Room controllers RXL21.1


RXL22.1
Communicating controllers
for fan-coil applications FC-10, FC-11, FC12

The RXL21.1 and RXL22.1 room controllers are used for temperature control in
individual rooms.
• For 2-pipe or 4-pipe fan-coil systems, with or without change-over
• PI control
• Proprietary bus communication
• Integration into the Desigo building automation and control system via
PX KNX
• Integration into Synco
• Control of AC 24 V PDM 1) thermic valve actuators, 3-position AC 24 V
motorized valve and damper actuators, or electric heating coils
• Volt-free relay contacts for control of fans and electric heating coils
• Commissioning with Synco ACS or "HandyTool"
• AC 24 V operating voltage
• Screw terminals

1) PDM = Pulse Duration Modulation

CM2N3877en_09
2015-12-23 Building Technologies
Application

The RXL21.1 and RXL22.1 room controllers are optimized for control of fan-coil
systems in individual rooms.
The following options are available with fan-coil systems:
• RXL21.1: Single-speed to 3-speed automatic fan control
• RXL22.1: Single-speed to 3-speed automatic fan control
with integrated relay for electric re-heater

The application of each controller is determined by the application software.

The controllers are delivered with a fixed set of applications, each of which contains
various individual applications. The relevant application is selected and activated during
commissioning using one of the following tools:
• Synco ACS
• "HandyTool" (the QAX34.3 room unit includes a tool function which allows you to set
the parameters of the connected RXL cotroller)

No use of spare Unlike the RXB controllers, the RXL controllers do NOT support the use of spare inputs
inputs/outputs and outputs by the building automation and control system.

Functions

The room controller functions are determined by the selected application and its
parameters, and by the input/output configuration.

For details, refer to the FNC description of functions, document CA110785.

When RXL controllers are integrated into a Desigo building automation and control
system, or into a Synco system, additional functions become available such as time
scheduling, central control of setpoints, etc.

2/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Applications

The following applications are available for the RXL2… room controllers:

Application group (type) Fan-coil applications


FC-10 FNC02 2-pipe system with changeover
(with RXL21.1) FNC04 4-pipe system
FNC08 4-pipe system and
room/supply air cascade control
FNC20 4-pipe system
with single damper control
FC-11 FNC10 2-pipe system with changeover and
(with RXL21.1) outside air damper
FNC12 4-pipe system with outside air damper
FNC18 2-pipe system with changeover and
radiator
FC-12 FNC03 2-pipe system with changeover and
(with RXL22.1) electric re-heater
FNC05 4-pipe system with electric re-heater

Note Only one application at a time can be activated with the tool (Synco ACS or
"HandyTool").

Types

The RXL21.1 and RXL22.1 room controllers differ only in the number of outputs
available:

Type AC 24 V triac outputs Relay outputs


RXL21.1 For 2 thermic valve actuators or For 3-speed fan control
two 3-position actuators
RXL22.1 For 2 thermic valve actuators or For 3-speed fan control;
one 3-position actuator internal relay for electric heating
coil
RXZ20.1 Accessories: Terminal covers

Ordering

When ordering please specify the quantity, product name, type code and application
group.

Example: 30 Room controllers, type RXL21.1/FC-10

3/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Compatibility

The RXL2… room controller is compatible with field devices from Siemens Building
Technologies.

For details, refer to the Desigo RX hardware overview, CA2N3804.

Design

The RXL2... controllers consist of a housing base, a housing cover and the printed
circuit board with connection terminals. The controllers also have a tool socket, a
service LED and a programming pin.

Cable restraints
Connection
terminals
Plug-in connection terminals
for the bus

3873J01
Housing cover
Housing base

Connection Service LED


terminals

Programming pin
Tool socket

Service LED The programming LED shows the operational status of the room controller as follows:

Green flashing OK, device is in operation


Red ON • Addressing mode (ACS / ETS)
• Fault
Orange / green flashing Parameter download
OFF • No supply voltage
• Fault
• Service LED disabled by software
Other patterns • Start-up (approx. [Link])
• Fault

Programming pin The programming pin is used to identify the controller in the commissioning phase.

