Product Specifications
Power Modules The hardware configuration Module along with the ATEX-certified
Each Tricon chassis is equipped with conflicts with the control programs 24 VDC power supply from Phoenix
two Power Moduleseither one is logical configuration Contact (part number: QUINT-PS-100-
fully capable of running the Tricon at A module fails 240AC/24DC/10/EX).
full load and rated temperature. Each A Main Processor detects a system
Power Module can be replaced online. fault
The Power Modules, located on the left
side of the chassis, convert line power Primary power to a Power Module
to DC power appropriate for all Tricon fails
modules. Terminal strips for system A Power Module has a Low
grounding, incoming power and hard- Battery or Over Temperature
wired alarms are located on the lower warning
left corner of the backplane. Incoming
power should be rated for a minimum WARNING: Do not use the Model
of 240 watts per power supply. 8312 Power Module in Tricon systems
that are located in hazardous locations
The Power Module alarm contacts are and must meet ATEX requirements. If
actuated when: you have 230 V line voltage and your
A module is missing from the system must meet ATEX requirements,
system use the Model 8311 24 VDC Power
Power Module Specifications
Isolation >1,000 VAC or 1,500 VDC, Input to Output
Input Terminations Protected by safety cover
Accepts three 12-gauge wires (3.310mm2): neutral, hot, and
protective earth (chassis ground)
Over-Temp. Sensor Temperature warning monitortrips when internal temp. is
greater than 181° F (83°C); this typically occurs at ambient
temperature 140°F (60°C) or higher
Alarm Contacts Normally open, normally closed and common
Each contact supports 120 VAC @ 1 amp
Accepts 12-gauge (3.310mm2) wire
Protected by safety cover
Input Power Required 240 watts minimum per Power Module
Output Power 175 watts at 140°F (60°C)
Output Voltage 6.5 VDC, ±1% under all operating conditions
Output Current 27 amps maximum at 140°F (60°C) ambient
Power Module Model 8310 8311 8312
Chassis Type Main/Expansion/RXM Main/Expansion/RXM Main/Expansion/RXM
Nominal Voltage 120 VAC/VDC 24 VDC 230 VAC
Input VAC @ 47-63 Hz 85140 n/a 185285
Input VDC 95180 2231 n/a
Fuse Rating and Type 5 amps, time-delay 15 amps, time-delay 2.5 amps, time-delay
Output Hold Time 20 ms minimum 2.8 ms minimum 20 ms minimum
(nominal to 0 volts)
Diagnostic Indicators PASS, FAULT, ALARM, TEMP, PASS, FAULT, ALARM, TEMP, PASS, FAULT, ALARM, TEMP,
BAT LOW BAT LOW BAT LOW
26