0% found this document useful (0 votes)
120 views7 pages

Capacity Check Example

Uploaded by

kheang meng
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
120 views7 pages

Capacity Check Example

Uploaded by

kheang meng
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Project Job Ref.

Section Sheet no./rev.


1
Calc. by Date Chk'd by Date App'd by Date
SE 16-Dec-24

RC COLUMN DESIGN (EN 1992)


In accordance with EN1992-1-1:2004 incorporating Corrigendum January 2008 and the UK national annex
Tedds calculation version 1.4.06

Design summary
Description Unit Provided Required Utilisation Result
Moment capacity (y) kNm 303 191 0.63 PASS
Moment capacity (z) kNm 233 148 0.64 PASS
Biaxial bending 0.99 PASS
z

8 no. 25 mm diameter longitudinal bars


500 mm

Max link spacing 400 mm generally, 240 mm for


y y
500 mm above and below slab/beam and at laps

z
400 mm

Column input details


Column geometry
Overall depth (perpendicular to y axis); h = 500 mm
Overall breadth (perpendicular to z axis); b = ;400; mm
Clear height between restraints about y axis; ly = ;3500; mm
Clear height between restraints about z axis; lz = ;3500; mm
Stability in the z direction; Braced
Stability in the y direction; Braced
Concrete details
Concrete strength class; C40/50
Partial safety factor for concrete ([Link](1)); C = 1.50
Coefficient cc (3.1.6(1)); cc = 0.85
Maximum aggregate size; dg = 20 mm
Reinforcement details
Nominal cover to links; cnom = 35 mm
Longitudinal bar diameter;  = 25 mm
Link diameter; v = 8 mm
Total number of longitudinal bars; N=8
Project Job Ref.

Section Sheet no./rev.


2
Calc. by Date Chk'd by Date App'd by Date
SE 16-Dec-24

No. of bars per face parallel to y axis; Ny = ;3


No. of bars per face parallel to z axis; Nz = ;3
Area of longitudinal reinforcement; As = N    2 / 4 = 3927 mm2
Characteristic yield strength; fyk = 500 N/mm2
Partial safety factor for reinft ([Link](1)); S = 1.15
Modulus of elasticity of reinft (3.2.7(4)); Es = 200 kN/mm2
Fire resistance details
Fire resistance period; R = 60 min
Exposure to fire; Exposed on more than one side
Ratio of fire design axial load to design resistance; fi = 0.70

Axial load and bending moments from frame analysis


Design axial load; NEd = 4500.0 kN
Moment about y axis at top; Mtopy = ;125.0; kNm
Moment about y axis at bottom; Mbtmy = ;125.0; kNm
Moment about z axis at top; Mtopz = ;75.0; kNm
Moment about z axis at bottom; Mbtmz = ;75.0; kNm
Joint details at end 1 of column
Beam/slab concrete strength class; C30/37
Beams/slabs providing rotational restraint about y axis
Depth on side A; hA1y = 500 mm
Width on side A; bA1y = 300 mm
Length on side A; lA1y = 7200 mm

Depth on side B; hB1y = 500 mm


Width on side B; bB1y = 300 mm
Length on side B; lB1y = 7200 mm
Beams providing rotational restraint about z axis
Depth on side A; hA1z = 400 mm
Width on side A; bA1z = 300 mm
Length on side A; lA1z = 6000 mm

Depth on side B; hB1z = 400 mm


Width on side B; bB1z = 300 mm
Length on side B; lB1z = 6000 mm
Joint details at 2 of column
Relative flexibility end 2 for buckling about y axis; k2y = 1000.000
Relative flexibility end 2 for buckling about z axis; k2z = 1000.000

Calculated column properties


Concrete properties
Area of concrete; Ac = h  b = 200000 mm2
Column characteristic comp. cylinder strength; fck = 40 N/mm2
Column design comp. strength (3.1.6(1)); fcd = cc  fck / C = 22.7 N/mm2
Column mean value of cyl. strength (Table 3.1); fcm = fck + 8 MPa = 48.0 N/mm2
Project Job Ref.

Section Sheet no./rev.


