0 ratings0% found this document useful (0 votes) 263 views274 pagesEMCP II+ (Troubleshooting-Testing)
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
Troubleshooting Section
Introduction
sseeroa
General Information
SMCS Code: 4490
FeO te
Personal injury or death can result from high volt-
age.
‘When power generation equipment must be in op-
ration to make tests and/or adjustments, high
voltage and current are present,
improper test equipment can fall and present a
high voltage shock hazard to its user.
Wake sure the testing equipment is designed for
and correctly operated for high voltage and cur-
rant tests belng made.
When servicing or repairing electric power gener-
ation equipment:
|* Make sure the unit is off-line (disconnected
‘rom utllity and/or other generators power
service) , and either locked out or tagged DO
NOT OPERATE.
+ Remove all fuses.
| Make sure the generator engine is stopped.
Make sure all batteries are disconnected.
Moke sure all capacitors are discharged.
lure to do so could result in personal Injury or
\. Make sure residual voltage in the rotor, sta-
‘and the generator Is discharged.
, OF any source to
the engine-generator is synchronized to, is
, voltages up to GOOV are present in the
Panel.
‘not short these terminal with line voltage to
with any part of the body or any conduc-
material. Loss of life or injury could result
electrical shock or Injury from molten met-
PON
Do not connect generator to a utility electrical dis-
tribution system unless itis isolated from the sys-
tem. Electrical feedback Into the distribution sys-
tem can occur and could cause personal injury or
death,
‘Open and secure main distribution system switch,
‘or if the connection is permanent, install a dou-
ble throw transfer switch to prevent electrical feed-
back. Some generators are specifically approved
by a utility to run in parallel with the distribution
‘system and isolation may not be required. Always
check with your utility as to the applicable ciroum-
ietse6r08
Service Tools
‘SMCS Code: 0785,
Table 18
‘Tools Needed
Part ‘Deseription| “Amount
Number
46-3406 | Connector Kit 1
4 mm Hex Wrench for 1
fastener on GSC+ connector
‘6V-7070 _| Digital Mutimeter 1
98-7930 | Multimeter {Optional for 4
frequency and duty cycle
measurements
148-4080 _| Digital Multimeter (RS-232) 1
7%-1710 | Cable Probes 1118
Troubleshooting Section
‘raser8
Fault Identification
SMCS Code: 4490-035
Tibie 1
Fault identification
Indleator Fault Cade on upper | DIAG Indicator
lett side of ase ‘slsplay Fault Type See Tople
Fault Alarm CID FM Flashing Active Alarm Troubleshooting:
Diagnostic Codes
SP1, SP2, SPS, SPat? ‘Absent ‘ative Alar Diagnostic System
Procedures, “SP
Fault Code”
"ALA th ALAS ‘Absent ‘tive Alarm Diagnostic Syatern
Procedures,“
Fault Cos
Fault Shutdown ID Fu Flashing “have Shutdown | Troubleshooting
. Diagnostic Codes
‘SP1, SP2, SP3, SP4 Absent Active Shutdown Diagnostic System
Procedures, “SP
Fault Code”
TALS thru ALIS ‘Absent ‘ative Alarm Diagnostic System
Procadures, “AL
Fault Cove"
Dedicated Shutdown
Flashing ‘Absent ‘Absent fetve Alarm | Troubleshooting
. Dedicated Shutdown
(on Continuously ‘Absent ‘Absent fete Shutdown | persancee
iD FMi@ ‘On Continuously Inactive Alerm Troubleshooting
Diagnostic Codes
iD FM ‘On Continuausly | inacive Shutdown | Troubleshooting
Diagnostic Codes
SPt, SP2, SP, SP4 ‘Absent inactive Shutdown | Diagnostic System
None Procedures, “SP
Fault Code”
"ALS through ALIS ‘absent inactive Alarm | O'agnostc Systern
Procedures, AL.
Fault Code"
‘Absent ‘Absent Undiagnosed | Symptom Procedures
Shutdown
{Fu codes shown afr elarm codes key i pressed
© faut ode s stored inthe aut og of te GSC. To view te fat coce, 869 Stems Oparaion, Fault Log Viewing OP win tho
top Serves ModeEREVAN a oc ee
\
37 !6 (QOOD s00
OP
‘mutation 91 614728
ae
Oe
(2) Spare fault indicators
{3} Fault shutdown indicator
a
{oto display
(@) DIAG incicator
Fautts that ate detected and diagnosed by the
GSC+ ate shown to service personne! in the display
area of the GSC+. The GSC+ uses dedicated
shutdown indicators (1), fault shutdown indicator
@, fault alarm indicator (4), "DIAG" indicator
(@), upper display (5) and lower display (6) to
tel service personne! about a fault. Perform the
following procedure in orcer to identity the fault tha:
is detected by the GSC+,
Note: The "DIAG" indicator (8) functions when
diagnostic information is available from the GSC+.
1. Make a note of the indicators that are functioning
on the ieft side of the "GSC+"
2. View the fauit code on the upper display (5). I
the fault alarm indicator (4) is FLASHING and
no fault code is present on the upper display
(6), press the alarm codes key in order to view
the fault code.
&. Make a note of whether or not "DIAG" indicator
(@) is FLASHING ON CONTINUOUSLY or
ABSENT.
4.0n the fault identification chart, look at the
first column, Locate the fault indicator that is
functioning.
119
“Troubleshooting Section
8. Go to the second column in the chart. Find the
fault code that is presently shown on the upper
display (8).
6. Go to the third column in the chart which
Gescribes the status of “DIAG" indicator (8).
7. Read the last two columns in order to find the
type of fault and comesponding topic within this
‘module.120
Troubleshooting Section
Symptom Procedures
so2esecr
Starting Motor Remains
Engaged (for EUI and PEEC
Engines)
SMCS Code: 1463-035
‘SN: 4BZ1-Up; 1EZ1-Up
‘SN: SKW1-Up; 1FZ1-Up,
‘SIN: 6GW1-Up: 1621-Up
S/N: BNW1-Up; 1HZ1-Up.
‘SIN: BAZ1-Up, 1MZ1-Up_
‘System Operation Description:
‘The starting motor remains engaged after the
‘engine has started.
‘OrNERATOR
Sey
OnE ROL eeces
ese
Onn aS
esPa ON
ENCE QSURE,
suagiaee syguee
IWustration 92
‘Schematic For Stating Motor Relay (SMR) On *PEEC" Enginescenegyon
oe a
aes
askation 93 080889
Schematic For Starting Motor Pela (SMR) On“EUM Engines
‘Test Step 1. CHECK THE SETPOINTS.
This test step checks the following setpoints: PO11
(crenk terminate speed), P01? (total cycle crank
time), and PO18 (cycle crank time).
‘A View the setpoints and make a note of setpoints
PO11, PO17 and PO18., See Systems Operation,
“Engine/Generator Setpoint Viewing OF2-0".
B. Compare the setpoints with the specified
setpoints of the particular generator set. The
default value for PO11 is 400 rpm. The default
value for PO17 is 90 seconds. The default value
for PO18 is 10 seconds,
Note: Engines that are equipped with prelube
pumps may require cycle crank times (setpoint
P08) of 380 seconds or more
Expected Result:
The setpoint vaiue that is being viewed should
match the specified setpoint value.
121
“Troubleshooting Section
‘© OK ~ The setpoint is correct. Proceed to test
step 2.
'* NOT OK ~ The setpoint that is being viewed does
not agree with the specified setpoint.
Repair: Reprogram setpoints PO11, PO17 and
PO18. See Systems Operation, “Engine/Generator
Programming OPS.0°.
STOP,
Test Step 2, CHECK THE START
FUNCTION OF THE ENGINE.
The foitowing procedure will require checks to be
made during simulated engine starting. Disable the
fuel system.
AA. Disable the fuel shutoff solenoid or the PEEC in
‘order to prevent the engine from starting but not
{from cranking. To disable the EU! engine ECM
rernove the J1-40 pin connector.
B. Prepare to manually stop the engine from
cranking, # necessary. Turn the battery
disconnect switch to the OFF position or shut the
engine off by using mechanicai means.