Pressing this pin causes the red programming LED to light up and remain on until
identification of the controller is complete.

Once the service pin has been pressed, the tool overwrites the hardware address in the
room controller.

If there are no terminal covers fitted, the service pin may be operated only by a
qualified electrician.

The adjacent terminal may be a live mains voltage conductor.

4/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Terminal cover Terminal covers (RXZ20.1) are available as an option, to protect the connection
terminals from physical contact and dirt. The service LED remains visible when the
terminal covers are in place, and the service pin can be operated with a pointed
implement. The cable is connected to the room controller by breaking out the
perforated cable entry guide.

3873J02
Removing the terminal cover

Label Identification number


(unique serial number)
(example for RXL21.1)

3877Z04
ID in bar-code form, code 128

Protection standard
Temperature range
(0 … 50 °C)

Serial No. 010025CA9900


Test date, series
(Z, A, B, C…) 060215B 513

Observe notes
in this document

Activated application

Location

Note Options for use of the labeling fields “Appl.” and “Loc.”:
− Handwritten identification of the location and the activated application group.

Connection terminals The connection terminals for the bus are detachable plug-in screw-terminals. All other
terminals are fixed. To avoid incorrect wiring, terminals which can be connected to AC
230 V (relay outputs) are physically separate from the other terminals.
3877J04

The cable restraints on the housing base must


be used for the connections to terminals 22 … 28
(AC 230 V). The conductors must be secured
with cable ties (see diagram).

5/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Communication The RXL2… controllers communicate with other devices via the following interfaces:

• PPS2 interface (proprietary) for the exchange of data with the room units
• Bus (terminals CE+ and CE-) for communication with:
− PX/KNX interface (to Desigo Insight)
− Interface OCI700 (to Synco)
− Other RXL controllers

The tool socket (RJ45) must be connected only by a qualified electrician. The adjacent
terminal may be a live mains voltage conductor.

Connecting the tool To facilitate commissioning, the tool Synco ACS can be connected at three different
points (marked (A) in the diagram) in the plant:
− to the bus cable at any point
− to the RXL2… controller (RJ45 tool socket)
− to the room unit (RJ45 tool socket)

Bus

3877A05 en
PPS2

A
Bus
CP+

CP+
CE+

CE+
CP–

CP–

CE–

QAX3... RXL2... CE–


C+
C–

RXZ90.1
Bus

PPS2 A ACS
Bus USB

Siemens OCI700
Tool PPS2
Bus
Tool
Siemens
connecting cable Bus
A Siemens
connecting cable
PPS2 A
B PPS2
HandyTool QAX34.3
B
HandyTool QAX34.3

Notes • The tool socket is a proprietary socket.


A Siemens connecting cable must be used (e.g. PXA-C1).
Caution! When connected to Ethernet, the device on the other end may be damaged!

• The ACS tool, even if connected to a tool socket, requires an interface (OCI700).

• The "HandyTool" is connected to the tool socket of the room controller or to the tool
socket of the room unit (QAX3…, RXZ90.1) (B).

• If you use OCI700 as an interface, it is connected to the service plug of the controller
or of the room unit.
As long as the OCI700 is connected to the service plug, it must be supplied by
the computer via the USB interface. Otherwise the LCD display of the room unit
will turn dark and the controller will switch to addressing mode.

6/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Disposal

The device is classified as waste electronic equipment in terms of the European Direc-
tive 2012/19/EU (WEEE) and should not be disposed of as unsorted municipal waste.
The relevant national legal rules are to be adhered to.
Regarding disposal, use the systems setup for collecting electronic waste.
Observe all local and applicable laws.

Engineering notes

Bus Topology Line or star


NO closed loops
Cable length Max. 1000 m
Cable length E.g. YCYM 2 x 2 x 0.8 mm
number of RXL Controllers per Network Max. 45
Bus supply Up to 45 RXL-controllers:
5WG1 125-1AB12
Bus terminator Not required

AC 24 V The RXL2… room controllers operate with a supply voltage of AC 24 V.


supply cables The controlled devices (valves and damper actuators) receive their power directly from
the room controller. This means that a separate AC 24 V supply is not necessary for
the field devices.

