001A in the URL bar. Example: http://10.0.50.100
2. The following authentication screen should appear. Enter the user name and password then click on “OK
/ Log in”. The default user name is admin and password is default.
28
User Manual Version 1.1
SE5001A Serial Device Server
29
User Manual Version 1.1
SE5001A Serial Device Server
Enable SNMP and Alert Events by checking “Enable” (Figure 3.20). Fill in SNMP information in the fields under the
SNMP header. Enable different Alert Events to send these events to a SNMP Trap Server.
Cold/Warm Start: Triggers when the device is rebooted from the application level or physical level.
Link Down: Triggers when the TCP connection of the designated COM port is closed
Link Up: Triggers when the TCP connection of the designated COM port is established
Authentication Failure: Triggers when the username/password entered in the Telnet console or the WebUI is
incorrect.
After all the settings are entered, please click on the “Save Configuration” button to save the changes. Note that
the settings would become active only after SE5001A is restarted.
30
User Manual Version 1.1
SE5001A Serial Device Server
Please enter the old password in the “Old Password” field and enter the new password in the “New Password” and
the “Verified Password” fields. Then click on the “Save Configuration” to save and apply the new password.
Note: Press the reset button next to the RJ-45 Jack to reset the settings back to the default value.
31
User Manual Version 1.1
SE5001A Serial Device Server
This backup function could recover settings from the Flash to the EEPROM if the settings in the EEPROM are lost. If
SE5001A detects that there is an EEPROM backup in the flash. It will compare the backup values in the Flash and
EEPROM. If the values do not match, it will write the backup settings in the Flash to the EEPROM. To enable this
function, follow Figure 3.21 in the Security Settings.
Click on Backup EEPROM to back up the settings from the EEPROM to the Flash. SE5001A would then
show Have Backup.
Click on Erase Backup to erase the settings stored in the Flash. SE5001A would then show No Backup.
SE5001A supports different Link Modes, which are TCP Server, TCP Client, and UDP (Figure 3.22). Under the three
Link Modes, TCP Server can support Virtual COM, Pair Connection, or Reverse Telnet applications. TCP Client can
support Virtual COM or Pair Connection application. If none of the application is enabled, the SE5001A will run in
RAW mode. In the upcoming sections, we will discuss how to setup different Link Modes properly.
SE5001A defaults in TCP Server mode, there are additional connection settings that can be configured (Figure 3.23).
By selecting the TCP Server mode, a TCP Client program should be prepared to connect to SE5001A.
Click on the “COM1” link on the left hand side.
Select TCP Server. TCP Server is the default link mode.
Enter the Local Listening Port. This is the port specified in the TCP Client program connecting to the serial
device server. The default local port is 4660.
IP Filter: Only the designated IP address will be able to access the COM port if this option is enabled. This
option is disabled by default.
TCP Keep-Alive: Specify the interval in the “Idle Time Before Sending TCP Alive Packet” to force
SE5001A to send TCP Keep-Alive packets in the set interval to prevent disconnection from the client. Note
that this field has a multiplier of 10, so the default value 4 means to send Keep-Alive packets every 40
seconds.
TCP Inactivity Timeout: Specify the value in “TCP Inactivity Time Before Disconnect” to force SE5001A
actively close a TCP connection after some specific inactivity time (no packets). The default value is 0,
which means the SE5001A would never actively close an established connection.
32
User Manual Version 1.1
SE5001A Serial Device Server
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
Go to the Application Configuration section starting from 3.3.9 to apply Virtual COM, Pair Connection, or
Reverse Telnet application if applicable. Otherwise go to the COM Configuration (section 3.3.19) for serial
settings directly.
33
User Manual Version 1.1
SE5001A Serial Device Server
By selecting the TCP Client mode, it means that a TCP Server program should be prepared to connect to SE5001A.
Figure 3.24 shows all the settings provided for the TCP Client.
Click on the “COM1” link on the left hand side.
Select TCP Client.
Enter the preferred Destination IP and Port. This should match the IP settings of the TCP Server program.
Connect Rule: Decide how SE5001A should connect to the TCP Server here. If SE5001A should always
keep the connection, select TCP Connect on Power-on. This means SE5001A would connect to the TCP
Server program when SE5001A is powered on. By default, TCP Connect on Any Serial Character is
selected. This means that SE5001A would only connect to the TCP Server program when it receives data
from its serial interface. If TCP Connect on Any Serial Character is selected, there are two additional
options to change, which are Serial Inactivity Time Before Disconnect and Waiting Time Between
Re-connect Attempts. Serial Inactivity Time Before Disconnect determines how long SE5001A should
wait before closing a TCP connection if there is no incoming serial data. The default value is 40 seconds.