©. Turn the engine control switch (ECS) to the
START posttion. Allow the engine to crank,
D. Turn the ECS to the OFF/RESET position,
Expected Result:
The engine should stop ranking,
Resutts:
'* OK ~The engine does not crank. Proceed to test
step 6.
‘* NOT OK — The engine continues to crank
Proceed to test step 3,
Test Step 3. CHECK THE START
FUNCTION OF THE ENGINE.
A. The conditions of the previous step remain. The
fuel system is disabled. The engine is cranking,
B. While the engine is still cranking, push the
emergency stop push button.
Expected Result:
The engine should stop cranking,122
Troubleshooting Section
Results:
‘© YES — The engine does not crank,
Repair: Check the wire on "RM-18" of the relay
‘module for a short to +battery. Repair the short
‘or replace the harness. if a short is not found,
replace the relay module, See Testing And
Adjusting, "Relay Module - Replace”.
STOP.
¢ NO -The engine continues to crank. Proceed
otest stop 4.
Test Step 4, CHECK THE START
FUNCTION OF THE ENGINE.
‘A. The conditions of the previous step remain, The
fuel system is disabled. The engine is cranking.
Stop the engine, Turn the battery disconnect
‘witch to the OFF or shut the engine off by using
mechanical means,
€. Remove all wires from TS1-25 in the generator
housing. For dual starting motors, remove all
wites trom TS1-26.
1D. Turn the ECS to START. Attempt to crank the
engine.
Expected Result:
The engine should not crank.
Results:
© OK ~ The engine does not crank,
Repair: The "SMS" or related wiring has failed.
Troubleshoot the “SMMS" and the related wiring
See the Generator Set Wiring Diagram in Testing
And Adjusting, “Schematics & Wiring Diagrams",
stop.
# NOT OK — The engine continues to crank
Proceed to test step 5.
Test Step 5. CHECK THE START
FUNCTION OF THE ENGINE.
‘A, The conditions of the previous step remain. The
fuel system is disabled. The engine is cranking.
Stop the engine. Tum the battery disconnect
switch to OFF of shut the engine off by using
mechanical means.
. Disconnect the “B+” wire on the pinion solenoid
of the starting motor.
1D, Tum the ECS to START and attemet to crank the
engine,
Expected Result:
The engine should not crank.
Results:
* OK ~ The engine does not crank.
Repair: On "PEEC” engines, wite 052-125 of
125-152 in the engine harness is shorted to
the battery. On "EUS" engines, wire 304-WH
or 314-PU in the engine harass is shorted to
the battery. Troubleshoot the wiring. See the
Generator Set Wiring Diagram in Testing And
Adjusting, "Schematics And Wiring Diagrams”
STOP,
* NOT OK - The engine continues to crank
Repair: The starting motor has failed. Troubleshoot
the starting motor Refer to the Starting Motor
and/or Engine Service Manuals.
STOP
Test Step 6. CHECK THE STARTING
MOTOR CYCLING.
‘A. The fuel delivery is disabled.
B. Turn the ECS to the START position,
Expected Result:
‘The starting motor shou'd cycle on and off
according 10 setpoint PO18 (cycle crank time).
Results:
© OK ~ If the starting motor cycles correctly, the
problem is not present. STOP.
* NOT OK ~ If the starting motor remains engaged,
the starting motor has faved.
Repair: Troubleshoot the starting motor. Refer to
the Starting Motor andjor Engine Service Manuals.
STOP,oman
Starting Motor Remains
Engaged (for MUI 3412C, 3508,
3512, 3516 Engines)
‘SMCS Code: 1453-035
SIN: BNS1-Up_
‘SIN: SES1-Up
‘SIN: SPW1-Up; 1JZ1-Up
SIN: BWW1-Up; 1KZ1-Up.
‘SIN: BTW1-Up; 1121-Up
‘SMM: 4BZ1-Up; 3FZ1-Up-
|’ System Operation Description:
The starting motor remains engaged after the
|, engine has started.
oReseyt
whet
Isai?
poarzeani
For Starting Motor Relay (SMA)
128,
‘Troubleshooting Section
Test Step 1. CHECK THE SETPOINTS.
‘This test step checks the following setpoints: PO11
(crank terminate speed), PO17 (total cycle crank
time), and P018 (cycle crank time).
A. View the setpoints and make a note of setpoints
PO11, PO17 and POIB. See Systerns Operation,
“Engine/Generator Setpoint Viewing OP2-0"
B. Compare the setpoints with the specitied
selpoints of the particular generator set. The
default value for P01 is 400 rpm. The default
value for PO17 is 90 seconds. The default value
for PO18 is 10 seconds.
Expected Result:
‘The setpoint value that is being viewed should
maich the specified setpoint value.
Resutts:
* OK ~The setpoint is correct. Proceed to test
step 2.
@ NOT OK ~The setpoint that is being viewed dooe
not agree with the specified setpoint,
Repair: Reprogram setpoints PO11, PO17 and
O18. See Systems Operation, “Engine/enerator
Programming OPS-0"
STOP.
Test Step 2, CHECK THE START
FUNCTION OF THE ENGINE.
The following procedure will require checks to be
‘made curing simulated engine starting. Disable the
fuel system.
‘A. Disable the fuel shutoff solenoid or the governor
in order to prevent the engine from starting but
not from cranking
B. Prepare to manualiy stop the engine from
‘cranking, if necessary. Turn the battery
disconnect switch to the OFF position or shut the
engine off by using mechanical means.
Turn the engine control switch (ECS) to the
START position. Allow the engine to crank,
D. Turn the ECS to the OFFIRESET position
Expected Result:
The engine should stop cranking124
‘Troubleshooting Section
Results:
# OK ~ The engine does not crank. Proceed to test
step 6.
© NOT OK ~The engine continues to crank
Proceed to test step 3.
Test Step 3. CHECK THE START
FUNCTION OF THE ENGINE.
A. The conditions of the previous step remain. The
fuel system is disabled. The engine is cranking
B. While the engine 's stil cranking, push the
‘emergenoy stop push button.
Expected Result:
The engine should stop cranking.
Results:
© YES ~ The engine does not crank.
Repair: Check the wire on “RM-18" of the relay
module for a short to +baltery. Repair the short
of replace the harness. If a short is not found,
replace the relay module. See Testing And
Adjusting, "Relay Module - Replace".
STOP,
‘* NO ~The engine continues to crank. Proceed
to test step 4.
Test Step 4. CHECK THE START
FUNCTION OF THE ENGINE.
‘A. The conditions of the previous step remain, The
fuel system is disabled. The engine is cranking,
B, Stop the engine. Turn the battery disconnect
‘switch to the OFF or shut the engine off by using
mechanical means.
C. Remove all wires from the output terminal of
slarling motor magnetic switch (SMMS) in the
junction box
D. Tum the ECS to START. Attempt to crank the
engine.
Expected Result:
The engine should not crank.
Results:
* OK — The engine does not crank,
Repair: The “SMS" or related wiring has failed
Troubleshoot the "SMMS" and the related wiring.
See the Generator Set Wiring Diagram in Testing
And Adjusting, “Schematics & Wiring Diagrams
STOP,
‘NOT OK ~ The engine continues to crank.
Procead to test step 5.
Test Step 5. CHECK THE START
FUNCTION OF THE ENGINE.
A. The conditions of the previous step remain. The
{ual system is disabled, The engine is cranking.
B. Stop the engine. Turn the battery disconnect
swfch to OFF or shut the engine off by using
mechanical means.
©. Disconnect the "B+" wire on the pinion solenoid
of the starting motor.
D. Tum the ECS to START and attempt to crank the
engine.
Expected Result:
The engine should not crank.
Results:
* OK — The engine does not crank.
Repair: The wire to the pinion solenoid in
the engine harness is shorted to the battery.
‘Troubleshoot the wiring. See the Generator
Set Wiring Diagram in Testing And Adjusting,
"Schematics And Wiring Diagrams"
stop.
* NOT OK — The engine continues to crank
Repair: The starting motor has failed. Troubleshoot
the starting motor. Refer to the Starting Motor
andior Engine Service Manuals.
STOP.
Test Step 6. CHECK THE STARTING
MOTOR CYCLING.
‘A. The fuel delivery is disabled.