This device has no circuit breakers for supply lines to external consumers (field power
supply)!

Line insulation must always be sufficient for the available rated voltage.

Caution When forwarding supply voltage (for 24 V low voltage as well) to external consumers,
the wiring cross sections must at any rate be adapted to the preswitched overcurrent
protection device. Please comply under all circumstances with local regulations.

Volt-free • The volt-free relay outputs allow the switching of loads up to AC 250 V, 5 A (4 A).
relay outputs The heating coil relay in the RXL22.1 switches resistive loads up to 1.8 kW.
AC 230 V The cable dimensions depend on the connected load and the local installation
regulations.
• The circuits must be externally fused (≤ 10 A) as there are no internal fuses.
• The cables connected to the room controller must be secured with cable restraints.

The fans must not be connected in parallel.

AC 24 V triac outputs The simultaneous load on outputs Y1 … Y4 must not exceed 9.5 VA.

Example: Y1 (heating) 2 thermic valve actuators, type STP73 5W


Y2 (cooling) 2 thermic valve actuators, type STP73 5W
Y3, Y4 (outside air) 3-position damper actuator 4.5 VA 4.5 VA

The maximum load is 9.5 VA for the heating sequence and 9.5 VA for the cooling
sequence.
This is acceptable because the two sequences never operate at the same time.

7/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Mounting instructions

The room controllers can be mounted in any orientation, and fixed as follows:

3873J06

3873J07
Rail mounting Surface mounting
The housing base is designed for snap- There are two drill holes for screw-mounting (see “Dimensions” for
mounting on DIN rails, type EN50022-35 x 7.5 drilling template). The housing base is fitted with raised supports.
(can be released with a screwdriver). Screws: Max. diameter 3.5 mm, min. length 38 mm

STOP Note!

Tightening torque for fixing screws max. 1.5 Nm

When mounting note the following:


• The controller should not be freely accessible after mounting. It must be mounted in
a cabinet or behind a cover that can only be opened / removed with a key or a tool.
• Ensure adequate air circulation to dissipate
heat generated during operation.
• Easy access is required for service personnel
• Local installation regulations must be observed.

Mounting instructions and a drilling template are printed on the controller packaging.

Commissioning

The RXL2... room controllers are commissioned with one of the following tools:
− Synco ACS via the OCI700 interface
− HandyTool" via PPS2

Labeling The definitive application and the controller's location are handwritten in the labeling
fields "Appl." and "Loc" in the commissioning stage.

Function test A special test mode (HandyTool) is available for operation of the outputs and
interrogation of the inputs.

8/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Technical data

Power supply Operating voltage AC 24 V ± 20 % (SELV / PELV)


Frequency 50/60 Hz
Power consumption with connected field devices Max. 15 VA (RXL21.1)
Max. 16 VA (RXL22.1)
Internal fuse None
External supply line protection Fuse slow max. 10 A
Caution
or
Circuit breaker max. 13 A
Characteristic B, C, D according to EN 60898
or
Power source with current limitation of max. 10 A
Operating data Control algorithm PI
Inputs
Signal inputs D1, D2 Quantity 2
(for volt-free contacts) Contact voltage DC 16 V
Contact current DC 5 mA
Contact transfer resistance Max. 100 Ω
Contact insulation resistance Min. 50 kΩ
Switch time: min. 20ms “ON”, min. 20ms “OFF”
Measured value input B1 Compatible temperature sensors LG-Ni 1000
Quantity 1
measuring range 0 ... 50 °C
Sensor current 0.5 mA
Resolution 0.1 K
Measuring error at 25 °C sensor temp. (without cable) max. 0.5 K
Outputs
AC24 V triac outputs , Y1 … Y4 Quantity 4 (RXL21.1)
2 (RXL22.1)
Output voltage (equal to supply voltage) AC 24 V ON/OFF, PWM or 3-position
Permissible load current Max. 0.5 A
Power limitation No internal limitations
Total nominal load Max. 9.5 VA (e.g. 2 thermic valves, type
(at both outputs simultaneously) STP73 per heating and cooling sequence
+ 1 damper actuator 4.5 VA)
Relay outputs Q14, Q24, Q34 Quantity 3
Relay type Monostable
Contact rating with AC voltage
Switching voltage Max. AC 250 V, min. AC 19 V
Nominal current, resistive/inductive Max. AC 5 A/4 A (cos ϕ = 0.6)
Making current 200 ms half-time Max. 20 A
Switching current at AC 29 V Min. AC 10 mA
Contact rating with DC voltage
Switching voltage Max. DC 250 V, min. DC 5 V
Switching current at DC 5 V Min. DC 100 mA
Switching capacity Max. 20 W
Inductive load L/R Max. 7 ms
External fuse (essential) Max. 10 A, see Power supply
Q44 Relay type Monostable
Contact rating with AC voltage
Max. admissible load (resistive only) Max. 1.8 kW
External fuse (essential) Max. 10 A, see Power supply
Ports/interfaces
Interface to room unit Number of room units connectable 1
Interface type for room unit PPS2
for ACS Bus
PPS2 baud rate 4.8 kbit/s
Baud rate on the bus 9.6 kbit/s
Bus Interface type Electrically isolated
Bus current 5 mA
Baud rate bus 9.6 kbit/s
Bus topology Refer to Engineering, page 7

