Worked Example of Retaining Wall Design
Worked Example of Retaining Wall Design
29
Shares
29
Our previous article, Retaining Wall: A Design Approach discusses the principle and concept behind and when
and where to consider a retaining wall in our design. We have learned the different checks against the mode of
failures in the retaining wall should be considered in the design. To further understand the designed approach, here
is a worked example of the design of the retaining wall.
This example is intended to be readily calculated by hand although a lot of structural spreadsheets and software
such as Prokon are available. The purpose of this article is for the reader to fully understand the principle behind it.
Worked Example:
[Link] w w .thestructuralw [Link]/2019/03/04/design-of-retaining-w all/ 1/22
12/26/24, 12:20 AM Worked Example: Retaining Wall Design | The Structural World
29
Shares
Consider the cantilever retaining wall with the cross-section shown in the above Figure A.1, which retains a 2m
29
depth of soil having the groundwater table at -1.0m level.
Design Parameters:
Soil Bearing Capacity, qall : 100 kPa
Surcharge, ω: 12 kN/m2
Ground Water Level: -1m from 0.00 level
Height of Surcharge, h: 0.8m
Height of Wall: 2.0m
f’c: 32 Mpa
fy: 460 Mpa
concrete cover: 75mm
29
Shares
where:
29
H: Height of the retaining wall
L: Width of the base
D: Thickness of the base
B: Width of the toe
C: Stem thickness at the bottom
T: Stem thickness at the top
Based on the above approximate geometric proportions, let us assumed the following parameters to be used in our
design:
3. Analytical Model
Sketches of the retaining wall forces should be considered to properly distinguish the different forces acting on our
retaining wall as tackled in the previous article, Retaining Wall: A Design Approach. Based on our example in
Figure A.1, we have the forces due to soil pressure, due to water and surcharge load to consider. Figure A.3 below
is most likely our analytical model.
29
Shares
READ ALSO: Choosing the Suitable Shoring or Earth Retaining Systems for your Project
29
Considering the Figure A.3, we can derive the following equation for the active pressures, Pa and passive pressure
Pp. Notice that the pressures acting on the wall are equivalent to the area (triangle) of the pressure distribution
diagram. Hence,
Ka= 0.33
Kp= 3
3. Stability Check:
There are two checks to consider the stability of the retaining wall. One is the check for an overturning moment and
the other one is the check for sliding. The weight of the retaining wall including the gravity loads within it plays a vital
role in performing the stability check. Refer to Figure A.4 for the mass or weight calculations.
29
The self-weight component of the retaining wall should be factored down or to be multiplied by weight reduction
factor (0.9) to account for uncertainty because they are “stabilizing” in this context. Hence,
To satisfy the Overturning Moment Stability, the following equation should follow:
where:
With reference to Figure A.4 diagram and taking moment at the point, P conservatively neglecting the effect of
passive pressure hence:
READ
29 ALSO: Criteria in Selecting Suitable Foundation in Structural Design of Buildings
where:
The sliding check should be carried out with reference to the Figure A.4 diagram and considering the summation of
vertical forces for resisting force and horizontal forces for sliding force conservatively neglecting the passive
pressure, hence:
For29the thickness of the wall to be safe in shear, the ultimate shear, Vu should less than the allowable shear, Vallow
Shares
as recommended by the ACI 318 code.
Vc = 0.17√fc’bw d
where: ф=0.75
29 bw=1000mm
d= 250mm-75mm-6mm = 169mm
Vc = 0.17√fc’bwd = 162.52kN
Vallow = 121.89kN
ω = 0.0216
ρ = ω fc’/fy= 0.00150
Hence: use T10-200 for vertical bar and T10-250 for horizontal bar.
foundation, is working very hard to resist the vertical bearing loads, sliding shear, and to provide passive resistance
to sliding. The bearing capacity of the soil should be calculated taking into account the effect of simultaneous
horizontal loads applied to the foundation from the soil pressure.