B. Turn the ECS to the START position.
Expected Result:
The starting motor should cycle on and off
according to setpoint PO18 (cycle crank time),Results:
« OK ~ If the starting motor cycles correctly, the
problem is not present, STOP.
© NOT OK ~ If the starting motor remains engaged,
the starting motor has failed.
Repair: Troubleshoot the starting motor. Refer to
the Starting Motor andlor Engine Service Manuals.
TOP.
‘ssra0s
Engine Does Not Shutdown
(for EUI Engines)
SMCS Code: 4490-035
‘SIN: SKW1-Up; 1FZ1-Up.
‘SN: 6GW1-Up; 1GZ1-Up
SIN: BNW1-Up; 1HZ1-Up
‘SN: 8AZ1-Up; 1MZ1-Up
‘System Operation Description:
The engine does not shut down when a shutdown
fault occurs.
ceagaion va =
comet (eoey fo Sean at
LBL sass
“aloe
Bann
ustration 95 900681895
‘System Schomatic For Electronic Control Relay
126
‘Troubleshooting Section
ease
©
aA CYLINDER ONLY
ons T008
IMustration 96
‘System Schematic For Air Shutol Relay (ASA)126
‘Troubleshooting Section
SENERATOR
ar
conreot
SAS
BaaLaBe eso
‘tuswation 67 porns
System Schomatic For Engine Contrat Switeh (ECS)
Note: Its critical that GSC+ setpoint PO23 is correct
tor the engine application. Ensure that setpoint PO23
is programmed correctly for the engine application
before continuing with this procedure.
‘There are several possible causes when a shutdown
fault occurs and an engine does not shut down:
© Operator Error: The operating conditions of the
generator may not be understood by the operator.
Ensure that the condition is one that should cause
an engine shutdown,
‘+ Programming Error - Fault Is Overridden Or
Disabled: itis possible to program the GSC+
in order to override certain shutdown faults. An
overridden shutdown fault will be treated as an
alarm fault, The YELLOW fault alarm indicator
will be FLASHING instead of the RED faut
shutdown indicator. If tne GSC+ 's programmed.
in order to disable a particular fault, there will
not be any fault indicators or codes shown on
the GSC+. In these cases, itis a good idea to
check any setpoints related to that fauit. For
example, if a genset is not shutting down when an
overvoltage fault occurs, make sure setpoint P104
(Overvoltage shutdown enable) is programmed
Correctly. Itis also possible to program the engine
ECM to override or ignore certain shutdown
faults. See Troubleshooting, SENR1003, “35008
EPG Engines" or Troubleshooting, RENR2227,
"3406 EPG Engines" for more information on
programming the engine ECM.
* Programming Error - Setpoints Incorrect For
Application Or Customer Needs: It is possible
to program the GSC+ setpoints to a value that
does not allow the situation to be recognized
by the GSC+ as a shutdown conaition. In
this case, chack the appropriate setpoints for
correct values. For example, if the genset is not
shutling down when a high coolant temperature
condition occurs, make sure setpoint PO15 (High
Water Temperature Shutdown) is correct fer the
application
* Faulty Component: Some examples of faulty
‘components that could prevent the GSC+ from
shutting down the engine are: engine ECM,
GSC+, and a broken or shorled harness wite.. In
this case, the GSC+ or engine ECM will be issuing
@ command to shut down the engine due to a
diagnostic code, but the engine remains running.
‘Test Step 1. CHECK FOR DIAGNOSTIC
CODES
‘A. Check the GSC+ for a diagnostic code on the
supper display.
Expected Result:
The GSC+ should show a diagnostic code on the
upper display.
© YES - The GSC+ shows a diagnostic code on
the upper display.127
Repair: See theTesting and Adjusting section of
this book for the diagnostic code that is displayed
on the GSC+
STOP
‘* NO ~The GSC+ does NOT shaw a diagnostic
code on the upper display. Proceed to Test Step
2.
‘Test Step 2. CHECK THE YELLOW FAULT
ALARM INDICATOR
A. Check the display of the GSC+ for the yellow
fauit alarm indicator.
Expected Result:
The yellow fault alarm indicator is ON
CONTINUOUSLY.
Results:
‘© YES - The yellow fault alarm indicator is
ON CONTINUOUSLY. The GSC+ has been
programmes to override the normal shutdown
response. The setpoints have been modified and.
the GSC+ treats the condition as an alarm fault
The engine will continue to run.
Repair: in order to view the selpoinis, seeSysters
Operation, “Engina/Generator Setpoint Viewing
0P2.0". In order to reprogram the setpoints,
see Systems Operation, “Engine/Generator
Programming OP5-0"
sToP.
© NO - The yellow fault alarm indicator is not
iluminated at all. Proceed 10 Test Step 3.
Test Step 3, CHECK FOR THE RED FAULT
SHI iN INDICATOR
A.Check the display area of the GSC+ for the red
faut shutdown indicator.
Expected Result:
The red fault shutdown should be FLASHING.
Results:
Je YES ~The red fault shutdown indicator is
FLASHING and the engine remains running.
Proceed to Test Step 4.
NO - All fault indicators are.OFF. A problem that
's occurring should cause Ihe GSC plus to shut
down the engine. It is possible to program the
GSC+ setpoints to a value that does not allow
the situation to be recognized by the GSC+ as
a shutdown condition.
Troubleshooting Section
Repair: Check the appropriate setpoints for correct
values. In order to view the setpoints, see System
Operation, “Engine/Generator Setpoint Viewing
OP2-0", In order to reprogram the selpoints,
see System Operation, “Engine/Generator
Programming OP5-0".
STOP,
Test Step 4. CHECK K1 INDICATOR ON
GSC+ DISPLAY
A. The red fault shutdown indicator is FLASHING
and the engine remains running.
B. Check the upper display of the GSC+
Expected Result:
The K1 symbol is showing on the GSC+ upper
display.
Results:
© YES ~ The K1 symbol is showing on the @SC+
upper display, The red fault shutdown indicator is
FLASHING and the engine remains running. The
GSC+ may have failed,
Repair: The GSC+ may have failed. jt is unlikely
that the GSC+ has failed. Exit this procedure
and perform this entire procedure again. It
the problem remains, replace the GSC+. See
Testing and Adjusting, "EMCP Electronic Control
(Generator Set)-Replace”
STOP.
'* NO ~The K1 symbol is not showing at call on the
GSC+ upper display. Proceed to Test Step 5.
Test Step 5. CHECK THE GSC+ RELAY
MODULE.
‘The engine remains running and the red fault
shutdown indicator is FLASHING.
AA. In the generator housing, remove BOTH of the
wires from RM-13 on the GSC+-
Expected Result:
The engine should shut down,
Results:
¢ OK = The engine shuts down,128
Troubleshooting Section
Repair, The GSC+ Relay Module ay have
failed. it Is unlikely that the GSC+ Relay Module
has failed. Exit this procedure and perform this
entire procedure again. If the problem remains,
replace the GSC+ Relay Module. See Testing
And Adjusting, “EMCP Electronic Control (Relay
Modula) - Replace”
stor
NOT OK ~The engine runs and the engine will
start. Proceed to Test Step 6.
Test Step 6. CHECK THE SYSTEM BY
USING THE ESPB.
The engine remains running and the red fault
shutdown indicator is FLASHING,
‘A. Push the emergency stop push button (ESP)
Expected Result:
‘The engine should shut down,
Resutts:
‘* OK — The engine does shutdown. Proceed 10
Test Step 7
«NOT OK ~The engine does NOT shut down.
Repair: The engine ECM made have failed. Refer
to Troubleshooting, SENR1003, "35008 EPG
Engines" or Troubleshooting, RENR2227, “3406E
EPG Engines"
STOP,
Test Step 7. CHECK THE WIRING
BETWEEN THE ENGINE ECM AND THE
GSC+.
The engine remains running and the red fault
shutdown indicator is FLASHING.
‘A. Check the wiring between RM-13 of the GSC+
and J1-8 and J1-14 of the engine ECM. Check
for shorts, open connections, or damaged wires.
Expected Result:
The wiring has @ short, open connection, of is
damaged.
Results:
© OK ~ The wiring is damaged.