3
Calc. by Date Chk'd by Date App'd by Date
SE 16-Dec-24

Column secant modulus of elasticity (Table 3.1); Ecm = 22000 MPa  (fcm / 10 MPa)0.3 = 35.2 kN/mm2
Beam/slab characteristic comp. cylinder strength; fck_b = 30 N/mm2
Beam/slab mean value of cyl. strength (3.1.6(1)); fcm_b = fck_b + 8 MPa = 38.0 N/mm2
Beam/slab secant mod. of elasticity (Table 3.1); Ecm_b = 22000 MPa  (fcm_b / 10 MPa)0.3 = 32.8 kN/mm2

Rectangular stress block factors


Depth factor (3.1.7(3)); sb = 0.8
Stress factor (3.1.7(3));  = 1.0

Strain limits
Compression strain limit (Table 3.1); cu3 = 0.00350
Pure compression strain limit (Table 3.1); c3 = 0.00175

Design yield strength of reinforcement


Design yield strength (3.2.7(2)); fyd = fyk / S = 434.8 N/mm2

Check nominal cover for fire and bond requirements


Min. cover reqd for bond (to links) ([Link](3)); cmin,b = max(v,  - v) = 17 mm
Min axis distance for fire (EN1992-1-2 T 5.2a); afi = 40 mm
Allowance for deviations from min cover ([Link]); cdev = 10 mm
Min allowable nominal cover; cnom_min = max(afi -  / 2 - v, cmin,b + cdev) = 27.0 mm
PASS - the nominal cover is greater than the minimum required
Effective depths of bars for bending about y axis
Area per bar; Abar =   2 / 4 = 491 mm2
Spacing of bars in faces parallel to z axis (c/c); sz = (h - 2  (cnom + v) - ) / (Nz - 1) = 194 mm
Layer 1 (in tension face); dy1 = h - cnom - v -  / 2 = 445 mm
Layer 2; dy2 = dy1 - sz = 250 mm
Layer 3; dy3 = dy2 - sz = 56 mm
2nd moment of area of reinft about y axis; Isy = 2  Abar (Ny  (dy1 - h /2)2) = 11142 cm4

Radius of gyration of reinft about y axis; isy = (Isy / As) = 168 mm


Effective depth about y axis ([Link](2)); dy = h / 2 + isy = 418 mm
Effective depths of bars for bending about z axis
Area of per bar; Abar =   2 / 4 = 491 mm2
Spacing of bars in faces parallel to y axis (c/c); sy = (b - 2  (cnom + v) - ) / (Ny - 1) = 145 mm
Layer 1 (in tension face); dz1 = b - cnom - v -  / 2 = 344 mm
Layer 2; dz2 = dz1 - sy = 200 mm
Layer 3; dz3 = dz2 - sy = 56 mm
2nd moment of area of reinft about z axis; Isz = 2  Abar (Nz  (dz1 - b /2)2) = 6150 cm4

Radius of gyration of reinft about z axis; isz = (Isz / As) = 125 mm


Effective depth about z axis ([Link](2)); dz = b / 2 + isz = 325 mm
Relative flexibility at end 1 for buckling about y axis
Second moment of area of column; Iy = b  h3 / 12 = 416667 cm4
Second moment of area of beam on side A; IA1y = bA1y  hA1y3 / 12 = 312500 cm4
Second moment of area of beam on side B; IB1y = bB1y  hB1y3 / 12 = 312500 cm4
Project Job Ref.

Section Sheet no./rev.


4
Calc. by Date Chk'd by Date App'd by Date
SE 16-Dec-24

Relative flexibility (PD6687 cl. 2.10); k1y = max(0.1, (Ecm  Iy / ly) / [2  Ecm_b  (IA1y/lA1y + IB1y/lB1y)]) = 0.735

