Uniflair™ Chilled-Water InRow Cooling

ACRC300 Series, ACRC600 Series


Technical Specifications
Up to 70 kW
990-5792B-001
10/2022

[Link]
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
This manual contains general information, safety instructions, and guidance. Updates
may be published from time to time and are available upon request. This manual is
not a substitute for the user conducting a detailed operational and site-specific
development plan.
This product is for industrial use only. It should only be used for the functions for
which it has been designed as set out in this manual. User must evaluate and take
adequate precautions to address risks associated with use of this product in
environments and/or processes not specifically addressed in this manual (e.g. heavy
industry, medical, marine environments, railway, etc.).

This product should be installed, configured, used, serviced, maintained, replaced or


have similar work carried out on it only by suitably qualified, trained, experienced and
competent personnel who hold any necessary authorizations (e.g. licenses, permits
or certifications) to perform such work. User must ensure that all work is carried out in
compliance with the manufacturer’s instructions (including the product labels/
markings, technical specification manual, installation manual, and operation and
maintenance manual) and with all applicable laws, regulations, standards and
guidance (including standards and guidance applicable to the installation location).

All work must be carried out in a way that does not give rise to danger and using
appropriate personal protective equipment (PPE).
Schneider Electric shall not be responsible for any works carried out by anyone other
than Schneider Electric; or for integration or use of the product with other products
(including spare parts and software) that are neither approved nor provided by
Schneider Electric for such purposes; or for any non-Schneider Electric software,
firmware, information or memory data contained in, stored on, or integrated with this
product.

To the maximum extent permitted by applicable law, neither Schneider Electric nor
any of its affiliates shall be liable for any claims, costs, losses, damages, death or
injuries arising out of the improper use of this product or any failure to comply with
any of the above [Link] Electric’s quality management system is
ISO 9001 certified and the products are marked
ACRC300 Series, ACRC600 Series

Table of Contents
General Information ....................................................................................9
Translation Reference.................................................................................9
Intended Use..............................................................................................9
Cross-Reference Symbol Used in This Manual .............................................9
Abbreviations .............................................................................................9
Unit Overview ............................................................................................10
Model Identification...................................................................................10
Safety Practices related to Refrigerants......................................................10
Equipment Disposal..................................................................................12
Waste Electrical and Electronic Equipment (WEEE) Disposal.................12
Environmental Considerations .............................................................12
Regulation on Fluorinated Greenhouse Gases ......................................12
Radio Frequency Interference..............................................................13
Technical Data ...........................................................................................14
Overview .................................................................................................14
Capacity.............................................................................................14
Room Air Distribution ..........................................................................14
Compliance approval ..........................................................................14
Scalable Solution for Critical Environments.................................................15
InRow Advantages..............................................................................15
Scalable for High Density ....................................................................15
EcoAisle™ aisle containment system ....................................................15
Configurations..........................................................................................19
Direct connection to chiller...................................................................19
Standard Features and Options .................................................................19
Standard features ...............................................................................19
Optional features ................................................................................21
Control type........................................................................................21
Functions ...........................................................................................22
Logging..............................................................................................22
Control ...............................................................................................22
Alarms ...............................................................................................22
ACRC600 series only ..........................................................................23
ACRC600P series only........................................................................23
InRow ACRC300 Series............................................................................25
External Components—ACRC301S .....................................................25
External Components—ACRC301H .....................................................26
Internal Components—ACRC301S ......................................................27
Internal Components—ACRC301H ......................................................28
User interface connection panel—ACRC301S ......................................29
User interface connection panel—ACRC301H ..................................30
Interface Connections .........................................................................31
InRow ACRC600 Series............................................................................32
External Components..........................................................................32
Internal Components (Front) ................................................................33
Internal Components (Rear) ................................................................35
Electrical Panel...................................................................................36
Main Controller Board .........................................................................39

990-5792B-001 5
ACRC300 Series, ACRC600 Series

Determining Cooling Capacity ...................................................................40


Recommended Capacity Limitations ..........................................................41
ACRC301S ........................................................................................41
ACRC301H ........................................................................................41
ACRC600 series .................................................................................41
ACRC301S ..............................................................................................43
Performance specifications 5°C (41°F) EWT .........................................43
Performance specifications 7.2°C (45°F) EWT (ACRC301S)..................45
Performance specifications 8.8°C (48°F) EWT (ACRC301S)..................47
Performance specifications 10°C (50°F) EWT (ACRC301S)...................48
Performance specifications 12.7°C (55°F) EWT (ACRC301S) ................50
Performance specifications 15°C (59°F) EWT (ACRC301S)...................51
ACRC301H ..............................................................................................53
Performance specifications 10°C (50°F) EWT .......................................53
Performance specifications 12.7°C (55°F) EWT (ACRC301H)................54
Performance specifications 15°C (59°F) EWT (ACRC301H)...................56
Performance specifications 17.5°C (63.5°F) EWT (ACRC301H) .............58
Performance specifications 20°C (68°F) EWT (ACRC301H)...................59
Performance specifications 22°C (72°F) EWT (ACRC301H)...................61
ACRC600 Series ......................................................................................62
Performance specifications 5.6°C (42°F) EWT ......................................62
Performance specifications 7.2°C (45°F) EWT (ACRC600
series)................................................................................................63
Performance specifications 8.8°C (48°F) EWT (ACRC600
series)................................................................................................65
Performance specifications 10°C (50°F) EWT (ACRC600
series)................................................................................................66
Performance specifications 12.7°C (55°F) EWT (ACRC600
series)................................................................................................67
Performance specifications 15.5°C (60°F) EWT (ACRC600
series)................................................................................................68
Performance Data-General .......................................................................69
ACRC301S ........................................................................................69
ACRC301H ........................................................................................71
ACRC600 series .................................................................................72
Glycol Correction Factors ..........................................................................73
Altitude Correction Factors ........................................................................73
Sound Performance Data ..........................................................................74
Electrical Data ..........................................................................................75
Dimensional Data .....................................................................................76
InRow ACRC300 series assembled module ..........................................76
InRow ACRC600 series assembled module ..........................................76
SX to VX height adapter—ACRC300 series ..........................................77
SX to 48U SX height adapter—ACRC300 series ...................................77
SX to VX height adapter—ACRC600 series ..........................................77
SX to 48U SX height adapter—ACRC600 series ...................................77
Piping Connections...................................................................................78
ACRC301S ........................................................................................78
ACRC301H ........................................................................................80
Internal Piping Diagram—ACRC301S ..................................................82
Internal Piping Diagram—ACRC301H ..................................................83

6 990-5792B-001
ACRC300 Series, ACRC600 Series

Connect with Customer Supplied Chiller ...............................................84


ACRC600 series .................................................................................85
ACRC600 Series ......................................................................................86
Top Piping and Power Access Locations (Top View) ..............................86
Bottom Piping and Power Access Locations (Bottom View) ....................87
Facility Planning ........................................................................................88

990-5792B-001 7
General Information ACRC300 Series, ACRC600 Series

General Information
Translation Reference
The original version of this manual has been written in the English language.
Manuals written in other languages have been translated from the original English
version.

Intended Use
The InRow system provide cooling capacity based on the combination of an
indoor and an outdoor unit which specifications are described in this manual. No
modifications may be made to the units or their parts without explicit written
consent from Schneider Electric. Any mechanical or electrical modification voids
factory warranty.

Cross-Reference Symbol Used in This Manual


See another section of this document or another document for more
information on this subject.

Abbreviations
The following are abbreviations and terms used in this manual:
• EEV: Electronic expansion valve
• VFD/VSD: Variable-frequency drive/variable-speed drive
• CW: Chilled Water
• BMS: Building management system
• ATS: Automatic transfer switch
• HACS: Hot aisle containment system
• CACS: Cold aisle containment system
• RACS: Rack aisle containment system

990-5792B-001 9
ACRC300 Series, ACRC600 Series Unit Overview

Unit Overview
Model Identification
The model number can be found on the outside of the shipping crate and on the
name plate located on the unit as shown. Use the table below to verify that the
equipment is the right type and voltage.
REAR

NAME PLATE
na4402b

SKU Width Range of Voltage Phase Frequency Power


Capacity Connection

ACRC301S 300 mm Up to 45 kW 100–240V 1 50/60 Hz NEMA L5-20P/


IEC 309-16A
ACRC301H 300 mm Up to 60 kW 208–230V 1 50/60 Hz HARDWIRED

NAME PLATE
na2600b

Model Width Voltage Reheat Humidifier Air Pattern

ACRC600 600 mm 200-240/3~/50-60 Hz N/A N/A Back to front


ACRC601 600 mm 460-480/3~/60 Hz N/A N/A Back to front
ACRC602 600 mm 380-415/3~/50-60 Hz N/A N/A Back to front

ACRC600P 600 mm 200-240/3~/50-60 Hz Electric Steam canister (replaceable) Back to front

ACRC601P 600 mm 460-480/3~/60 Hz Electric Steam canister (replaceable) Back to front

ACRC602P 600 mm 380-415/3~/50-60 Hz Electric Steam canister (replaceable) Back to front

Safety Practices related to Refrigerants

WARNING
QUALIFIED AND CERTIFIED PERSONNEL ONLY
Charging and maintaining the refrigeration circuit must only be performed by
qualified and certified personnel.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

10 990-5792B-001
Unit Overview ACRC300 Series, ACRC600 Series

Installation Area
Carry out all safety checks to minimize the risk of ignition prior to the beginning of
any work on systems containing flammable refrigerants. Moreover, comply with
the following requirements, prior to carrying out any work/service on the system:
• Work shall be undertaken under a controlled procedure so as to minimise the
risk of a flammable gas or vapor being present while the work is being
performed.
• All maintenance staff and other personnel working in the installation area
shall be instructed on the nature of work being carried out. Work in confined
spaces shall be avoided.
• The area shall be checked with an appropriate refrigerant detector prior to
and during any maintenance and installation work, to inform the personnel
about potentially toxic or flammable atmospheres.
• Ensure that the leak detection equipment being used is suitable for all
applicable refrigerants, i. e. non-sparking, adequately sealed or intrinsically
safe.
• If any hot work is to be conducted on the refrigerating equipment or any
associated parts, appropriate fire extinguishing equipment shall be available
to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging
area.
• No person carrying out work in relation to a refrigerant system which involves
exposing any pipe work shall use any sources of ignition in such a manner
that it may lead to the risk of fire or explosion. All possible ignition sources,
including cigarette smoking, should be kept sufficiently far away from the site
of installation, repairing, removing and disposal, during which refrigerant can
possibly be released to the surrounding space. Prior to work taking place, the
area around the equipment is to be surveyed to make sure that there are no
flammable hazards or ignition risks. “No Smoking” signs shall be displayed.

Ventilated Area
Before breaking into the system or conducting any hot work, ensure that the area
is in the open or adequately ventilated. A degree of ventilation shall be maintained
while the work is being carried out. The ventilation should safely disperse any
released refrigerant and preferably expel it externally into the atmosphere.

Detection of Flammable Refrigerants


Under no circumstances shall potential sources of ignition be used in the
searching for or detection of refrigerant leaks. No halide torch (or any other
detector using a naked flame) shall be used.
The following leak detection methods are deemed acceptable for all refrigerant
systems:
• Electronic leak detectors may be used to detect any refrigerant leaks but, in
the case of flammable refrigerants, the sensitivity may not be adequate, or
may need re-calibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector does not represent a potential
source of ignition itself, and that it is suitable for the refrigerant used. Leak
detection equipment shall be set at a specific LFL percentage of refrigerant
and shall be calibrated to the refrigerant employed, and the appropriate
percentage of gas (25 % maximum).
• Leak detection fluids are also suitable for use with most refrigerants but the
use of detergents containing chlorine shall be avoided, as the chlorine may
react with the refrigerant and corrode the copper pipe-work.
• If a leak is suspected, all naked flames shall be removed/extinguished.

990-5792B-001 11
ACRC300 Series, ACRC600 Series Unit Overview

Equipment Disposal
Waste Electrical and Electronic Equipment (WEEE) Disposal
Schneider Electric products comply with international directives on
the Restriction of Hazardous Substances (RoHS) in electronic and
electrical equipment and the disposal of Waste Electrical and
Electronic Equipment (WEEE). Dispose of any waste electronic or
electrical equipment with the appropriate recycling center. Contact
Schneider Electric for assistance.
At the end of an EEE (Electrical and Electronic Equipment) useful
life, any battery included in the same must be removed and
separated according to the instructions provided by the supplier,
before disposing of the product. Used batteries must be disposed of
at an appropriate waste collection center, as required by local
regulations.

Environmental Considerations
Wind
The equipment is not intended for installation in areas of high wind. Consult the
sales representative for information on any applicable options for installation in
areas of high wind.

Earthquakes
The equipment is not intended for installation in areas at risk of seismic activity.
Consult the sales representative for information on any applicable options for
installation in areas at risk of seismic activity.

ATEX
The equipment is not intended for use in potentially explosive atmospheres and
does not comply with Directive 2014/34 / EU (ATEX).

Dust
The equipment is not intended for use in dusty environments and in environments
with conductive dust.

Corrosion
The equipment is not intended for use in a potentially corrosive environment.

Regulation on Fluorinated Greenhouse Gases


According to Regulation (EU) No. 517/2014 on fluorinated greenhouse gases,
operators of stationary equipment that contain fluorinated greenhouse gases shall
ensure that the recovery of those gases is carried out by natural persons that hold
the relevant certificates provided for by Article 10, so that those gases are
recycled, reclaimed or destroyed.

12 990-5792B-001
Unit Overview ACRC300 Series, ACRC600 Series

NOTE: ‘Recovery’ means the collection and storage of fluorinated greenhouse


gases from products, including containers, and equipment during
maintenance or servicing or prior to the disposal of the products or equipment.

Radio Frequency Interference


NOTE: The Radio Frequency Interference directive applies to units installed in
US and in Canada only.
Cooling units comply with part 15 of the FCC Rules. Operation is subject to the
following two conditions:
1. These devices may not cause harmful interference.
2. These devices must accept any interference received, including interference
that may cause undesired operation.
Any changes or modifications not expressly approved by the party responsible for
compliance could void the user’s authority to operate the equipment.

990-5792B-001 13
ACRC300 Series, ACRC600 Series Technical Data

Technical Data
Overview
This modular, row-based computer room cooling system offers efficient,
predictable, and economical cooling for a variety of spaces.
Critical environmental requirements now reach far beyond the confines of the
traditional data center or computer room to encompass a larger suite of
applications, referred to as technology rooms. Critical environment applications
include the following:
• Computer rooms
• Telecommunication facilities
• Clean rooms
• Power equipment
• Medical equipment rooms
• LAN/WAN environments
• Edge data centers
• Traditional data centers
A worldwide network by Schneider Electric representatives is fully qualified to
provide engineering, sales, installation, and service for our products.

Capacity
The InRow® Chilled Water (CW) configuration is available in two sizes with a
capacity that is up to 70 kW based on the particular application of the unit.

Room Air Distribution


Row-based systems are placed in line with rack enclosures. At least one system is
used in each hot aisle. Air is drawn in through the rear of the system, cooled, and
discharged into the cold aisle, thereby neutralizing the sensible heating effects of
the data processing equipment. UniflairTM Direct Expansion InRow products
deliver high volumes of airflow to eliminate hot spots in densely populated
environments.
Configuration:
• Air-cooled

Compliance approval
Agency ACRC301S ACRC301H ACRC600 ACRC601 ACRC602 ACRC600P ACRC601P ACRC602P

UL&cUL X X X X X X X
RCM X X X X
CE X X X X

14 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Scalable Solution for Critical Environments


InRow Advantages
The row-based solution improves energy efficiency and cooling capacity in a
number of ways. First, the UniflairTM Direct Expansion InRow unit draws air
directly from the hot aisle, taking advantage of higher heat transfer efficiency due
to higher temperature differences. It can then discharge room-temperature air
directly in front of the servers or IT applications installed in the room. The In-Row
configuration allows the unit to operate at higher return and supply air
temperatures, reaching 100% sensible capacity. This significantly reduces the
need for humidification.

na5859a
HOT AISLE

Scalable for High Density


The predictable performance of the row-based architecture makes it well-suited
for high density applications. The focus on heat removal instead of cold-air
delivery is the key to making this approach scalable. The modular design of the
UniflairTM Direct Expansion InRow unit allows it to be easily added in the row as
the demand for cooling increases.
The additional benefit of the row-based architecture consists in adding hot-aisle
containment. Containing the hot aisle further reduces any chance of hot and cold
air streams mixing. This provides ultimate predictability and allows the cooling
capacity to be matched to the IT heat load.

EcoAisle™ aisle containment system


Modular ceiling tiles and doors/curtains can be used to enclose the hot aisle. This
increases the densities that can be handled in a single rack enclosure by
eliminating mixing of hot and cold air streams. This method, called load
neutralization, removes the heat from the hot aisle, cools it, and then returns it to
the surrounding room area. The warmer return air temperatures that are achieved
in this application increase the capacity of the air conditioner and, in many cases,
eliminate the need for make-up humidification.
Use of modular ceiling tiles across a 3- to 6-ft. hot aisle that connects two opposite
rack enclosures makes expansion quick and simple. Expansion kits, with the

990-5792B-001 15
ACRC300 Series, ACRC600 Series Technical Data

necessary ceiling tile and all baying hardware, can be ordered to increase the size
of the hot aisle. The end doors/curtains can be easily removed and re-attached for
expansion.
The enclosed hot aisle prevents any warm return air from mixing with cooler
supply air. In effect, all surrounding room air can act as supply air to the system.
The EcoAisle aisle containment system is beneficial in any environment. It can be
deployed quickly in any controlled space without expensive additions to the
infrastructure, such as raised floor or ductwork.

Hot aisle containment dimensions


900
1200 1200 1200
1070 1070
HOT AISLE
1070 1070
1200
900 900 900

Nominal Aisle
Width
991 (39.00) 991 (39.00) 991 (39.00) 1291 (50.83) 1291 (50.83) 1591 (62.64)

— 991 (39.00) 991 (39.00) 1161 (45.71) 1161 (45.71) 1461 (57.52)

— — 991 (39.00) 1161 (45.71) 1161 (45.71) 1331 (52.40)


914 (36.00)
— — — — — —
— — — — — —
— — — — —
1296 (51.02) 1296 (51.02) 1296 (51.02) 1596 (62.84) 1596 (62.84) 1896 (74.65)

— 1296 (51.02) 1296 (51.02) 1466 (57.75) 1466 (57.75) 1766 (69.53)

— — 1296 (51.02) 1466 (57.75) 1466 (57.75) 1636 (64.41)


Hot Aisle -
1219 (48.00)
Middle or End
— — — 1296 (51.02) 1296 (51.02) 1596 (62.84)
of Aisle,
Frame to
— — — — 1296 (51.02) 1466 (57.75)
Frame, With
Depth
— — — — — 1296 (51.02)
Extenders
1600 (63.00) 1600 (63.00) 1600 (63.00) 1900 (74.80) — —

— 1600 (63.00) 1600 (63.00) 1770 (69.69) 1770 (69.69) —

— — 1600 (63.00) 1770 (69.69) 1770 (69.69) —


1524 (60.00)
— — — 1600 (63.00) 1600 (63.00) 1900 (74.80)

— — — — 1600 (63.00) 1770 (69.69)

— — — — — 1600 (63.00)

1905 (75.00) 1905 (75.00) 1905 (75.00) — — —


1829 (72.00)
— 1905 (75.00) 1905 (75.00) — — —

16 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

— — 1905 (75.00) — — —

— — — 1905 (75.00) 1905 (75.00) —

— — — — 1905 (75.00) —

— — — — — 1905 (75.00)

* All dimensions shown in millimeters (inches).