Repair: Troubleshoot and repair the wiring. See
Generator Set Wiring Diagram in Tasting And
Adjusting, “Schematics And Wiring Diagrams”
Verify that the repair corrects the probiem.
stor.
* NOT OK — The wiring is not damaged et all. The
engine ECM may have failed,
Repair; The engine ECM made have failed. Refer
to Troubleshooting, SENR1003, "35008 EPG
Engines" or Troubleshooting, RENR2227, “3400
EPG Engines".
STOR,
iors
Engine Does Not Shutdown
(for MUI 3306B, 3406C Engines)
SMCS Code: 4490-035.
SIN: BNS1-Up
‘SIN: 9ES1-Up
‘System Operation Description:
The engine does not shut down when a shutdown
fault occurs.ed
Troubleshooting Section
me iF 3 ae
@249F 6 Op“
z Esra ps
eugeyaowse 7
seteaan 7°
280
SLAVE RELAY
Two FUEL ao
station 98
Fil Control Reisy For ETR Systems
court _
Relae
| 3
rary)
ALR suurore
Seer Bt
ie RrauIRES.
conitedy a "SBAne
PACT Coane
Isvavon 09 cess
‘System Schematic For Air Shutott Relay
Note: It is critical that GSC+ setpoint P023 is correct
tor the engine application, Ensure that setpoint PO23
is programmed correctly for the engine application
before continuing with this procedure.
There are several possible causes when a shutdown
fault occurs and an engine does not shut down:
‘* Operator Error: The operating conditions of the
‘generator may not be understood by the operator.
Ensure that the condition is one that should cause
fan engine shutdown.130
‘Troubleshooting Section
* Programming Error - Fault Is Overridden Or
Disabled: It is possible to program the GSC+
in order to override certain shutdown faults. An
‘overridden shutdown fault will be treated as an
alarm fault. The YELLOW fault alarm indicator
will be FLASHING instead of the RED fault
shutdown indicator. If the GSC+ is programmed
in order to disable a particular fault, there will
not be any fault indicators or codes shown on
the GSC+. In these cases, itis @ good idea to
check any setpoinis related to that fault. For
example, if a genset is not shutting down when an
overvoltage fault occurs, meke sure setpoint P104
(Overvoltage shutdown enable) is programmed
correctly Is also possible to program the engine
ECM 10 override oF ignore certain shutdown
faults. See Troubleshooting, SENR1003, “25008
EPG Engines” or Troubleshooting, RENR2227.
"9406E EPG Engines" for more information on
programming the engine ECM.
‘* Programming Error - Setpoints Incorrect For
Application Or Customer Needs: It is possible
to program the GSC+ setpoints to a value that
does not allow the situation to be recognized
by the GSC+ as a shutdown condition: In
this case, check the appropriate setpoints for
Correct values. For example, it the genset is not
shutting down when a high coolant temperature
condition occurs, make sure setpoint PO15 (High
Water Temperature Shutdown) is correct for the
application
* Faulty Component: Some examples of faulty
‘components that could prevent the GSC+ from
shutting down the engine are: GSC+ and a
broken or shorted harness wire...In this case, the
GSC+ will be issuing a command to shut down
the engine due to a diagnostic code, but the
‘engine remains running
‘Test Step 1. CHECK FOR DIAGNOSTIC
CODES
A. Chook the GSC+ for a diagnostic code on the
upper display.
Expected Result
‘The GSC+ should show a diagnostic code on the
upper display,
Results:
* YES ~ The GSC+ shows a diagnostic code on
the upper display.
Repair: See theTesting and Adjusting s
this book for the diagnostic code that is displayed
on the GSC+
STOP,
© NO -The GSC+ does NOT show a diagnostic
code on the upper display. Proceed to Test Step
2
Test Step 2. CHECK THE YELLOW FAULT
ALARM INDICATOR
‘A. Check the display aroa of the GSC+ for the
yellow fauit alarm indicator.
Expected Result:
‘The yellow fault alarm indicator should be
illuminated CONTINUOUSLY.
Results:
YES - The yellow fault alarm indicator is
imirvatogs CONTINUOUSLY.
Repair: The GSC+ has been programmed to
‘override the normal shutdown response and
the GSC+ treats the condition as an alarm
fault, Tha engine will continue to run. In order
10 view the setpoints, see System Operation,
“Engine/Generator Setpoint Viewing OP2-0". In
‘order to reprogram the setpoints, see System
Operation, “Engine/Generator Programming
OPS."
STOP,
‘© NO - The yellow fault alarm indicator is not
illuminated at all, Proceed to Test Step 3.
Test Step 3. CHECK FOR RED FAULT
SHUTDOWN INDICATOR.
A. Check the display area of the GSC+ fer a red
fault shutdown indicator,
Expected Result:
‘The red fault shutdown indicator should be
FLASHING.
Results:
© YES — The red fault shutdown indicator is
FLASHING and the engine remains running
Proceed to Test Step 4,a
NO ~All taut indicators are OFF. A problem
that is occurring should cause the GSC+ to shut
down the engine. It is possible to program the
GSC+ setpoints to a value that does not allow
the situation to be recognized by the GSC+ as
a shutdown condition.
Repair: Check the appropriate setpoints for correct
values. In order to view the setpoints. see Systern
Operation, “Engine/Generator Setpoint Viewing
OP2.0°. In order to reprogram the setpoints,
306 System Operation, "Engine/Generator
Programming OP5-0"
STOP.
Test |. CHECK THE SYSTEM BY
USING THE ESPB.
The engine remains running and the ted fauit
shutdown indicator is FLASHING.
‘A. Push the emergency stop push button (ESPB).
Expected Result:
Tre engine should shut down,
Results:
* OK ~ The engine does shutdown, The relay
module has failed.
Repair: Replace the relay module. See Testing
‘And Adjusting, “Relay Module - Replace”
STOP,
«NOT OK ~ The engine does NOT shut down.
Proceed to Test Step 5,
Test Step 5. CHECK FOR FUEL CONTROL
SOLENOID AND ENGINE PROBLEMS.
‘he engine remains running and the red fault
shutdown indicator is FLASHING.
A. Remove F14 in the Junction Box.
Expected Result:
The engine should shut down.
Results:
* YES - The engine shuts down. Therefore, the fuet
control solenoid (FCS) has failed.
epair: Replace the fuel control solenoid. Verity
that the repair corrects the problem,
STOP.
131
Troubleshooting Section
© NOT OK ~ The engine continues to run and the
red fault shutdown indicator is FLASHING. There
is @ problem with the engine.
Repair: Refer to the appropriate engine service
‘manual in order to troubleshoot the engine.
STOP.
owrmn
Engine Does Not Shutdown
(for MUI 3412C, 3508,3512,
3516 Engines)
‘SMCS Code: 4490-035
SIN: 5PW1-Up; 102 1-Up
SIN: BWW1-Up; 1KZ1-Up
‘S/N: 8TW1-Up; 1LZ1-Up_
‘S/N: 4BZ1-Up; 3FZ1-Up
‘System Operation Description:
The engine does not shut down when a shutdown
fault occurs,132
‘Troubleshooting Section
ceNggaToR
eet
conto.
tesey
ceMegaTOR
cokiRo.
(esc)
SPEED
contre,
evechnange
EQNEROL
nae at 2
| frwe poet
wehako
ReUay
Tacupoe
ae step
Benger’
‘ohty
Mustraton 100
Fuel Control Relay For ETR 8)
°
1
UH |», »
L SLL is ie :
a aroutrep, |
conned t"SBawe
FAUCT chanel
AZR shuTorr
ia ave
JeRhat “Box
1465
pred
‘Mustation 101
‘System Schematic For Ar Shuto Relay (ASA)
Note: It is extremely important that GSC+ setpoint
P23 is correct for the engine application, Make
certain setpoint P023 is programmed correctly for
the engine application before continuing with this
procedure
Note: It is extremely important that GSC+ setpoint
O01 is correct for the engine. All generator sets
packaged in Larne, Ireland covered by this manual
must ALWAYS have this setpoint programmed to
0 ETR fue! solenoid) for both fuel solenoid types
{ETR or ETS).
