Annexture 6.1.
Project - Façade Electrical Works
Building - WHRM-Commercial BLDG, Siemens Plot, Worli, Siemens Ltd
PO 4800168606 PO Date- 02.05.2023
Vendor - Rulka Electricals Pvt. Ltd
Type of Work Supply, Installation, Testing & Comissioning of Electrical Works for Installation of Façade lights.
Sr. NO. DESCRIPTION OF ITEM UNIT Qty
3.0 ISOLATOR
SITC of MCCB/MCB/RCBO/BUSBAR BOX/TIMER with 16G MS powder coated
enclosure, necessary busbar /spreader links, rotary handle etc complete. All
MCCB upto and including 250A shall be thermal magnetic adjustable and above
250 A shall be with microprocessor trip units. Only O/L AND S/C releases to be
given. Approval of GA Drawing By Electrical Consultants/Client is must before
fabrication. (SCOPE BY ELECTRICAL CONTRACTOR)
3.1 40 A FP 100 mA RCBO in MS Enclsoure (Near Facade Dimmer DB/Panel) (IP54) Nos 2
4.0 LIGHT FIXTURES
Installation, testing & commissioning of standard light fittings and lighting
accessories including lamp.The scope shall include, providing of all required
accessories, connectors, housing hardware mounting accessories such as
nuts,anchor fastners, bolts, screws, cleats, clamps, PVC insulated wires / cables
from Junction box to lighting fixtures, ball and socket 'arrangement with J.B.,
suspension conduit pipe for drop for flourescent fitting. All fixtures shall be with
APFC type electronic ballasts of less than 10% THD. All fixtures shall be with high
lumen output lamps. All external fixtures shall be including necessary IP65 / 66
loop in loop out junction boxes with connector and space to mount ballast in case
of non integral fixtures. Min IP rating for all external fixtures shall be IP66. For
Mounting Accessories & details Refer Document: AWA-IT Park Worli-LD-xxx.
(Lighting Fixture Zoning & Dimming Schedule)
XRW1: Exterior Recessed Wall Mounted 11W/RMT LED Wide Distribution Light 186
4.3 RMT
Fixture (Located In Facade)
XSG2: Exterior Surface Ground Mounted 12W/RMT LED Asymmetric Distribution 366
4.5 RMT
Uplight Fixture (Located In Amenity Floor)
XSW3: Exterior Surface Wall Mounted 33W LED Narrow Distribution Uplight 70
4.8 Nos
Fixture (Located in Façade Fin)
6.0 Mains Wiring & Conduiting Work
Providing
Providingand andlaying ofPVC
laying following PVC copper
insulated insulatedconductor
copper conductor 1100
1100 volt volt grade
grade
6.1 stranded flexible FRLS wire in existing raceway or PVC conduits concealed / GI
stranded flexible FRLS wires
conduits surface mounted making connections where ever required to complete
6.1.1 the
3 x installation.
1 C, 2.5 sq.Earth
mm wire shall be of Green colour or Green colour with Rmt. 500
yellow band for earthing of fixtures, outlet boxes etc
6.1.2 3 x 1 C, 1.5 sq. mm (For Ligting Automation control signal) Rmt. 500
6.2 Providingand
Providing & laying
laying GI Rigid Conduit &
of IS-9537-Part-1 - Surface installation
2 compliant I.S.I. marked screwed GI
conduit 16G thickness upto 32 mm Dia and 14G for above 32mm thickness as
per with all necessary threaded type accessories GI junction/pull boxes, G.I fish
6.2.2 wire,
25 mm fixing
dia accessories etc as required. The rates shall include chasing of walls, Rmt. 500
floors etc & plastering the chased portion as required.
SITC of PVC glands suitable for 3c x 1.5sqmm flexible PVC cable ( for 200
7.0 Nos
termination of Façade light fixture cables)