9/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Cable connections Connection terminals for signals and power supply Solid or stranded conductors
0.25 … 2.5 mm2
or 2 x 1.5 mm2
Bus connection terminals Solid or stranded conductors 2 x max. 1.0 mm2
(plug-in screw terminals) e.g. YCYM 2x2x0.8
Single cable lengths For field devices, see also the RXB & RXL
installation guide, CM110381
Signal inputs D1, D2 Max. 100 m with diameters ≥ 0.6 mm
Measured value input B1 Max. 100 m
AC24 V triac outputs , Y1 … Y4 Max. 100m where A ≥ 1.5 mm2
Relay outputs Q14, Q24, Q34, Q44 Depends on load and local regulations
Interface to room unit Max. 115 m where A= 0.75 mm2
(including connecting cable for tool)
Cable type 4-core, twisted pair, unscreened
Bus Max. 500 m (see Engineering, page 7)
Tool connecting cable Max. 3 m

Housing Protection standard to EN 60529 IP30 with terminal cover fitted and
protection standard wall mounted without DIN rail
IP20 for all other mounting arrangements
Protection class Suitable for use in systems with protection class I or II
Ambient conditions Normal operation Class 3K5 to IEC 60721-3-3
Temperature 0 ... 50 °C
Humidity < 85 % rh
Transport Class 2K3 to IEC 60721-3-2
Temperature – 25 ... 65 °C
Humidity < 95 % rh
Standards, directives and Product standard EN 60730-1 Automatic electrical controls for household and
approvals similar use
Electromagnetic compatibility (Applications) For use in residential, commerce, light-industrial
and industrial environments
EU conformity (CE) CM2T3877xx *)
RCM-conformity (EMC) CA2T3834en_C1 *)
[Link] Meets the requirements for [Link] certification
See product list at: [Link] [Link]
Type License Application Control accuracy [K]
RXL21.1/FC-10 20860 Fancoil 2 pipes heating 0.2
coooling 0.1
Fancoil 4 pipes heating 0.2
coooling 0.1
RXL22.1/FC-12 20131 Fancoil 2 pipes heating 0.2
coooling 0.1
Fancoil 2 pipes / 2 wires heating 0.2
coooling 0.1
Environmental compatibility Product environmental declaration (contains data CA2E3871 *)
on RoHS compliance, materials composition,
packaging, environmental benefit, disposal)
Dimensions See dimension diagrams
Weight excluding packaging 0.300 kg
including packaging 0.340 kg

*) The documents can be downloaded from [Link]

10/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Connection terminals

3877A08
RXL21.1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

GND

CP +
CE +

CE +
CP –

CE –

CE –
N.C.