‘There are several possible causes why an engine is
rot shutting down when a shutdown fault occurs,
Operator Error: The operating conditions of the
.generator may not be undersicad by the operator.
Ensure that the condition is one thal should cause
an engine shutdown,rs
‘+ Programming Error - Fault is Overridden Or
Disabled: It is possible to program the GSC+
in order to override certain shutdown faults. An
overridden shutdown fault will be treated as an
alarm fault. The YELLOW fauit alarm indicator wil
be FLASHING instead of the RED fault shutdown
indicator. If the GSC+ is programmed in order to
disable a particular fault, there will not be any fault
indicators or codes shown on the GSC+. In these
cases, itis a 900d idea to check any setpoints
related to that fault. For example, if a generator
is not shutting down when an overvoltage fault
‘occurs, make sure setpoint P104Overvoltage
shutdown enable) is programmed correctly.
‘ Programming Error - Setpoints Incorrect For
‘Application Or Customer Needs: It is possible
to program the GSC+ setpoinis to a vaiue that
‘does not allow the situation to be recognized
by the GSC+ as a shutdown condition. In this
‘case, check the appropriate setpoints for correct
values. For example, if the generator is not
shutting down when a high Coolant temperature
condition occurs, make sure satpoint PO15 (High
‘Water Temperature Shutdown) is correct for the
application
+ Faulty Component: Some examples of fauty
components that could prevent the GSC+ from
shuiting down the engine are: GSC+ and a
broken or shorted harness wire. In this case, the
GSC+ will be issuing a command to shut down
the engine due to a diagnostic code, bul the
engine remains running,
Test Step 1. CHECK FOR DIAGNOSTIC
CODES
‘A. Check the GSC+ for a diagnostic code on the:
upper display.
Expected Result:
The GSC+ should show a diagnostic code on the
upper display.
Results:
* YES ~ The GSC+ shows a diagnostic code on
the upper display.
Repair: See theTesting and Adjusting section of
this book for the diagnostic code that is displayed
‘on the GSC+.
sTor.
#NO —The GSC+ doas NOT show a diagnostic
code on the upper display. Proceed to Test Step
2
133
‘Troubleshooting Section
‘Test Step 2. CHECK THE YELLOW FAULT
ALARM INDICATOR:
‘A. Check the display area of the GSC+ for the
yellow fault alarm indicator.
Expected Rest
The yellow fault alarm indicator should be
illuminated CONTINUOUSLY.
Results:
* YES ~ The yellow fault alarm indicator is
illuminated CONTINUOUSLY.
Repair: The GSC+ has been programmed to
override the normal shutdown response and
the GSC+ treats the condition as an alarm
fault. The engine will continue to run. In order
to view the setpoints, see Systern Operation,
“Engine/Generator Setpoint Viewing OP2-0". in
order to reprogram the setpaints, sea System
Operation, “Engine/Generator Programming
OP 5-0"
STOP,
NO ~The yellow fault aiarm indicator is not
illuminated at all. Proceed to Test Step 3.
Test Step 3. CHECK FOR RED FAULT
SHUTDOWN INDICATOR.
‘A. Check the display area of the GSC+ for the red
fault shutdown indicator
Expected Result:
‘The red fault shutdown indicator should be
FLASHING.
Results:
* YES — The red fault shutdown indicator is
FLASHING and the engine remains running,
Proceed to Test Step 4
* NO —All fault indicators are OFF. A problem
that is occurring should cause the GSC+ to shut
down the engine. It is possible to program the
GSC+ setpoints to a value that does not allow
the situation to be recognized by the GSC+ as
fa shutdown condition.
Repair: Check the appropriate setpoints for
correct values. In order to view the setpoints,
see Systems Operation, "Engine/Generator
Setpoint Viewing OP2-0°, in order to reprogram
the setpoints, see Systems Operation,
“Engine/Generator Programming OPS-0"
STOP,134
‘Troubleshooting Section
Test Step 4. CHECK THE SYSTEM BY
USING THE ESPB.
The engine remains running and the fault shutdown
indicator is FLASHING.
‘A. Push the emergency stop push button (ESPB).
Expected Result:
The engine should shut down,
Resutts:
'* OK - The engine does shutdown. The relay
module is faulty,
Repair: Replace the GSC+ relay module. See
Testing and Adjusting, "Relay Module - Replace”
Verify that the repair corrects the problem.
STOP,
‘* NOT OK ~ The engine does NOT shut down,
Proceed to Test Step 5
Test Ste. 5. CHECK GSC+ SETPOINT
P001 (FUEL SOLENOID TYPE)
‘The engine remains running after pushing the ESPB.
and he red fault shutdown indicator is flashing,
‘A. Check setpoint POO1 (Fuel Solenoid Type).
Jn order to view the setpoints, see Systems
Operation, “Engine/Generator Setpoint Viewing
rg
Expected Result:
‘Setpoint POO1 should be programmed to *O”
Note: All generator sets packaged in Larne, Ireland,
that are covered by this manual must always have
this setpoint programmed to *0" (ETR fuel solenoid)
fer both fuel solenoid types (ETR or ETS).
Results:
* YES — Setpoint POO1 is programmed to “0”
Proceed to Test Step 6
* NO ~ Setpoint P001 is programmed to “1”. The
setpoint is programmed incorrectly.
Repair: Reprogram the setpoint 10 @ value of “O"
1 order to reprogram the setpoint, see Systems
Speraton,“Engine/Generatr Programming
5.0"
STOR.
Test Step 6. CHECK VOLTAGE AT THE
FUEL CONTROL SOLENOID
The engine remains running after pushing the ESPB
and the ted faull shutdown indicator is FLASHING,
A. At the fuel contro! solenoid, measure the voltage.
Expected Result:
The voltage measured at the fuel control solenoid
should be approximately the same as the nominal
battery vottage (+/- 2 volts)
Resutts:
© OK ~ The battery voltage is correct at the FCS.
‘The FCS has failed or there is a problem with the
engine fuel system.
Ropair: Refer to the appropriate engine service
manual. Replace the FCS or repair the fuel
system,
STOP.
‘* NOT OK — Battery voltage is not correct at the
FCS. The Emergency Fuel Control Relay (EFCR)
has failed,
Repair: Replace the Emergency Fuel Control
Relay (EFCR). Verity that the repair corrects the
problem.
‘STOP.
varie
Engine Does Not Shutdown
(for PEEC Engines)
‘SMCS Code: 4490-035
‘SIN: 4BZ1-Up; 1EZ1-Up
‘System Operation Descripti
‘The engine does not shut down when a shuldown
fautt occurs.
There are several possible causes why an engine is
not shutting down when a shutdown fault occurs:Ero *
cenggavon
otro
erHer
Start |
Switen! 2)
Sena
convenver
ean),
so sof
vy
4 ¥
xo [ree | Vf
a GB
Ph ENGINE is
ba prea
Iara 102 gonsre7o
Sistem Schomatic For Unexpected Shutdown
Yale: tis extremely important that GSC+ setpoint
F023 is correct for the engine application. Make
certain selpoint PO23 is programmed correctly for
{te engine application before continuing with this
procedure.
Note: itis extremely important that GSC+ setpoint,
1 is cortect for the engine. All generator sets
.ged in Lame, ireland with serial numbers
{ist of S/N’s) must ALWAYS have this setpoint
yammed to G (ETR fuel solenoid) for both fuel
eid types (ETR or ETS).
are several possible causes why an engine is
‘shutting down when a shutdown fault occurs.
135
‘Troubleshooting Section
‘© Operator Error: The operating conditions of the
‘generator may not be understood by the operator.
Ensure that the condition is one that should cause
an engine shutdown.
‘© Programming Error - Fault Is Overridden Or
Disabled: it is possible to program the GSC+
in order to override certain shutdown faults. An
‘overridden shutdown favit will be treated as an
alarm fault. The YELLOW fault alarm indicator will
be FLASHING instead of the RED fault shutdown
indicator. I the GSCs is programmed in order to
disable a particular faut, there will not be any fault
indicators or codes shown on the GSC-. In these
cases, it's a good idea to check any setpoints
related to that fault. For example, ia genset is not
shutting down when an overvoitage fault occurs,
make sure setpoint P104(Overvoltage shutdown
enable) is programmed correctly.
