1
Important terms
Solid Earth: A conductor is said to be solidly earthed when it is electrically
connected to an earth electrode without a fuse, switch, circuit-breaker or resistance
in the earth connection.
Earth Wire: A conductor connected to earth and usually situated in proximity to the
associated line conductors.
Earth Electrode: A metal plate, pipe or other conductor, or an array of conductors
electrically connected to the general mass of earth.
2
Cont’d
Earthing conductor: is a conductor which connects part of an electrical installation
to an earthing electrode.
Leakage: The passage of electricity in path, other than that desired, due to imperfect
insulation.
Earth Continuity Conductor: The conductor, including any clamp connecting to
the earthing lead or to each other, those parts of an installation which are required to
be earthed. It may be in whole or in part the metal conduit or metal sheath/the armor
of the cables or a special continuity conductor, cable/flexible cord incorporating
such a conductor.
3
Cont.
• Extraneous conductive part: is a conductive part liable to introduce a potential and
not forming part installation.
• Exposed Conductive part: a conductive part of equipment which can be touched &
which is not a live part but which may become live under fault condition.
4
Cont.
Protection in electrical installation design means:
Protection of human beings from electric shock and hazards in case of occurrence
of contact with a powered circuit or any part thereof.
Protection of equipment and devices from overcurrents and also some faults.
Protection against fire that may be caused by overheating of cables, accessories
and devices.
5
Cont.
Electrical protection against the above risks is provided by two methods.
1. By provision of automatic devices (fuses, circuit breakers, overload relays,…)
which immediately cutoff the supply. in case of over-currents.
2. By provision of a separate and direct path to earth using grounding systems.
6
5.1. Earthing and Bonding
• Earthing means connection of the neutral point of a supply system or the non-current
carrying parts of electrical apparatus such as:
Metallic frame work,
metallic covering cables,
metal covers of switches,
metal casing of portable apparatus,
frame of every generator and motor etc. to the general mass of earth in such a
manner that at all times immediate discharge of electrical energy takes place
without danger.
7
Cont.
Earthing or grounding is classified as:
System earthing and
Equipment earthing
Earthing of neutral in power-houses and sub-stations belongs to the system earthing.
It is employed to restrict the voltage of live conductors with respect to the
potential of the general mass of earth to a value consistent with the insulation
level.
Equipment earthing signifies earthing of non-current-carrying metal parts of
electrical equipment.
8
Cont.
Earthing provides protection to personnel and equipment by ensuring operation of
the protective control gear and isolation of the faulty circuit in the following cases:
Insulation failure: in case of a ground developing on one of the phase
conductors, as a result of insulation failure, electric current will flow through the
ground path.
Accidental contact between wires of high and low voltage lines
Breakdown of insulation b/n primary & secondary windings of a
transformer
Lightening stroke
9
Cont.
Bonding: is the act of joining two electrical conductors together. These may be two
wires, a wire and a pipe, or two equipment's.
It has to be done by connecting of all the metal parts that are not supposed to be
carrying current during normal operations to bringing them to the same electrical
potential.
That means we would not get electricity building up in one equipment or between
two different equipment.
10
Cont.
No current flow can take place b/n two bonded bodies b/c they have the same
potential.
Bonding itself, does not protect anything. However, if one of those boxes is
earthed there can be no electrical energy build-up. If the grounded box is bonded to
the other box, the other box is also at zero electrical potential.
11
Cont.
Grounding/earthing is done to dissipate the energy into a low impedance
grounding system.
All ground points are bonded together to eliminate ground loops and create an
equipotential plane.
12
Cont.
Grounding reduces the risk of serious electric shock from current leaking into
uninsulated metal parts of an appliance, power tool, or other electrical device.
Grounding is also used in manufacturing industries to prevent accumulation of
hazardous static electrical charges.
13
5.2. Grounding/Earthing Electrodes
An earth electrode should be able to resist corrosion for a long time. The
recommended materials are copper, copper-clad iron, cast iron & galvanized
steel.