Waiting Time Between Re-connect Attempts determines the time SE5001A should wait before it tries to
establish a connection with a TCP Server again if it fails to connect to the TCP Server. The default value is 1
minute.
TCP Keep-Alive: Specify the interval in the “Idle Time Before Sending TCP Alive Packet” to force
SE5001A to send TCP Keep-Alive packets in the set interval to prevent disconnection from the client. Note
that this field has a multiplier of 10, so the default value 4 means to send Keep-Alive packets every 40
seconds.
TCP Inactivity Timeout: Specify the value in “TCP Inactivity Time Before Disconnect” to force SE5001A
actively close a TCP connection after some specific inactivity time (no packets). The default value is 0,
which means the SE5001A would never actively close an established connection.
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
Go to the Application Configuration section starting from 3.3.11 to apply Virtual COM, Pair Connection, or
Reverse Telnet application if applicable. Otherwise go to the COM Configuration (section 3.3.19) for serial
settings directly.
34
User Manual Version 1.1
SE5001A Serial Device Server
35
User Manual Version 1.1
SE5001A Serial Device Server
SE5001A also supports connectionless UDP protocol compared to the connection-oriented TCP protocol. Please be
aware that even though UDP provides better efficiency in terms of response time and resource usage, it does not
guarantee data delivery. It is recommended to utilize UDP only with cyclic polling protocols where each request is
repeated and independent, such as Modbus Protocol. Figure 3.25 shows the UDP settings.
Click on the “COM1” link on the left hand side.
Select UDP.
Destination IP and Port: Specify the Begin and End IP here. Four groups of range IPs are allowed. This is
the IP address of the UDP program and the Port it is listening to. Note that the maximum number of UDP
nodes that SE5001A can handle would highly depend on the traffic load. We have tested that SE5001A can
handle up to 32 UDP nodes (baud rate 9600 bps, request interval 100ms, and data length 30bytes).
Enter the Local Listening Port. This is the port that SE5001A should listen to. Match this setting in the
UDP program (usually called destination port in the UDP program).
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
Go to the section 3.3.16 to apply Pair Connection application if applicable. Otherwise go to the COM
Configuration (section 3.3.19) for serial settings directly.
36
User Manual Version 1.1
SE5001A Serial Device Server
37
User Manual Version 1.1
SE5001A Serial Device Server
38
User Manual Version 1.1
SE5001A Serial Device Server
39
User Manual Version 1.1
SE5001A Serial Device Server
40
User Manual Version 1.1
SE5001A Serial Device Server
41
User Manual Version 1.1
SE5001A Serial Device Server
Sample Configuration:
IP Address Link Mode Local Listening Port Destination IP Destination Port
SE5001A Master 10.0.50.100 UDP 5000 10.0.50.200~10.0.50.207 5000
SE5001A Slave 1 10.0.50.200 UDP 5000 10.0.50.100 5000
SE5001A Slave 2 10.0.50.201 UDP 5000 10.0.50.100 5000
SE5001A Slave 3 10.0.50.202 UDP 5000 10.0.50.100 5000
SE5001A Slave 4 10.0.50.203 UDP 5000 10.0.50.100 5000
SE5001A Slave 5 10.0.50.204 UDP 5000 10.0.50.100 5000
SE5001A Slave 6 10.0.50.205 UDP 5000 10.0.50.100 5000
42
User Manual Version 1.1
SE5001A Serial Device Server
43
User Manual Version 1.1
SE5001A Serial Device Server
44
User Manual Version 1.1
SE5001A Serial Device Server
Alias Name:
This field is for identification purpose only.
Baud Rate:
Select one of the baud rates from the dropdown box, or select Other and then enter the desired baud rate in the
input box. Baud rates higher than 230400bps are not supported.
Flow Control:
Choose between No Flow Control, RTS/CTS (Hardware Flow Control), DTR/DSR, Xon/Xoff (Software Flow Control).
If Xon/Xoff is selected, Xon and Xoff characters are changeable. Defaults are 0x11 for Xon and 0x13 for Xoff. If the
serial device uses Xon/Xoff in conjunction with DTR/DSR, enable Controlling DTR to simulate receiving Xon/Xoff
and reading DSR to get Xon/Xoff currently.