Supply, installation, testing and commissioning of following Powder Coated
1.6mm thick MS junction box with connector of 10Amps rating (IP-65) suitable for
GI Conduits & PVC glands for connection to Facade Lighting fixture complete as
8.0 Nos 100
required. Refer DWG: (M-349-TD-EL-100-FC-WB-01-CONDUIT). Minimum 2 nos
of Knockouts suiable for 25mm dia conduit shall be provided on each side of the
Junction bo x. Knockouts shall be as per site requirement
7.0 Providing and laying PVC insulated copper conductor 1100 volt grade
stranded flexible
Providing and FRLS
laying wires PVC insulated copper conductor 1100 volt grade
of following
7.1 stranded flexible
3 C, 2.5 sq. mm FRLS wire & Power)
(for Lighting cables in existing raceway or PVC conduits / GI Rmt. 500
conduits concealed / surface mounted making connections wherever required to
complete the installation. Earth wire shall be of Green colour or Green colour
LANDSCAPE BOQ
1 ELECTRICAL PANELS & DISTRIBUTION BOARDS.
Providing, Unloading at site, shifting to final location, assembling, levelling,
grouting, erecting, testing and commissioning of following Panels & External
Lighting Distribution Boards (LDBs), Double Door with canopy, IP 55 . Any sort of
fabrication work required for erection of LDBs at site shall be done by the
contractor. The contractor shall also check for all the loose joints and continuity of
the panel. Any physical or technical defects envisaged by the contractor shall be
Distribution Boards shall be fabricated (CRCA Sheet shall be of minimum 1.2 mm
thick) Out door duty IP 55, Distribution Board surface mounted / Free-stand
mounted as per the site requirements, front operated, suitable for use on
240/415Volts 1/3-phase, 3/4wire, 50Hz system, protection, complete with all
accessories Like Bus bars, Neutral Links, Proper bonding to earth Link between
the board & its hinged door, PPI Bus links ,Detachable Cable End Plates with
suitable knock outs, Spreaders, Per Phase Isolation Kits, Blank plates,
interconnections, connectors , Reversible Doors, Pre-fitted Masking Sheet, Cable
ties ,angle supports for Installations etc. Complete as per schematic drawing,
relevant standards & including all accessories as per site conditions to make the
system fully operational.
DB and Low Voltage switchgear shall comply to IS13032, IS13947, IEC61439
1.2 Providing, Installing, Testing And Commissioning of Outdoor duty IP55 Lighting
Distribution Boards (LDBs), 8 - Way PPI With:
a) 16 A FP MCB, 10 kA as Incoming
b) 16 A DP RCCB, 30 mA Leakage Current - 03 Nos.
c) 10 Amp SP MCB - 24 Nos Nos 4
d) Phase wise Timer - 3 No, Phase wise DP contactor - 3 Nos & Auto manual
selector switches - 3 Nos
2.0 LIGHT FIXTURES
Installation, testing & commissioning of light fittings and lighting
accessories including lamp for Landscape & Street lighting as follows:
The scope shall include, providing of all required accessories, connectors,
housing hardware mounting accessories such as nuts, anchor fasteners, bolts,
screws, cleats, clamps, PVC insulated wires / cables from Junction box to lighting
fixtures, ball and socket 'arrangement with J.B., suspension conduit pipe for drop
for fluorescent fitting. All fixtures shall be with APFC type electronic ballasts of
less than 10% THD. All fixtures shall be with high lumen output lamps. All external
fixtures shall be including necessary IP65 / 66 loop in loop out junction boxes with
connector and space to mount ballast in case of non integral fixtures. Min IP rating
for all external fixtures shall be IP66. For Mounting Accessories & details
Refer Documents:
1) AWA-IT Park Worli-LD100-21OCT22 - LANDSCAPE LIGHTING LAYOUT, (LD-
100)
Landscape Lighting at Ground level
2.1 XPB1: Exterior Post Top (600 mm Tall) Bollard 13 W LED Asymmetric Forward 17
Nos
Distribution Fixture
2.2 XPB2: Exterior Surface Floor Mounted Decorative Bollard (To Be Provided By The 9
Nos
Architect)
2.3 XRG5: Exterior Recessed Ground Mounted 12 W LED Wide Distribution Up light 9
Nos
Fixture (Fixture To Be Mounted In The XPB2 Decorative Fixture)
2.4 XPT1: Exterior Post Top (4000mm Tall) 1 Head 45 W LED Type II Distribution 4
Nos
Fixture
2.6 XRB4:Exterior Recessed Built-Into Steps 6.7 W/RMT LED Wide Distribution Light 80
RMT
Fixture
2.7 XRB6: Exterior Recessed Built-Into Handrail 6.7 W/RMT LED Wide Distribution 65
RMT
Light Fixture
2.10 XRG3: Exterior Recessed Ground Mounted 12 W LED Medium Distribution Up 41
Nos
light Fixture
Landscape Lighting at Podium level
2.14 UW1: 23.6
UW2: Underwater
Underwater Wall Mounted
Recessed 10W/RMT
Ground LED
Mounted 5WWide
LED Distribution Light Fixture
Diffused Distribution Upplight RMT
2.15 Fixture Nos 33
2.16
Nos 8
XPB3: Exterior Post Top (300mm Tall) Bollard 13W LED Asymmetric Forward Distribution
Fixture
2.17 XRB4: Exterior Recessed Built-Into Steps 6.7W/RMT LED Wide Distribution Light Fixture RMT 119
2.18 XRW1: 10
XSW10:Exterior
ExteriorRecessed WallMounted
Surface Wall Mounted48W4W LED
LEDAsymmetric Distribution
Narrow Distribution Light Fixture
Downlight Fixture Nos
2.21 With Snoot For Moon Light Nos 10
3 CABLES & CABLE TERMINATION
3.1 Supply, Laying, Dressing, testing & commissioning of cables as per IS:7098 Part
2:
a) 90 % cable to be laid by excavation of earth, 300 mm thick and all around the
FRLS Cables
cable, brick protection refilling, watering and ramming or providing to earth etc.