The various type of earth electrodes in use are:
a) pipe electrodes
b) Rod electrodes
c) Strip electrodes
d) Plate electrodes
14
Cont.
a) Pipe electrodes : is made of cast-iron pipe 2m long and
buried in a coke-filled pit. It shall not be smaller than 38 mm
internal diameter of galvanized iron or steel, and 100 mm
internal diameter made of cast iron.
b) Rod electrodes:- are very economical and require no
excavation for their installation. It shall be at least 16mm in
diameter of steel, and 12.5 mm in diameter of copper. The
length of rod electrodes shall not be less than 2.5 m
15
Cont.
c) Strip electrodes: are usually copper strip. They are
most useful in shallow soil overlying rock. It shall not
be smaller in cross-section than 25 mm * 1.60mm of
copper, and 25 mm* 4mm of galvanized iron and steel.
d) Plate Electrode: a cast-iron plate electrode buried
vertically with the center about 1m below the surface;
provide a large surface area and are used mainly where
the ground is shallow (where the resistivity is low near
the surface but increases rapidly with depth). 16
Components of ground electrode
• Ground conductor
• Connection b/n ground conductor and electrode
• Ground electrode
Note that: the connection b/n grounding conductor and the
grounding electrode should be very tight. Loose connections
result in high grounding resistance.
17
Overall ground system
Colour of grounding conductor: yellow +green
18
Type of connections
• Welded, bolted and clamped joints are permissible. All bolted and screwed
connections shall be protected against corrosion.
• Special care should be taken to protect connections of dissimilar metals against
corrosion.
• All surfaces where connections are made should be free of grease, paint, dirt or any
other extraneous material.
19
Cont’d
• Water and gas pipes and members of structural steel-work shall not be used as earth
continuity conductor.
• Flexible conduit shall not be used as E.C.C. A separate earth wire should be
provided either inside or outside the flexible conduit which should be connected by
means of earth clips to the earth system at one end, & to the equipment at the other
end.
20
Cont.
• Earthing of domestic fittings and appliances: Earthing of all domestic appliances
except those provided with double insulation is obligatory. All plugs & sockets shall
be a three-pin type, the earth pins being connected to the earth wire.
– Radio sets should be earthed preferably through an electrode different from that of the
main earth system for better reception. Where it is not possible to have a separate earth
electrode, they may be earthed through the main earth system.
21
Cont.
• Earthing of machine tools: Irrespective of the size and type of a machine tool, its
bed plate shall be earthed by means of a strip of conductor of not less than 6.5mm2
cross-sectional area of copper, and 16 mm2 of galvanized iron. The strip should be
securely fastened by means of a bolt.
22
Grounding resistance
• The value of resistance as measured by the conductive earth and the grounding
terminal needs to be as small as possible.
• The grounding resistance depends on
the length and cross-sectional area of the electrode,
the type of soil and its moisture content. .
• While many factors come into play in determining the overall effectiveness of the
grounding system, the resistance of the earth itself (earth resistivity) can
significantly impact the overall impedance of the grounding system
23
Contd
• Several factors, such as moisture content, mineral content, soil type, soil
contaminants, etc., determine the overall resistivity of the earth.
• In general, the higher the soil moisture content, the lower the soil’s resistivity.
• Systems designed for areas which typically have very dry soil and arid climates may
need to use enhancement materials or other means to achieve lower soil resistivity.
24
Cont.
• Typical values for soil resistivity in ohms are as follows:
Type of soil Resistivity in Ωm
Garden Soil 5-50
Clay 10-100
Sand 250-500
Rock 1000-10,000
25
Earthing systems
• Contact with metalwork made live by a fault is called indirect contact.
• One popular method of providing some measure of protection against such contact
is by earthed equipotential bonding and automatic disconnection of supply.
• This entails the bonding together and connection to earth of:
26
Cont.
• All metalwork associated with electrical apparatus and systems, termed as exposed
Conductive parts.
– Examples include conduit, trunking and the metal cases of apparatus.
• All metalwork liable to introduce a potential including earth potential, termed as
extraneous conductive parts.