D1

D2

Y3

Y4
B1

Y1

Y2
M

G
G
Bus
T
2 1 4 3
QAX...
M M

AC 24 V
SELV / PELV AC 230V 5(4)A

Q24
Q34
Q13
Q14
G0
G0
G
G
19 19 21 21 25 26 27 28

Measured value input


B1 1 Measured value input for LG-Ni 1000 sensors
M 2 Measured value input ground
Signal inputs
D1 4 Signal input
GND 5 Signal ground
D2 6 Signal input
Triac outputs
Y1 7 AC 24 V, 0.5 A switching output
G 8 AC 24 V actuator supply
Y2 9 AC 24 V, 0.5 A switching output
Y3 10 AC 24 V, 0.5 A switching output
G 11 AC 24 V actuator supply
Y4 12 AC 24 V, 0.5 A switching output
Room unit
CP– 13 PPS2 ground
CP+ 14 PPS2 data
CE+ 15 Bus
CE– 16 Bus
Bus (plug-in connection)
CE+ 17 Bus
CE– 18 Bus
Power supply
G0 19 Controller ground
G 21 AC 24 V +/- 20 %
Relay outputs
Q13 25 Common feed for Q14, Q24 and Q34
Q14 26 Normally-open contact, max. AC 250 V, 5 (4) A (Stage 1)
Q24 27 Normally-open contact, max. AC 250 V, 5 (4) A (Stage 2)
Q34 28 Normally-open contact, max. AC 250 V, 5 (4) A (Stage 3)

Caution • Observe the technical data for the relay outputs: max. AC 250 V, 5 (4) A
• Local installation regulations must be observed.

Tool socket Proprietary RJ45-type tool socket


12 3 45 67 8 1 Bus (CE+) 5 +12VDC
2 Bus (CE–) 6 RxD
3 Not used 7 PPS2 (CP+) / TxD
4 Not used 8 PPS2 (CP–)
3206Z01

11/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Connection terminals

3877A09
RXL22.1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

CP +
CE +

CE +
GND

CP –

CE –

CE –
N.C.

N.C.
N.C.
N.C.
D1

D2
B1

Y1

Y2
M

G
Bus
T
2 1 4 3
QAX...
M

AC 24 V
SELV / PELV AC 230V 10A AC 230V 5(4)A

N.C.

Q24
Q34
Q43
Q44

Q13
Q14
G0
G0
G
G

19 19 21 21 22 23 24 25 26 27 28

Measured value input


B1 1 Measured value input for LG-Ni 1000 sensors
M 2 Measured value input ground
Signal inputs
D1 4 Signal input
GND 5 Signal ground
D2 6 Signal input
Triac outputs
Y1 7 AC 24 V, 0.5 A switching output
G 8 AC 24 V actuator supply
Y2 9 AC 24 V, 0.5 A switching output
Room unit
CP– 13 PPS2 ground
CP+ 14 PPS2 data
CE+ 15 Bus
CE– 16 Bus
Bus (plug-in connection)
CE+ 17 Bus
CE– 18 Bus
Power supply
G0 19 Controller ground
G 21 AC 24 V +/- 20 %
Relay outputs
Q13 25 Common feed for Q14, Q24 and Q34
Q14 26 Normally-open contact, max. AC 250 V, 5 (4) A (Stage 1)
Q24 27 Normally-open contact, max. AC 250 V, 5 (4) A (Stage 2)
Q34 28 Normally-open contact, max. AC 250 V, 5 (4) A (Stage 3)
Q43 23 Lead wire for Q44
Q44 21 N/O contact AC max. 250 V, 10 A...(electric heating coil)

Caution • Observe the technical data for the relay outputs: Max. AC 250 V, 5 (4) A and 10
A, respectively

• Local installation regulations must be observed.

Tool socket Proprietary RJ45-type tool socket


12 3 45 67 8 1 Bus (CE+) 5 +12VDC
2 Bus (CE–) 6 RxD
3 Not used 7 PPS2 (CP+) / TxD
4 Not used 8 PPS2 (CP–)
3206Z01

12/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Connection diagrams Connection of field devices, room unit, bus and power supply