Cold aisle containment dimensions


1070 1070
1200 1200 1200
900
COLDAISLE
900 900 900
1200
1070 1070

Nominal Aisle
Width
991 (39.00) 1121 (44.13) 1251 (49.25) — 1121 (44.13) —

— 991 (39.00) 1121 (44.13) — 1121 (44.13) —

— — 991 (39.00) — — —
914 (36)
— — — — — —
— — — — — —
— — — — —
1296 (51.02) 1426 (56.14) 1556 (61.26) 1296 (51.02) 1426 (56.14) 1296 (51.02)

— 1296 (51.02) 1426 (56.14) 1296 (51.02) 1426 (56.14) 1296 (51.02)

— — 1296 (51.02) 1166 (45.91) 1296 (51.02) 1296 (51.02)


1219 (48)
— — — 1296 (51.02) 1426 (56.14) 1296 (51.02)

— — — — 1296 (51.02) 1296 (51.02)


Cold Aisle -
Middle or End
— — — — — 1296 (51.02)
of Aisle,
Frame to
1600 (63.00) 1730 (68.11) 1860 (73.23) 1600 (63.00) 1730 (68.11) 1600 (63.00)
Frame, With
Depth
— 1600 (63.00) 1730 (68.11) 1600 (63.00) 1730 (68.11) 1600 (63.00)
Extenders
— — 1600 (63.00) 1470 (57.88) 1600 (63.00) 1600 (63.00)
1524 (60)
— — — 1600 (63.00) 1730 (68.11) 1600 (63.00)

— — — — 1600 (63.00) 1600 (63.00)

— — — — — 1600 (63.00)

1905 (75.00) 2035 (80.12) 2165 (85.24) 1905 (75.00) — 1905 (75.00)

— 1905 (75.00) 2035 (80.12) 1905 (75.00) — 1905 (75.00)

— — 1905 (75.00) 1775 (69.88) 1905 (75.00) 1905 (75.00)


1829 (72)
— — — 1905 (75.00) — 1905 (75.00)

— — — — 1905 (75.00) 1905 (75.00)

— — — — — 1905 (75.00)

914 (36.00) 991 (39.00) 991 (39.00) 991 (39.00) — — —


Cold Aisle -
End of Aisle, 1219 (48.00) 1296 (51.02) 1296 (51.02) 1296 (51.02) 1296 (51.02) 1296 (51.02) 1296 (51.02)
Frame to
Frame, With 1524 (60.00) 1600 (63.00) 1600 (63.00) 1600 (63.00) 1600 (63.00) 1600 (63.00) 1600 (63.00)
Depth
Extenders 1829 (72.00) 1905 (75.00) 1905 (75.00) 1905 (75.00) 1905 (75.00) 1905 (75.00) 1905 (75.00)

990-5792B-001 17
ACRC300 Series, ACRC600 Series Technical Data

* All dimensions shown in millimeters (inches).

18 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Configurations
Chilled water systems utilize water from a chiller plant for cooling. Chilled water is
commonly used in large buildings and high rises and can serve multiple indoor
units, which can be cost effective for large installation options. There are various
methods for chilled water piping.

Direct connection to chiller

na2826b
Item Description Item Description

InRow RC Chiller

Valve Strainer

NOTE: Install isolation valves and particulate strainers with 20 mesh stainless steel screen (opening size = 865 micron) in the supply
line between the chiller and InRow RC cooling unit.

Standard Features and Options


Standard features
Insulated side panels The frame is constructed of 16-gauge formed steel for maximum strength. Cabinet is serviceable from the front
and rear. All exterior panels and corner posts on the frame are powder coated for durability and an attractive
finish. Front and rear exterior panels are constructed of 18-gauge perforated steel with 84% open free area.
Insulation is 80.1 kg/m3 (5 lb/ft3) density and complies with ASTM E84 rating of 25/50. All panels allow easy
access and removal: ACRC600 series units include a key latch for safety and security.

Variable speed fans Each unit is equipped with variable speed fans. In order to provide uniform airflow over the cooling coil, the
fans provide a draw-through air pattern. Quiet, low maintenance, and producing very low vibration, fans are
controlled through a signal from the microprocessor controller that constantly adjusts airflow to match the heat
load in the data center without need for a VFD (Variable Frequency Drive). In ACRC300 series, the fans are
easily replaceable while the unit is in operation.

Shutdown input/alarm The unit provides one field connection input for remote shutdown and four field connections for an alarm
output output.

Chilled water flow meter An internal flow meter is integrated with the microprocessor controller to display the chilled water flow rate of
the unit.

2-way/3-way valve A fully modulating valve is microprocessor-controlled to regulate the amount of chilled water into the cooling
coil to maintain optimal cooling conditions. The standard valve pressure rating is 2068 kPa (300 PSI). The
valve is user configurable to be twoway or three-way.

Fan power supply The unit includes two fan power supplies, each capable of running ACRC300 series at fan speeds of 75% in
the event of a single power supply failure.

990-5792B-001 19
ACRC300 Series, ACRC600 Series Technical Data

(ACRC300 series only)

Primary/secondary The system features two power feeds. This allows a level of system fault tolerance and uninterruptible cooling.
power feeds Each feed powers 100% of the unit.

Cross circuited cooling Designed for high sensible heat ratios, the coil is constructed with copper tubes, aluminum fins, and
coil galvanized steel end plates.

Washable filter The filtration of conditioned air is extremely vital to maintaining the clean, particle-free environment required by
electrical equipment. The system uses a <20% efficiency ASHRAE 52.1, 12.7 mm (1/2 in.) washable filter that
(ACRC300 series only) meets HF-1 standards for electronics (MERV 1 per ASHRAE 52.2).

30% ASHRAE 52.1 filter The filtration of conditioned air is extremely vital to maintaining the clean, particle-free environment required by
electrical equipment. The system uses a 30% efficient, 102 mm (4 in), deep loading, pleated filter. Deeper
(ACRC600 series only) filters produce a lower pressure drop, requiring less energy during normal operation. The filter is moisture
resistant up to a 100% relative humidity. Filters are easily replaceable from the rear of the unit. (MERV 8 per
ASHRAE 52.2, EN779 G4)

Selectable top or bottom NOTE: Unit includes both top and bottom piping connections. Top piping connects to internal piping
piping connections connectors and routes piping upward out of the unit. Bottom piping connects to internal piping connectors
and routes piping downward out of the unit. All connections are unions for ease of installation and service.
NOTE: Top piping for ACRC300 series is available as an optional kit.

Dual float condensate The factory-installed condensate pump is piped internally to the condensate pan. Dual floats are included with
management the unit. One float is used for condensate pump control, the other to generate condensate pan overflow
alarms. For technical specifications, see Performance Data—General.
(Does not include
ACRC301H)

Network management Permits multi-level access to monitoring, control, and event notification features over the user’s network.

Service notifications Several components within the unit will provide a warning that service is needed. There are multiple faults that
(ACRC300 series only) can be detected and reported (see Alarms). Notification is also provided when a service interval expires.

Joining kit InRow RC/ Joining kits made of 16-gauge metal enable joining of the cooling system to NetShelter SX enclosures.
NetShelter SX

Remote temperature To control the unit based on rack inlet temperature, one remote sensor is provided with ACRC300 series
sensor (fieldinstalled) and three remote sensors are provided with ACRC600 series units (field-installed).

4.3-in. touch screen High-definition screen displays more data. Provides easytoread system status information.

Casters Allows for the unit to be moved easily.

Easy-access electrical Slide-out electrical box enables maintenance without removing the unit from the row.
box

(ACRC300 series only)

Active Flow Controller Monitors pressure inside and outside the contained aisle and adjusts cooling unit fan speed to match the
compatibility airflow with that of the IT equipment.

20 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Optional features
Cable water detector A leak detection cable for 300-mm units (NBES0308 and NBES0309) or 600-mm units (AP9325 and AP9326) is
placed on the floor or sub-floor around all possible leak sources. If water or other conductive liquids contact the
cable anywhere along its length, the microprocessor controller visually and audibly announces a leak. The 6.1-m
(20-ft) cable may be cascaded to make custom lengths up to 24.4 m (80 ft).

Network cable Various lengths of network cable are available to ship with your cooling system. The network cable is used to
interconnect multiple cooling units in a redundant group, as well as to connect the network management card to
your local area network (LAN).

Power trough Overhead power distribution between adjacent NetShelter racks allows for removal of the InRow RC unit without
disrupting overhead power cabling.

Data partition Overhead cable distribution between adjacent NetShelter racks allows for removal of the InRow RC unit without
disrupting overhead cabling.

Height adapters To match the height of the InRow RC unit to various rack heights, height adapters are available for NetShelter 42-
U VX, 45-U SX, and 48-U SX racks.

Depth extender Used to match the depth of the InRow RC unit to deeper racks.

Rack Air Containment The Containment Solution isolates the airflow of individual racks and InRow cooling units from the whole IT
environment, increasing efficiency while allowing for high density deployment.

Aisle Containment The Containment Solution isolates pods (two rows of racks sharing a common aisle) from the whole IT
environment, increasing cooling efficiency at any density. For details, see EcoAisle™ aisle containment system.

Upper piping kit Available for top-piping configurations and can be field installed.
NOTE: Pre-installed in ACRC600 series units.

Dew point control The DPCP provides a second layer of protection in case the IT room humidity control system or humidity barrier
pump (DPCP) fails. It allows the unit to operate 100% condensate-free (unlike traditional forms of condensation removal that
requires condensate removal piping) by stopping condensation before it can form. The DPCP works by
(ACRC301H only) recirculating coil water to keep the unit operating above the dew point at all times.

Disposable pleated The filtration of conditioned air is extremely vital to maintaining the clean, particle-free environment required by
filter electrical equipment. As an optional feature, the system uses a 50.8-mm (2-in) pleated, deep-loading, 30%
ASHRAE 52.1 filter (MERV 8 per ASHRAE 52.2).
(ACRC300 series
only)

85% ASHRAE 52.1 Electrical equipment requires clean, particle free air, thus making the filtration of the air extremely important.
filter Optionally, the system uses an 85% efficient, 102-mm (4-in.), deep loading, pleated filter. Deeper filters produce a
lower pressure drop, requiring less energy during normal operation. The 100% synthetic media will not absorb
(ACRC600 series moisture and is resistant to most common chemicals. The filter is moisture resistant up to a 100% relative
only) humidity. Filters are easily replaceable from the rear of the unit. (MERV 13 per ASHRAE 52.2, EN779 F7).

Seismic latch kit Users must obtain and install the seismic latch kit for locations that require seismic certification.

Control type
The controller utilizes proportional/integral/derivative (PID) settings, a time-proven
precision environmental control method. This allows for custom tuning of control
variables to achieve optimal system response.

990-5792B-001 21
ACRC300 Series, ACRC600 Series Technical Data

Functions
• Supply and Return Air Conditions
• Operational Mode Control
• Data Logging
• Event Logging
• Alarms
• Redundant Group Control
• Fan Speed Adjustment
• Input/Output Module Programming

Logging
The event log keeps a record of all alarms and events. Each event log contains a
time/date stamp as well as operating conditions at the time of occurrence. The
controller also displays run time, in hours, for major components (air filters, fans,
power supplies, and condensate pump).
The data log displays measurements about the cooling unit, the power input to the
cooling unit, and the ambient temperature of the cooling unit.

Control
The touch-screen LCD display interface is protected by a configurable password
and provides access to information and settings for the unit.
• Supply Temperature Setpoint 15–30.2°C (59–86.4°F)
• Cool Setpoint 18–35°C (64.4–95°F)
• Rack Inlet High Temperature Threshold 10–65.6°C (50–150.1°F)
• Entering Chilled Water High Temperature Threshold 1.7–37.8°C (35–100°F)
• Supply Air High Temperature Threshold 10–65.6°C (50–150.1°F)
• Return Air High Temperature Threshold 10–65.6°C (50–150.1°F)

Alarms
The microprocessor controller shall activate a visible and audible alarm in the
following occurrences:
• Active Flow Controller sensor fault
• Air filter clogged
• Air filter run hours violation
• Check condensate management system (excluding ACRC301H)
• Chilled water flow meter fault
• Chilled water valve actuator fault
• Chilled water valve control not set to automatic
• Coil chilled water temperature sensor error
• Coil condensation possible (ACRC301H only)
• Condensate pan full (excluding ACRC301H)
• Controller power supply X fault
• Cool fail
• EcoAisle door open (AFC only)

22 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

• Entering chilled water high temperature high violation


• Entering/leaving chilled water temperature sensor fault
• Factory configuration not completed
• Fan X error
• Fan power supply X current sense fault
• Fan power supply X fault
• Filter differential pressure sensor fault
• Humidity sensor fault
• Input contact fault
• Insufficient airflow
• Internal communication fault
• Lower return air/supply air sensor fault
• Primary/secondary power source fail
• Rack high temperature condition
• Rack temperature sensor X error
• Return air/supply air high temperature violation
• Shutdown due to input contact
• Unexpected number of AFCs/leak detectors/rack inlet temperature sensors/
units in group
• Unit is in maintenance mode
• Unit service required
• Upper return air/supply air sensor fault
• Water detected fault/shutdown
• Circulation pump error (ACRC301H only)
• Circulation pump communication loss (ACRC301H with Stratos Maxos only)
• Circulation pump warning present (ACRC301H with Stratos Maxos only)
• Circulation pump needs service (ACRC301H with Stratos Maxos only)

ACRC600 series only


• Fan run hours exceeded
• Condensate run hours exceeded
• Invalid supply setpoint
• Link isolation relay fault

ACRC600P series only


• Humidifier water conductivity high
• Humidifier fault tolerance exceeded
• Humidifier low water
• Humidifier excessive output reduction
• Humidifier drain fault
• Humidifier cylinder full
• Humidifier replace cylinder
• Humidifier RS485 communication fault
• Humidity high/low violation
• Supply humidity sensor fault

990-5792B-001 23
ACRC300 Series, ACRC600 Series Technical Data

• Return humidity sensor fault


• Heater fault
• Heater run hours exceeded

24 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

InRow ACRC300 Series


External Components—ACRC301S

na4303a

Item Description
Upper side panels
Fans
Display interface
Lower side panels
Front panel
Rear panel
Air filters
Upper piping installation holes

990-5792B-001 25
ACRC300 Series, ACRC600 Series Technical Data

External Components—ACRC301H

Item Description
Upper side panels
Fans
Display interface
Lower side panels
Front panel
Rear panel
Air filters
Upper piping installation holes

26 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Internal Components—ACRC301S

na4397a

Item Description Item


Fan Inlet shutoff valve (1 in.)
Supply air temperature sensor, Pipe connection, water inlet
top
Coil Pipe connection, water outlet
Condensate drain pan, top Service valve (outlet water
pressure test)
Supply air temperature sensor, 3-way actuator valve
bottom
Condensate drain pan, bottom Flow meter
Drain valve Auto-transfer switch (ATS) box
Condensate drain pan float Electrical box
switch
Condensate pump Return air temperature sensors
Return air temperature sensor, Power cord connections, top
bottom
Service valve (inlet water Rack joining brackets
pressure test)
2-way–(3/4-in.) bypass shut-off Service valve (air purging)
valve

990-5792B-001 27
ACRC300 Series, ACRC600 Series Technical Data

Internal Components—ACRC301H

Item Description Item


Fan Pipe connection, water outlet
Supply air temperature sensor, Return air temperature sensor,
top bottom
Supply air temperature sensor, 3-way valve actuator
bottom
Coil Top pipe connection for optional
recirculation pump
Flow meter Humidity sensor
Bottom pipe connection for Auto transfer switch (ATS) box
optional recirculation pump
Drain valve Electrical box
Inlet shutoff valve (1 1/4-in.) Return air temperature sensor,
top
Pipe connection, water inlet Junction box, top position
2-way valve (1-in.) bypass shut- Service valve (air purging)
off
Rack joining brackets Service valve (inlet water
pressure test)
Service valve (outlet water
pressure test)

28 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

User interface connection panel—ACRC301S

na4335a

Item Description

Upper electrical box cover

User interface connection panel

Control module cover

990-5792B-001 29
ACRC300 Series, ACRC600 Series Technical Data

User interface connection panel—ACRC301H

na5053a

Item Description

Upper electrical box cover

User interface connection panel

Control module cover

30 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Interface Connections

Item Description Item Description


Universal sensor ports USB host port
Network connection A-Link port
Touchscreen display Reset button
connection
Modbus connection Output relay 4/standby input
Modbus configuration Output relay 1–3
switches
Processor status LED Not in use
USB device port

990-5792B-001 31
ACRC300 Series, ACRC600 Series Technical Data

InRow ACRC600 Series


External Components

na5724a

Item Description Item Description

Removable rear doors Adjustable leveling foot

Side panel lock Door handle and lock

Removable side panel Removable front door

Caster Display Interface

32 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Internal Components (Front)


ACRC60x

EDB
F
A
F EE
D

na5926a

Item Description Item Description


Fan Main feed breakers
Fan Guard Customer interface connectors
Condensate drain pan Ground wire
Condensate pump Supply air humidity sensor
Electrical panel Supply air temperature sensor

990-5792B-001 33
ACRC300 Series, ACRC600 Series Technical Data

ACRC60xP

DB
FEE
DA
FEE

na5925a

Item Description Item Description


Fan Main feed breakers
Fan Guard Customer interface connectors
Condensate drain pan Ground wire
Condensate pump Supply air humidity sensor
Electrical panel Supply air temperature sensor

34 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Internal Components (Rear)


ACRC60x, ACRC60xP

na2105a

Item Description Item Description

Chilled-water coil Rear doors

Chilled-water control actuator Air filters

Chilled-water three-way valve body Return humidity sensors (ACRC60xP only)

Flow meter Return temperature sensor

Pipe Chase

990-5792B-001 35
ACRC300 Series, ACRC600 Series Technical Data

Electrical Panel
ACRC60x

na2729b

Item Description Item Description

Transformers Main circuit breaker-Power Feed B

Customer interface connectors Automatic Transfer Switch (ATS) contactors

Display interface connection ATS Timers

ATS transformer (ACRC 601 and ACRC 602


Main controller board only)

Relay board ATS timer circuit breakers

36 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Item Description Item Description

Ground lug Fan circuit breakers

Main circuit breaker-Power Feed A Controller fuse assembly

990-5792B-001 37
ACRC300 Series, ACRC600 Series Technical Data

ACRC60x

na2008b

Item Description Item Description

Transformers ATS Timers

ATS transformer (ACRC 601P and ACRC


Customer interface connectors 602P only)

Display interface connection ATS timer circuit breakers

Main controller board Fan circuit breakers

Relay board Controller fuse assembly

Ground lug Humidifier circuit breaker

Main circuit breaker-Power Feed A Heater circuit breaker

38 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Item Description Item Description

Main circuit breaker-Power Feed B Heater contactor

Automatic Transfer Switch (ATS) contactor Humidifier contactor

Main Controller Board

na5927a

Item Description

Display interface connection

R2 SIMM card

Differential pressure SIMM

Internal RS485 SIMM

OPTO-isolated input SIMM

Temperature sensor connectors

990-5792B-001 39
ACRC300 Series, ACRC600 Series Technical Data

Determining Cooling Capacity


IT equipment requires two acceptable limits in order for effective cooling to occur.
These parameters are inlet air temperature and flow rate of air through the IT
equipment. It is entirely possible, though undesirable, to design a computer room
with enough heat removal capacity, but with an inadequate volumetric flow rate of
cool air supply. When this condition exists, IT equipment will be subjected to
excessively high operating temperatures on a localized basis due to recirculation,
and cooling equipment will operate at less than optimal efficiency. Schneider
Electric provides the necessary data to prevent this undesirable situation. The first
table, titled “Recommended Capacity Limitations,” shows the capacity limits based
on air flow of the InRow RC. The following tables, titled “Performance
Specifications”, show the recommended maximum amount of load that should be
placed upon the cooling unit solely based on heat removal capability. The lesser of
the two capacity numbers obtained from the “Recommended Capacity Limitations”
table and “Performance Specification” table should be considered the maximum
load capable of being served by the InRow RC. A definition of the terms in these
tables follows:
IT equipment air flow (kW/CFM and kW/l/s)— The average cooling air flow rate
demanded by IT equipment in liters per second (cubic feet per minute) divided by
the total actual power dissipation of IT equipment in kilowatts.
Recommended capacity limit (kW)— The corresponding maximum load in
kilowatts capable of being served by the cooling unit solely based on conservation
of volumetric air flow.
DB (°C and °F)— The dry bulb temperature in degrees Fahrenheit and Celsius of
the return air stream to the cooling unit.
WB (°C and °F)— The wet bulb temperature in degrees Fahrenheit and Celsius of
the return air stream to the cooling unit.
CW delta T (°C and °F)— The difference in temperature in degrees Fahrenheit
and Celsius between chilled water entering and exiting the cooling unit.
Sensible net capacity (kW and BTU/hr)— The sensible net heat removal
capacity of fan heat, of the cooling unit at stated operating conditions.
Total net capacity (kW and BTU/hr)— The total (sensible + latent) net heat
removal capacity of fan heat, of the cooling unit at stated operating conditions.
Sensible heat ratio (SHR)— The sensible heat ratio of the unit at stated
conditions. Sensible Heat Ratio is the ratio of sensible capacity to total capacity.
CW flow rate (l/s and GPM)— The volumetric flow rate of chilled water through
the cooling unit in gallons per minute, and liters per second, that is required to
result in the stated performance. For base loads, ACRC301S units should not
have a flow rate greater than 1.3 l/s (20.8 GPM), ACRC301H units should not
have a flow rate greater than 1.95 l/s (30.9 GPM), and ACRC600 series units
should not have a flow rate greater than 2.08 l/s (33 GPM); peak loads may
exceed these flow rates by up to 25 percent for short time spans.
Total CW pressure drop (kPa and ft H2O) — The differential pressure observed
between inlet and outlet chilled water connections for the stated CW flow rate.