– Examples are gas, oil and water pipes, structural steelwork, radiators, sinks and
baths.
27
5.3. Location of system earthing
An internal wiring system that is supplied by an AC service and which is to be
earthed shall have at each service, an earthing conductor to an earth electrode.
The earthing conductor shall be connected to the earthed service conductor at any
accessible point from the load end of service drop or service lateral.
28
Contd
Where the transformer supplying the services is located outside the building, at least
one additional earthing connection shall be made from the earthed service conductor
to an earth electrode, either at the transformer or elsewhere outside the building.
An earthing connection shall not be made to any earthed circuit conductor on the
load side of the service disconnecting means.
29
Cont.
For circuits that are supplied from two sources in a common enclosure or grouped
together in separate enclosure and employing a tie, a single earthing electrode
connection to the tie point of the earthed circuit conductors from each power supply
source shall be permitted.
30
5.4. Grounding Arrangements
There are different types of earthing systems. These systems have been designated in the
IEE Regulations using the letters T, N, C and S. These letters stand for:
T - Terre (French for earth) and meaning a direct connection to earth.
N - Neutral
C - Combined
S –Separate
There are three types of earthing arrangements. These are:
TT
IT and
TN 31
TT System
• A TT system has a direct connection of the supply source to earth and a direct
connection of the installation metalwork to earth.
• An example is an overhead line supply with earth electrodes, and the mass of earth
as a return path for the line.
32
Cont.
TT system
The supply will have the neutral connected to earth at the supply transformer
together with the metalwork of all casing or enclosures of the electrical
equipment.
Therefore, the first letter, T, signifies that the supply has been earthed (T = terra
firma = earth). And the second letter, T, indicates that the installation has its own
earth electrode.
This system is commonly met in rural districts where the incoming supply is by
overhead cables supported on insulators mounted on poles.
33
IT Systems
• As in TT systems, the exposed conductive parts of electrical equipment in IT
systems are connected to ground individually, in groups, or altogether.
34
Cont.
• In IT systems, the following requirements must be satisfied.
The ground resistance of the exposed conductive parts must be sufficiently low.
An insulation monitoring device is required which issues an acoustic and/or
visual signal to indicate the first fault b/n a live part and an exposed conductive
part or with respect to ground.
Once the first fault has occurred, the requirement for automatic disconnection of
the power supply must be satisfied in the event of a 2nd fault.
35
TN Systems
Here we have TN-S, TN-C, and TN-C-S systems
TN–S system: has the supply source directly connected to earth, the installation
metalwork connected to the earthed neutral of the supply source via the metal
sheath of the supply cable, and the neutral and protective conductors throughout
the whole system performing separate functions.
36
TN–S Systems
37
TN–C systems
• Again the first letter indicates that the supply is earthed while the second & third
letters N & C show that the supply neutral & protective conductor is combined in
one.
38
TN–C–S System
A TN–C–S system is as the TN–S system but the supply cable sheath is also the
neutral, i.e. it forms a combined earth/neutral conductor known as a PEN (Protective
Earthed Neutral) conductor.
The installation earth and neutral are separate conductors.
This system is also known as PME (Protective Multiple Earthing).
39
TN–C–S system
40
Earth fault loop impedance
The speed of operation of the protection depends on the magnitude of the fault
current, which in turn depends on the impedance of the earth fault loop path.
Starting at the fault, the path comprises:
1. The circuit protective conductor (CPC).
2. The consumer’s earthing terminal and earth conductor.
3. The return path, either metallic or earth.
4. The earthed neutral of the supply transformer.
5. The transformer winding.
6. The phase conductor from the transformer to the fault.
41
Cont.
42
The simplified version of this path be:
43
Cont.
• Zs = Ze + R1 + R2
Where: Zs- is the actual total loop impendence,
Ze- is the impedance external to the installation,
R1- is the resistance of the phase conductor and
R2- is the resistance of the CPC.
We also have:
I = Uoc /Zs
Where: I- is the fault current and Uoc is the supply transformer open circuit
voltage
(Usually 220 V) and Uoc is the voltage to earth at consumer terminals.