For the footing to be safe in soil pressure, the maximum soil pressure under working load shall be less than the
allowable soil bearing capacity. The maximum soil bearing pressure under the footing considering 1m strip is:
29
where:
P= 62.69kN
A= (1×1.5) m2
M=10.88 kNm
b= 1m
d=1.5m
where:
A= (1×1.5) m2
M=17.40kNm
b= 1m
d=1.5m
29
e=M/P = 0.181
where:
a=length of pressure
qe= qumax
29
Shares
a= 1.74m
29
29
Vu= 44.75kN
Shares
qc=y
y/1.244=
29 112.24/1.75; y = 79.79 kPa
qc=79.79kPa
Vu=34.18kN
Vallow= фVc
Vc = 0.17√fc’bwd
where:
ф=0.75
bw =1000mm
d= 250mm-75mm-6mm = 169mm
Vc = 0.17√fc’bwd = 162.52kN
Vallow = 121.89kN
29
Shares
29
Mu= (73.57×0.625) x (0.625/2) + (38.67×0.625) (1/2) x (2/3) (0.625) → (area of trapezoid x lever arm)
Mu=19.40 kNm
qc= qumin + y
Mu = (88.39×0.75) x (0.75/2) + (23.85×0.75) (1/2) x (2/3) (0.75) → (area of trapezoid x lever arm)
Mu= 19.40kNm
ω = 0.0364
ρ = ω fc/fy= 0.002532
The presented calculations above are actually too tiring to perform manually especially if you are doing a trial and
error design. Thanks to structural design soft wares and spreadsheets, available nowadays, our design life will be
[Link] w w .thestructuralw [Link]/2019/03/04/design-of-retaining-w all/ 13/22
12/26/24, 12:20 AM Worked Example: Retaining Wall Design | The Structural World
easier.
Our team developed a user-friendly spreadsheet for the design of cantilever retaining wall based on the above
calculation. Grab your copy here!
What do you think about this article? Tell us your thoughts! Leave a comment on the section below. Subscribe to
our newsletter to be updated with the latest posts or follow us on our social media pages on the below icons.
29
Shares
Advertisements
29
53 Comments
i need for your help minimum depth for stone masonry wall refer to ACI code is how much?
kindly send me with Ref of ACI code
You can use the parameters written in section 2 of this article and confirm whether the thickness is adequate
using a shear check.
This is a helpful guide to Retaining Wall design. However, I have noticed errors in Section 3’s loadings. For example, Pp is not
substituted correctly. I have not checked further than this.
It would be worth double-checking the spreadsheet you are selling as this is a dangerous error that would show a retaining wall
having a higher capacity than it actually does.
Thanks for pointing out. We have checked and found out that that is merely a typo error and it has been
updated accordingly. We have also double-checked the attached spreadsheet and it is not affecting the results
as we conservatively neglect the effect of passive pressure in the calculation.
Hello
Can you explain why the height of the surcharge is only 0.8m and why is it not reflected on the Analytical model ?
29
Edgar October 29, 2019 at 12:33 pm
Also ,would you be able to explain how is the d in critical shear calculated ? number 1.044 is used for similar
triangles,however I struggle to find exact theory how you arrived to this number as I get different.
Substitute the values from (L-T)/2 + T + d, where L=1.5, T=0.25 and d=.169. That will give us 1.044.
In this example, a 0.80m surcharge height is a given parameter. In the analytical model, the surcharge, ω is
mentioned and the height corresponds to that is 0.80 m.
Thanks Rosina!
where do you get this 1.244 on similar triangles under (qc = y) condition. Thanks in advance!
29
You need to use effective stress when doing the calculation.
Shares
we have to learned the different checks against the mode of failures in the retaining wall should be considered in the design. Here
some worked examples of the design of the retaining wall are described.I like the I have also found this resource [Link]
useful and its related to what you are mentioning.
Could you please clarify why in section 7 you determine L=1.6m, but later in the calculation you still use L=1.5m? thanks a lot.
why we used 18 kn/m^3 insted of 12 kn/m^3 when we calculate the weight of surcharge?
This is just a typo error and we corrected this according to 12KPa as per the attached spreadsheet.
while calculating restoring moment is it good to take moment due to surcharge load because surcharge
load may be transient in some cases , like fire tender or other vehicular load
Why did you put 1/2 for Pa1 instead of 1/3 as it is H/3 with triangular load?
Notice that the pressures acting on the wall are equivalent to the area (triangle) of the pressure distribution diagram.
Upon getting the Pressure, we will multiply it by h/3 to get the moment.
What does the height of the surcharge, h, represent? You have given us the value of the surcharge, so I can’t work out what the h
is referring to?
I’m amazed at your Math skills! However, retaining walls can also be built through stone masonry construction. But yeah, the
cost and quality should be considered.