40 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Recommended Capacity Limitations


ACRC301S
IT Equipment Air Flow – l/s per kW (CFM/
IT Equipment ∆T – °C (°F) Recommended Capacity Limit – (kW)
kW)

5.56 (10) 150 (317) 10.1

8.33 (15) 100 (211) 15.1

11.11 (20) 75 (158) 20.3

13.89 (25) 60 (128) 25.0

16.67 (30) 50 (107) 30.0

19.44 (35) 43 (92) 34.7

22.22 (40) 38 (81) 39.7

25 (45) 34 (72) 40.0

ACRC301H
IT Equipment Air Flow – l/s per kW (CFM/
IT Equipment ∆T – °C (°F) Recommended Capacity Limit – (kW)
kW)

5.56 (10) 150 (317) 13.3

8.33 (15) 100 (211) 19.9

11.11 (20) 75 (158) 26.5

13.89 (25) 60 (128) 32.9

16.67 (30) 50 (107) 39.4

19.44 (35) 43 (92) 45.6

22.22 (40) 38 (81) 52.1

25 (45) 34 (72) 58.6

ACRC600 series
IT Equipment Air Flow – l/s per kW (CFM/
IT Equipment ∆T – °C (°F) Recommended Capacity Limit – (kW)
kW)

11.0 (19.8) 75.5 (160) 43

11.3 (20.4) 73.2 (155) 45

11.7 (21.1) 70.8 (150) 46

12.1 (21.8) 68.4 (145) 48

12.5 (22.6) 66.1 (140) 49

13.0 (23.4) 63.7 (135) 51

13.5 (24.3) 61.4 (130) 53

14.1 (25.3) 59.0 (125) 55

14.6 (26.4) 56.6 (120) 58

15.3 (27.5) 54.3 (115) 60

15.9 (28.7) 51.9 (110) 63

990-5792B-001 41
ACRC300 Series, ACRC600 Series Technical Data

IT Equipment Air Flow – l/s per kW (CFM/


IT Equipment ∆T – °C (°F) Recommended Capacity Limit – (kW)
kW)

16.7 (30.1) 49.6 (105) 66

17.5 (31.6) 47.2 (100) 69

42 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

ACRC301S
Performance specifications 5°C (41°F) EWT
Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB,63°F WB)

5.5°C (10°F) 21.3 (73000) 20.9 (71000) 0.98 0.97 (15.4) 49.8 (16.7)

6.6°C (12°F) 19.5 (67000) 19.1 (65000) 0.98 0.71 (11.3) 29.3 (9.8)

7.7°C (14°F) 18.0 (62000) 17.7 (60000) 0.98 0.59 (9.3) 20.5 (6.9)

8.8°C (16°F) 16.6 (57000) 16.3 (56000) 0.98 0.48 (7.6) 13.9 (4.7)

10.0°C (18°F) 15.3 (52000) 15.0 (51000) 0.98 0.39 (6.2) 9.1 (3.0)

11.1°C (20°F) 14.1 (48000) 13.8 (47000) 0.98 0.33 (5.2) 6.0 (2.0)

29.4°C DB, 18.1°C WB (85°F DB, 65°F WB)

5.5°C (10°F) 24.8 (85000) 24.3 (83000) 0.98 1.13 (17.9) 64.5 (21.6)

6.6°C (12°F) 23.0 (78000) 22.5 (77000) 0.98 0.86 (13.6) 41.0 (13.7)

7.7°C (14°F) 21.4 (73000) 21 (72000) 0.98 0.69 (11.0) 27.5 (9.2)

8.8°C (16°F) 20.0 (68000) 19.6 (67000) 0.98 0.57 (9.0) 19.2 (6.5)

10.0°C (18°F) 18.7 (64000) 18.4 (63000) 0.98 0.48 (7.5) 13.7 (4.6)

11.1°C (20°F) 17.5 (60000) 17.2 (59000) 0.98 0.40 (6.4) 9.7 (3.3)

32.2°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 28.2 (96000) 27.6 (94000) 0.98 1.27 (20.1) 79.5 (26.7)

6.6°C (12°F) 26.3 (90000) 25.7 (88000) 0.98 0.97 (15.4) 49.8 (16.7)

7.7°C (14°F) 24.8 (85000) 24.3 (83000) 0.98 0.80 (12.7) 35.5 (11.9)

8.8°C (16°F) 23.4 (80000) 23.0 (78000) 0.98 0.66 (10.5) 25.5 (8.5)

10.0°C (18°F) 22.1 (75000) 21.7 (74000) 0.98 0.56 (8.8) 18.5 (6.2)

11.1°C (20°F) 20.9 (71000) 20.5 (70000) 0.98 0.48 (7.5) 13.7 (4.6)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

6.6°C (12°F) 29.7 (101000) 29.1 (99000) 0.98 1.08 (17.1) 61.9 (20.7)

7.7°C (14°F) 28.3 (96000) 27.7 (95000) 0.98 0.91 (14.4) 44.2 (14.8)

8.8°C (16°F) 26.9 (92000) 26.4 (90000) 0.98 0.76 (12.0) 32.3 (10.8)

10.0°C (18°F) 25.6 (87000) 25.0 (85000) 0.98 0.64 (10.2) 23.9 (8.0)

11.1°C (20°F) 24.31 (83000) 23.8 (81000) 0.98 0.55 (8.7) 18.1 (6.1)

37.78°C DB, 20.7°C WB (100°F DB, 69°F WB)

6.6°C (12°F) 33.2 (113000) 32.5 (111000) 0.98 1.23 (19.5) 75.5 (25.3)

7.7°C (14°F) 31.7 (108000) 31.1 (106000) 0.98 1.02 (16.1) 54.1 (18.1)

8.8°C (16°F) 30.2 (103000) 29.6 (101000) 0.98 0.85 (13.5) 39.5 (13.2)

10.0°C (18°F) 28.9 (99000) 28.3 (97000) 0.98 0.72 (11.5) 29.6 (9.9)

11.1°C (20°F) 27.7 (95000) 27.2 (93000) 0.98 0.63 (9.9) 22.9 (7.7)

40.50°C DB, 21.5°C WB (105°F DB, 71°F WB)

7.7°C (14°F) 34.8 (119000) 34.1 (116000) 0.98 1.11 (17.6) 63.1 (21.1)

8.8°C (16°F) 33.5 (114000) 32.8 (112000) 0.98 0.94 (14.9) 46.8 (15.7)

10.0°C (18°F) 32.1 (110000) 31.5 (107000) 0.98 0.80 (12.7) 35.5 (11.9)

990-5792B-001 43
ACRC300 Series, ACRC600 Series Technical Data

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

11.1°C (20°F) 31.0 (106000) 30.3 (104000) 0.98 0.70 (11.0) 27.7(9.3)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

7.7°C (14°F) 38.5 (131000) 37.8 (12900) 0.98 1.24 (19.6) 75.8 (25.4)

8.8°C (16°F) 37.0 (126000) 36.3 (124000) 0.98 1.04 (16.4) 55.7 (18.7)

10.0°C (18°F) 35.7 (122000) 35.0 (119000) 0.98 0.89 (14.1) 42.6 (14.3)

11.1°C (20°F) 34.5 (118000) 33.8 (115000) 0.98 0.78 (12.3) 33.5 (11.2)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

8.8°C (16°F) 40.5 (138000) 39.6 (135000) 0.98 1.13 (17.9) 64.7 (21.7)

10.0°C (18°F) 39.1 (133000) 38.3 (131000) 0.98 0.97 (15.4) 49.7 (16.7)

11.1°C (20°F) 37.9 (129000) 37.2 (127000) 0.98 0.85 (13.5) 39.4 (13.2)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

8.8°C (16°F) 43.9 (150000) 43.0 (147000) 0.98 1.22 (19.4) 74.4 (24.9)

10.0°C (18°F) 42.6 (145000) 41.7 (142000) 0.98 1.05 (16.7) 57.2 (19.2)

11.1°C (20°F) 41.4 (141000) 40.6 (138000) 0.98 0.93 (14.7) 45.8 (15.4)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.

44 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Performance specifications 7.2°C (45°F) EWT (ACRC301S)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB,63°F WB)

5.5°C (10°F) 18.4 (63000) 18.2 (62000) 0.99 0.84 (13.3) 38.7 (13.0)

6.6°C (12°F) 16.6 (57000) 16.5 (56000) 0.99 0.62 (9.8) 22.3 (7.5)

7.7°C (14°F) 15.2 (52000) 15.1 (51000) 0.99 0.50 (8.0) 15.2 (5.1)

8.8°C (16°F) 13.8 (47000) 13.7 (47000) 0.99 0.40 (6.3) 9.6 (3.2)

10.0°C (18°F) 12.6 (43000) 12.5 (43000) 0.99 0.33 (5.2) 6.1 (2.1)

11.1°C (20°F) 11.5 (39000) 11.4 (39000) 0.99 0.27 (4.3) 3.7 (1.2)

29.4°C DB, 18.1°C WB (85°F DB, 65°F WB)

5.5°C (10°F) 21.8 (74000) 21.6 (74000) 0.99 0.99 (15.8) 51.9 (17.4)

6.6°C (12°F) 19.8 (68000) 19.6 (67000) 0.99 0.76 (12.0) 32.3 (10.8)

7.7°C (14°F) 18.7 (64000) 18.5 (63000) 0.99 0.61 (9.6) 21.7 (7.3)

8.8°C (16°F) 17.3 (59000) 17.2 (59000) 0.99 0.50 (7.9) 14.8 (5.0)

10.0°C (18°F) 16.1 (55000) 15.9 (54000) 0.99 0.41 (6.5) 10.2 (3.4)

11.1°C (20°F) 14.9 (51000) 14.7 (50000) 0.99 0.34 (5.4) 6.8 (2.3)

32.2°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 25.2 (86000) 25.0 (85000) 0.99 1.14 (18.1) 65.7 (22.0)

6.6°C (12°F) 23.5 (80000) 23.3 (79000) 0.99 0.87 (13.8) 41.3 (13.9)

7.7°C (14°F) 22.1 (75000) 21.9 (75000) 0.99 0.72 (11.4) 29.2 (9.8)

8.8°C (16°F) 20.7 (71000) 20.5 (70000) 0.99 0.59 (9.3) 20.5 (6.9)

10.0°C (18°F) 19.5 (66000) 19.3 (66000) 0.99 0.49 (7.8) 14.6 (4.9)

11.1°C (20°F) 18.3 (62000) 18.1 (62000) 0.99 0.42 (6.6) 10.6 (3.5)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

5.5°C (10°F) 28.7 (98000) 28.4 (97000) 0.99 1.29 (20.5) 81.7 (27.4)

6.6°C (12°F) 27.0 (92000) 26.7 (91000) 0.99 0.99 (15.7) 51.4 (17.2)

7.7°C (14°F) 25.5 (87000) 25.3 (86000) 0.99 0.82 (13.1) 37.3 (12.5)

8.8°C (16°F) 24.2 (83000) 24.0 (82000) 0.99 0.69 (10.9) 27.0 (9.1)

10.0°C (18°F) 22.9 (78000) 22.7 (77000) 0.99 0.58 (9.1) 19.7 (6.6)

11.1°C (20°F) 21.7 (74000) 21.5 (73000) 0.99 0.49 (7.8) 14.7 (4.9)

37.78°C DB, 20.7°C WB (100°F DB, 69°F WB)

6.6°C (12°F) 30.4 (104000) 30.1 (103000) 0.99 1.13 (17.9) 65.0 (21.8)

7.7°C (14°F) 28.9 (99000) 28.6 (98000) 0.99 0.93 (14.8) 46.5 (15.6)

8.8°C (16°F) 27.5 (94000) 27.3 (93000) 0.99 0.78 (12.3) 33.6 (11.3)

10.0°C (18°F) 26.3 (90000) 26.0 (89000) 0.99 0.66 (10.4) 25.0 (8.4)

11.1°C (20°F) 25.1 (86000) 24.9 (85000) 0.99 0.57 (9.0) 19.1 (6.4)

40.50°C DB, 21.5°C WB (105°F DB, 71°F WB)

6.6°C (12°F) 33.6 (115000) 33.3 (114000) 0.99 1.25 (19.8) 77.3 (25.9)

7.7°C (14°F) 32.1 (110000) 31.8 (109000) 0.99 1.03 (16.3) 55.1 (18.5)

8.8°C (16°F) 30.8 (105000) 30.5 (104000) 0.99 0.87 (13.7) 10.7 (13.7)

10.0°C (18°F) 29.6 (101000) 29.3 (100000) 0.99 0.74 (11.7) 30.8 (10.3)

990-5792B-001 45
ACRC300 Series, ACRC600 Series Technical Data

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

11.1°C (20°F) 28.4 (97000) 28.1 (96000) 0.99 0.64 (10.1) 23.8 (8.0)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

7.7°C (14°F) 35.8 (122000) 35.4 (121000) 0.99 1.15 (18.2) 66.9 (22.4)

8.8°C (16°F) 34.4 (117000) 34.0 (116000) 0.99 0.96 (15.3) 49.1 (16.5)

10.0°C (18°F) 33.1 (113000) 32.8 (112000) 0.99 0.82 (13.0) 37.1 (12.5)

11.1°C (20°F) 31.9 (109000) 31.6 (108000) 0.99 0.72 (11.4) 29.2 (9.8)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

7.7°C (14°F) 39.2 (134000) 38.8 (132000) 0.99 1.26 (20.0) 78.3 (26.3)

8.8°C (16°F) 37.8 (129000) 37.4 (128000) 0.99 1.06 (16.8) 57.7 (19.3)

10.0°C (18°F) 36.5 (124000) 36.1 (123000) 0.99 0.90 (14.3) 43.9 (14.7)

11.1°C (20°F) 35.3 (120000) 35.0 (119000) 0.99 0.79 (12.5) 34.8 (11.7)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

8.8°C (16°F) 43.9 (150000) 40.8 (140000) 0.99 1.15 (18.2) 66.8 (22.4)

10.0°C (18°F) 39.9 (136000) 39.5 (135000) 0.99 0.99 (15.7) 51.3 (17.2)

11.1°C (20°F) 38.8 (132000) 38.4 (131000) 0.99 0.87 (13.8) 40.9 (13.7)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.

46 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Performance specifications 8.8°C (48°F) EWT (ACRC301S)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB,63°F WB)

5.5°C (10°F) 16.2 (55000) 16.0 (55000) 0.99 0.75 (11.8) 31.4 (10.5)

6.6°C (12°F) 14.6 (50000) 14.5 (49000) 0.99 0.56 (8.8) 17.9 (6.0)

7.7°C (14°F) 13.2 (45000) 13.1 (45000) 0.99 0.44 (7.0) 11.7 (3.9)

8.8°C (16°F) 11.9 (41000) 11.8 (40000) 0.99 0.35 (5.5) 7.1 (2.4)

10.0°C (18°F) 10.7 (37000) 10.6 (36000) 0.99 0.28 (4.4) 4.0 (1.3)

29.4°C DB, 18.1°C WB (85°F DB, 65°F WB)

5.5°C (10°F) 19.7 (67000) 19.5 (66000) 0.99 0.90 (14.3) 43.5 (14.6)

6.6°C (12°F) 18.2 (62000) 18.0 (61000) 0.99 0.69 (10.9) 26.1 (8.8)

7.7°C (14°F) 16.7 (57000) 16.5 (56000) 0.99 0.55 (8.6) 17.8 (6.0)

8.8°C (16°F) 15.4 (52000) 15.2 (52000) 0.99 0.44 (7.0) 11.8 (4.0)

10.0°C (18°F) 14.2 (48000) 14.0 (48000) 0.99 0.36 (5.8) 7.8 (2.6)

11.1°C (20°F) 13.0 (44000) 12.8 (44000) 0.99 0.30 (4.8) 4.9 (1.7)

32.2°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 23.0 (79000) 22.8 (78000) 0.99 1.04 (16.6) 56.5 (18.9)

6.6°C (12°F) 21.5 (73000) 21.2 (72000) 0.99 0.82 (13.0) 36.8 (12.3)

7.7°C (14°F) 20.1 (69000) 19.9 (68000) 0.99 0.65 (10.4) 24.8 (8.3)

8.8°C (16°F) 18.8 (64000) 18.6 (63000) 0.99 0.54 (8.5) 17.3 (5.8)

10.0°C (18°F) 17.5 (60000) 17.4 (59000) 0.99 0.45 (7.1) 12.1 (4.1)

11.1°C (20°F) 16.4 (56000) 16.2 (55000) 0.99 0.38 (6.0) 8.5 (2.9)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

5.5°C (10°F) 26.5 (91000) 26.3 (90000) 0.99 1.20 (19.0) 71.7 (24.0)

6.6°C (12°F) 25.0 (85000) 24.8 (85000) 0.99 0.95 (15.1) 46.6 (15.6)

7.7°C (14°F) 23.6 (80000) 23.3 (80000) 0.99 0.76 (12.1) 32.5 (10.9)

8.8°C (16°F) 22.3 (76000) 22.0 (75000) 0.99 0.63 (10.0) 23.4 (7.8)

10.0°C (18°F) 21.0 (72000) 20.8 (71000) 0.99 0.53 (8.4) 16.9 (5.7)

11.1°C (20°F) 19.8 (68000) 19.6 (67000) 0.99 0.45 (7.2) 12.3 (4.1)

37.78°C DB, 20.7°C WB (100°F DB, 69°F WB)

6.6°C (12°F) 28.5 (97000) 28.2 (96000) 0.99 1.08 (17.0) 59.5 (19.9)

7.7°C (14°F) 26.9 (92000) 26.7 (91000) 0.99 0.87 (13.8) 41.2 (13.8)

8.8°C (16°F) 25.6 (87000) 25.3 (86000) 0.99 0.72 (11.5) 29.7 (10.0)

10.0°C (18°F) 24.4 (83000) 24.1 (82000) 0.99 0.61 (9.7) 22.0 (7.4)

11.1°C (20°F) 23.2 (79000) 23.0 (78000) 0.99 0.53 (8.4) 16.7 (5.6)

40.50°C DB, 21.5°C WB (105°F DB, 71°F WB)

6.6°C (12°F) 32.1 (109000) 31.8 (108000) 0.99 1.21 (19.2) 72.2 (24.2)

7.7°C (14°F) 30.2 (103000) 29.9 (102000) 0.99 0.97 (15.4) 49.6 (16.6)

8.8°C (16°F) 28.9 (99000) 28.6 (98000) 0.99 0.81 (12.9) 36.5 (12.2)

10.0°C (18°F) 27.7 (94000) 27.4 (93000) 0.99 0.69 (11.0) 27.5 (9.2)

11.1°C (20°F) 26.5 (90000) 26.2 (90000) 0.99 0.60 (9.5) 21.1 (7.1)

990-5792B-001 47
ACRC300 Series, ACRC600 Series Technical Data

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

7.7°C (14°F) 33.8 (115000) 33.4 (114000) 0.99 1.09 (17.2) 60.6 (20.3)

8.8°C (16°F) 32.4 (111000) 32.1 (110000) 0.99 0.91 (14.4) 44.5 (14.9)

10.0°C (18°F) 31.2 (106000) 30.9 (105000) 0.99 0.78 (12.3) 33.7 (11.3)

11.1°C (20°F) 30.0 (102000) 29.7 (101000) 0.99 0.68 (10.7) 26.4 (8.9)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

7.7°C (14°F) 37.2 (127000) 36.8 (126000) 0.99 1.20 (19.0) 71.6 (24.0)

8.8°C (16°F) 35.8 (122000) 35.5 (121000) 0.99 1.00 (15.9) 52.8 (17.7)

10.0°C (18°F) 34.6 (118000) 34.2 (117000) 0.99 0.86 (13.6) 40.2 (13.5)

11.1°C (20°F) 33.4 (114000) 33.1 (113000) 0.99 0.75 (11.9) 31.8 (10.7)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

7.7°C (14°F) 40.7 (139000) 40.3 (137000) 0.99 1.31 (20.7) 83.5 (28.0)

8.8°C (16°F) 39.3 (134000) 38.9 (133000) 0.99 1.10 (17.4) 61.5 (20.6)

10.0°C (18°F) 38.0 (130000) 37.6 (128000) 0.99 0.94 (14.9) 27.2 (15.8)

11.1°C (20°F) 36.8 (126000) 36.5 (124000) 0.99 0.83 (13.1) 37.5 (12.6)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.