Joint details at 2 of column


Relative flexibility end 2 for buckling about y axis; k2y = 1000.000
Relative flexibility at end 1 for buckling about z axis
Second moment of area of column; Iz = h  b3 / 12 = 266667 cm4
Second moment of area of beam on side A; IA1z = bA1z  hA1z3 / 12 = 160000 cm4
Second moment of area of beam on side B; IB1z = bB1z  hB1z3 / 12 = 160000 cm4
Relative flexibility (PD6687 cl. 2.10); k1z = max(0.1, (Ecm  Iz / lz) / [2  Ecm_b  (IA1z/lA1z + IB1z/lB1z)]) = 0.766
Relative flexibility end 2 for buckling about z axis; k2z = 1000.000
Calculated effective length (cl. [Link])
Eff. length about y axis (braced) ([Link](3)); l0y = 0.5  ly  [(1 + k1y/(0.45+k1y))(1 + k2y/(0.45+k2y))]0.5 = 3150 mm
Eff. length about z axis (braced) ([Link](3)); l0z = 0.5  lz  [(1 + k1z/(0.45+k1z))(1 + k2z/(0.45+k2z))]0.5 = 3159 mm

Column slenderness about y axis


Radius of gyration; iy = h / (12) = 14.4 cm
Slenderness ratio ([Link](1)); y = l0y / iy = 21.8

Column slenderness about z axis


Radius of gyration; iz = b / (12) = 11.5 cm
Slenderness ratio ([Link](1)); z = l0z / iz = 27.4

Design bending moments


Frame analysis moments about y axis combined with moments due to imperfections (cl. 5.2 & 6.1(4))
Ecc. due to geometric imperfections (y axis); eiy = l0y /400 = 7.9 mm
Min end moment about y axis; M01y = min(abs(Mtopy), abs(Mbtmy)) + eiy  NEd = 160.4 kNm
Max end moment about y axis; M02y = max(abs(Mtopy), abs(Mbtmy)) + eiy  NEd = 160.4 kNm
Slenderness limit for buckling about y axis (cl. [Link])
Factor A; A = 0.7
Mechanical reinforcement ratio;  = As  fyd / (Ac  fcd) = 0.377
Factor B; B = (1 + 2  ) = 1.324
Moment ratio; rmy = M01y / M02y = ;1.000
Factor C; Cy = 1.7 - rmy = 0.700
Relative normal force; n = NEd / (Ac  fcd) = 0.993
Slenderness limit; limy = 20  A  B  Cy / (n) = 13.0
y>=limy - Second order effects must be considered

Frame analysis moments about z axis combined with moments due to imperfections (cl. 5.2 & 6.1(4))
Ecc. due to geometric imperfections (z axis); eiz = l0z /400 = 7.9 mm
Min end moment about z axis; M01z = min(abs(Mtopz), abs(Mbtmz)) + eiz  NEd = 110.5 kNm
Max end moment about z axis; M02z = max(abs(Mtopz), abs(Mbtmz)) + eiz  NEd = 110.5 kNm
Slenderness limit for buckling about y axis (cl. [Link])
Factor A; A = 0.7
Mechanical reinforcement ratio;  = As  fyd / (Ac  fcd) = 0.377
Factor B; B = (1 + 2  ) = 1.324
Project Job Ref.

Section Sheet no./rev.


