TECHNICAL DATA
Specification: LOW VOLTAGE UNARMOURED CABLE,
CONFORMING TO IEC 60502-1 ISO 9001:2008
Certificate N°
2006/7034b
Customer : DEGREMONT - BANGLADESH
Customer's Appellation:
Manufacturer's Appelation/Type : E X 1*500
RATED VOLTAGE KV: 0.6 / 1
DESCRIPTION: CU/XLPE/PVC
CONDUCTOR STRANDED ANNEALED COPPER CLASS 2 acc. to IEC 60228
INSULATION XLPE
OVERSHEATH PVC
DIMENSIONAL CHARACTERISTICS
ITEM N° 1
CABLE SIZE mm2 1*500
Size mm2 500
CONDUCTOR
Shape Circular
INSULATION Nom. thickness mm 2.2
Nom. thickness mm 2
OVERSHEATH
Color BLACK
MARKING By yellow or white ink jet printing on one line over the outer jacket
OVERALL DIAM. Nom. Diam. (-3%+7%) mm 35
CABLE WEIGHT Approx. kg/km 4750
ELECTRICAL & MECHANICAL CHARACTERISTICS
Spark test during insulation KVAC 14
Max. DC conductor resist. at 20°C. ohm/Km 0.0366
Max. current carrying capacity in air * A 870
Max. current carrying capacity in ground * A 780
* Above current carrying capacities are calculated at the following laying conditions:
- Ambient Temperature of air 30° C
- Soil Temperature 20°C
- Depth of laying 0.6m
- Thermal resistivity of soil 1°Cm/W Flame retardant
For other conditions correction factors should be applied. According to IEC 60332-1-2
• Operating conditions: • Minimum bending radius:
Max. Continuous operating Temp. : 90°C 9 x outer Diameter
Max. short circuit Temp. : 250°C To be doubled during laying conditions
Prepared by: GCH Customer Ref. N° Our Ref: 13115 Approved by:
Customer Ref. N°
13115T EX (1C)
TECHNICAL DATA
Specification: LOW VOLTAGE UNARMOURED CABLE
CONFORMING TO IEC 60502-1 ISO 9001:2008
Certificate N°
2006/7034b
Customer : DEGREMONT - BANGLADESH
Customer's Appellation:
Manufacturer's Appelation/Type : E X 1*500
Items number : 1
TEST AT WORKS
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag.15.1&15.2
- Spark test during insulation
Liban Cables will carry out these tests on all the length and tests certificates will be provided
Sample tests
Check of the build - up and color coding of the cable
Check of dimensions
Insulation : according to IEC 60502-1 Parag. 16.5.2
Oversheath : according to IEC 60502-1 Parag. 16.5.3
These tests will be carried out on one length during of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation
at break) in accordance with IEC 60502-1.
These tests will be carried out on one length of the order
Tests certificates will be provided by Liban Cables
Prepared by: GCH Customer Ref. N° Our Ref: 13115 Approved by:
13115T test (EX1C)
TECHNICAL DATA
Specification: LOW VOLTAGE, ARMOURED CABLE
CONFORMING TO IEC 60502-1 ISO 9001:2008
Certificate N°
2006/7034b
Customer : DEGREMONT - BANGLADESH
Customer's Appellation:
Manufacturer's Appelation/Type : E XR
RATED VOLTAGE KV: 0.6 / 1
DESCRIPTION: CU/XLPE/PVC/GSWA/PVC
CONDUCTOR STRANDED ANNEALED COPPER Class 2 acc. to IEC 60228
INSULATION XLPE
INNER COVERING PVC
ARMOUR GALVANIZED STEEL WIRES
OVERSHEATH PVC
DIMENSIONAL CHARACTERISTICS
ITEM N° 2 5 6
CABLE SIZE mm2 3*240 3*120 4*70
Size mm2 240 120 70
CONDUCTOR
Shape Shaped Shaped Shaped
INSULATION Nom. thickness mm 1.7 1.2 1.1
ARMOUR Nom. Diam. of each wire mm 2.5 2.0 2.0
Nom. thickness mm 2.8 2.3 2.2
OVERSHEATH
Color BLACK BLACK BLACK