Performance specifications 10°C (50°F) EWT (ACRC301S)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB,63°F WB)

5.5°C (10°F) 14.6 (50000) 16.0 (55000) 1.00 0.67 (10.7) 26.2 (8.8)

6.6°C (12°F) 13.1 (45000) 14.5 (49000) 1.00 0.48 (7.7) 13.6 (4.6)

7.7°C (14°F) 11.7 (40000)) 13.1 (45000) 1.00 0.39 (6.2) 9.2 (3.1)

8.8°C (16°F) 10.7 (36000) 11.8 (40000) 1.00 0.31 (4.9) 5.2 (1.7)

10.0°C (18°F) 9.4 (32000) 10.6 (36000) 1.00 0.25 (4.0) 2.8 (0.9)

29.4°C DB, 18.1°C WB (85°F DB, 65°F WB)

5.5°C (10°F) 18.0 (62000) 18.0 (62000) 1.00 0.83 (13.1) 37.6 (12.6)

6.6°C (12°F) 16.5 (56000) 16.5 (56000) 1.00 0.61 (9.7) 21.6 (7.2)

7.7°C (14°F) 15.2 (52000) 15.2 (52000) 1.00 0.50 (7.9) 15.0 (5.0)

8.8°C (16°F) 13.9 (47000) 13.9 (47000) 1.00 0.40 (6.4) 9.8 (3.3)

10.0°C (18°F) 12.7 (43000) 12.7 (43000) 1.00 0.33 (5.2) 6.2 (2.1)

11.1°C (20°F) 11.5 (39000) 11.5 (39000) 1.00 0.27 (4.3) 3.6 (1.2)

32.2°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 21.4 (73000) 21.4 (73000) 1.00 0.97 (15.4) 50.1 (16.8)

6.6°C (12°F) 19.9 (68000) 19.9 (68000) 1.00 0.74 (11.7) 31.0 (10.4)

7.7°C (14°F) 18.6 (63000) 18.6 (63000) 1.00 0.61 (9.6) 21.7 (7.3)

48 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

8.8°C (16°F) 17.3 (59000) 17.3 (59000) 1.00 0.50 (7.9) 14.8 (5.0)

10.0°C (18°F) 16.1 (55000) 16.1 (55000) 1.00 0.41 (6.6) 10.4 (3.5)

11.1°C (20°F) 15.0 (51000) 15.0 (51000) 1.00 0.34 (5.5) 6.9 (2.3)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

5.5°C (10°F) 24.9 (85000) 24.9 (85000) 1.00 1.13 (17.9) 64.5 (21.6)

6.6°C (12°F) 23.5 (80000) 23.5 (80000) 1.00 0.87 (13.8) 40.8 (13.7)

7.7°C (14°F) 22.1 (75000) 22.1 (75000) 1.00 0.72 (11.3) 29.1 (9.8)

8.8°C (16°F) 20.8 (71000) 20.8 (71000) 1.00 0.59 (9.4) 20.7 (7.0)

10.0°C (18°F) 19.6 (67000) 19.6 (67000) 1.00 0.49 (7.8) 14.8 (5.0)

11.1°C (20°F) 18.4 (63000) 18.4 (63000) 1.00 0.42 (6.7) 10.7 (3.6)

37.78°C DB, 21.5°C WB (100°F DB, 71°F WB)

5.5°C (10°F) 28.2 (96000) 28.2 (96000) 1.00 1.27 (20.2) 79.8 (26.8)

6.6°C (12°F) 26.6 (91000) 26.6 (91000) 1.00 1.00 (15.9) 52.7 (17.7)

7.7°C (14°F) 25.4 (87000) 25.4 (87000) 1.00 0.82 (13.0) 37.3 (12.5)

8.8°C (16°F) 24.1 (82000) 24.1 (82000) 1.00 0.68 (10.8) 26.8 (9.0)

10.0°C (18°F) 22.9 (78000) 22.9 (78000) 1.00 0.58 (9.2) 19.8 (6.7)

11.1°C (20°F) 21.8 (74000) 21.8 (74000) 1.00 0.49 (7.8) 14.7 (4.9)

40.50°C DB, 21.5°C WB (105°F DB, 71°F WB)

6.6°C (12°F) 29.6 (101000) 29.6 (101000) 1.00 1.12 (17.7) 64.1 (21.5)

7.7°C (14°F) 28.7 (98000) 28.7 (98000) 1.00 0.92 (14.6) 45.6 (15.3)

8.8°C (16°F) 27.4 (94000) 27.4 (94000) 1.00 0.77 (12.3) 33.5 (11.2)

10.0°C (18°F) 26.2 (90000) 26.2 (90000) 1.00 0.66 (10.4) 25.1 (8.4)

11.1°C (20°F) 25.1 (86000) 25.1 (86000) 1.00 0.57 (9.0) 19.2 (6.4)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

6.6°C (12°F) 33.5 (114000) 33.5 (114000) 1.00 1.26 (20.0) 78.9 (38.7)

7.7°C (14°F) 32.3 (110000) 32.3 (110000) 1.00 1.04 (16.5) 56.0 (18.8)

8.8°C (16°F) 31.0 (106000) 31.0 (106000) 1.00 0.87 (13.8) 41.0 (13.8)

10.0°C (18°F) 29.7 (101000) 29.7 (101000) 1.00 0.74 (11.) 31.1 (10.4)

11.1°C (20°F) 28.6 (98000) 28.6 (98000) 1.00 0.64 (10.2) 24.0 (8.1)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

7.7°C (14°F) 35.7 (122000) 35.7 (122000) 1.00 1.15 (18.2) 66.6 (22.3)

8.8°C (16°F) 34.4 (117000) 34.4 (117000) 1.00 0.96 (15.3) 49.0 (16.4)

10.0°C (18°F) 33.1 (113000) 33.1 (113000) 1.00 0.83 (13.1) 37.5 (12.6)

11.1°C (20°F) 32.0 (109000) 32.0 (109000) 1.00 0.72 (11.4) 29.2 (9.8)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

7.7°C (14°F) 39.1 (134000) 39.1 (134000) 1.00 1.26 (19.9) 78.0 (26.2)

8.8°C (16°F) 37.8 (129000) 37.7 (129000) 1.00 1.06 (16.7) 57.6 (19.3)

10.0°C (18°F) 36.5 (125000) 36.5 (125000) 1.00 0.91 (14.4) 44.2 (14.8)

11.1°C (20°F) 35.4 (121000) 35.4 (121000) 1.00 0.79 (12.6) 35.0 (11.7)

990-5792B-001 49
ACRC300 Series, ACRC600 Series Technical Data

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.

Performance specifications 12.7°C (55°F) EWT (ACRC301S)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB,63°F WB)

5.5°C (10°F) 11.0 (37000) 11.0 (37000) 1.00 0.51 (8.2) 15.9 (5.3)

6.6°C (12°F) 9.6 (33000) 9.6 (33000) 1.00 0.38 (6.0) 8.5 (2.9)

7.7°C (14°F) 8.3 (28000) 8.3 (28000) 1.00 0.28 (4.5) 4.2 (1.4)

29.4°C DB, 18.1°C WB (85°F DB, 65°F WB)

5.5°C (10°F) 14.4 (49000) 14.4 (49000) 1.00 0.67 (10.6) 25.6 (8.6)

6.6°C (12°F) 13.1 (45000) 13.1 (45000) 1.00 0.51 (8.1) 15.7 (5.2)

7.7°C (14°F) 11.8 (40000) 11.8 (40000) 1.00 0.39 (6.3) 9.4 (3.1)

8.8°C (16°F) 10.6 (36000) 10.6 (36000) 1.00 0.31 (4.9) 5.4 (1.8)

10.0°C (18°F) 9.4 (32000) 9.4 (32000) 1.00 0.25 (4.0) 2.7 (0.9)

32.2°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 17.8 (61000) 17.8 (61000) 1.00 0.82 (12.9) 36.7 (12.3)

6.6°C (12°F) 16.6 (56000) 16.6 (56000) 1.00 0.63 (10.0) 23.3 (7.8)

7.7°C (14°F) 15.2 (52000) 15.2 (52000) 1.00 0.50 (8.0) 15.2 (5.1)

8.8°C (16°F) 14.1 (48000) 14.1 (48000) 1.00 0.41 (6.5) 10.1 (3.4)

10.0°C (18°F) 12.9 (44000) 12.9 (44000) 1.00 0.33 (5.3) 6.4 (2.1)

11.1°C (20°F) 11.7 (40000) 11.7 (40000) 1.00 0.27 (4.3) 3.7 (1.2)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

5.5°C (10°F) 21.3 (73000) 21.3 (73000) 1.00 0.97 (15.4) 49.6 (16.6)

6.6°C (12°F) 20.0 (68000) 20.0 (68000) 1.00 0.76 (12.0) 32.4 (10.8)

7.7°C (14°F) 18.7 (64000) 18.7 (64000) 1.00 0.61 (9.7) 22.0 (7.4)

8.8°C (16°F) 17.5 (60000) 17.5 (60000) 1.00 0.50 (8.0) 15.2 (5.1)

10.0°C (18°F) 16.3 (56000) 16.3 (56000) 1.00 0.42 (6.6) 10.5 (3.5)

11.1°C (20°F) 15.2 (52000) 15.2 (52000) 1.00 0.35 (5.5) 7.2 (2.4)

37.78°C DB, 21.5°C WB (100°F DB, 71°F WB)

5.5°C (10°F) 24.6 (84000) 24.6 (84000) 1.00 1.12 (17.7) 63.4 (21.3)

6.6°C (12°F) 23.4 (80000) 23.4 (80000) 1.00 0.88 (14.0) 42.3 (14.2)

7.7°C (14°F) 22.1 (75000) 22.1 (75000) 1.00 0.72 (11.4) 29.2 (9.8)

8.8°C (16°F) 20.9 (71000) 20.9 (71000) 1.00 0.60 (9.4) 20.9 (7.0)

10.0°C (18°F) 19.7 (67000) 19.7 (67000) 1.00 0.50 (7.9) 15.0 (5.0)

11.1°C (20°F) 18.5 (63000) 18.5 (63000) 1.00 0.42 (6.7) 10.8 (3.6)

40.50°C DB, 21.5°C WB (105°F DB, 71°F WB)

5.5°C (10°F) 27.9 (95000) 27.9 (95000) 1.00 1.25 (19.9) 77.7 (26.1)

6.6°C (12°F) 26.9 (92000) 26.9 (92000) 1.00 1.01 (16.0) 53.0 (17.8)

7.7°C (14°F) 25.4 (87000) 25.4 (87000) 1.00 0.82 (13.0) 37.2 (12.5)

50 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

8.8°C (16°F) 24.2 (83000) 24.2 (83000) 1.00 0.69 (10.9) 27.0 (9.0)

10.0°C (18°F) 23.1 (79000) 23.1 (79000) 1.00 0.58 (9.2) 20.1 (6.7)

11.1°C (20°F) 21.9 (75000) 21.9 (75000) 1.00 0.50 (7.9) 15.0 (5.0)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

6.6°C (12°F) 30.3 (103000) 30.3 (103000) 1.00 1.14 (18.0) 65.5 (22.0)

7.7°C (14°F) 28.9 (99000) 28.9 (99000) 1.00 0.93 (14.8) 46.3 (15.5)

8.8°C (16°F) 27.7 (94000) 27.7 (94000) 1.00 0.78 (12.4) 34.1 (11.4)

10.0°C (18°F) 26.5 (90000) 26.5 (90000) 1.00 0.66 (10.5) 25.5 (8.5)

11.1°C (20°F) 25.4 (87000) 25.4 (87000) 1.00 0.57 (9.1) 19.5 (6.5)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

6.6°C (12°F) 33.7 (115000) 33.7 (115000) 1.00 1.26 (20.0) 78.8 (26.4)

7.7°C (14°F) 32.3 (110000) 32.3 (110000) 1.00 1.04 (16.5) 56.0 (18.8)

8.8°C (16°F) 31.1 (106000) 31.1 (106000) 1.00 0.88 (13.9) 41.5 (13.9)

10.0°C (18°F) 29.9 (102000) 29.9 (102000) 1.00 0.75 (11.8) 31.4 (10.5)

11.1°C (20°F) 28.8 (98000) 28.8 (98000) 1.00 0.65 (10.3) 24.3 (8.2)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

7.7°C (14°F) 35.7 (122000) 35.7 (122000) 1.00 1.15 (18.1) 66.4 (22.2)

8.8°C (16°F) 34.5 (118000) 34.5 (118000) 1.00 0.97 (15.3) 49.3 (16.5)

10.0°C (18°F) 33.3 (114000) 33.3 (114000) 1.00 0.83 (13.1) 37.8 (12.7)

11.1°C (20°F) 32.2 (110000) 32.2 (110000) 1.00 0.72 (11.5) 29.7 (10.0)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.

Performance specifications 15°C (59°F) EWT (ACRC301S)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB,63°F WB)

5.5°C (10°F) 7.9 (27000) 7.9 (27000) 1.00 0.38 (6.0) 8.5 (2.9)

6.6°C (12°F) 7.0 (24000) 7.0 (24000) 1.00 0.28 (4.4) 5.3 (1.8)

29.4°C DB, 18.1°C WB (85°F DB, 65°F WB)

5.5°C (10°F) 11.3 (39000) 11.3 (39000) 1.00 0.53 (8.4) 16.8 (5.6)

6.6°C (12°F) 10.4 (36000) 10.4 (36000) 1.00 0.41 (6.4) 10.2 (3.4)

7.7°C (14°F) 9.0 (31000) 9.0 (31000) 1.00 0.31 (4.8) 5.1 (1.7)

8.8°C (16°F) 7.8 (27000) 7.8 (27000) 1.00 0.24 (3.7) 2.1 (0.7)

32.22°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 14.7 (50000) 14.7 (50000) 1.00 0.68 (10.8)) 26.5 (8.9)

6.6°C (12°F) 13.6 (46000) 13.6 (46000) 1.00 0.53 (8.4) 17.0 (5.7)

7.7°C (14°F) 12.5 (42000) 12.5 (42000) 1.00 0.42 (6.6) 10.5 (3.5)

990-5792B-001 51
ACRC300 Series, ACRC600 Series Technical Data

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

8.8°C (16°F) 11.3 (38000) 11.3 (38000) 1.00 0.33 (5.3) 6.3 (2.1)

10.0°C (18°F) 10.1 (34000) 10.1 (34000) 1.00 0.27 (4.2) 3.4 (1.1)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

5.5°C (10°F) 18.1 (62000) 18.1 (62000) 1.00 0.83 (13.2) 38.2 (12.8)

6.6°C (12°F) 17.3 (59000) 17.3 (59000) 1.00 0.66 (10.5) 24.4 (8.2)

7.7°C (14°F) 15.9 (54000) 15.9 (54000) 1.00 0.52 (8.3)) 16.5 (5.5)

8.8°C (16°F) 14.7 (50000) 14.7 (50000) 1.00 0.43 (6.7) 11.0 (3.7)

10.0°C (18°F) 13.5 (46000) 13.5 (46000) 1.00 0.35 (5.5) 7.1 (2.4)

11.1°C (20°F) 12.4 (42000) 12.4 (42000) 1.00 0.29 (4.6) 4.4 (1.5)

37.78°C DB, 20.7°C WB (100°F DB, 69°F WB)

5.5°C (10°F) 21.5 (73000) 21.5 (73000) 1.00 0.98 (15.5) 50.5 (16.9)

6.6°C (12°F) 20.7 (71000) 20.7 (71000) 1.00 0.78 (12.4) 34.1 (11.4)

7.7°C (14°F) 19.2 (66000) 19.2 (66000) 1.00 0.63 (10.0) 23.1 (7.7)

8.8°C (16°F) 18.1 (62000) 18.1 (62000) 1.00 0.52 (8.2) 16.2 (5.4)

10.0°C (18°F) 16.9 (58000) 16.9 (58000) 1.00 0.43 (6.9) 11.4 (3.8)

11.1°C (20°F) 15.8 (54000) 15.8 (54000) 1.00 0.36 (5.8) 7.8 (2.6)

40.50°C DB, 21.59°C WB (105°F DB, 71°F WB)

5.5°C (10°F) 24.8 (85000) 24.8 (85000) 1.00 1.12 (17.7) 63.8 (21.4)

6.6°C (12°F) 23.7 (81000) 23.7 (81000) 1.00 0.91 (14.4) 42.7 (14.3)

7.7°C (14°F) 22.6 (77000)) 22.6 (77000) 1.00 0.74 (11.7) 30.6 (10.2)

8.8°C (16°F) 21.4 (73000) 21.4 (73000) 1.00 0.61 (9.7) 21.9 (7.3)

10.0°C (18°F) 20.4 (69000) 20.4 (69000) 1.00 0.52 (8.2) 16.1 (5.4)

11.1°C (20°F) 19.2 (66000) 19.2 (66000) 1.00 0.44 (7.0) 11.7 (3.9)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

5.5°C (10°F) 28.3 (97000) 28.3 (97000) 1.00 1.28 (20.3) 80.5 (27.0)

6.6°C (12°F) 27.3 (93000) 27.3 (93000) 1.00 01.03 (16.4) 55.4 (18.6)

7.7°C (14°F) 26.0 (89000) 26.0 (89000) 1.00 0.84 (13.3) 38.6 (13.0)

8.8°C (16°F) 24.9 (85000) 24.9 (85000) 1.00 0.70 (11.2) 28.3 (9.5)

10.0°C (18°F) 23.8 (81000) 23.8 (81000) 1.00 0.60 (9.5) 21.1 (7.1)

11.1°C (20°F) 22.6 (77000) 22.6 (77000) 1.00 0.51 (8.1) 15.8 (5.3)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

6.6°C (12°F) 30.7 (108000) 30.7 (108000) 1.00 1.16 (18.4) 67.7 (22.7)

7.7°C (14°F) 29.4 (100000) 29.4 (100000) 1.00 0.95 (15.0) 47.6 (16.0)

8.8°C (16°F) 28.3 (96000) 28.3 (96000) 1.00 0.80 (12.6) 35.3 (11.8)

10.0°C (18°F) 27.2 (93000) 27.2 (93000) 1.00 0.68 (10.8) 26.7 (9.0)

11.1°C (20°F) 26.0 (89000) 26.0 (89000) 1.00 0.59 (9.3) 20.4 (6.8)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

6.6°C (12°F) 34.0 (116000) 34.0 (116000) 1.00 1.28 (20.3) 79.4 (26.6)

7.7°C (14°F) 32.8 (112000) 32.8 (112000) 1.00 1.05 (16.6) 57.0 (19.1)

8.8°C (16°F) 31.7 (108000) 31.7 (108000) 1.00 0.89 (14.1) 42.7 (14.3)

52 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

10.0°C (18°F) 30.5 (104000) 30.5 (104000) 1.00 0.76 (12.1) 32.6 (10.9)

11.1°C (20°F) 29.4 (104000) 29.4 (104000) 1.00 0.66 (10.5) 25.4 (8.5)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.