44
5.5. Protection of Buildings & Structures against Lightning
• Lightning is formed as a result of a natural build-up of electrical charge separation in
storm clouds.
• It is an atmospheric discharge of electricity accompanied by thunder, w/h typically
occurs during thunderstorms, & sometimes during volcanic eruptions or dust storms.
• In the atmospheric electrical discharge, a leader of lightning can travel at speeds of
220,000 km/h (140,000 mph), & can reach temperatures approaching 30,000°C.
45
Cont.
Lightening protection is a system designed to protect a structure from damage due to
lightning strikes by intercepting such strikes and safely passing their extremely high
voltage currents (up to 300kA) to "ground".
It includes a network of lightning rods, metal conductors, and ground electrodes
designed to provide a low resistance path to ground for potential strikes.
Lightning conductors include
Copper
Aluminum
Class I
Class II
Structural steel 46
Cont.
All buildings and structures, which are susceptible for lightning strokes by virtue of
their height or location in an exposed situation and the important buildings like
power houses, large warehouses, magazines, monuments, observatories, etc. should
be protected against lightning strokes.
This is done by installing lightning arrestors at the top of the structures and
connecting the same to the general mass of earth through a system of connecting
conductors and earth electrodes so that the structure is not subjected to dangerously
high potential of the cloud discharges.
For a protective system to be effective, the system should be designed and
maintained with low ground resistance. 47
Interceptor or Air Terminations
The projecting wire which is intended to collect the lightning discharge from the
atmosphere is known as interceptor or air termination.
It should project at least 30cm above the object on which it is fixed. In case of more
than one termination, the same should be fixed 15-23m apart. relevant points, even if
they are less than 15m apart, should be provided with separate air terminations.
All metallic finals, chimneys, ducts, vent pipes, railing, gutters and the like on or
above the main surface of the roof of a structure should be bonded, and form part of
48
the air termination network.
Cont.
Roof conductors: are conductors laid around a building near the top to interconnect
the various air terminations, in order to extend the zone of protection,.
Down conductors: are conductors which connect the air termination with earth.
They should follow shortest routes to earth without any sharp bends, and should not
be protected by metallic pipes.
Zone of protection: of a single vertical conductor is taken as the cone with its apex
at the highest point of the conductor and with a base of radius equal to the height.
Conductor materials: copper is the most preferred material for use in the lightning
protection systems because of its mechanical strength, high conductivity, and
49
resistance to corrosion.
Cont.
Earth terminations: are the earth electrodes used for connection of down
conductors to mass of earth. The efficiency of a lightning protection system depends
on low earth resistance. For this, it is essential to fix electrodes in ground with
permanent sub-soil moisture.
The earth resistance, in no case, shall exceed 5 ohms and in case of rocky soils 8
ohms. More than one electrode may be used if the required earth resistance is not
achieved with one electrode.
50
51
5.6. Testing of Electrical Installation
Every installation shall, during erection and/or on completion before being put into
service, be inspected & tested to verify, as it is reasonably practical, that the
requirements of the electrical installation code have been met.
The method of test shall be such that no danger to persons, livestock/ property or
damage to equipment can occur even if the circuit tested is defective.
The tests to be performed before a new installation or an addition to an existing
installation are connected to the supply mains are as follows:
52
Inspection
Information such as general characteristics, design procedure, drawings, diagrams,
charts & similar information related to the installation must be available for the
verifier.
A sequence of inspections must be conducted prior to testing for any installation.
These are:
Diagrams: are diagrams, instructions and similar information related to the
installation available?
Connection of Conductors: are terminations electrically and mechanically
sound, and whether insulation and sheathing is removed only to a minimum to
allow to satisfactory termination? Is there any loose connection?
53
Cont.
Identification of conductors: Are conductors correctly identified in accordance
with regulations and standards; color, size and type?
Labeling: are all protective devices, switches (where necessary) and terminals of
conductors correctly labeled? Is numbering used in distribution boards?
Routing of cables: are cables installed in such a way that account is taken of
external influences such as mechanical damage, corrosion, heat, etc. ?