3.12 complete.
4 C, 16 sq. mm A2XFY FRLS 1.1 kV Cable (from Lighting VTPN To LDB) Rmt. 100
3.13 4 C, 2.5 sq. mm 2XWY FRLS 1.1 kV Cable (for Street Light) Rmt. 100
3.2 Cable Glanding & Terminations
Supply & Fixing Double compression Glands & making joint with necessary
3.2.2 AL./CU. crimping
4 C, 16 sq. socket
mm 2XFY (As 1.1
FRLS per kV
Cable Conductor) of long neck type connecting
Cable Nos 10
3.2.3 the
4 C, 2.5 sq. mm 2XWY FRLS 1.1 kV Cable pillar, switch, starter, motor etc. for the
same to various equipment like section 10
Nos
following sizes Crimping shall be done with use of Hydraulic Crimping tool only.
4.0 Mains Wiring & Conduiting Work
4.2 Providing & laying PVC HMS Conduit - Embedded installation as per IS
9537-
Scope:1 & 3
4.2.1 Providing
25 mm dia specified 2 mm Thick PVC HMS heavy duty Conduit and erecting as
Rigid conduit Rmt. 500
per IS 9537-3: Conduits for electrical installations, Part 2: Rigid Non-metallic
conduits / as per approved Method of Construction; on surface of wall / ceiling,
5.0 Providing, Fabricating,
etc. including Installing
entries through walls /&slabs
Handing overasofper
/ flooring Heavy duly Mild
requirement Steel
along with
Hot Dipped Galvanized Raceway
Designing, Fabricating, Providing, Loading, Unloading, Storing, Handling,
5.1 Installing
50 mm x 38 & Handing
mm Over of 16 SWG heavy duty hot dipped galvanized (65 - 70 Rmt. 50
Micron as per IS 2629) Raceway of following sizes, suspended from ceiling or
5.2 100 50
fixedmm x 38 mm
vertically on walls / columns / frame structures as per drawings, technical Rmt.
6.0 Supply, installation, testing and commissioning of following polycarbonate weather
proof junction box IP 66 / IP 67 suitable for pole mounting / underground complete
as required size 100 mm x 100 mm x 70 mm (L x B x H) with 3 way 15 Amp
connectors. (Make - Hensel or equivalent) Nos 200
8.0 Earthing System:
Providing, Installing Testing & Commissioning of Maintenance Free Complete
8.3 Earthing
Providing,System.
Installing, connecting, Testing & Commissioning Cu./GI. earthing strips
8.3.2 for interconnecting the earthing stations, panels, Light fixtures & lighting poles
8 SWG GI bare conductor RMT 100
DB's etc. in built-up trenches, on walls/ceiling, buried in ground generally as
specified and shown on drawings complete with all necessary accessories like
9.0
Providing fabricating & installing GI structural supports using 'C' channels,'I'
beams, Angles, 'Z' angles, GI sheets, plates suitable for Electrical equipment,
Panels, DBs, Bus bars, cable trays, including any other electrical installations
including necessary hardware & fasteners. 250
kg
a) All structural steel support shall be coated with at least 55 micron by hot-dip
process.
b)The joints & cuts of all MS / GI hot dipped structural supports shall be painted
with anti - corrosion paint.
Total
Other Works
1 Installation of 6 way SPN DBs Nos 58
2 Installation of 6 way TPN DBs Nos 5
3 Installation of Racks Nos 12
4 Installation of Hensel Box Nos 13
5 ITC of XSG4A type fixture at Podium façade area Nos 47
6 PITC of 25mm GI flexible Conduit with accessories Rmt 500
7 PITC of 25mm PVC flexible Conduit with accessories Rmt 500
8 Manpower
a Skilled Manpower Nos 60
b Non Skilled Nos. 120
Installation of Façade lights.
Rate Amount
0
0
2000 4000
0
0
0
300 55800
300 109800
500 35000
0
0
0
0
0
0
35 17500
0
32 16000
0
0
0
60 30000
0
200 40000
300 30000
0
0
0
30 15000
0
0
0
0
0
0
1500 6000
0
350 5950
350 3150
250 2250
400 1600
120 9600
120 7800
200 8200
0
0
120 2832
350 11550
350 2800
120 14280
150 1500
200 2000
0
0
0
0
45 4500
30 3000
0
0
0
300 3000
200 2000
0
0
0
0
0
35 17500
0
0
0
0
0
0
150 30000
0
0
0
0
0
10 1000
0
32 8000
0
0
0
700 40600
900 4500
500 6000
350 4550
200 9400
25 12500
20 10000
0
1000 60000
800 96000
745162