ACRC301H
Performance specifications 10°C (50°F) EWT
Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 16.2°C WB (80°F DB,61°F WB)

5.5°C (10°F) 23.0 (79000) 23.0 (79000) 1.00 1.12 (17.8) 31.3 (10.5)

6.6°C (12°F) 21.5 (73000) 21.5 (73000) 1.00 0.88 (14.0) 20.0 (6.7)

7.7°C (14°F) 19.8 (68000) 19.8 (68000) 1.00 0.70 (11.1) 13.0 (4.4)

8.8°C (16°F) 18.1 (62000) 18.1 (62000) 1.00 0.56 (8.9) 8.8 (2.9)

10.0°C (18°F) 16.3 (56000) 16.3 (56000) 1.00 0.45 (7.2) 6.0 (2.0)

11.1°C (20°F) 14.6 (50000) 14.6 (50000) 1.00 0.37 (5.9) 4.2 (1.4)

29.4°C DB, 17.1°C WB (85°F DB, 63°F WB)

5.5°C (10°F) 27.3 (93000) 27.3 (93000) 1.00 1.32 (20.9) 42.3 (14.2)

6.6°C (12°F) 26.1 (89000) 26.1 (89000) 1.00 1.09 (17.3) 30.8 (10.3)

7.7°C (14°F) 24.4 (83000) 24.4 (83000) 1.00 0.84 (13.3) 18.3 (6.1)

8.8°C (16°F) 22.6 (77000) 22.6 (77000) 1.00 0.69 (10.9) 12.8 (4.3)

10.0°C (18°F) 20.8 (71000) 20.8 (71000) 1.00 0.57 (9.0) 9.0 (3.0)

11.1°C (20°F) 19.1 (65000) 19.1 (65000) 1.00 0.47 (7.5) 6.4 (2.2)

32.2°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 33.5 (114000) 33.5 (114000) 1.00 1.60 (25.3) 60.7 (20.4)

6.6°C (12°F) 32.1 (110000) 32.1 (110000) 1.00 1.30 (20.6) 41.3 (13.8)

7.7°C (14°F) 30.5 (104000) 30.5 (104000) 1.00 1.05 (16.6) 27.4 (9.2)

8.8°C (16°F) 28.9 (99000) 28.9 (99000) 1.00 0.87 (13.8) 19.6 (6.6)

10.0°C (18°F) 27.2 (93000) 27.2 (93000) 1.00 0.73 (11.6) 14.2 (4.8)

11.1°C (20°F) 25.6 (87000) 25.6 (87000) 1.00 0.62 (9.8) 10.5 (3.5)

35°C DB, 19°C WB (95°F DB, 66°F WB)

5.5°C (10°F) 39.4 (134000) 39.4 (134000) 1.00 1.88 (29.8) 82.6 (27.7)

6.6°C (12°F) 38.0 (130000) 38.0 (130000) 1.00 1.52 (24.0)) 55.4 (18.6)

7.7°C (14°F) 36.6 (125000) 36.6 (125000) 1.00 1.25 (19.8) 38.3 (12.8)

8.8°C (16°F) 35.2 (120000) 35.2 (120000) 1.00 1.05 (16.6) 27.6 (9.3)

10.0°C (18°F) 33.6 (115000) 33.6 (115000) 1.00 0.89 (14.1) 20.3 (6.8)

11.1°C (20°F) 32.2 (110000) 32.2 (110000) 1.00 0.77 (12.2) 15.6 (5.2)

37.78°C DB, 20.7°C WB (100°F DB, 69°F WB)

990-5792B-001 53
ACRC300 Series, ACRC600 Series Technical Data

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

6.6°C (12°F) 43.1 (147000) 43.1 (147000) 1.00 1.72 (27.3) 70.2 (23.5)

7.7°C (14°F) 41.5 (141000) 41.5 (141000) 1.00 1.40 (22.2) 47.5 (15.9)

8.8°C (16°F) 40.0 (136000) 40.0 (136000) 1.00 1.19 (18.8) 34.7 (11.6)

10.0°C (18°F) 38.4 (131000) 38.4 (131000) 1.00 1.01 (16.1) 25.9 (8.7)

11.1°C (20°F) 36.9 (126000) 36.9 (126000) 1.00 0.88 (13.9) 19.8 (6.6)

40.50°C DB, 20.8°C WB (105°F DB, 69°F WB)

6.6°C (12°F) 48.2 (164000) 48.2 (164000) 1.00 1.92 (30.4) 88.3 (29.6)

7.7°C (14°F) 46.7 (159000) 46.7 (159000) 1.00 1.57 (24.9) 58.7 (19.7)

8.8°C (16°F) 45.3 (155000) 45.3 (155000) 1.00 1.33 (21.1) 43.1 (14.5)

10.0°C (18°F) 43.8 (149000) 43.8 (149000) 1.00 1.14 (18.1) 32.4 (10.9)

11.1°C (20°F) 42.3 (144000) 42.3 (144000) 1.00 1.00 (15.8) 25.2 (8.4)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

7.7°C (14°F) 52.4 (179000) 52.4 (179000) 1.00 1.76 (27.9) 73.0 (24.5)

8.8°C (16°F) 51.1 (174000) 51.1 (174000) 1.00 1.50 (23.8) 54.0 (18.1)

10.0°C (18°F) 49.6 (169000) 49.6 (169000) 1.00 1.29 (20.5) 40.9 (13.7)

11.1°C (20°F) 48.2 (164000) 48.2 (164000) 1.00 1.13 (17.9) 31.7 (10.6)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

7.7°C (14°F) 57.9 (198000) 57.9 (198000) 1.00 1.94 (30.7) 87.7 (29.4)

8.8°C (16°F) 56.6 (193000) 56.6 (193000) 1.00 1.66 (26.3) 65.3 (21.9)

10.0°C (18°F) 55.2 (189000) 55.2 (189000) 1.00 1.44 (22.8) 49.7 (16.7)

11.1°C (20°F) 53.9 (184000) 53.9 (184000) 1.00 1.26 (19.9) 38.7 (13.0)

48.89°C DB, 23.3°C WB (120°F DB, 74°F WB)

8.8°C (16°F) 62.0 (212000) 62.0 (212000) 1.00 1.81 (28.7) 77.3 (25.9)

10.0°C (18°F) 60.7 (207000) 60.7 (207000) 1.00 1.57 (24.9) 59.0 (19.8)

11.1°C (20°F) 59.3 (202000) 59.3 (202000) 1.00 1.38 (21.9) 46.3 (15.5)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Overall cooling capacity will be reduced if the optional dew point
control pump (DPCP) is operating. The DPCP should only be operating if the
dedicated IT room humidity control system or humidity barrier fails. The DPCP
can be disabled via the display interface.

Performance specifications 12.7°C (55°F) EWT (ACRC301H)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB, 63°F WB)

5.5°C (10°F) 17.9 (61000) 17.9 (61000) 1.00 0.89 (14.1) 20.3 (6.8)

6.6°C (12°F) 16.2 (55000) 16.2 (55000) 1.00 0.68 (10.8) 12.4 (4.2)

7.7°C (14°F) 14.5 (49000) 14.5 (49000) 1.00 0.53 (8.3) 7.8 (2.6)

8.8°C (16°F) 12.7 (43000) 12.7 (43000) 1.00 0.41 (6.5) 5.0 (1.7)

54 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

29.4°C DB, 18.1°C WB (85°F DB, 65°F WB)

5.5°C (10°F) 22.3 (76000) 22.3 (76000) 1.00 1.09 (17.2) 29.6 (9.9)

6.6°C (12°F) 20.8 (71000) 20.8 (71000) 1.00 0.85 (13.5) 18.8 (6.3)

7.7°C (14°F) 19.1 (65000) 19.1 (65000) 1.00 0.68 (10.7) 12.3 (4.1)

8.8°C (16°F) 17.4 (59000) 17.4 (59000) 1.00 0.54 (8.6) 8.3 (2.8)

10.0°C (18°F) 15.4 (52000) 15.4 (52000) 1.00 0.44 (6.9) 5.6 (1.9)

11.1°C (20°F) 13.8 (47000) 13.8 (47000) 1.00 0.35 (5.6) 3.8 (1.3)

32.2°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 28.4 (97000) 28.4 (97000) 1.00 1.36 (21.6) 45.1 (15.1)

6.6°C (12°F) 27.1 (92000) 27.1 (92000) 1.00 1.08 (17.2) 29.4 (9.8)

7.7°C (14°F) 25.3 (86000) 25.3 (86000) 1.00 0.88 (13.9) 19.8 (6.6)

8.8°C (16°F) 23.6 (81000) 23.6 (81000) 1.00 0.72 (11.4) 13.8 (3.4)

10.0°C (18°F) 21.7 (75000) 21.7 (75000) 1.00 0.60 (9.6) 10.0 (3.4)

11.1°C (20°F) 20.2 (69000) 20.2 (69000) 1.00 0.51 (8.0) 7.3 (2.4)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

5.5°C (10°F) 34.2 (117000) 34.2 (117000) 1.00 1.64 (26.0) 64.0 (21.5)

6.6°C (12°F) 33.0 (117000) 33.0 (117000) 1.00 1.29 (20.5) 40.9 (13.7)

7.7°C (14°F) 31.4 (107000) 31.4 (107000) 1.00 1.08 (17.1) 29.1 (9.8)

8.8°C (16°F) 29.9 (102000) 29.9 (102000) 1.00 0.90 (14.2) 20.7 (7.0)

10.0°C (18°F) 28.2 (96000) 28.2 (96000) 1.00 0.75 (11.9) 15.0 (5.0)

11.1°C (20°F) 26.7 (91000) 26.7 (91000) 1.00 0.64 (10.2) 11.3 (3.8)

37.78°C DB, 20.7°C WB (100°F DB, 69°F WB)

5.5°C (10°F) 39.2 (134000) 39.2 (134000) 1.00 1.84 (29.2) 79.8 (26.8)

6.6°C (12°F) 37.9 (129000) 37.9 (129000) 1.00 1.51 (23.9) 54.2 (18.2)

7.7°C (14°F) 36.4 (124000) 36.4 (124000) 1.00 1.22 (19.3) 36.3 (12.2)

8.8°C (16°F) 34.8 (119000) 34.8 (119000) 1.00 1.04 (16.4) 27.0 (9.1)

10.0°C (18°F) 33.1 (113000) 33.1 (113000) 1.00 0.89 (14.1) 20.5 (6.9)

11.1°C (20°F) 31.7 (108000) 31.7 (108000) 1.00 0.77 (12.2) 15.6 (5.2)

40.50°C DB, 21.5°C WB (105°F DB, 71°F WB)

6.6°C (12°F) 43.1 (147000) 43.1 (147000) 1.00 1.71 (27.1) 69.3 (23.2)

7.7°C (14°F) 41.8 (143000) 41.8 (143000) 1.00 1.42 (22.5) 48.8 (16.3)

8.8°C (16°F) 40.2 (137000) 40.2 (137000) 1.00 1.19 (18.8) 34.8 (11.7)

10.0°C (18°F) 38.8 (132000) 38.8 (132000) 1.00 1.06 (16.9) 28.4 (9.5)

11.1°C (20°F) 37.3 (127000) 37.3 (127000) 1.00 0.93 (14.8) 22.1 (7.4)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

6.6°C (12°F) 48.9 (167000) 48.9 (167000) 1.00 1.93 (30.5) 86.7 (29.1)

7.7°C (14°F) 47.4 (162000) 47.4 (162000) 1.00 1.55 (24.6) 57.6 (19.3)

8.8°C (16°F) 46.0 (157000) 46.0 (157000) 1.00 1.35 (21.5) 44.5 (14.9)

10.0°C (18°F) 44.5 (152000) 44.5 (152000) 1.00 1.18 (18.7) 34.4 (11.5)

11.1°C (20°F) 43.2 (147000) 43.2 (147000) 1.00 1.03 (16.4) 26.9 (9.0)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

990-5792B-001 55
ACRC300 Series, ACRC600 Series Technical Data

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

7.7°C (14°F) 52.9 (181000) 52.9 (181000) 1.00 1.72 (27.3) 70.1 (23.5)

8.8°C (16°F) 51.5 (176000) 51.5 (176000) 1.00 1.51 (24.0) 54.8 (18.4)

10.0°C (18°F) 50.2 (171000) 50.2 (171000) 1.00 1.32 (21.0) 42.7 (14.3)

11.1°C (20°F) 48.9 (167000) 48.9 (167000) 1.00 1.17 (18.5) 33.6 (11.3)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

7.7°C (14°F) 58.3 (199000) 58.3 (199000) 1.00 1.85 (29.4) 80.6 (27.0)

8.8°C (16°F) 57.0 (194000) 57.0 (194000) 1.00 1.67 (26.5) 66.2 (22.2)

10.0°C (18°F) 55.7 (190000) 55.7 (190000) 1.00 1.45 (22.9) 50.4 (16.9)

11.1°C (20°F) 54.3 (185000) 54.3 (185000) 1.00 1.28 (20.2) 39.8 (13.3)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Overall cooling capacity will be reduced if the optional dew point
control pump (DPCP) is operating. The DPCP should only be operating if the
dedicated IT room humidity control system or humidity barrier fails. The DPCP
can be disabled via the display interface.

Performance specifications 15°C (59°F) EWT (ACRC301H)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB, 63°F WB)

5.5°C (10°F) 13.4 (46000) 13.4 (46000) 1.00 0.69 (10.9) 12.6 (4.2)

6.6°C (12°F) 11.4 (39000) 11.4 (39000) 1.00 0.49 (7.7) 6.6 (2.2)

7.7°C (14°F) 9.7 (33000) 9.7 (33000) 1.00 0.37 (5.9) 4.2 (1.4)

29.4°C DB, 18.1°C WB (85°F DB, 65°F WB)

5.5°C (10°F) 18.0 (61000) 18.0 (61000) 1.00 0.90 (14.2) 20.6 (6.9)

6.6°C (12°F) 16.7 (57000) 16.7 (57000) 1.00 0.73 (11.5) 13.9 (4.7)

7.7°C (14°F) 14.7 (50000) 14.7 (50000) 1.00 0.53 (8.4) 8.0 (2.7)

8.8°C (16°F) 12.9 (44000) 12.9 (44000) 1.00 0.42 (6.6) 5.1 (1.7)

10.0°C (18°F) 11.1 (38000) 11.1 (38000) 1.00 0.32 (5.1) 3.2 (1.1)

32.2°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 24.0 (82000) 24.0 (82000) 1.00 1.17 (18.5) 33.8 (11.3)

6.6°C (12°F) 22.8 (78000) 22.8 (78000) 1.00 0.94 (14.9) 22.5 (7.6)

7.7°C (14°F) 21.1 (72000) 21.1 (72000) 1.00 0.74 (11.8) 14.6 (4.9)

8.8°C (16°F) 19.1 (65000) 19.1 (65000) 1.00 0.59 (9.4) 9.7 (3.2)

10.0°C (18°F) 17.3 (59000) 17.3 (59000) 1.00 0.48 (7.6) 6.6 (2.2)

11.1°C (20°F) 16.2 (55000) 16.2 (55000) 1.00 0.41 (6.4) 4.9 (1.6)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

5.5°C (10°F) 29.9 (102000) 29.9 (102000) 1.00 1.44 (22.8) 50.0 (16.8)

6.6°C (12°F) 28.7 (98000) 28.7 (98000) 1.00 1.18 (18.7) 33.5 (11.2)

7.7°C (14°F) 26.9 (92000) 26.9 (92000) 1.00 0.93 (14.8) 22.2 (7.5)

56 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

8.8°C (16°F) 25.4 (87000) 25.4 (87000) 1.00 0.77 (12.2) 15.6 (5.2)

10.0°C (18°F) 23.6 (80000) 23.6 (80000) 1.00 0.64 (10.1) 11.0 (3.7)

11.1°C (20°F) 22.1 (75000) 22.1 (75000) 1.00 0.54 (8.6) 8.2 (2.7)

37.78°C DB, 20.7°C WB (100°F DB, 69°F WB)

5.5°C (10°F) 34.9 (119000) 34.9 (119000) 1.00 1.65 (26.2) 64.9 (21.8)

6.6°C (12°F) 33.8 (115000) 33.8 (115000) 1.00 1.37 (21.8) 45.7 (15.3)

7.7°C (14°F) 32.7 (111000) 32.7 (111000) 1.00 1.13 (17.8) 31.5 (10.6)

8.8°C (16°F) 30.9 (105000) 30.9 (105000) 1.00 0.91 (14.5) 21.4 (7.2)

10.0°C (18°F) 29.3 (100000) 29.3 (100000) 1.00 0.77 (12.2) 15.5 (5.2)

11.1°C (20°F) 27.6 (94000) 27.6 (94000) 1.00 0.66 (10.5) 11.9 (4.0)

40.50°C DB, 21.5°C WB (105°F DB, 71°F WB)

5.5°C (10°F) 40.3 (137000) 40.3 (137000) 1.00 1.92 (30.4) 86.0 (28.8)

6.6°C (12°F) 39.0 (133000) 39.0 (133000) 1.00 1.59 (25.3) 59.1 (19.8)

7.7°C (14°F) 37.6 (128000) 37.6 (128000) 1.00 1.32 (20.9) 41.1 (13.8)

8.8°C (16°F) 35.9 (122000) 35.9 (122000) 1.00 1.06 (16.9) 28.4 (9.5)

10.0°C (18°F) 34.2 (117000) 34.2 (117000) 1.00 0.88 (14.0) 20.1 (6.7)

11.1°C (20°F) 33.1 (113000) 33.1 (113000) 1.00 0.79 (12.6) 16.5 (5.5)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

6.6°C (12°F) 44.6 (152000) 44.6 (152000) 1.00 1.81 (28.6) 76.6 (25.7)

7.7°C (14°F) 43.2 (147000) 43.2 (147000) 1.00 1.51 (23.9) 54.5 (18.3)

8.8°C (16°F) 41.6 (142000) 41.6 (142000) 1.00 1.23 (19.6) 37.4 (12.5)

10.0°C (18°F) 40.1 (137000) 40.1 (137000) 1.00 1.05 (16.7) 27.8 (9.3)

11.1°C (20°F) 38.8 (132000) 38.8 (132000) 1.00 0.92 (14.6) 21.6 (7.3)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

7.7°C (14°F) 48.8 (167000) 48.8 (167000) 1.00 1.70 (26.9) 68.3 (22.9)

8.8°C (16°F) 47.3 (161000) 47.3 (161000) 1.00 1.40 (22.1) 47.0 (15.8)

10.0°C (18°F) 45.8 (156000) 45.8 (156000) 1.00 1.20 (19.0) 35.3 (11.8)

11.1°C (20°F) 44.4 (152000) 44.4 (152000) 1.00 1.05 (16.6) 27.5 (9.2)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

7.7°C (14°F) 55.0 (188000) 55.0 (188000) 1.00 1.89 (29.9) 82.1 (27.5)

8.8°C (16°F) 52.7 (180000) 52.7 (180000) 1.00 1.55 (24.6) 57.4 (19.3)

10.0°C (18°F) 51.7 (175000) 51.7 (175000) 1.00 1.34 (21.2) 43.5 (14.6)

11.1°C (20°F) 50.0 (171000) 50.0 (171000) 1.00 1.17 (18.6) 34.0 (11.4)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Overall cooling capacity will be reduced if the optional dew point
control pump (DPCP) is operating. The DPCP should only be operating if the
dedicated IT room humidity control system or humidity barrier fails. The DPCP
can be disabled via the display interface.