‘* Programming Error - Setpoints incorrect For
Application Or Customer Needs: It is possiole
to program the GSC+ setpoints to a value that
does not allow the situation to be recognized
by the GSC+ as @ shutdown condition. In
this case, check the appropriate setpoints for
correct values. For example, if the genset is not
shutting down when a high coolant temperature
condition occurs, make sure setpoint PO16 (High
‘Water Temperature Shutdown) is correct for the
application
‘* Faulty Component: Some examples of faulty
‘components that could prevent the GSC+ from
shutting down the engine are: PEEC, GSC», and
4 broken or shorted harness wire.. In this case,
the GSC+ or PEEC will be issuing a command to
shut down the engine due to a diagnostic code,
but the engine remains running.
Test Step 1. CHECK FOR DIAGNOSTIC
CODES
‘A. Check the GSC+ for a diagnostic code on the
upper display.
Expected Resutt:
‘The GSC+ should show a diagnostic code on the
upper display.
Results:
* YES ~The GSC+ shows a diagnostic code on
the upper display.
Repair: See theTesting and Adjusting section of
this book for the diagnostic code that is displayed
on the GSC+.
STOP.136
‘Troubleshooting Section
‘¢ NO ~The GSC+ does NOT show a diagnostic
code on the upper display, Proceed to Test Step
2
‘Test Step 2. CHECK THE YELLOW FAULT
ALARM INDICATOR
‘A. Check the display area of the GSC+ for the
yellow fault alarm indicator.
Expected Result:
‘The fault alarm indicator should be illuminated
‘CONTINUOUSLY,
Results:
© YES ~ The fault alarm indicator is illuminated
CONTINUOUSLY.
Repair: The GSC+ has been programmed to
‘override the normal shutdown response and
the GSC+ treats the condition as an alarm
faut. The engine will continue to run. In order
to view the setpoints, see System Operation,
“Engine/Generator Setpoint Viewing OP2-0". In
order to reprogram the setooints, see System
Operation, “Engine/Generator Programming
Ore",
STOP,
* NO ~The yellow fault alarm indicator is not
‘lluminated at all. Proceed to Test Step 3.
Test Step 3. CHECK FOR RED FAULT
SHUTDOWN INDICATOR.
A. Check the display area of the GSC+ for a red
fault shutdown indicator.
Expected Resutt:
The fed fault shutdown indicator should be
FLASHING.
Resuits:
© YES — The red fault shutdown indicator is
FLASHING and the engine remains running,
Proceed to Test Step 4.
‘* NO -All fault indicators are OFF. A problem
that is occurring should cause the GSC+ to shut
down the engine. Itis possible to program the
GSC+ setpoints to a value that does not allow
the situation to be recognized by the GSC+ as.
a shutdown condition
Repair: Check the eppropriate setpoints for correct
values. In order to view the seipoints, see System
Operation, “Engina/Generator Setpoint Viewing
OP2.0". In order to teprogram the setpoints,
see System Operation, “Engine/Generator
Programming OP5-0"
STOP.
Test Step 4. CHECK THE SYSTEM BY
USING THE ESPB.
‘The engine remains running and the red fault
shutdown indicator is FLASHING
A Push the emergency stop push button (ESPB).
Expected Result
‘The engine should shut down
Results:
¢ OK ~The engine does shutdown,
Repair: Replace the PEC or the ESDR. Verify
that the repair corrects the problem.
STOP.
‘* NOT OK — The engine does NOT shut down,
There is an engine problem,
Repair: Cheok the fuel shutoff solenoid (FSS)
and the engine fuel system. Refer to the
appropriate engine service manuals.
STOP,
evan |
GSC Operation Is Erratic
‘SMCS Code: 4490-035
‘System Operation Description:
Fault shutdown indicator on the GSC+ flashes at
the rate of four to five times per second (4 10 5 H2).
The displays of the GSC+ may not be responding
‘The GSC+ does not respond to any position of the
engine control switch (ECS).
peThis is an internal fault of the GSC+ that can be
lemporary or permanent. The fault is caused by
@ component failure in the GSC+. Also, the fauit
may be caused by severe electromagnetic fields
oF radio frequency interference. The relays in the
relay module are automatically turned off when this
fault occurs. The effect of this fault on the engine
depends on the type of fuel system.
‘* For engines with 8290 governor, the engine runs
atidlo speed, The emergency stop push button
(ESPB) will shut down the engine.
«For engines with a mechanical governor, the
engine will shut down,
RESET THE GSC+
‘A. Tum the ECS to OFF/RESET. If the GSC+
does not power down, remove the jumper that
connects terminals 6 and 10 on the ECS.
B. Turn the ECS to STOP.
Expected Result:
‘The GSC+ should power up with a normal display
and the GSC+ should respand to the ECS
Results:
© OK — The GSC+ is operating normally.
Repair: The GSC+ will need to be replaced it the
problem reoccurs.
STOP.
= NOT OK ~The GSC+ does NOT operate correctly
and the fault shutdown indicator stil flashes at the
fata of four to five times per second (4 to 5 Hz).
Ropair: The GSC+ has failed. Replace the GSC+.
See Testing And Adjusting, “EMCP Electronic
Contral (Generator Set ) - Replace”
STOP.
137 .
‘Troubleshooting Section
wrseseue
Display of Voltage or Current
Is Zero (for MUI 3306B, 3406C
Engines)
‘SMCS Code: 4490-035
‘SIN: BNS1-Up.
‘SIN: 9ES1-Up
‘System Operation Description:
Zero volts or zero amperes are showing on the
display of the GSC+ for one or more AC phases.
This is showing while the genset is running and the
load is connected.138
‘Troubleshooting Section.
* — $
G 2 ca
» a
A rae
OD (Teo fo jo fo a
so) so
O51 % 68 O+
(aTB+)
(ouassts ero)
(ic oReuno)
oa ay
1 “sy eset (wa ani
AC TRANSFORMER BOX+
mea ue Np
$F ese-6 ae 1)
je cse-4 cra 0 ozngaaron
165 eset (ve tm conten, +
station 103
‘Systom Schematic For AC Tranetormer Box +
|A.Wye Connection Is Shown For The Generator
FLU}
When the engine-generator, or any source to
which the engine-generator is synchronized to, is
operating, voltages up to GOOV are present In the
control panel.
Do not short these terminal with line voltage to
ground with any part of the body or any conduc
tive material. Loss of life or injury could result
from electrieal shock or Injury from molten met-
see
Test Step 1. THE PROBLEM IS WITH AC
VOLTAGE OR THE PROBLEM IS WITH AC
CURRENT.
A. Determine if the problem is with AC voltage
or with AC current, Check the display of the
GSC+ while the genset is runing and the load
is connected.
AC VOLTAGE — Zero volts are showing on the
display of the GSC+ for one or more AC phases.
Proceed to Test Step 2.* AC CURRENT ~ Zero. ampotos ere showing on
the display of the GSC+ for one or more AC
phases. Proceed to Test Step 7.
Test Step 2. CHECK THE FUSES.
‘A. Check the three {uses on the AC transformer box
+ (ATB+).
Expected Result:
‘The fuses should not be open.
Results:
© OK ~ The fuses are not open. Proceed to Test
Step 3.
‘* NOT OK ~ One or mote of the fuses are open.
pair: One or more of the fuses are open. Check
for a shorted component or damaged wiring.
Troubleshoot and! repair the problem. See the
Generator Set Wiring Diagram in Testing And
Agjusting, “Schematics And Wiring Diagrams”.
‘ter the problem has been repaired, replace
the fuses,
STOP,
Test Step 3. CHECK THE GENERATOR
OUTPI
‘A. Open the circuit breaker or remove the load.
8 Start the engine and run the genset.
C. Measure the voltage between all three fuses on
the ATB+.
Expected Result:
The line to line voltage should measure the rated
votage of the genset,
Results:
* OK — The voltages are correct and the problem
remains. Proceed to Test Step 4.
"NOT OK — One or more of the voltages are NOT
const.