Hi,
in the section “Check for Sliding”, I think you have forgotten to multiply the vertical weight to “tan([Link]/3)”. if you do that Rf would
be reduced 55.94 x 0.35= 19.50, as a result, the design cannot pass the sliding check.
the active lateral load should be against the passive lateral load, not the vertical load.
Does this spreadsheet allow for an offset footing where the toe length is different than the heel lenth.
Also, why vertical rebar on both faces of the stem? Primary vertical rebar should be on the tension (back/burried) face.
29
Shares
This excel is for retaining walls with concentric walls to its foundation only. Yeah, that’s right theoritically, the
primary bar should place on the tension side of the wall only. But, practically speaking, or in actual it’s best for
the designer to add another rebar on the other side, just in case.
I bought the file, yet why cant I edit the file so i may be able to put my own logo for the finished output?
29
Is it not allowed? I mean like I already paid for the file.
Hi Ruben, you can actually put your own logo on the space provided. Either editing some option setting on your excel
or typing your company name on it. If none of these options are working, do it manually. Once you finish the design,
convert the file to pdf and paste your logo from there.
IT CAN BE ALLOWED TO USED THE MINIMUM STEEL RATIO OF 1.4/fy ? for vertical reinf of retaining wall.
I think your RM is incorrect in its total value. Each time I calculate it I get 57.91KN, not 60.02KN
Thanks, Aaron for pointing it out. We have checked and found out that that is merely a typo error and it has
been updated accordingly. We have also double-checked the attached spreadsheet and it is not affecting the
results in the calculation.
Sir,29
would you please to explain about qumax 112.24 and qumin 19.44 respectively of article [Link].
Hi, Thanks for the detailed calculation. How if the surcharge height is not given, what estimation can we use?
Good day
Our lecturer used this exact extract as a curveball to calculate retaining walls with water, I found this before we had to give it in…
Why do you not use friction forces to calculate FR, FR = ΣV * tan(k1*Φ1) + k2C2B + Pp
Could you elaborate on your method for sliding and where the 0.9 safety factor comes from for the concrete weight. I have tried to
29
find this info in our foundations handbook with no success.
Shares
I also see your turning point is not at an extreme point. You use the top of your toe instead of the bottom. From what I can
see this means your moments won’t be accurate, but it will give similar results.
There is also a comment earlier about a typo of MoT = 57.91, the figure was right at 60.02, the weight of section 1 was not
added to the equation. Though all of these moments are taken from the top of the toe and not the furthest point, thus
29
moments are not accurate.
sir, Thank you for your valuable information. this is very much useful and one more plea that can we have any examples for
considering wings & returns with head wall can be treated as a retaining wall any such kind of examples please post to mail if
any thanks in advance
Hi
Great example. Thanks. Wouldn’t you think you need to add the vertical stress applied on the wall base due to the surcharge and
also calculate its moment?
Thanks
Mike
Good day. May I ask if why bw is equal to 1000 mm? As per ACI R11.1:
The shear strength is based on an average shear stress on the full effective cross section (bw x d). In a member without shear
reinforcement, shear is assumed to be carried by the
concrete web. In a member with shear reinforcement, a portion of the shear strength is assumed to be provided by the concrete
and the remainder by the shear reinforcement.
29
Shares
Thus, the assumed cross section must be 250 mm (base thickness where shear failure is expected) x 169 mm.
where
29
did 0.75, 1.19, 0.67, 0.33 and 0.4 came from? are those USA safety factors or what?
Those are lever arms! With reference to Figure A.4 diagram and taking moment at the point P.
would you please to explain about qumax 112.24 and qumin 19.44 respectively ???
Thank for this detailed design to follow; It has been very helpful. One thing I noticed is that the calculation for the wall stem does
29
not match the value you then indicated for the moment when checking for wall stem flexure. You have listed that Mu=19.40KNm
Shares
again for tension, but the calculation comes out to the 29.33KNm you used. I believe it was just a typo but it made it a bit
confusing to follow then. Thanks again, and God bless.
Just an FYI, with water behind the retaining wall, the soil weight should be submerged (subtracting water unit weight from soil) to
determine the active pressure. Without water in front of the wall, you’ll also have an uplift force along the underside of the footing
due29to buoyancy, equal to the depth of water behind the wall at the heel, tapering to the depth of water in front of the wall at the
toe.