990-5792B-001 57
ACRC300 Series, ACRC600 Series Technical Data

Performance specifications 17.5°C (63.5°F) EWT (ACRC301H)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB, 63°F WB)

5.5°C (10°F) 8.3 (28000) 8.3 (28000) 1.00 0.46 (7.3) 6.1 (2.0)

6.6°C (12°F) 6.3 (22000) 6.3 (22000) 1.00 0.30 (4.8) 2.9 (1.0)

29.4°C DB, 18.1°C WB (85°F DB, 65°F WB)

5.5°C (10°F) 13.3 (45000) 13.3 (45000) 1.00 0.68 (10.8) 12.5 (4.2)

6.6°C (12°F) 11.6 (40000) 11.6 (40000) 1.00 0.51 (8.0) 7.3 (2.4)

7.7°C (14°F) 9.8 (33000) 9.8 (33000) 1.00 0.37 (5.9) 4.2 (1.4)

32.22°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 19.2 (66000) 19.2 (66000) 1.00 0.95 (15.1) 23.1 (7.7)

6.6°C (12°F) 17.5 (60000) 17.5 (60000) 1.00 0.72 (11.5) 14.0 (4.7)

7.7°C (14°F) 15.9 (54000) 15.9 (54000) 1.00 0.57 (9.1) 9.1 (3.1

8.8°C (16°F) 14.7 (50000) 14.7 (50000) 1.00 0.57 (9.0) 9.0 (3.0)

10.0°C (18°F) 12.8 (44000) 12.8 (44000) 1.00 0.37 (5.8) 4.1 (1.4)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

5.5°C (10°F) 25.1 (86000) 25.1 (86000) 1.00 1.22 (19.4) 36.8 (12.3)

6.6°C (12°F) 23.5 (80000) 23.5 (80000) 1.00 0.95 (15.0) 22.8 (7.7)

7.7°C (14°F) 22.1 (75000) 22.1 (75000) 1.00 0.77 (12.3) 15.8 (5.3)

8.8°C (16°F) 20.4 (70000) 20.4 (70000) 1.00 0.63 (10.0) 10.9 (3.6)

10.0°C (18°F) 18.6 (63000) 18.6 (63000) 1.00 0.51 (8.1) 7.4 (2.5)

11.1°C (20°F) 17.0 (58000) 17.0 (58000) 1.00 0.43 (6.7) 5.3 (1.8)

37.78°C DB, 20.7°C WB (100°F DB, 69°F WB)

5.5°C (10°F) 30.1 (103000) 30.1 (103000) 1.00 1.44 (22.9) 50.1 (16.8)

6.6°C (12°F) 28.7 (98000) 28.7 (98000) 1.00 1.14 (18.1) 32.4 (10.9)

7.7°C (14°F) 27.1 (93000) 27.1 (93000) 1.00 0.94 (14.9) 22.4 (7.5)

8.8°C (16°F) 25.9 (88000) 25.9 (88000) 1.00 0.82 (12.9) 17.4 (5.8)

10.0°C (18°F) 24.2 (82000) 24.2 (82000) 1.00 0.65 (10.3) 11.5 (3.9)

11.1°C (20°F) 22.7 (77000) 22.7 (77000) 1.00 0.65 (10.3) 11.5 (3.9)

40.50°C DB, 21.5°C WB (105°F DB, 71°F WB)

5.5°C (10°F) 35.6 (122000) 35.6 (122000) 1.00 1.71 (27.2) 69.4 (23.3)

6.6°C (12°F) 34.2 (117000) 34.2 (117000) 1.00 1.35 (21.4) 44.4 (14.9)

7.7°C (14°F) 32.8 (112000) 32.8 (112000) 1.00 1.12 (17.8) 31.3 (10.5)

8.8°C (16°F) 31.1 (106000) 31.1 (106000) 1.00 0.93 (14.8) 22.1 (7.4)

10.0°C (18°F) 29.7 (101000) 29.7 (101000) 1.00 0.79 (12.5) 16.4 (5.5)

11.1°C (20°F) 28.2 (96000) 28.2 (96000) 1.00 0.68 (10.8) 12.5 (4.2)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

5.5°C (10°F) 41.1 (140000) 41.1 (140000) 1.00 1.93 (30.6) 87.2 (29.2)

6.6°C (12°F) 39.9 (136000) 39.9 (136000) 1.00 1.56 (24.7) 58.1 (19.5)

7.7°C (14°F) 38.4 (131000) 38.4 (131000) 1.00 1.30 (20.6) 41.3 (13.8)

8.8°C (16°F) 36.9 (126000) 36.9 (126000) 1.00 1.11 (17.6) 30.6 (10.3)

58 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

10.0°C (18°F) 35.4 (121000) 35.4 (121000) 1.00 0.94 (14.8) 22.3 (7.5)

11.1°C (20°F) 34.0 (116000) 34.0 (116000) 1.00 0.91 (14.4) 21.2 (7.1)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

6.6°C (12°F) 45.3 (154000) 45.3 (154000) 1.00 1.77 (28.1) 73.8 (24.7)

7.7°C (14°F) 44.0 (150000) 44.0 (150000) 1.00 1.48 (23.5) 52.8 (17.7)

8.8°C (16°F) 42.5 (145000) 42.5 (145000) 1.00 1.25 (19.9) 38.6 (12.9)

10.0°C (18°F) 41.1 (140000) 41.1 (140000) 1.00 1.08 (17.1) 29.0 (9.7)

11.1°C (20°F) 39.7 (135000) 39.7 (135000) 1.00 1.04 (16.4) 27.0 (9.1)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

7.7°C (14°F) 49.3 (168000) 49.3 (168000) 1.00 1.53 (24.2) 55.7 (18.7)

8.8°C (16°F) 48.1 (164000) 48.1 (164000) 1.00 1.42 (22.5) 48.6 (16.3)

10.0°C (18°F) 46.7 (159000) 46.7 (159000) 1.00 1.22 (19.4) 36.7 (12.3)

11.1°C (20°F) 45.4 (155000) 45.4 (155000) 1.00 1.07 (16.9) 28.6 (9.6)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Overall cooling capacity will be reduced if the optional dew point
control pump (DPCP) is operating. The DPCP should only be operating if the
dedicated IT room humidity control system or humidity barrier fails. The DPCP
can be disabled via the display interface.

Performance specifications 20°C (68°F) EWT (ACRC301H)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

29.4°C DB, 18.1°C WB (85°F DB, 65°F WB)

5.5°C (10°F) 8.4 (29000) 8.4 (29000) 1.00 0.46 (7.3) 6.2 (2.1)

6.6°C (12°F) 6.5 (22000) 6.5 (22000) 1.00 0.31 (4.9) 3.0 (1.0)

32.22°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 14.4 (49000) 14.4 (49000) 1.00 0.74 (11.7) 14.4 (4.8)

6.6°C (12°F) 12.5 (43000) 12.5 (43000) 1.00 0.54 (8.5) 8.2 (2.7)

7.7°C (14°F) 11.3 (39000) 11.3 (39000) 1.00 0.42 (6.7) 5.3 (1.8)

8.8°C (16°F) 9.3 (32000) 9.3 (32000) 1.00 0.31 (5.0) 3.1 (1.0)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

5.5°C (10°F) 20.4 (69000) 20.4 (69000) 1.00 1.00 (15.9) 25.5 (8.5)

6.6°C (12°F) 18.4 (63000) 18.4 (63000) 1.00 0.76 (12.0) 15.1 (5.1)

7.7°C (14°F) 17.2 (59000) 17.2 (59000) 1.00 0.62 (9.8) 10.4 (3.5)

8.8°C (16°F) 15.5 (53000) 15.5 (53000) 1.00 0.49 (7.8) 6.9 (2.3)

10.0°C (18°F) 13.5 (46000) 13.5 (46000) 1.00 0.38 (6.1) 4.4 (1.5)

11.1°C (20°F) 11.9 (41000) 11.9 (41000) 1.00 0.31 (4.9) 3.0 (1.0)

37.78°C DB, 20.7°C WB (100°F DB, 69°F WB)

5.5°C (10°F) 25.4 (87000) 25.4 (87000) 1.00 1.23 (19.5) 37.3 (12.5)

990-5792B-001 59
ACRC300 Series, ACRC600 Series Technical Data

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

6.6°C (12°F) 23.7 (81000) 23.7 (81000) 1.00 0.95 (15.1) 23.2 (7.8)

7.7°C (14°F) 22.6 (77000) 22.6 (77000) 1.00 0.76 (12.1) 15.4 (5.2)

8.8°C (16°F) 20.9 (71000) 20.9 (71000) 1.00 0.64 (10.2) 11.2 (3.8)

10.0°C (18°F) 19.3 (66000) 19.3 (66000) 1.00 0.53 (8.4) 7.9 (2.6)

11.1°C (20°F) 17.7 (60000) 17.7 (60000) 1.00 0.44 (7.0) 5.7 (1.9)

40.50°C DB, 21.5°C WB (105°F DB, 71°F WB)

5.5°C (10°F) 31.0 (106000) 31.0 (106000) 1.00 1.50 (23.8) 54.1 (18.2)

6.6°C (12°F) 29.4 (100000) 29.4 (100000) 1.00 1.18 (18.6) 34.2 (11.5)

7.7°C (14°F) 28.1 (96000) 28.1 (96000) 1.00 0.98 (15.5) 24.2 (8.1)

8.8°C (16°F) 26.4 (90000) 26.4 (90000) 1.00 0.80 (12.6) 16.6 (5.6)

10.0°C (18°F) 24.9 (85000) 24.9 (85000) 1.00 0.67 (10.6) 12.0 (4.0)

11.1°C (20°F) 23.3 (80000) 23.3 (80000) 1.00 0.57 (9.0) 9.0 (3.0)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

5.5°C (10°F) 36.4 (124000) 36.4 (124000) 1.00 1.73 (27.4) 70.4 (23.6)

6.6°C (12°F) 34.8 (119000) 34.8 (119000) 1.00 1.37 (21.7) 45.4 (15.2)

7.7°C (14°F) 33.6 (115000) 33.6 (115000) 1.00 1.07 (17.0) 28.8 (9.7)

8.8°C (16°F) 32.2 (110000) 32.2 (110000) 1.00 0.96 (15.3) 23.7 (7.9)

10.0°C (18°F) 30.7 (105000) 30.7 (105000) 1.00 0.82 (12.9) 17.4 (5.8)

11.1°C (20°F) 29.2 (100000) 29.2 (100000) 1.00 0.70 (11.1) 13.2 (4.4)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

6.6°C (12°F) 40.4 (138000) 40.4 (138000) 1.00 1.58 (25.0) 59.2 (19.9)

7.7°C (14°F) 39.2 (134000) 39.2 (134000) 1.00 1.23 (19.5) 37.0 (12.4)

8.8°C (16°F) 37.8 (129000) 37.8 (129000) 1.00 1.13 (17.8) 31.5 (10.6)

10.0°C (18°F) 36.4 (124000) 36.4 (124000) 1.00 0.96 (15.2) 23.4 (7.9)

11.1°C (20°F) 34.9 (119000) 34.9 (119000) 1.00 0.83 (13.2) 18.05 (6.1)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

6.6°C (12°F) 45.7 (156000) 45.7 (156000) 1.00 1.77 (28.0) 73.7 (24.7)

7.7°C (14°F) 44.7 (152000) 44.7 (152000) 1.00 1.36 (21.5) 44.5 (14.9)

8.8°C (16°F) 43.4 (148000) 43.4 (148000) 1.00 1.29 (20.4) 40.5 (13.6)

10.0°C (18°F) 42.1 (144000) 42.1 (144000) 1.00 1.10 (17.5) 30.4 (10.2)

11.1°C (20°F) 40.7 (139000) 40.7 (139000) 1.00 0.96 (15.3) 23.6 (7.9)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Overall cooling capacity will be reduced if the optional dew point
control pump (DPCP) is operating. The DPCP should only be operating if the
dedicated IT room humidity control system or humidity barrier fails. The DPCP
can be disabled via the display interface.

60 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Performance specifications 22°C (72°F) EWT (ACRC301H)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

32.22°C DB, 18.9°C WB (90°F DB, 66°F WB)

5.5°C (10°F) 10.8 (37000) 10.8 (37000) 1.00 0.57 (9.0) 9.0 (3.0)

6.6°C (12°F) 9.0 (31000) 9.0 (31000) 1.00 0.41 (6.4) 4.9 (1.6)

7.7°C (14°F) 6.9 (24000) 6.9 (24000) 1.00 0.28 (4.4) 2.5 (0.8)

35°C DB, 19.8°C WB (95°F DB, 68°F WB)

5.5°C (10°F) 16.6 (57000) 16.6 (57000) 1.00 0.83 (13.2) 18.0 (6.0)

6.6°C (12°F) 14.9 (51000) 14.9 (51000) 1.00 0.61 (9.6) 10.3 (3.4)

7.7°C (14°F) 13.3 (46000) 13.3 (46000) 1.00 0.49 (7.7) 6.8 (2.3)

8.8°C (16°F) 11.6 (40000) 11.6 (40000) 1.00 0.38 (6.0) 4.4 (1.5)

10.0°C (18°F) 9.5 (32000) 9.5 (32000) 1.00 0.28 (4.5) 2.6 (0.9)

37.78°C DB, 20.7°C WB (100°F DB, 69°F WB)

5.5°C (10°F) 21.8 (74000) 21.8 (74000) 1.00 1.07 (17.0) 28.6 (9.6)

6.6°C (12°F) 19.8 (68000) 19.8 (68000) 1.00 0.81 (12.9) 17.2 (5.8)

7.7°C (14°F) 18.6 (63000) 18.6 (63000) 1.00 0.66 (10.4) 11.7 (3.9)

8.8°C (16°F) 17.2 (59000) 17.2 (59000) 1.00 0.54 (8.6) 8.2 (2.7)

10.0°C (18°F) 15.3 (52000) 15.3 (52000) 1.00 0.43 (6.9) 5.5 (1.8)

11.1°C (20°F) 13.1 (45000) 13.1 (45000) 1.00 0.34 (5.4) 3.6 (1.2)

40.50°C DB, 21.5°C WB (105°F DB, 71°F WB)

5.5°C (10°F) 27.1 (93000) 27.1 (93000) 1.00 1.32 (21.0) 42.6 (14.3)

6.6°C (12°F) 25.7 (88000) 25.7 (88000) 1.00 1.03 (16.3) 27.1 (9.1)

7.7°C (14°F) 24.2 (83000) 24.2 (83000) 1.00 0.84 (13.3) 18.4 (6.2)

8.8°C (16°F) 22.6 (78000) 22.6 (78000) 1.00 0.69 (11.0) 12.8 (4.3)

10.0°C (18°F) 21.1 (72000) 21.1 (72000) 1.00 0.58 (9.2) 9.3 (3.1)

11.1°C (20°F) 19.4 (66000) 19.4 (66000) 1.00 0.48 (7.6) 6.6 (2.2)

43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)

5.5°C (10°F) 32.7 (111000) 32.7 (111000) 1.00 1.56 (24.7) 58.0 (19.4)

6.6°C (12°F) 31.1 (106000) 31.1 (106000) 1.00 1.21 (19.2) 36.2 (12.1)

7.7°C (14°F) 29.8 (102000) 29.8 (102000) 1.00 1.02 (16.2) 26.3 (8.8)

8.8°C (16°F) 28.4 (97000) 28.4 (97000) 1.00 0.86 (13.6) 19.2 (6.4)

10.0°C (18°F) 26.6 (92000) 26.6 (92000) 1.00 0.72 (11.5) 13.9 (4.7)

11.1°C (20°F) 25.1 (86000) 25.1 (86000) 1.00 0.61 (9.7) 10.3 (3.4)

46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)

5.5°C (10°F) 38.1 (130000) 38.1 (130000) 1.00 1.80 (28.6) 76.5 (25.6)

6.6°C (12°F) 36.6 (125000) 36.6 (125000) 1.00 1.41 (22.4) 48.3 (16.2)

7.7°C (14°F) 35.5 (121000) 35.5 (121000) 1.00 1.21 (19.1) 35.8 (12.0)

8.8°C (16°F) 34.1 (116000) 34.1 (116000) 1.00 1.02 (16.2) 26.3 (8.8)

10.0°C (18°F) 32.6 (111000) 32.6 (111000) 1.00 0.87 (13.8) 19.5 (6.5)

11.1°C (20°F) 31.1 (106000) 31.1 (106000) 1.00 0.75 (11.8) 14.8 (4.9)

48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)

990-5792B-001 61
ACRC300 Series, ACRC600 Series Technical Data

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

6.6°C (12°F) 42.2 (144000) 42.2 (144000) 1.00 1.61 (25.5) 63.6 (21.3)

7.7°C (14°F) 41.0 (140000) 41.0 (140000) 1.00 1.38 (21.9) 46.3 (15.5)

8.8°C (16°F) 39.7 (136000) 39.7 (136000) 1.00 1.18 (18.7) 34.5 (11.6)

10.0°C (18°F) 38.3 (131000) 38.3 (131000) 1.00 1.01 (16.0) 25.8 (8.7)

11.1°C (20°F) 37.0 (126000) 37.0 (126000) 1.00 0.88 (14.0) 20.0 (6.7)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Overall cooling capacity will be reduced if the optional dew point
control pump (DPCP) is operating. The DPCP should only be operating if the
dedicated IT room humidity control system or humidity barrier fails. The DPCP
can be disabled via the display interface.

ACRC600 Series
Performance specifications 5.6°C (42°F) EWT
Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)

6.6°C (12°F) 44.3 (151000) 40.7 (139000) 0.92 1.6 (25.9) 66 (21.95)

7.7°C (14°F) 40.8 (139000) 37.9 (129000) 0.93 1.3 (20.6) 42 (14.1)

8.8°C (16°F) 37.8 (129000) 35.2 (120000) 0.93 1.1 (16.8) 29 (9.5)

10.0°C (18°F) 34.6 (118000) 32.5 (111000) 0.94 0.9 (13.8) 19 (6.5)

11.1°C (20°F) 31.8 (109000) 29.9 (102000) 0.94 0.7 (11.5) 14 (4.6)

29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)

6.6°C (12°F) 50.8 (174000) 47.8 (163000) 0.94 1.9 (29.5) 84 (28.4)

7.7°C (14°F) 47.7 (163000) 44.8 (153000) 0.94 1.5 (23.9) 56 (18.7)

8.8°C (16°F) 44.1 (151000) 41.9 (143000) 0.95 1.2 (19.4) 38 (12.5)

10.0°C (18°F) 41.2 (141000) 39.1 (134000) 0.95 1.0 (16.2) 26 (8.8)

11.1°C (20°F) 37.8 (129000) 36.3 (124000) 0.96 0.8 (13.5) 19 (6.2)

32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)

7.7°C (14°F) 54.5 (186000) 52.3 (179000) 0.96 1.7 (27.1) 71 (23.8)

8.8°C (16°F) 51.4 (175000) 49.3 (168000) 0.96 1.4 (22.4) 49 (16.6)

10.0°C (18°F) 47.8 (163000) 46.3 (158000) 0.97 1.2 (18.6) 35 (11.6)

11.1°C (20°F) 44.8 (153000) 43.4 (148000) 0.97 1.0 (15.7) 25 (8.32)

35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)

7.7°C (14°F) 62.0 (212000) 60.2 (205000) 0.97 1.9 (30.6) 90 (30.3)

8.8°C (16°F) 58.8 (201000) 57.0 (195000) 0.97 1.6 (25.4) 63 (21.3)

10.0°C (18°F) 55.6 (190000) 53.9 (184000) 0.97 1.4 (21.4) 45 (15.2)

11.1°C (20°F) 52.4 (179000) 50.9 (174000) 0.97 1.2 (18.3) 33 (11.1)

37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)

62 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

8.8°C (16°F) 66.4 (227000) 65.0 (222000) 0.98 1.8 (28.6) 79 (26.6)

10.0°C (18°F) 63.1 (215000) 61.8 (211000) 0.98 1.5 (24.2) 57 (19.2)

11.1°C (20°F) 59.8 (204000) 58.7 (200000) 0.98 1.3 (20.7) 42 (14.3)

40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)

8.8°C (16°F) 74.8 (256000) 73.3 (250000) 0.98 2.0 (32.1) 99 (33.3)

10.0°C (18°F) 71.4 (244000) 70.0 (239000) 0.98 1.7 (27.3) 72 (24.3)

11.1°C (20°F) 68.1 (233000) 66.7 (228000) 0.98 1.5 (23.4) 54 (18.02)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Reduce airflow and cooling capacity specifications by 7% for cooling
units run at low input voltage (380 V).