Conductor Selection: are conductors selected for current carrying capacity and
voltage drop in accordance with the design requirements? 54
Cont.
Connection of single pole devices: are single pole protective and switching devices
connected in the live (phase) conductor only?
Protection against shock: what methods have been used to provide protection
against an electric shock?
Isolation and Switching: are there correctly located and installed appropriate
devices for isolation and switching?
Protective Devices: are protective devices, monitoring devices, and meters correctly
chosen and set to ensure fault protection against indirect contact and/or overcurrent?
55
Cont.
Access: are all means of access to switches, switchgears and equipment adequate?
Notes and signs: are danger and warning signs present?
Thermal effect: are fire barriers present where required, and protection against
thermal effects provided?
Accessories and Equipment: are all accessories and equipment connected?
56
Testing of Electrical Installation
The tests to be performed before a new installation or an addition to an existing
installation is connected to the supply mains are the following:
a. Insulation Resistance
The insulation resistance b/n the wiring and earth with all fuses (breakers) and
lamps in and all switches ‘ON’.
The insulation resistance b/n the conductors with all lamps out & all switches
‘ON’
b. Testing of polarity of non-linked single pole switches.
c. Testing of earth continuity path.
d. Testing of earth-electrode resistance.
57
a. Insulation Resistance
The aim of this test is to know whether the wires or cables used in the wiring are
sufficiently insulated to avoid leakage current.
Test is performed by a DC source not less than twice of working voltage but not
exceeding 500V.
A 500V tester, known as ‘Megger’ is used for this purpose.
Since installation circuits are wired in parallel, one can see that for a very large
installations an insulation resistance test at the intake position may show a low
value, which isn’t actually due to bad insulation.
In order to overcome this problem, installations should be broken down into smaller
sections such as floor by floor, distribution circuit by distribution circuit
58
Testing of Insulation Resistance b/n the Wiring & the
Earth
The resistance offered to leakage from conductors to earth is known as insulation
resistance test between the wiring and earth.
Before making insulation test ensure that:
a. Supply is isolated, i.e. the main switch, breaker/fuse is in OFF position.
b. All protective devices are in place.
c. All the switches are in ON position.
d. All the lamps are in their positions or the holders are short-circuited.
e. Link all the poles of the supply together i.e. line and neutral terminals are
shorted on the installation side.
59
Cont.
60
Cont.
The line terminal of the Megger (marked as L) is connected to the point where the
conductors have been shorted at the main switch and the E terminal is connected to
the earth.
The handle of the tester is turned, then it begins to slip & the reading on the dial
gives the insulation resistance b/n the wiring & earth.
The insulation resistance to earth measured should not be less than 0.5 Mega ohm.
61
The insulation resistance b/n the conductors
The objective of this test is to ensure that the insulation is sound b/n the conductors
so that there may not be a significant leakage b/n them.
In this test the circuit diagram is the same except that all of the lamps and all
metallic connections b/n the two wires of the installation are removed from the
holders.
62
Cont.
a) Supply is isolated, i.e. main switch, breaker/fuse is in OFF position.
b) All protective devices are in place.
c) All the switches are in ON position.
d) All the lamps are out of their positions.
e) The terminals of the Megger are connected between poles (R - S, R - T, S - T and
each pole in turn to N). The reading should not be less than 1 Mega ohm.
63
Cont.
64
2. Polarity check
A verification of polarity shall be made & ensured that all fuses & all single pole
control devices are connected in the live conductor only, that the outer contacts lamp
holders are connected to the neutral or earthed conductor, & the wiring has been
correctly connected to plugs & socket outlets”.
A convenient and quicker method of performing this test is by means of a small
neon tube tester.
An alternative method is using a test lamp. In this method one end of the test lamp is
connected to earth & the other end is tapped to each contact of the switch in turn. If
the test lamp is in the live wire, it gives light, otherwise the installation is wrong.
65
Cont.
66
Reading Assignment:
• Testing of Earth Continuity Path
• Testing of earth-electrode resistance.
67
68