5
Calc. by Date Chk'd by Date App'd by Date
SE 16-Dec-24

Moment ratio; rmz = M01z / M02z = ;1.000


Factor C; Cz = 1.7 - rmz = 0.700
Relative normal force; n = NEd / (Ac  fcd) = 0.993
Slenderness limit; limz = 20  A  B  Cz / (n) = 13.0
z>=limz - Second order effects must be considered
Local second order bending moment about y axis (cl. [Link] & [Link])
Relative humidity of ambient environment; RH = 50 %
Column perimeter in contact with atmosphere; u = 1800 mm
Age of concrete at loading; t0 = 28 day
Parameter nu; nu = 1 +  = 1.377
Approx value of n at max moment of resistance; nbal = 0.4
Axial load correction factor; Kr = min(1.0 , (nu - n) / (nu - nbal)) = 0.393
Reinforcement design strain; yd = fyd / Es = 0.00217
Basic curvature; curvebasic_y = yd / (0.45  dy) = 0.0000115 mm-1
Notional size of column; h0 = 2  Ac / u = 222 mm
Factor 1 (Annex B.1(1)); 1 = (35 MPa / fcm)0.7 = 0.802
Factor 2 (Annex B.1(1)); 2 = (35 MPa / fcm)0.2 = 0.939
Relative humidity factor (Annex B.1(1)); RH = [1 + ((1 - RH / 100%) / (0.1 mm-1/3  (h0)1/3))  1]  2 = 1.560
Concrete strength factor (Annex B.1(1)); fcm = 16.8  (1 MPa)1/2 / (fcm) = 2.425
Concrete age factor (Annex B.1(1)); t0 = 1 / (0.1 + (t0 / 1 day)0.2) = 0.488
Notional creep coefficient (Annex B.1(1)); 0 = RH  fcm  t0 = 1.848
Final creep development factor; (at t = ; c = 1.0
Final creep coefficient (Annex B.1(1));  = 0  c = 1.848
Ratio of SLS to ULS moments; rMy = 0.65
Effective creep ratio; efy =   rMy = 1.201
Factor ; y = 0.35 + fck / 200 MPa - y / 150 = 0.405
Creep factor; Ky = max(1.0 , 1 + y  efy) = 1.486
Modified curvature; curvemod_y = Kr  Ky  curvebasic_y = 0.0000067 mm-1
Curvature distribution factor; c = 10
Deflection; e2y = curvemod_y  l0y2 / c = 6.7 mm
Nominal 2nd order moment; M2y = NEd  e2y = 30.1 kNm

Design bending moment about y axis (cl. [Link] & 6.1(4))


Equivalent moment from frame analysis; M0ey = max(0.6  M02y + 0.4  M01y, 0.4  M02y) = ;160.4; kNm
Design moment; MEdy = max(M02y, M0ey + M2y, M01y + 0.5M2y, NEd  max(h/30, 20 mm))
MEdy = 190.6 kNm
Local second order bending moment about z axis (cl. [Link] & [Link])
Basic curvature; curvebasic_z = yd / (0.45  dz) = 0.0000149 mm-1
Ratio of SLS to ULS moments; rMz = 0.65
Effective creep ratio (5.8.4(2)); efz =   rMz = 1.201
Factor ; z = 0.35 + fck / 200 MPa - z / 150 = 0.368
Creep factor; Kz = max(1.0 , 1 + z  efz) = 1.441
Modified curvature; curvemod_z = Kr  Kz  curvebasic_z = 0.0000084 mm-1
Project Job Ref.

Section Sheet no./rev.


6
Calc. by Date Chk'd by Date App'd by Date
SE 16-Dec-24

Curvature distribution factor; c = 10


Deflection; e2z = curvemod_z  l0z2 / c = 8.4 mm
Nominal 2nd order moment; M2z = NEd  e2z = 37.8 kNm

Design bending moment about z axis (cl. [Link] & 6.1(4))


Equivalent moment from frame analysis; M0ez = max(0.6  M02z + 0.4  M01z, 0.4  M02z) = ;110.5; kNm
Design moment; MEdz = max(M02z, M0ez + M2z, M01z + 0.5M2z, NEd  max(b/30, 20 mm))
MEdz = 148.4 kNm

Moment capacity about y axis with axial load (4500.0 kN)


Moment of resistance of concrete
By iteration:-
Position of neutral axis; y = 481.2 mm
Concrete compression force (3.1.7(3)); Fyc =  fcd  min(sb  y , h)  b = 3490.7 kN
Moment of resistance; MRdyc = Fyc  [h / 2 - (min(sb  y , h)) / 2] = 200.7 kNm