Performance specifications 7.2°C (45°F) EWT (ACRC600 series)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)

5.5°C (10°F) 40.8 (139000) 39.6 (135000) 0.97 1.8 (28.8) 81 (27.03)

6.6°C (12°F) 37.9 (130000) 36.8 (126000) 0.97 1.4 (22.5) 50 (16.6)

7.7°C (14°F) 35.1 (120000) 34.1 (116000) 0.97 1.1 (18.0) 32 (10.9)

8.8°C (16°F) 32.5 (111000) 31.5 (108000) 0.97 0.9 (14.6) 22 (7.4)

10.0°C (18°F) 29.8 (102000) 28.9 (99000) 0.97 0.8 (12.0) 15 (5.1)

11.1°C (20°F) 27.3 (93000) 26.5 (90000) 0.97 0.6 (10.0) 11 (3.7)

29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)

6.6°C (12°F) 45.0 (154000) 43.7 (149000) 0.97 1.7 (26.4) 68 (22.6)

7.7°C (14°F) 42.0 (144000) 40.8 (139000) 0.97 1.3 (21.2) 44 (14.8)

8.8°C (16°F) 39.1 (134000) 38.0 (130000) 0.97 1.1 (17.4) 30 (10.2)

10.0°C (18°F) 36.3 (124000) 35.2 (120000) 0.97 0.9 (14.4) 21 (7.2)

11.1°C (20°F) 33.3 (114000) 32.6 (111000) 0.98 0.8 (11.9) 15 (5.1)

32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)

6.6°C (12°F) 52.3 (179000) 51.2 (175000) 0.98 1.9 (30.4) 89 (29.8)

7.7°C (14°F) 49.2 (168000) 48.2 (165000) 0.98 1.5 (24.5) 59 (19.9)

8.8°C (16°F) 46.1 (157000) 45.2 (154000) 0.98 1.3 (20.2) 41 (13.6)

10.0°C (18°F) 42.7 (146000) 42.3 (144000) 0.99 1.1 (16.7) 28 (9.5)

11.1°C (20°F) 39.8 (136000) 39.4 (135000) 0.99 0.9 (14.1) 20 (6.9)

35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)

7.7°C (14°F) 57.2 (195000) 56.0 (191000) 0.98 1.8 (28.3) 78 (26.1)

8.8°C (16°F) 53.4 (182000) 52.9 (181000) 0.99 1.5 (23.2) 53 (17.8)

10.0°C (18°F) 50.3 (172000) 49.8 (170000) 0.99 1.2 (19.5) 38 (12.7)

11.1°C (20°F) 47.2 (161000) 46.7 (160000) 0.99 1.0 (16.5) 28 (9.2)

990-5792B-001 63
ACRC300 Series, ACRC600 Series Technical Data

Temperature Total Net Sensible Net Total CW


CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)

8.8°C (16°F) 61.6 (210000) 61.0 (208000) .99 1.7 (26.6) 69 (23.1)

10.0°C (18°F) 58.3 (199000) 57.7 (197000) .99 1.4 (22.4) 50 (16.6)

11.1°C (20°F) 55.1 (188000) 54.5 (186000) .99 1.2 (19.1) 36 (12.2)

40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)

8.8°C (16°F) 69.6 (238000) 69.6 (238000) 1.00 1.9 (29.9) 86 (28.9)

10.0°C (18°F) 66.1 (226000) 66.1 (226000) 1.00 1.6 (25.3) 63 (21.02)

11.1°C (20°F) 62.7 (214000) 62.7 (214000) 1.00 1.4 (21.7) 46 (15.5)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Reduce airflow and cooling capacity specifications by 7% for cooling
units run at low input voltage (380 V).

64 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Performance specifications 8.8°C (48°F) EWT (ACRC600 series)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)

5.5°C (10°F) 35.7 (122000) 34.6 (118000) 0.97 1.6 (25.5) 63 (21.3)

6.6°C (12°F) 32.9 (112000) 31.9 (109000) 0.97 1.2 (19.7) 39 (12.9)

7.7°C (14°F) 30.3 (103000) 29.4 (100000) 0.97 1.0 (15.7) 25 (8.3)

8.8°C (16°F) 27.7 (95000) 26.9 (92000) 0.97 0.8 (12.7) 17 (5.5)

10.0°C (18°F) 25.3 (86000) 24.5 (84000) 0.97 0.7 (10.4) 11 (3.9)

29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)

5.5°C (10°F) 42.3 (145000) 41.5 (142000) 0.98 1.9 (29.9) 86 (28.9)

6.6°C (12°F) 39.4 (134000) 38.6 (132000) 0.98 1.5 (23.3) 53 (17.8)

7.7°C (14°F) 36.5 (125000) 35.8 (122000) 0.98 1.2 (18.6) 35 (11.6)

8.8°C (16°F) 33.7 (115000) 33.1 (113000) 0.98 1.0 (15.1) 23 (7.9)

10.0°C (18°F) 31.1 (106000) 30.4 (104000) 0.98 0.8 (12.5) 16 (5.3)

11.1°C (20°F) 28.5 (97000) 27.9 (95000) 0.98 0.7 (10.4) 12 (3.9)

32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)

6.6°C (12°F) 47.0 (161000) 46.1 (157000) 0.98 1.7 (27.5) 73 (24.5)

7.7°C (14°F) 43.9 (150000) 43.0 (147000) 0.98 1.4 (22.1) 48 (16.2)

8.8°C (16°F) 40.9 (140000) 40.1 (137000) 0.98 1.1 (18.1) 33 (10.9)

10.0°C (18°F) 37.6 (128000) 37.2 (127000) 0.99 0.9 (14.9) 23 (7.6)

11.1°C (20°F) 34.8 (119000) 34.4 (118000) 0.99 0.8 (12.5) 16 (5.3)

35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)

7.7°C (14°F) 51.4 (176000) 50.9 (174000) 0.99 1.6 (25.6) 64 (21.5)

8.8°C (16°F) 48.2 (165000) 47.7 (163000) 0.99 1.3 (21.1) 44 (14.8)

10.0°C (18°F) 45.0 (154000) 44.6 (152000) 0.99 1.1 (17.6) 31 (10.4)

11.1°C (20°F) 42.0 (143000) 41.6 (142000) 0.99 0.9 (14.8) 22 (7.6)

37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)

7.7°C (14°F) 60.0 (205000) 59.4 (203000) 0.99 1.9 (29.7) 85 (28.6)

8.8°C (16°F) 56.0 (191000) 56.0 (191000 1.00 1.5 (24.3) 58 (19.4)

10.0°C (18°F) 52.6 (180000) 52.6 (180000 1.00 1.3 (20.4) 41 (13.9)

11.1°C (20°F) 49.4 (169000) 49.4 (169000) 1.00 1.1 (17.3) 30 (9.9)

40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)

7.7°C (14°F) 68.6 (234000) 68.6 (234000) 1.00 2.1 (33.7) 109 (36.5)

8.8°C (16°F) 64.9 (222000) 64.9 (222000) 1.00 1.8 (28.0) 76 (25.4)

10.0°C (18°F) 61.3 (209000) 61.3 (209000) 1.00 1.5 (23.5) 54 (18.2)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Reduce airflow and cooling capacity specifications by 7% for cooling
units run at low input voltage (380 V).

990-5792B-001 65
ACRC300 Series, ACRC600 Series Technical Data

Performance specifications 10°C (50°F) EWT (ACRC600 series)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)

5.5°C (10°F) 32.6 (111000) 31.8 (109000) 0.98 1.5 (23.5) 54 (18.02)

6.6°C (12°F) 29.9 (102000) 29.2 (100000) 0.98 1.1 (18.1) 33 (11.1)

7.7°C (14°F) 27.4 (93000) 26.7 (91000) 0.98 0.9 (14.3) 21 (6.9)

8.8°C (16°F) 24.9 (85000) 24.3 (83000) 0.98 0.7 (11.5) 14 (4.6)

10.0°C (18°F) 22.6 (77000) 22.0 (75000) 0.98 0.6 (9.4) 10 (3.2)

11.1°C (20°F) 20.4 (70000) 19.9 (68000) 0.98 0.5 (7.7) 7 (2.3)

29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)

5.5°C (10°F) 39.6 (135000) 38.6 (132000) 0.98 1.8 (28.0) 76 (25.6)

6.6°C (12°F) 36.6 (125000) 35.7 (122000) 0.98 1.4 (21.8) 47 (15.7)

7.7°C (14°F) 33.8 (115000) 32.9 (112000) 0.98 1.1 (17.3) 30 (10.2)

8.8°C (16°F) 31.1 (106000) 30.3 (103000) 0.98 0.9 (14.0) 20 (6.7)

10.0°C (18°F) 28.5 (97000) 27.7 (95000) 0.98 0.7 (11.5) 14 (4.6)

11.1°C (20°F) 26.0 (89000) 25.3 (86000) 0.98 0.6 (9.5) 10 (3.2)

32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)

6.6°C (12°F) 43.6 (149000) 43.2 (147000) 0.99 1.6 (25.6) 64 (21.5)

7.7°C (14°F) 40.5 (138000) 40.1 (137000) 0.99 1.3 (20.5) 42 (13.9)

8.8°C (16°F) 37.6 (128000) 37.2 (127000) 0.99 1.1 (16.7) 28 (9.5)

10.0°C (18°F) 34.7 (119000) 34.4 (117000) 0.99 0.9 (13.8) 20 (6.5)

11.1°C (20°F) 32.0 (109000) 31.7 (108000) 0.99 0.7 (11.5) 14 (4.6)

35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)

6.6°C (12°F) 51.9 (177000) 51.4 (175000) 0.99 1.9 (30.1) 88 (29.3)

7.7°C (14°F) 48.5 (166000) 48.0 (164000) 0.99 1.5 (24.2) 58 (19.4)

8.8°C (16°F) 45.3 (155000) 44.8 (153000) 0.99 1.3 (19.9) 39 (13.2)

10.0°C (18°F) 42.1 (144000) 41.7 (142000) 0.99 1.0 (16.5) 28 (9.2)

11.1°C (20°F) 38.7 (132000) 38.7 (132000) 1.00 0.9 (13.7) 19 (6.5)

37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)

7.7°C (14°F) 56.7 (194000) 56.7 (194000) 1.00 1.8 (28.1) 77 (25.6)

8.8°C (16°F) 53.2 (182000) 53.2 (182000) 1.00 1.5 (23.1) 53 (17.6)

10.0°C (18°F) 49.8 (170000) 49.8 (170000) 1.00 1.2 (19.3) 37 (12.5)

40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)

8.8°C (16°F) 62.3 (213000) 62.3 (213000) 1.00 1.7 (26.9) 70 (23.6)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Reduce airflow and cooling capacity specifications by 7% for cooling
units run at low input voltage (380 V).

66 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Performance specifications 12.7°C (55°F) EWT (ACRC600 series)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)

5.5°C (10°F) 24.7 (85000) 24.7 (85000) 1.00 1.2 (18.3) 33 (11.3)

6.6°C (12°F) 22.3 (76000) 22.3 (76000) 1.00 0.9 (13.9) 20 (6.7)

7.7°C (14°F) 20.0 (68000) 20.0 (68000) 1.00 0.7 (10.8) 12 (4.2)

8.8°C (16°F) 17.8 (61000) 17.8 (61000) 1.00 0.5 (8.6) 8 (2.8)

10.0°C (18°F) 15.8 (54000) 15.8 (54000) 1.00 0.4 (6.9) 5 (1.8)

11.1°C (20°F) 13.9 (48000) 13.9 (48000) 1.00 0.4 (5.6) 4 (1.2)

29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)

5.5°C (10°F) 31.3 (107000) 31.3 (107000) 1.00 1.4 (22.6) 50 (16.9)

6.6°C (12°F) 28.5 (97000) 28.5 (97000) 1.00 1.1 (17.3) 30 (10.2)

7.7°C (14°F) 25.8 (88000) 25.8 (88000) 1.00 0.9 (13.6) 19 (6.5)

8.8°C (16°F) 23.3 (80000) 23.3 (80000) 1.00 0.7 (10.8) 8 (4.2)

10.0°C (18°F) 21.0 (72000) 21.0 (72000) 1.00 0.6 (8.8) 8 (2.8)

11.1°C (20°F) 18.7 (64000) 18.7 (64000) 1.00 0.5 (7.2) 6 (1.8)

32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)

5.5°C (10°F) 39.1 (133000) 39.1 (133000) 1.00 1.7 (27.7) 75 (24.9)

6.6°C (12°F) 35.9 (123000) 35.9 (123000) 1.00 1.3 (21.3) 45 (15.02)

7.7°C (14°F) 32.8 (112000) 32.8 (112000) 1.00 1.1 (16.9) 29 (9.7)

8.8°C (16°F) 30.0 (102000) 30.0 (102000) 1.00 0.9 (13.6) 19 (6.5)

10.0°C (18°F) 27.2 (93000) 27.2 (93000) 1.00 0.7 (11.1) 13 (4.4)

35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)

6.6°C (12°F) 44.2 (151000) 44.2 (151000) 1.00 1.6 (25.9) 66 (21.9)

7.7°C (14°F) 40.8 (139000) 40.8 (139000) 1.00 1.3 (20.6) 42 (14.1)

8.8°C (16°F) 37.5 (128000) 37.5 (128000) 1.00 1.1 (16.7) 28 (9.5)

37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)

7.7°C (14°F) 49.8 (170000) 49.8 (170000) 1.00 1.6 (24.8) 60 (20.1)

40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)

7.7°C (14°F) 59.7 (204000) 59.7 (204000) 1.00 1.9 (29.5) 84 (28.2)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Reduce airflow and cooling capacity specifications by 7% for cooling
units run at low input voltage (380 V).

990-5792B-001 67
ACRC300 Series, ACRC600 Series Technical Data

Performance specifications 15.5°C (60°F) EWT (ACRC600 series)


Temperature Total Net Sensible Net Total CW
CW Delta T – °C Sensible Heat CW Flow Rate –
DB, WB – °C (° Capacity – kW Capacity – kW Pressure Drop
(°F) Ratio – SHR l/s (GPM)
F) (BTU/hr) (BTU/hr) – kPa (ft H2O)

26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)

5.5°C (10°F) 17.5 (60000) 17.5 (60000) 1.00 0.9 (13.5) 19 (6.2)

6.6°C (12°F) 15.2 (52000) 15.2 (52000) 1.00 0.6 (10.0) 11 (3.7)

7.7°C (14°F) 13.1 (45000) 13.1 (45000) 1.00 0.5 (7.6) 6 (2.1)

8.8°C (16°F) 11.1 (38000) 11.1 (38000) 1.00 0.4 (5.8) 4 (1.4)

10.0°C (18°F) 9.3 (32000) 9.3 (32000) 1.00 0.3 (4.5) 3 (0.9)

11.1°C (20°F) 7.7 (26000) 7.7 (26000) 1.00 0.2 (3.5) 2 (0.5)

29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)

5.5°C (10°F) 23.8 (81000) 23.8 (81000) 1.00 1.1 (17.7) 31 (10.4)

6.6°C (12°F) 21.1 (72000) 21.1 (72000) 1.00 0.8 (13.2) 18 (6.01)

7.7°C (14°F) 18.5 (63000) 18.5 (63000) 1.00 0.6 (10.1) 11 (3.7)

8.8°C (16°F) 16.1 (55000) 16.1 (55000) 1.00 0.5 (7.9) 7 (2.3)

32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)

5.5°C (10°F) 31.5 (108000) 31.5 (108000) 1.00 1.4 (22.8) 51 (17.1)

6.6°C (12°F) 28.3 (97000) 28.3 (97000) 1.00 1.1 (17.2) 30 (9.9)

35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)

5.5°C (10°F) 40.6 (139000) 40.6 (139000) 1.00 1.8 (28.7) 80 (26.8)

NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
NOTE: Reduce airflow and cooling capacity specifications by 7% for cooling
units run at low input voltage (380 V).

68 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Performance Data-General
ACRC301S
MODULATING VALVES
Size 3-Way Ball Valve – NPT mm (in.) (Cv) 31.75 (1 1/4) 29.3

AIR SYSTEM
200-mm (7.9-in.)
Standard filter 51-mm (2-in.) pleated filter
Mixed Flow Direct Drive DC Tubeaxial Fans
Air Volume – l/s (SCFM) 1510 (3200) 1345 (2850)

Fan Motor – Watts (each) 95 100

Number of Fans 8 8
Performance Specifications Table Multiplier* 1.0 0.94

WATER TEMPERATURE
Minimum Entering Temperature – °C (°F) 5 (41)

Maximum Entering Temperature – °C (°F) 15.5 (60)

COOLING COIL - COPPER TUBE/ALUMINUM FIN


Face Area – m2 (ft2) 0.510 (5.5)

Rows Deep 3

Face Velocity – m/s (FPM) 2.95 (582)

FILTERS - WASHABLE (STANDARD)

Quantity 2

Size – mm (in.) 238 x 933 (9.375 x 36.75)

Depth – mm (in.) 12.7 (1/2)

Efficiency (%) <20% MERV 1

FILTERS – PLEATED (OPTIONAL)

Quantity 2

Size – mm (in.) 238 x 933 (9.375 x 36.75)

Depth – mm (in.) 51 (2)

Efficiency (%) 30% MERV 8

PHYSICAL DATA
Net Weight - kg (lbs) 184 (406)

Operating Weight – kg (lbs) 192 (423)

Height – mm (in.) 1991 (78.39)

Width – mm (in.) 300 (11.81)

Depth – mm (in.) 1095 (43.11)

CONNECTION SIZES
Supply Line - mm (in.) 25.4 (1) NPT connection
Chilled Water
Return Line - mm (in.) 25.4 (1) NPT connection

Condensate Drain Drain Line - mm (in) 4.77 (3/16) ID, 6.35 (1/4) OD

DUAL FLOAT CONDENSATE MANAGEMENT


Flow Rate – L/hr (GPH) 5 (1.3)

Maximum Distance – m (ft)† 15.2 (50)

990-5792B-001 69
ACRC300 Series, ACRC600 Series Technical Data

MODULATING VALVES
Maximum Lift – m (ft) 4.9 (16)

Maximum flow rate is 4720 l/hr (20.8 GPM) for continuous operation.

Maximum working pressure for the unit is 2068.4 kPa (300 psig).

†Maximum distance includes the maximum lift.

*Example: Performance at 29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB) with a 7.2°C (45°F) EWT, and a 5.5°C (10°F) CW delta T is
21.8 kW (74000 BTU/hr) (total net capacity) with the standard filter. Using a 50-mm (2-in.) pleated filter with single fan failure, the
performance of the unit would be 21.8 X 0.94 = 20.5 kW
(74000 X .94 = 69560 BTU/hr).

70 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

ACRC301H
MODULATING VALVES
Size 3-Way Ball Valve – NPT mm (in.) (Cv) 31.75 (1 1/4) 29.3

AIR SYSTEM
200-mm (7.9-in.)
Standard filter 51-mm (2-in.) pleated filter
Mixed Flow Direct Drive DC Tubeaxial Fans
Air Volume – l/s (SCFM) 1982 (4200) 1793 (3800)

Fan Motor – Watts (each) 235 245

Number of Fans 8 8
Performance Specifications Table Multiplier* 1.0 0.94

WATER TEMPERATURE
Minimum Entering Temperature – °C (°F) 10 (50)

Maximum Entering Temperature – °C (°F) 22 (71.6)

COOLING COIL - COPPER TUBE/ALUMINUM FIN


Face Area – m2 (ft2) 0.65 (7.0)

Rows Deep 6

Face Velocity – m/s (FPM) 3.05 (600)

FILTERS - WASHABLE (STANDARD)

Quantity 2

Size – mm (in.) 238 x 933 (9.375 x 36.75)

Depth – mm (in.) 12.7 (1/2)

Efficiency (%) <20% MERV 1

FILTERS – PLEATED (OPTIONAL)

Quantity 2

Size – mm (in.) 238 x 933 (9.375 x 36.75)

Depth – mm (in.) 51 (2)

Efficiency (%) 30% MERV 8

PHYSICAL DATA
Net Weight - kg (lbs) 210 (463)

Operating Weight – kg (lbs) 220 (485)

Height – mm (in.) 1991 (78.39)

Width – mm (in.) 300 (11.81)

Depth – mm (in.) 1095 (43.11)

POWER CONNECTION
Minimum Input Wire Size - AWG 14

CONNECTION SIZES
Supply Line - mm (in.) 31.75 (1 1/4) NPT connection
Chilled Water
Return Line - mm (in.) 31.75 (1 1/4) NPT connection

Maximum flow rate is 7020 l/hr (30.9 GPM) for continuous operation.

Maximum working pressure for the unit is 2068.4 kPa (300 psig). If ACRC301H contains the Dew Point Control Pump (DPCP), the
maximum working pressure is 1600 kPa (232 psig).

*Example: Performance at 29.4°C DB, 18.1°C WB (85° DB, 64.5°F WB) with a 10°C (50°F) EWT, and a 5.5°C (10°F) CW delta T is 27.3
kW (93000 BTU/hr) (total net capacity) with the standard filter. Using a 50-mm (2-in.) pleated filter with single fan failure, the
performance of the unit would be 27.3 X 0.94 = 25.7 kW (93000 X .94 = 87420 BTU/hr).