Repair: The wiring or the connections are
damaged. Check for damaged wiring between
the ATB+ and the bus. See the Generator
‘Set Wiring Diagram in Testing And Adjusting,
“Schematics And Wiring Diagrams”, Also, check
the electrical connections at the terminal of the
ATBs . See Testing And Adjusting, “Electrical
Connector - inspect,
‘STOP,
139
‘Troubleshooting Section
Test Step 4. CHECK THE CONNECTIONS
A, Shut down the engine,
B. Check the harness connector and the terminals,
of the ATB+
©. Check the GSC+ harness connector, See Testing
And Adjusting, "Electrical Connector - inspect”.
D. Check for one or more damaged wires between
the ATB+ and the GSC+. See the Generator
Set Wiring Diagram in Testing And Adjusting,
“Schematics And Wiring Diagrams".
Expected Result:
The wiring and the connactors should have been
‘good.
Results:
# OK — NO problem was found with the connectors
or with the wiring. Proceed to Test Step 5.
© NOT OK ~The problem was with the connectors
‘of with the wiring.
Repair: Repair the connectors or replace the
wiring hares.
STOP,
Test Ste
THE Al
‘A. Remove the GSC+ harness connector from the
ATB+.
CHECK THE OUTPUTS OF
B. At the terminal of the ATB+, measure the
resistance between the following terminals:
terminal J1-7 to terminal J1-1, terminal J1-7 to
terminal J7-2, and terminal J1-7 to terminal J1-3
Expected Result:
Each of the resistance measurements should be
7.0 + 1.0 Onms,
Results:
'* OK ~ Each of the resistance measurements is 7.0
= 1.0 Ohms. Proceed to Test Step 6.
‘* NOT OK ~ One or more of the resistance
measurements is NOT 7.0 + 1.0 Ohms.
Repair: The ATS+ has failed. Replace the ATB+.
‘See Testing and Adjusting Section, "EMCP
Electronic Control (AC Transformer Box} -
Replace’.
STOP,440
Troubleshooting Section
Test Step 6. CHECK THE INPUTS OF THE
ATB+
‘A. Remove the three fuses on the ATB#: F11, F12,
and FA3
B. At the terminal of the ATB+, measure the
resistance between the following terminals:
terminal T11 to terminal H21, terminal T12 to
terminal H21, and terminal T13 to terminal H21
Expected Result:
Each of the resistance measurements should be
4,050 100 Ohms.
Results:
* OK — Each of the resistance measurements is
4,050 + 100 Ohms.
Repair: The GSO+ may have failed, It is unlikely
that the GSC+ has failed. Exit this procedure
and perform this entire procedure again. If
the problem remains, replace the GSC+. See
Testing And Adjusting, "EMCP Electronic Control
(Generator Set) - Replace”
stop.
‘© NOT OK — One or more of the resistance
measurements was NOT 1,050 = 100 Ohms.
Repair: The ATB+ has failed. Replace the ATB+,
See Testing and Adjusting Section, “EMCP
Electronic Control (AC Transformer Box) ~
Replace”.
STOP.
Test Step 7. CHECK THE CURRENT
TRANSFORMERS
A. Shut down the engine
B. At terminals 5%, 52, and 53 of the ATB-,
disconnect only the wires that ead away from
the ATB+. These disconnected wires go to the
current transformers. These current transformers
are CT1, CT2, and CTS.
, Measure the resistance from terminal 50 to each
of the disconnected wires.
Expected Result:
‘The resistance should be approximately § Ohms.
Results:
'* OK — The resistances are approximately 5 Ohms,
‘Therefore, the current transformers are good.
Proceed to Test Step 8.
¢ NOT OK ~ One or more of the resistance
measurements are NOT correct. A related current
transformer or related wire is open.
Ropair: Replace the open current transformer or
repair the wiring. See the Generator Set Wiring
Diagram in Testing And Adjusting, “Schematics
‘And Wiring Diagrams".
STOP.
Test Step 8. CHECK THE OUTPUTS OF
THE ATB+
A. Shut down the engine.
'B. Remove the hamess connector from the GSC+
©. At the hamess connector of the GSC+ , measure
the resistance between the following contacts:
contact 4 to contact 16, contact § to contact 18,
‘and contact 6 to contact 16, Be sure to allow
each measurement to stabilize.
Expected Result:
Each of the three resistances should be 120 + 20
‘Ohms.
Results:
© OK ~ Each of the three resistances is 120 + 20
Ohms. Proceed to Test Step 10.
‘® NOT OK - One or more of the resistance
measurements are NOT correct, Proceed to Test
Step 9.
‘Test Step 9. CHECK THE GSC+ HARNESS:
CONNECTOR
‘A. Remove the GSC+ hamess from the ATB+.
B. Check the resistance of the wires in the GSC+
amass for an open wire. See the Generator
‘Sot Wiring Diagram in Testing And Adjusting,
"Schematics And Wiring Diagrams”
Expected Resutt:
‘The wires in the GSC+ hamess should measure
less than § Ohms.Repair: The ATB+ has failed. Replace the
ATB+. See the Testing and Adjusting Section,
*EMPC Electronic Control (AC Transformer Box) -
Replace”.
sToR,
* NOT OK — The wires in the GSC+ harness do
NOT measure less than 5 Ohms.
Repair: Repair the wiring or replace the GSC+
hamess. Verify that the repairs fixed the problem,
STOP.
Test Step 10. CHECK THE INPUTS OF
THE ATB+
‘A. The wires that were previously disconnected
from terminals 51, 82, and 53 will remain
disconnected. The only wires which are
comected to these terminals should lead ito
6 ATB+
B. At the terminal strip of the ATB+, measure the
resistance between the following terminals:
terminal $1 to terminal 50, terminal 52 to terminal
50, and terminal 53 to terminal 50.
Expected Result:
All the resistance measurements should read less
than 1 Ohm,
Results:
+ OK ~All the resistance measurements do read
fess than 1 Ohm,
Repair: The GSC+ may have felled. It is unlikely
that the GSC+ has failed. Exit this procedure
and perform this entire procedure again. It
{he problem remains, replace the GSC+. See
Testing And Adjusting, “EMCP Electronic Control
{Generator Set) - Replace”
STOR,
}s NOT OK - One or more of the resistance
measurements are NOT correct.
Regal: The ATB- has faled, Replace the
+. See the Testing and Adjusting Section,
*EMPC Electronic Control (AC Transformer Box) -
Replace”.
STOR,
141 :
Troubleshooting Section
Results: ‘orsronst
* OK ~The wires in the GSC+ hamess measure Display of Voltage or Current
tess than 5 Ohms. Is Zero (for MUI 3412C, 3508,
3512, 3516 and EUI and PEEC
Engines)
‘SMCS Code: 4490-035
‘S/N: 4821-Up; 1EZ1-Up
‘S/N: SKW1-Up: 1FZ1-Up
‘SIN: 6GW1-Up; 1GZ1-Up
SN: BNW1-Up; 1HZ1-Up
‘S/N: 5PW1-Up; 1JZ1-Up
‘S/N: 6WW1-Up; 1KZ1-Up-
SIN: 8TW1-Up; 1L21-Up
SIN: 8AZ1-Up; 1MZ1-Up
‘SM: 4821-Up; 3FZ1-Up
‘System Operation Description:
Zero volts or zeto amperes are snowing on the
display of the GSC+ for one or more AC phases.
‘This is showing while the genset is running and the
load is connected,142
Troubleshooting Section
: _
~ i 2
(& Jos z = 5
PO7O 7S PO}OPS }2 8 ‘®
|
be bebade
(ATBH)
AC TRANSFORMER BOX+
‘950-17 {OHASSIS.eROUNDY
(e5c-18 (RE oROUND)
‘se-8 (06 18)
ese-8 (U9 18)
osc-4 GA aN)
fescmtz «ve aM
‘scm (¥8 Om)
scm10 (uA aH
lesen)
cenggaror
Se
stration 104
‘System Schematic For An AC Transformer Box (ATB#)
‘Aye Connection Is Shown For The Generatr.
7 eG ics
When the engine-generator, or any source to
which the engine-generator Is synchronized to, Is.
‘operating, voltages up to GOOV are present in the
control panel.