MARKING By yellow or white ink jet printing on one line over the outer jacket
OVERALL DIAM. Nom. Diameter (-3%+7%) mm 56 41 38
CABLE WEIGHT Approx. kg/km 9650 5000 4080
ELECTRICAL & MECHANICAL CHARACTERISTICS
A.C Voltage test for 5 minutes KV 3.5 3.5 3.5
Max. DC conductor resist. at 20°C. ohm/Km 0.0754 0.153 0.268
Max. current carrying capacity in air * A 522 339 242
Max. current carrying capacity in ground * A 504 345 252
* Above current carrying capacities are calculated at the following laying conditions:
- Ambient Temperature of air 30° C
- Soil Temperature 20°C
- Depth of laying 0.6m
- Thermal resistivity of soil 1°Cm/W Flame retardant
For other conditions correction factors should be applied. According to IEC 60332-1-2
• Operating conditions: • Minimum bending radius:
Max. Continuous operating Temp. : 90°C 10 x outer Diameter
Max. short circuit Temp. : 250°C To be doubled during laying conditions
Prepared by: [Link] Customer Ref. Our Ref: 13115 Approved by:
13115T EXR (2)
TECHNICAL DATA
Specification: LOW VOLTAGE, ARMOURED CABLE
CONFORMING TO IEC 60502-1 ISO 9001:2008
Certificate N°
2006/7034b
Customer : DEGREMONT - BANGLADESH
Customer's Appellation:
Manufacturer's Appelation/Type : E XR
Items number : 2,5,6
TEST AT WORKS
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag.15.1&15.2
- Voltage test acc. to IEC 60502-1 parag.15.1& 15.3
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided
Sample tests
Check of the build - up and color coding of the cable
Check of dimensions
Insulation : according to IEC 60502-1 Parag. 16.5.2
Armour : according to IEC 60502-1 Parag. 16.7
Oversheath : according to IEC 60502-1 Parag. 16.5.3
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation
at break ) in accordance with IEC 60502-1.
These tests will be carried out on one length of the order
Tests certificates will be provided by Liban Cables
Prepared by: [Link] Customer Ref. N° Our Ref: 13115 Approved by:
13115T test (EXR)
TECHNICAL DATA
Specification: LOW VOLTAGE UNARMOURED CABLE,
CONFORMING TO IEC 60502-1 ISO 9001:2008
Certificate N°
2006/7034b
Customer : DEGREMONT - BANGLADESH
Customer's Appellation:
Manufacturer's Appelation/Type : EX
RATED VOLTAGE KV : 0.6/1
DESCRIPTION: CU/XLPE/PVC
CONDUCTOR STRANDED ANNEALED COPPER CLASS 2 acc. to IEC 60228
INSULATION XLPE
OVERSHEATH PVC
DIMENSIONAL CHARACTERISTICS
ITEM N° 3 4 7 8 9
CABLE SIZE mm2 4*185 3*120 4*70 4*16 4*10
Size mm2 185 120 70 16 10
CONDUCTOR
Shape Shaped Shaped Shaped Circular Circular
INSULATION Nom. thickness mm 1.6 1.2 1.1 0.7 0.7
Nom. thickness mm 2.6 2.1 2.0 1.8 1.8
OVERSHEATH
Color BLACK BLACK BLACK BLACK BLACK
MARKING By yellow or white ink jet printing on one line over the outer jacket
OVERALL DIAM. [Link].(-3% +7%) mm 49 34 31 18.5 16.5
CABLE WEIGHT Approx. kg/km 7250 3550 2760 770 535
ELECTRICAL & MECHANICAL CHARACTERISTICS
A.C Voltage test for 5 minutes KV 3.5 3.5 3.5 3.5 3.5
Max. DC conductor resist. at 20°C. ohm/Km 0.0991 0.153 0.268 1.15 1.83
Max. current carrying capacity in air * A 444 339 242 96 71
Max. current carrying capacity in ground * A 435 345 252 111 88
* Above current carrying capacities are calculated at the following laying conditions:
- Ambient Temperature of air 30° C
- Soil Temperature 20°C
- Depth of laying 0.6 m
- Thermal resistivity of soil 1°Cm/W
For other conditions correction factors should be applied. Flame retardant
According to IEC 60332-1-2
• Operating conditions:
Max. Continuous operating Temp. : 90°C
Max. short circuit Temp. : 250°C
• Minimum bending radius:
6 x outer Diameter
To be doubled during laying conditions
Prepared by: GCH Customer Ref. N° Our Ref: 13115 Approved by:
Customer Ref. N°
13115T EX (4)
TECHNICAL DATA
Specification: LOW VOLTAGE UNARMOURED CABLE,
CONFORMING TO IEC 60502-1 ISO 9001:2008
Certificate N°
2006/7034b
Customer : DEGREMONT - BANGLADESH
Customer's Appellation:
Manufacturer's Appelation/Type : EX
RATED VOLTAGE KV : 0.6/1
DESCRIPTION: CU/XLPE/PVC
CONDUCTOR STRANDED ANNEALED COPPER CLASS 2 acc. to IEC 60228
INSULATION XLPE
OVERSHEATH PVC
DIMENSIONAL CHARACTERISTICS
ITEM N° 10 11 12 13 14
CABLE SIZE mm2 4*4 4*2.5 3*1.5 5*1.5 7*1.5
Size mm2 4 2.5 1.5 1.5 1.5
CONDUCTOR
Shape Circular Circular Circular Circular Circular
INSULATION Nom. thickness mm 0.7 0.7 0.7 0.7 0.7
Nom. thickness mm 1.8 1.8 1.8 1.8 1.8
OVERSHEATH
Color BLACK BLACK BLACK BLACK BLACK
MARKING By yellow or white ink jet printing on one line over the outer jacket
OVERALL DIAM. [Link].(-3% +7%) mm 13 12 10 11.5 12.5
CABLE WEIGHT Approx. kg/km 271 198 128 167 208
ELECTRICAL & MECHANICAL CHARACTERISTICS
A.C Voltage test for 5 minutes KV 3.5 3.5 3.5 3.5 3.5
Max. DC conductor resist. at 20°C. ohm/Km 4.61 7.41 12.1 12.1 12.1
Max. current carrying capacity in air * A 40 30 22 24 24
Max. current carrying capacity in ground * A 51 40 29 34 34
* Above current carrying capacities are calculated at the following laying conditions:
- Ambient Temperature of air 30° C
- Soil Temperature 20°C
- Depth of laying 0.6 m
- Thermal resistivity of soil 1°Cm/W
For other conditions correction factors should be applied. Flame retardant
According to IEC 60332-1-2
• Operating conditions:
Max. Continuous operating Temp. : 90°C
Max. short circuit Temp. : 250°C • Minimum bending radius:
6 x outer Diameter
To be doubled during laying conditions
Prepared by: GCH Customer Ref. N° Our Ref: 13115 Approved by:
Customer Ref. N°
13115T EX (11)
TECHNICAL DATA
Specification: LOW VOLTAGE UNARMOURED CABLE
CONFORMING TO IEC 60502-1 ISO 9001:2008
Certificate N°
2006/7034b
Customer : DEGREMONT - BANGLADESH
Customer's Appellation:
Manufacturer's Appelation/Type : EX
Item's numbers : 3,4,7 TO 14
TEST AT WORKS
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag.15.1&15.2
- Voltage test acc. to IEC 60502-1 parag.15.1& 15.3
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided
Sample tests
Check of the build - up and color coding of the cable
Check of dimensions
Insulation : according to IEC 60502-1 Parag. 16.5.2
Oversheath : according to IEC 60502-1 Parag. 16.5.3
These tests will be carried out on one length during of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation
at break) in accordance with IEC 60502-1.
These tests will be carried out on one length of the order
Tests certificates will be provided by Liban Cables
Prepared by: GCH Customer Ref. N° Our Ref: 13115 Approved by:
13115T test (EX)