N1 N2

3877A11_01
B1 1 B1 1
T B1 T B1
M 2 M 2

D1 4 D1 D1 4 D1
GND 5 GND 5
D2 6 D2 D2 6 D2

Y1 Y1.1 Y1.2 Y1.1 Y1.2


Y1
Y1 7 Y1 7
M M
G 8 GL M G 8 GL M
Y2 9 Y2 9 M
Y2
Y2 Y2.2
Y3 Y3.1 Y3.2
Y3 10
M
G 11 GL M
Y4 12
Y4
CP – 13 2 CP – 13 2
PPS2 PPS2
CP + 14 1 CP + 14 1
B2 B2
CE + 15 4 CE + 15 4
Bus Bus
CE – 16 3 CE – 16 3

CE + 17 CE + 17
Bus Bus
CE – 18 CE – 18

G0 19 G0 19
G0 19 G0 19
AC 24 V AC 24 V
G 21 G 21
G 21 G 21

N.C. 22 L
Q2
Q43 23
Q44 24 N

Q13 25 L L Q13 25 L L
Q14 26 1 1 N Q14 26 1 1 N
Q24 27 2 N Q1.1 Q24 27 2 N Q1.1
Q34 28 3 Q34 28 3
Q1 Q1

N1 / N2 RXL21.1 / RXL22.1
B1 LG-Ni 1000 temperature sensor
D1, D2 Volt-free contacts (window contact, occupancy sensor, etc.)
Y1...Y4 AC 24 V thermic valve actuators
Y1.1, Y3.1 Motorized AC 24 V, 3-position valve or damper actuator
Y1.2, Y2.2, Y3.2 Electromechanic AC 24 V, 2-position valve actuator
B2 QAX… room unit
Q1 3-speed fan
Q1.1 1-speed fan
Q2 Electric heating coil

Twisted pair

• Fans connected to relay outputs Q14 … Q34 must not be operated in


parallel. For parallel operation use cut-off relays or slave room controllers.
• At Q2 (1.8 kW max. resistive load), use additional external fuses of max. 10 A
to protect the pcb tracks.

Note For information on the compatibility of field devices with the RXL21.1 and RXL22.1
room controller, refer to the various application descriptions (see the FNC description of
functions, document CA110785)

13/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Parallel connection of Up to two thermic actuators per sequence may be connected directly to the room
several thermic valve controller. With more than two thermic actuators, a UA1T power amplifier is required.
actuators
The principle is the same for output Y2. Do not exceed the maximum simultaneous load
on outputs Y1 and Y2 (max. 9.5 VA).
Power consumption at input X1 of the UA1T: 0.5 VA.

Mixed operation: It is not permissible to connect thermic actuators both to the


controller and to the power amplifier.
Owing to the difference in voltage between the controller's internal transformer and the
power supply of the UA1T, this could cause the valve positions to deviate substantially.

Connection to the N1
controller G
AC 24 V
G0

Y1
Y1 Y1.1
G
3877Z12

AC 24 V AC 24 V 3877Z13
Connection to the
power amplifier N1 G G0 G G0

G0

Y1
Y1
G

N2
Y1.1 Y1.3
1 NS COM 8
2 LS Y1 7
Y1.2 Y1.4
3 COM COM 6
4 X1 Y1 5

N2
Y1.5 Y1.7
1 NS COM 8
2 LS Y1 7
Y1.6 Y1.8
3 COM COM 6
4 X1 Y1 5

N1 Room controller RXL21.1, RXL22.1


N2 UA1T power amplifier (see data sheet CA2N3591)
Y1 AC 24 V thermic valve actuators connected to the controller
Y1.x AC 24 V thermic valve actuators
(max. 2 STA73 / STP73 actuators per Y1 output on the UA1T)

Notes – The UA1T requires an AC 24 V supply voltage


– The UA1T is not suitable for the connection of 3-position actuators.

14/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Dimensions

Dimensions in mm

4,4
Without terminal cover

3873M14

133,2
35,3

3,3
3,9
62 1

51,5
With terminal covers
5
3877M15
35,3

167

3,9
62 1 112,4
107,8

15/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23
Drilling diagram (1:1)

3,6

78
39
3873M16

43,2

86,3

Published by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel. +41 41-724 24 24 © Siemens Switzerland Ltd 2006
[Link]/buildingtechnologies Delivery and technical specifications subject to change

16/16

Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09


Building Technologies 2015-12-23