990-5792B-001 71
ACRC300 Series, ACRC600 Series Technical Data

ACRC600 series
MODULATING VALVES
Size 3-Way Ball Valve – NPT mm (in.) (Cv) 25.4 (1)

AIR SYSTEM 400-mm (15.8-in.)—BACKWARD INCLINE DIRECT DRIVE FANS (Standard Filter Installed)

Air Volume – l/s (SCFM) 2832 (6000)

Fan Motor – kW (HP) 1.00 (1.5)

Number of Fans 3
COOLING COIL - COPPER TUBE/ALUMINUM FIN
Face Area – m2 (ft2) 0.74 (7.9)

Rows Deep 4

FPM (FPI) 468 (12)

FILTERS - PLEATED (STANDARD)

Quantity 4

Size – mm (in.) 418 x 470 (16.45 x 18.5)

Depth – mm (in.) 101.6 (4)

Efficiency (%) 30

FILTERS – PLEATED (OPTIONAL)

Quantity 4

Size – mm (in.) 418 x 470 (16.45 x 18.5)

Depth – mm (in.) 101.6 (4)

Efficiency (%) 85

PHYSICAL DATA
ACRC600 345 (760)
Net Weight - kg (lbs)
ACRC600P 352 (776)

ACRC600 363(800)
Operating Weight – kg (lbs)
ACRC600P 370 (816)

Height – mm (in.) 1991 (78.4)

Width – mm (in.) 600 (23.6)

Depth – mm (in.) 1070 (42.1)

CONNECTION SIZES
Supply Line - mm (in.) 38.1 (1 1/2) NPSM
Chilled Water
Return Line - mm (in.) 38.1 (1 1/2) NPSM

Condensate Drain Drain Line - mm (in.) 9.5 (3/8) ID, 12.7 (1/2) OD

Humidifier
Supply line – mm (in.) 6.35 (1/4)
(ACRC600P series only)

DUAL FLOAT CONDENSATE MANAGEMENT


Flow Rate – L/m (GPH) 0.53 (8.45)

Maximum Distance – m (ft)† 18 (60)

Maximum Lift – m (ft) 3.5 (11.5)

HUMIDIFICATION – SOLID STATE ELECTRODE CANISTER (ACRC600P series only)

Flush Cycle Automatic

Capacity – kg/hr (lb/hr) 3.0 (6.6)

72 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

MODULATING VALVES
kW 2.25
REHEAT – ELECTRIC (Equally Loaded Three Stage, Finned Tubular, Low-Watt Density)
(ACRC600P series only)

Capacity – kW (BTU/hr) 9.0 (30,700)

Stages 3

Maximum flow rate is 2.08 l/s (33 GPM) for continuous operation. May be exceeded by 25% for peak loads.

Maximum working pressure for the unit is 2068.4 kPa (300 psig).

†Maximum distance includes the maximum lift.


NOTE: For ACRC600 series, reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage
(380V).

Glycol Correction Factors


Perform- Percent Weight of Solution***
Glycol
ance
Solution 0% 10% 20% 30% 40% 50%
Criteria
Ethylene 1.00 0.97 0.93 0.88 0.81 0.75
Capacity*
Propylene 1.00 0.96 0.90 0.82 0.77 0.74

Pressure Ethylene 1.00 1.04 1.13 1.21 1.31 1.41


Drop** Propylene 1.00 1.09 1.20 1.35 1.52 1.67
All correction factors are based on unit entering the following conditions: 29.4°C (85°F) DB, 18.1°C (64.5°F)
WB, 1368.6 L/S (6950 CFM), 1.72 L/S (27.3 GPM), and 7.2°C (45°F) EFT.
*Multiply capacity of device or system by factor above for % solution.
**Multiply pressure drop of system by factor above for % solution.
***Glycol concentrations over 50% are not recommended.

Altitude Correction Factors


Room Conditions: 22°C (72°F) DB/50%RH

Altitude – m (ft) Specific Volume – cm3/ Density –g/m3 (lb/ft3) Density Ratio* Capacity Correction**
kg (ft3/lb)

0 (0) 847.77 (13.58) 1185.37 (0.074) 1.000 1.000

305 (1000) 879.61 (14.09) 1137.31 (0.071) 0.964 0.981

610 (2000) 912.70 (14.62) 1089.26 (0.068) 0.929 0.962

915 (3000) 947.66 (15.18) 1057.22 (0.066) 0.895 0.933

1219 (4000) 983.86 (15.76) 1009.16 (0.063) 0.862 0.913

1524 (5000) 1021.32 (16.36) 977.13 (0.061) 0.830 0.884

1829 (6000) 1061.28 (17.00) 945.10 (0.059) 0.799 0.865

2134 (7000) 1103.10 (17.67) 913.05 (0.057) 0.769 0.846

2438 (8000) 1146.80 (18.37) 865.00 (0.054) 0.739 0.826

2743 (9000) 1193.00 (19.11) 832.97 (0.052) 0.711 0.807

3048 (10,000) 1241.69 (19.89) 80.92 (0.050) 0.683 0.787

*Density ratio is used for air flow correction factor.


**Capacity correction is used to de-rate performance.

990-5792B-001 73
ACRC300 Series, ACRC600 Series Technical Data

Sound Performance Data


ACRC301S Tested Sound Data
Sound Power dB at Lp Sound Pressure dB 20
Fan Speed% Airflow – l/s (SCFM) Frequency Hz re: 10-12W – µPa* – dBA
dBA

30 430 (900) 64.8 49.8

40 610 (1300) 69.6 56.4

60 940 (2000) 78.2 65.4

80 1270 (2700) 87.5 73.8

100 1510 (3200) 90.5 77.1

*Sound tested at 1.8 m (6 ft) distance from the unit and 1 m (3.3 ft) from the floor.

ACRC301H Tested Sound Data


Sound Power dB at Lp Sound Pressure dB 20
Fan Speed% Airflow – l/s (SCFM) Frequency Hz re: 10-12W – µPa* – dBA
dBA

30 570 (1200) 67 52.5

40 800 (1700) 76.3 62.0

60 1230 (2600) 85.5 71.3

80 1650 (3500) 93 79.0

100 1980 (4200) 95.3 81.3

*Sound tested at 1.8 m (6 ft) distance from the unit and 1 m (3.3 ft) from the floor.

ACRC600 Series Tested Sound Data


Sound Power dB at Lp Sound Pressure dB 20
Fan Speed% Airflow – l/s (SCFM) Frequency Hz re: 10-12W – µPa* – dBA
dBA

30 1180 (2500) 65.4 54.9

50 1790 (3800) 76.9 66.8

70 2550 (5400) 85.9 75.0

85 3040 (6450) 90.6 80.7

100 3260 (6900) 91.7 81.9

*Weighted Sound Pressure dBA in a 232.2 m3 (8,200 ft3) room at 1.8 m (6 ft) distance.

74 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Electrical Data
Power
Power
Model Voltage Phase Frequency MCA MOP FLA Power – kW Connection
Standard NEMA L5-
filter: 0.85 20P
100–120 1 50/60 N/A N/A 11A
Pleated
filter: 0.90
ACRC301S
Standard IEC-309
filter: 0.80 16A
200–240 1 50/60 N/A N/A 11A
Pleated
filter: 0.84
Standard
filter: 1.9**
ACRC301H 208–230 1 50/60 15A 15A 12A Hardwired
Pleated
filter: 2.0**
Dew point
control 208–230 1 50/60 N/A N/A 1.6A 0.025– 0.31 N/A
pump

NEMA L21-
ACRC600* 200–240 3 50/60 11 15 N/A 3.2
20P
ACRC601 460–480 3 50/60 7 15 N/A 3.3 Hard-wired
IEC-309 16
ACRC602* 380–415 3 50/60 7 15 6 3
A
ACRC600P 200–240 3 50/60 46.8 50 N/A 14 Hardwired
ACRC601P 460–480 3 50/60 24.8 30 N/A 14 Hardwired
ACRC602P 380–415 3 50/60 N/A N/A 24** 15 Hardwired

*ACRC600 and ACRC602 have the option of being hardwired.


** Power consumption will be increased by 25 - 310 W if the optional dew point
control pump is installed.
NOTE: Above data is based on maximum operating condition.
NOTE: Installation must comply with local and/or national electrical codes.
MCA—Minimum Circuit Amps
MOP—Maximum Overcurrent Protection
FLA—Full Load Amps

990-5792B-001 75
ACRC300 Series, ACRC600 Series Technical Data

Dimensional Data
InRow ACRC300 series assembled module

1991 (
78.39)
na4339a

1095 (
43.11)
1.80)
300 (1

*Dimensions shown in mm (in.)

InRow ACRC600 series assembled module


600 (2
42.1) 3.6)
1070 (

1991
(78.4)
na5963a

*Dimensions shown in mm (in.)

76 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

SX to VX height adapter—ACRC300 series

na2823a
74.8 (2.94)

300 (11.8)

*Dimensions shown in mm (in.)

SX to 48U SX height adapter—ACRC300 series

na2824a
265.30 (10
.44)

300 (11.8)

*Dimensions shown in mm (in.)

SX to VX height adapter—ACRC600 series


na2445a

74.8 (
2.94)

600 (2
3.6)

SX to 48U SX height adapter—ACRC600 series

265.3
na2446a

(10.44
)

600 (2
3.6)

*Dimensions shown in mm (in.)

990-5792B-001 77
ACRC300 Series, ACRC600 Series Technical Data

Piping Connections
ACRC301S
110 (4.31) 83 (3.27)
204 (8.02)
116 (4.55)
110 (4.35)
56 (2.22)

97 (3.83)
147 (5.80)

145 (5.72)

180 (7.10)
TOP VIEW
184 (7.26)

53 (2.08)
90 (3.54)

157 (6.20)
174 (6.84)

199 (7.85)

240 (9.46)
189 (7.43)
na4353a

161 (6.34)

BOTTOM VIEW
(LOOKING UP)
NOTE: Dimensions are shown in mm (in.).

78 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

BOTTOM VIEW
TOP VIEW (LOOKING UP)

na4463a

Item Description
Power connections
Condensate line—0.25 in. ID/0.38 in. OD
1-in. NPT female return pipe (outlet)
1-in. NPT female supply pipe (inlet)
Low voltage input wiring

990-5792B-001 79
ACRC300 Series, ACRC600 Series Technical Data

ACRC301H

233 (9.17)
81 (3.19) 132 (5.21)
193 (7.60)
116 (4.55)
61 (2.38)

126 (4.95)
152 (6.00)

97 (3.83)
TOP VIEW

170 (6.69)
130 (5.12)
56 (2.22)

158 (6.23)

240 (9.46)
280 (11.02)
156 (6.14)

224 (8.82)

na4334a
BOTTOM VIEW
(LOOKING UP)
NOTE: Dimensions are shown in mm (in.).

80 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

BOTTOM VIEW
TOP VIEW (LOOKING UP)

na4464a

Item Description
Power connections
1 1/4-in. NPT female return pipe (outlet)
1 1/4-in. NPT female supply pipe (inlet)
Low voltage input wiring

990-5792B-001 81
ACRC300 Series, ACRC600 Series Technical Data

Internal Piping Diagram—ACRC301S

na4343a

Item Description Item Description


Outlet water union (top piping Outlet water union (bottom
option) piping option)
Inlet water union (top piping Inlet water union (bottom piping
option) option)
3-way actuator control valve—1 Drain valve
1/4 in.
Flow meter Condensate pump
Bypass shutoff ball valve—3/4 Bottom condensate pan
in.
Inlet shutoff valve—1 in. Top condensate pan
Condensate drain Coil

82 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Internal Piping Diagram—ACRC301H

na4358a

Item Description Item Description


Outlet water union (top piping Drain valve
option)
Inlet water union (top piping Outlet water union (bottom
option) piping option)
3-way actuator control valve—1 Inlet water union (bottom piping
1/4 in. option)
Flow meter Coil
Bypass shutoff valve—1 in. Circulation pump (optional)
Inlet shutoff valve—1 1/4 in. Circulation pump check valve
(optional)

990-5792B-001 83
ACRC300 Series, ACRC600 Series Technical Data

Connect with Customer Supplied Chiller


TOP PIPING
CONFIGURATION

TO
CUSTOMER-SUPPLIED
CHILLER

INROW CW
UNITS

BOTTOM PIPING
CONFIGURATION

INROW CW
UNITS
na4405a

TO
CUSTOMER-SUPPLIED
CHILLER

na2609a

––– Flex hose or copper tubing Strainer with 20 mesh screen


–– with opening size of 865
micron, (field installed)
——- Copper tubing Isolation shutoff valve (field
—— installed)

84 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

ACRC600 series
Top piping

TO CUSTOMER-SUPPLIED
CHILLER

Bottom piping
na1936b

TO CUSTOMER-SUPPLIED
CHILLER

Flexible piping adapters* Shutoff valve (field-installed)


Balancing valve (field- Y-strainer with 20-mesh
installed) screen (field-installed)**

*Recommended at these locations when the equipment is connected to rigid


piping. Consult local codes for proper installation.
**A redundant strainer in the bypass line is recommended for systems with
possible debris or heavy particulates during system startup and normal operation.

990-5792B-001 85
ACRC300 Series, ACRC600 Series Technical Data

ACRC600 Series
Top Piping and Power Access Locations (Top View)
REAR—HOT AISLE

554 (21.81)
554 (21.81)
40 (1.58)
40 (1.58)
59 (2.32)
59 (2.32)
0
105 (4.12)

160 (6.3)
112 (4.4)
73 (2.86)
0
737 (29.02)
635 (24.99)
380 (14.98)
325 (12.81)
177 (6.97)

na3816b

211 (8.29) 176 (6.92)

FRONT—COLD AISLE
NOTE: Dimensions are shown in mm (in.)

Item Description

Chilled-water inlet

Chilled-water outlet

Trough for communication cables

Power connections—dual feed

Humidifier supply (ACRC60xP only)

Condensate drain

86 990-5792B-001
Technical Data ACRC300 Series, ACRC600 Series

Bottom Piping and Power Access Locations (Bottom View)


REAR—HOT AISLE

479 (18.86)

397 (15.63)

345 (13.58)
345 (13.58)
0

138 (5.43)
187 (7.35)
184 (7.24)

172 (6.77)
425 (16.72)

796 (31.34)
115 (4.53)

156 (6.13)
na3809b

141 (5.54)
57.25 (2.25)
176 (6.91)

FRONT—COLD AISLE
NOTE: Dimensions are shown in mm (in.)

Item Description

Humidifier supply (ACRC60xP only)

Condensate drain

Power connections—dual feed

Communication connections—27.80 mm (1.09 in.)

Condensate overflow

Chilled-water inlet

Chilled-water outlet

990-5792B-001 87
ACRC300 Series, ACRC600 Series Facility Planning

Facility Planning
ACRC ACRC ACRC ACRC ACRC ACRC ACRC ACRC
Model
301S 301H 600 601 602 600P 601P 602P
Input Voltage 100–240 208–230 200–240 460–480 380–415 200–240 460–480 380–415

Phases 1 1 3 3 3 3 3 3
Frequency 50/60 50/60 50/60 60 50/60 50/60 50/60 60

Total NET Capacity – kW 23.5 39.0 45 45 45 45 45 45


(BTU/hr)* (80,000) (133,000) (154,000) (154,000) (154,000) (154,000) (154,000) (154,000)

Sensible NET Capacity – 23.5 39.0 43.7 43.7 43.7 43.7 43.7 43.7
kW (BTU/hr) * (80,000) (133,000) (159,000) (159,000) (159,000 (159,000) (159,000) (159,000)

Chilled Water Flow Rate 13.8 (0.87) 25.3 (1.59) 26.4 (1.7) 26.4 (1.7) 26.4 (1.7) 26.4 (1.7) 26.4 (1.7) 26.4 (1.7)
– GPM (l/s)*

Chilled Water Pressure 40.76 59.08 68 (22.6) 22.6 (68) 22.6 (68) 22.6 (68) 22.6 (68) 22.6 (68)
Drop – kPa (ft H2O)* (13.7) (19.8)

Cabinet Width – mm (in.) 300 (11.81) 300 600(23.62) 60023.62 60023.62 60023.62 60023.62 60023.62
(11.81)

Cabinet Depth – mm (in.) 1095 1095 1070 1070 1070 1070 1070 1070
(43.11) (43.11) (42.13) (42.13) (42.13) (42.13) (42.13) (42.13)

Cabinet Height – mm 1991 1991 1991 1991 1991 1991 1991 1991
(in.) (78.39) (78.39) (78.39) (78.39) (78.39) (78.39) (78.39) (78.39)

Net Weight – kg (lbs) 184 (406) 210 (463) 345 (760) 345 (760) 345 (760) 352 (776) 352 (776) 352 (776)

Operating Weight – kg 192 (423) 220 (485) 363 (800) 363 (800) 363 (800) 370 (816) 370 (816) 370 (816)
(lbs)

Power Connection Type Plug Hardwired Hard- Hardwired Hard- Hard-wired Hard-wired Hard-
wired** wired*** wired
Plug Type NEMAL5- N/A NEMA N/A IEC 309- N/A N/A N/A
20P/ L21-20P 16A
IEC309-
16A
FLA (Full Load Amps) 11 12 N/A N/A 6.0 N/A N/A 24.0
****
MCA (Minimum Current N/A 15 11.0 7.0 N/A 42.0 22.0 N/A
Amps)****

MOP (Maximum N/A 15 15.0 15.0 N/A 40.0 20.0 N/A


Overvoltage Protection)
****
Power Connection 2 2 2 2 2 2 2 2
Quantity.

Features/Options

Fan Type EC Axial EC Axial BI ECM BI ECM BI ECM BI ECM BI ECM BI ECM

Maximum Airflow – l/s 1510 1982 2832 2832 2832 2832 2832 2832
(CFM) (3200) (4200) (6000) (6000) (6000) (6000) (6000) (6000)

Fan Control Variable Variable Variable Variable Variable Variable Variable Variable
Speed Speed Speed Speed Speed Speed Speed Speed

Fan Quantity 8 8 3 3 3 3 3 3

Hot Swappable Fans Yes Yes No No No No No No

Hot Aisle Containment Yes Yes Yes Yes Yes Yes Yes Yes
Compatible

Rack Air Containment Yes Yes Yes Yes Yes Yes Yes Yes
Compatible

Chilled Water Control 2-way /3- 2-way /3- 2-way /3- 2-way /3- 2-way / 3- 2-way / 3- 2-way 3- 2-way /3-
Valve way way way way way way way way

Network Management Included Included Included Included Included Included Included Included
Card

88 990-5792B-001
Facility Planning ACRC300 Series, ACRC600 Series

ACRC ACRC ACRC ACRC ACRC ACRC ACRC ACRC


Model
301S 301H 600 601 602 600P 601P 602P
Standard Filter Type 1/2-in. 1/2-in. 4-in. 4-in. 4-in. 4-in. 4-in. 4-in.
Washable Washable Pleated Pleated Pleated Pleated Pleated Pleated

Standard Filter Efficiency < 20% < 20% 30% 30% 30% 30% 30% 30%

Optional Filter Type 2-in. 2-in. 4-in 4- 4-inPleated 4- 4-in 4-


Pleated Pleated Pleated inPleated inPleated Pleated inPleated
Optional Filter Efficiency 30% 30% 85% 85% 85% 85% 85% 85%

Condensate Pump Included N/A Included Included Included Included Included Included

Humidifier Type N/A N/A N/A N/A N/A Steam Steam Steam
Canister Canister Canister
Reheat Type N/A N/A N/A N/A N/A S/S Finned S/S Finned S/S
Tubular Tubular Finned
Tubular
Rack Inlet Temperature 1 1 3 3 3 3 3 3
Sensor Quantity

Piping Connections Top or Top or Top or ToporBot- ToporBot- ToporBot- Topor ToporBot-
Bottom Bottom Bottom tom tom tom Bottom tom
Electrical Connections Top or Top or ToporBot- ToporBot- ToporBot- Topor Topor Topor
Bottom Bottom tom† tom tom† Bottom Bottom Bottom

CW Flow Meter Included Included Included Included Included Included Included Included
Cable Type Water Optional Optional Optional Optional Optional Optional Optional Optional
Detector

*Capacity rated at the following conditions:


• EFT: 50F (10C) / CW Delta T 6.6°C (12°F)—ACRC301S
• EFT: 59F (15C) / CW Delta T 6.6°C (12°F)—ACRC301H
• EFT: 45F (7.2C) / CW Delta T 6.6°C (12°F)—ACRC600 Series
**Optional: NEMA L21-20P
***Optional: NEMA IEC-309 16A
****Cells marked N/A indicate that this information is not required because of
regional differences in electrical codes.
†Plugconnection can only be top wired. Hardwired can be done via the top or
bottom of the unit.

990-5792B-001 89
Worldwide Customer Support
Customer support for this product is available at no charge in any of the following
ways:
• Visit the Schneider Electric Web site to access documents in the Schneider
Electric Knowledge Base and to submit customer support requests.
◦ [Link] (Corporate Headquarters)
Connect to localized Schneider Electric websites for specific countries, each
of which provides customer support information.
◦ [Link]/support/
Get global support by searching the Schneider Electric Knowledge Base and
using esupport.
• Contact the Schneider Electric Customer Support Center by telephone or e-mail.
Go to [Link] > Support > Contact Support to find contact information for
country-specific centers.
For information on how to obtain local customer support, contact the representative
or other distributors from whom you purchased your product.
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
[Link]