Do not short these terminal with line voltage to
‘ground with any part of the body or any conduc-
tive material. Loss of Iife or injury could result
from electrical shock or injury from molten met-
al.
oo
Test Step 1. THE PROBLEM IS WITH AC
VOLTAGE OR THE PROBLEM IS WITH AC.
CURRENT.
A. Determine if the problem is with AC voltage
‘or with AC current. Check the display of the
GSC+ while the genset is running and the load
is comnected.
Results:
© AC VOLTAGE — Zero volts are showing on the
display of the GSC+ for one or more AC phases.
Proceed to Test Step 2+ AC. CURRENT ~ Zoro amperes are showing on
the display of the GSC+ for one or more AC
phases. Proceed to Test Step 7.
Test Step 2. CHECK THE FUSES.
‘A. Check the three fuses on the AC transformer box
+ (TBs).
Expected Result:
‘The luses should not be open.
Results:
© OK - The fuses are not open, Proceed to Test
Step 3.
¢ NOT OK — One or more of the fuses are open.
Repair: One or more of the fuses are open, Check
for a shorted component or damaged wiring.
Toubleshoot and repair the problem, See the
Generator Set Winng Diagram in Testing And
Adjusting, “Schematics And Wiring Diagrams"
Aer the problem has been repaired, replace
the fuses,
STOP.
Test Step 3. CHECK THE GENERATOR
outeue
‘A. Open the circuit breaker or remove the load.
B, Start the engine and run the genset.
. Measure the voltage between all three fuses on
the ATE,
Expected Result:
The line to line voltage should measure the rated
voltage of the genset.
Results:
© OK ~The voltages are correct and the problem
remains. Proceed to Test Step 4.
‘* NOT OK — One or more of the voltages are NOT
correct.
Repair: The wiring or the connections are
damaged. Check for damaged wiring between
the ATB+ and the bus. See the Generator
‘Set Wiring Diagram in Testing And Adjusting,
“Schematics And Wiring Diagrams”. Also, check
the electrical connections at the terminal of the
ATB+ . See Testing And Adjusting, "Electrical
Connector - Inspect”
STOP.
ta
‘Troubleshooting Section
Test Step 4, CHECK THE CONNECTIONS
A. Shut down the engine,
B. Check the harness connector and the terminals
of the ATB+.
©. Check the GSC+ harness connector. See Testing
And Adjusting, “Electrical Connector - Inspect’
D. Chock for one or more damaged wires between
the ATB+ and the GSC+. See the Generator
Set Wiring Diagram in Testing And Adjusting,
*Schematics And Wiring Diagrams".
Expected Result:
‘The wiring and the connectors should have been
good.
Resutts:
*¢ OK — NO problem was found with the connectors
or with the wiring. Proceed to Test Step 5.
‘* NOT OK ~The problem was with the connectors
‘or with the wiring
Repair: Repair the connectors or replace the
wiring harness.
STOP.
Test Step 5. CHECK THE OUTPUTS OF
THE ATB+
‘A. Remove the GSC+ harness connecior from the
ATB+.
B. At the terminat of the ATB+ , measure the
resistance between the following terminals:
terminal J1-7 to terminal J1-1, terminal J1-7 to
terminal J1-2, and terminal J1.7 to terminal J1-3
Expected Result:
Each of the resistance measurements should be
7.0 # 1.0 Ohms.
Results:
© OK ~ Each of the resistance measurements is 7.0,
# 1.0 Ohms. Proceed to Test Step 6.
* NOT OK - One or more of the resistance
measurements is NOT 7.0 + 1.0 Ohms.
Ropair: The ATB+ has failed. Replace the ATB+.
See Testing and Adjusting Section, “EMCP.
Electronic Control (AC Transformer Box) -
Replace”
STOP.
—144
‘Troubleshooting Section
Test Step 6. CHECK THE INPUTS OF THE
ATB+
A. Remove the three fuses on the ATB+: F11, F12,
and F13
B. At the terminal of the ATB+, measure the
resistance between the following terminals:
terminal T11 to terminal H21, terminal T12 10
terminal H21, and terminal T13 to termina) H21
Expected Result:
Each of the resistance measurements should be
4,050 + 100 Ohms.
Results:
* OK —Each of the resistance measurements is.
4,050 + 100 Ohms.
Repair: The GSC+ may have tated. It is unlikely
that the GSC+ has failed. Exit this procedure
and pertorm this entire procedure again. It
the problem remains, replace the GSC+. See
Testing And Adjusting, "EMCP Electronic Control
(Generator Set) - Replace’.
STOP,
® NOT OK - One of more of the resistance
measurements was NOT 1,050 + 100 Ohms.
Repair: The ATB+ has failed. Rep'ace the ATB+.
See Testing and Adjusting Section, “EMCP
Electronic Contro! (AC Transformer Box} -
Replace’,
stor.
Test Step 7. CHECK THE CURRENT
TRANSFORMERS
A. Shut down the engine.
B. At terminals 51, 52, and 53 of the ATB+,
disconnect only the wires that iead away from
the ATB+. These disconnected wires go to the
current transformers, These current transformers
are CT1, CT2, ang C73.
C. Measure the resistance from terminal 60 to each
of the disconnected wires.
Expected Result:
The resistance should be approximately 5 Ohms.
Results:
# OK — The resistanoas are approximately 5 Ohms.
Therefore, the current transformers are good
Proceed to Test Step &.
‘* NOT OK - One or more of the resistance
measurements are NOT correct. A related current
transformer or related wire is open.
Repair: Replace the open current transformer or
repair the wiring. See the Generator Set Wiring
Diagram in Testing And Adjusting, “Schematics
‘And Wiring Diagrams”
STOP.
Test Step 8. CHECK THE OUTPUTS OF
THE ATB+
A. Shut down the engine.
B. Remove the harness connector from the GSC+.
. At the hamess connector of the GSC+ . measure
the resistance between the following contacts:
contact 4 to contact 16, contact 5 to contact 16,
and contact 6 to contact 18. Be sure to allow
each measurement to stabilize.
Expected Result:
Each of the three resistances should be 120 + 20
Ohms.
Resul
* OK = Each of the three resistances is 120 + 20
Ohms. Proceed to Test Step 10.
‘* NOT OK ~ One or more of the resistance
measurements are NOT correct, Proceed to Test
Step 9.
Test Step 9. CHECK THE GSC+ HARNESS:
CONNECTOR
‘A. Remove the GSC+ harass from the ATB+.
B. Check the resistance of the wites in the GSC+
harness for an open wire. See the Generator
Set Wiring Diagram in Testing And. Adjusting,
“Schematics And Wiring Diagrams”.
Expected Result:
The wires in the GSC+ hamess should measure
legs than 5 Ohms.Results:
+ OK ~The wires in the GSC+ harness measure
ess than 5 Ohms.
Repair: The ATB+ has failed. Replace the
ATB+. See the Testing and Adjusting Section,
"EMPC Electronic Control (AC Transformer Box) -
Replace’.
STOR
* NOT OK - The wires in the GSC+ harness do
NOT measure less than 5 Ohms.
Repair: Repair the wiring or replace the GSC+
hamess. Verify that the repairs fixed the problem,
STOP,
Test Step 10. CHECK THE INPUTS OF
THE ATB+
‘A. The wires that were previously disconnected
from terminals 51, 52, and 53 will remain
disconnected. The only wires which are
connected to these terminals should lead into
the ATB+.
B. At the terminal strip of the ATB+, measure the
resistance between the following terminals:
terminal 51 to terminal 50, termina! 62 ta terminal
50, and terminal 53 to terminal 50.
Expected Result:
All the resistance measurements should read less
than 1 Ohm.
Results:
+ 0K — All the resistance measurements do read
less than 1 Ohm.
Repalr: The GSC+ may have failed. I is unlicely
that the GSC+ has failed. Exit this procedure.
and perform this entire procedure again. If
the problem remains, repiace the GSC+. See
Testing And Adjusting, “EMCP Electronic Controt
(Generator Set) - Replace’.
STOP.
«NOT OK - One or more of the resistance
measurements are NOT correct.
Repair: The ATB+ has failed. Replace the
AIB+. See the Testing and Adjusting Section,
“EMPC Electronic Control (AC Transformer Box) -
Replace’
STOP.
——™
Troubleshooting Section