Moment of resistance of reinforcement


Strain in layer 1; y1 = cu3  (1 - dy1 / y) = 0.00027
Stress in layer 1; y1 = min(fyd, Es  y1) = 53.5 N/mm2
Force in layer 1; Fy1 = Ny  Abar  y1 = 78.7 kN
Moment of resistance of layer 1; MRdy1 = Fy1  (h / 2 - dy1) = -15.3 kNm
Strain in layer 2; y2 = cu3  (1 - dy2 / y) = 0.00168
Stress in layer 2; y2 = min(fyd, Es  y2) -   fcd = 313.7 N/mm2
Force in layer 2; Fy2 = 2  Abar  y2 = 308.0 kN
Moment of resistance of layer 2; MRdy2 = Fy2  (h / 2 - dy2) = 0.0 kNm
Strain in layer 3; y3 = cu3  (1 - dy3 / y) = 0.00310
Stress in layer 3; y3 = min(fyd, Es  y3) -   fcd = 412.1 N/mm2
Force in layer 3; Fy3 = Ny  Abar  y3 = 606.9 kN
Moment of resistance of layer 3; MRdy3 = Fy3  (h / 2 - dy3) = 118.0 kNm
Resultant concrete/steel force; Fy = 4484.2 kN
PASS - This is within half of one percent of the applied axial load
Combined moment of resistance
Moment of resistance about y axis; MRdy = 303.4 kNm
PASS - The moment capacity about the y axis exceeds the design bending moment

Moment capacity about z axis with axial load (4500.0 kN)


Moment of resistance of concrete
By iteration:-
Position of neutral axis; z = 385.0 mm
Concrete compression force (3.1.7(3)); Fzc =  fcd  min(sb  z , b)  h = 3490.7 kN
Moment of resistance; MRdzc = Fzc  [b / 2 - (min(sb  z , b)) / 2] = 160.6 kNm

Moment of resistance of reinforcement


Strain in layer 1; z1 = cu3  (1 - dz1 / z) = 0.00037
Stress in layer 1; z1 = min(fyd, Es  z1) = 73.6 N/mm2
Force in layer 1; Fz1 = Nz  Abar  z1 = 108.4 kN
Project Job Ref.

Section Sheet no./rev.


7
Calc. by Date Chk'd by Date App'd by Date
SE 16-Dec-24

Moment of resistance of layer 1; MRdz1 = Fz1  (b / 2 - dz1) = -15.7 kNm


Strain in layer 2; z2 = cu3  (1 - dz2 / z) = 0.00168
Stress in layer 2; z2 = min(fyd, Es  z2) -   fcd = 313.7 N/mm2
Force in layer 2; Fz2 = 2  Abar  z2 = 308.0 kN
Moment of resistance of layer 2; MRdz2 = Fz2  (b / 2 - dz2) = 0.0 kNm
Strain in layer 3; z3 = cu3  (1 - dz3 / z) = 0.00300
Stress in layer 3; z3 = min(fyd, Es  z3) -   fcd = 412.1 N/mm2
Force in layer 3; Fz3 = Nz  Abar  z3 = 606.9 kN
Moment of resistance of layer 3; MRdz3 = Fz3  (b / 2 - dz3) = 87.7 kNm
Resultant concrete/steel force; Fz = 4514.0 kN
PASS - This is within half of one percent of the applied axial load
Combined moment of resistance
Moment of resistance about z axis; MRdz = 232.6 kNm
PASS - The moment capacity about the z axis exceeds the design bending moment

Biaxial bending
Determine if a biaxial bending check is required (5.8.9(3))
Ratio of column slenderness ratios; ratio = max(y, z) / min(y, z) = 1.25
Eccentricity in direction of y axis; ey = MEdz / NEd = 33.0 mm
Eccentricity in direction of z axis; ez = MEdy / NEd = 42.3 mm
Equivalent depth; heq = iy  (12) = 500 mm
Equivalent width; beq = iz  (12) = 400 mm
Relative eccentricity in direction of y axis; erel_y = ey / beq = 0.082
Relative eccentricity in direction of z axis; erel_z = ez / heq = 0.085
Ratio of relative eccentricities; ratioe = min(erel_y, erel_z) / max(erel_y, erel_z) = 0.973
ratioe > 0.2 - Biaxial bending check is required
Biaxial bending (5.8.9(4))
Design axial resistance of section; NRd = (Ac  fcd) + (As  fyd) = 6240.7 kN
Ratio of applied to resistance axial loads; ratioN = NEd / NRd = 0.721
Exponent a; a = 1.54
Biaxial bending utilisation; UF = (MEdy / MRdy)a + (MEdz / MRdz)a = 0.991
PASS - The biaxial bending capacity is adequate

You might also like