Empty Serial Buffer When TCP Connection is Established:
By default, SE5001A will empty its serial buffer when a new TCP connection is established. This means that the TCP
application will not receive buffered serial data during a TCP link breakage. To keep the serial data when there is no
TCP connection and send out the buffered serial data immediately after a TCP connection is established, set this
option to No.
45
User Manual Version 1.1
SE5001A Serial Device Server
46
User Manual Version 1.1
SE5001A Serial Device Server
To run Virtual COM in Linux, there is a separate package called TTYredirector available for download on Atop
website or in the product CD. The zipped package includes a binary file for installation and a manual for Linux
systems.
4.1.2 Limitation
The Virtual COM driver allows up to 256 Virtual COM ports in a single PC. Selecting in the range from COM1
to COM4096 is allowed. Note that COM ports already occupied by the system or other devices will not be
available.
47
User Manual Version 1.1
SE5001A Serial Device Server
4.1.3 Installation
Run the Virtual COM setup file included in the CD or download a copy from our website to install the Virtual
COM driver for the operating system. Turn off anti-virus software and try again if installation fails. At the end of
the installation, please select at least one Virtual COM port from the Serial/IP Control Panel.
4.1.4 Uninstalling
From Windows Start Menu select Control Panel, Add/Remove Programs.
Select Serial/IP Version x.x.x in the list of installed software.
Click the Remove button to remove the program.
4.2 Enable Virtual COM Serial device servers and Select Virtual COM in Windows
It is also possible to enable Virtual COM in serial device servers using Telnet. Please refer to the section 3.2.8 on
Telnet.
48
User Manual Version 1.1
SE5001A Serial Device Server
If no Virtual COM port is selected, a dialog will pop up and asks to select at least one port as the Virtual COM port
before proceeding (Figure 4.6).
49
User Manual Version 1.1
SE5001A Serial Device Server
After at least one Virtual COM port is selected, the Control Panel will show (Figure 4.7).
The left hand side of the Control Panel shows the list of selected Virtual COM ports. Click on Select Ports to add or
remove Virtual COM ports from the list. The right hand side of the Control Panel shows the configurations of the
selected Virtual COM port marked in blue. Each Virtual COM port can have its own settings.
Note: The changes to Virtual COM ports apply immediately, so there is no need to save the settings manually.
However, if the Virtual COM port is already in use, it is necessary to close the Virtual COM port and open it after the
TCP connection closes completely in order for the changes to take effect.
available in limited serial device servers), it is necessary to enable Use Credentials From
and select Use Credentials Below from the list (Figure 4.8). Enter the Username and
Password of the serial device server in the respective fields.
iv.
v. Enable Restore Failed Connections to force Virtual COM to automatically restore failed
connections with the serial device server in the case of unstable network connections.
vi. To test the Virtual COM connection, click the Configuration Wizard button and then click Start
button in the pop up window (Figure 4.9). If the test passes, all checks should be in green. To
apply the changes in the Configuration Wizard window to the Control Panel, click on Use
Settings. Click on Copy to copy the results to the system clipboard.
vii. To transfer the settings between Virtual COM ports, click on the Copy Settings To button.
51
User Manual Version 1.1
SE5001A Serial Device Server
52
User Manual Version 1.1
SE5001A Serial Device Server
Exceptions:
53
User Manual Version 1.1
SE5001A Serial Device Server
54
User Manual Version 1.1
SE5001A Serial Device Server
55
User Manual Version 1.1
SE5001A Serial Device Server
56
User Manual Version 1.1
SE5001A Serial Device Server
57
User Manual Version 1.1
SE5001A Serial Device Server
58
User Manual Version 1.1
SE5001A Serial Device Server
59
User Manual Version 1.1
SE5001A Serial Device Server
60
User Manual Version 1.1
SE5001A Serial Device Server
In the Serial/IP Control Panel, Click on the Advanced button to open Advanced Settings window (Figure 4.18). Click
on Use Default Settings to load the default settings.
61
User Manual Version 1.1
SE5001A Serial Device Server
62
User Manual Version 1.1
SE5001A Serial Device Server
The Serial/IP Redirector supports TCP network connections made through a proxy server, which may be controlling
access to external networks (such as the Internet) from a private network that lacks transparent IP-based routing,
such as NAT. Find Proxy Server settings from the Advanced Settings windows and switch to the Proxy Server tab
(Figure 4.19)
63
User Manual Version 1.1
SE5001A Serial Device Server
5 Diagnostics
There are several ways to can check the status and availability of the serial device server.
From the Windows Start menu, select Run and type in “ping <TCP Server IP address>”.
If the serial device server can receive ping requests sent from the host, it will reply to the ping message (Figure
6.1). If the ping request cannot reach the serial device server, timed out message will show (Figure 6.2).
64
User Manual Version 1.1
SE5001A Serial Device Server
65
User Manual Version 1.1
SE5001A Serial Device Server
Appendix
Specifications
Network Interface
Ethernet 1x RJ-45 IEEE802.3 10/100Mbps, Auto MDI/MDI-X
Serial Interface
D-Sub9 RS-232/422/485 software selectable
Connector
3.81mm TB5 RS-232/422/485 software selectable (TB models)
Ports 1 Port
Baud Rate 1200~230Kbps
Data Bits 7,8
Stop Bits 1,2
Flow Control None, Xon/Xoff, RTS/CTS
Power Characteristics
Input Voltage 9VDC-48VDC
Input Current(9VDC) 0.30A
Power Consumption Approx. 2.70W (max)
Reverse Polarity Protection Yes
Connector 5.08mm 3-pin Lockable Terminal Block
Mechanicals
Dimensions 75mm x 85mm x 28mm
Installation Wall Mount, DIN Rail (optional)
Reset Button Yes
Weight 200g
Environmental Limits
Operating Temperature 0°C~60°C (32°F~140°F)
Storage Temperature -40°C~85°C (-40°F~185°F)
Ambient Relative Humidity 5~95% RH, (non-condensing)
Software
Protocols IPv4, ICMP, TCP, UDP, DHCP Client, SNMP, HTTP, Telnet, RFC2217
Configuration Device Management Utility, Web UI, Telnet
Virtual COM Windows / Linux redirection software
Internal Buffer Size TCP receiving buffer = 8K bytes, TCP transmitting buffer = 16K bytes
Serial receiving buffer = 4K bytes, Serial transmitting buffer = 4K bytes
66
User Manual Version 1.1
SE5001A Serial Device Server
Link Modes
TCP Server 4 connections, Virtual COM, or Reverse Telnet
TCP Client Single destination or Virtual COM
UDP Up to 4 ranges of IPs
Firmware is available for download on Atop website: http://www.atop.com.tw. Subscribe to our RSS system
http://www.atop.com.tw/en/rss.php to receive our latest firmware updates automatically.
Upgrade Procedures
This section introduces the command-line firmware upgrade utility included in the CD. Alternatively, use the Device
Management Utility to upgrade the system firmware. Refer to Device Management Utility’s manual to use it to
upgrade the system firmware.
After the new firmware is obtained, follow the procedures below to upgrade SE5001A.
1. Connect a PC (Windows systems) and the SE5001A to the same subnet. Use ping command or Serial
Manager utility to verify its availability.
2. Locate dapdl.cfg (configuration file), gwdl.exe (download executable utility), and download.bat (download
batch file) in the \download folder of the CD. Copy them to the system disk.
3. Locate the new system kernel and/or AP firmware to download. Move them inside the copied \download
directory.
4. Double click on download.bat to start the firmware upgrade process.
67
User Manual Version 1.1
SE5001A Serial Device Server
68
User Manual Version 1.1
SE5001A Serial Device Server
Note: After the upgrading process finishes, SE5001A will program the flash memory and buzzer beeps 6
times then restarts. Normally, it takes around 10 seconds to complete the programming process. If an error
occurs during the programming process, SE5001A will clear the corresponding memory and the system
remains intact of what it was.
Error Messages
Firmware upgrade may not be successful if errors occur during the process.
69
User Manual Version 1.1
SE5001A Serial Device Server
The AP (application program) firmware of SE5001A can be disabled to restore the device to the proper firmware in
case an incompatible firmware was downloaded and the system crashes while loading the AP.
To disable the AP firmware and prevent it from executing, please do the following.
1. Power off the device.
2. While the reset button is pressed, power on the device.
3. In Device Management Utility, SE5001A will show up with a default kernel firmware and no AP firmware.
4. Download the correct AP firmware to SE5001A.
5. The device will restart and recover to the downloaded firmware.
70