Energy Metering & Monitoring Solutions

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Topics covered

  • Dimmers,
  • Ventilation Control,
  • Safety Features,
  • Installation,
  • kWh Meters,
  • Screw Terminals,
  • Digital Time Switches,
  • Push Buttons,
  • Thermostats,
  • Specifications
0% found this document useful (0 votes)
65 views64 pages

Energy Metering & Monitoring Solutions

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Topics covered

  • Dimmers,
  • Ventilation Control,
  • Safety Features,
  • Installation,
  • kWh Meters,
  • Screw Terminals,
  • Digital Time Switches,
  • Push Buttons,
  • Thermostats,
  • Specifications

Modular Devices

& Connection
Dimmers, time switches, meters and thermostats are among our varied
range of devices, and they can all be perfectly housed in our expansive
range of enclosures to tailor a building’s energy to an individual’s style.
It’s just like a home, miniaturised.

2.1
02 Page

Devices

Metering & Monitoring 2.3

Switching 2.7

Contactors 2.14

Relays 2.20

Push Buttons 2.23

Indication 2.24

Timers 2.26

Connection

Modular Devices
& Connection
Insulated Busbars 2.31

Distribution Blocks 2.32

Junction Blocks 2.33

Screw Terminals 2.34

Brass Terminals 2.39

Quick Connect & Cage Terminals 2.41

Technical Pages 2.43

The relevant part of the BS EN 61439 series applies to the integration of mechanical and electrical components (switching devices, control devices, busbars,
functional units, etc.), into an enclosure. Hager systems such as consumer unit, distribution board and panel board ranges are certified to the appropriate part
of the BS EN 61439 series. When selecting other device / enclosure arrangements, please contact Hager technical support for guidance - 01 8835844.

2.2
Metering & Monitoring
kWh Meters

Single Phase kWh Meters

Description:
- Energy meters are used to measure the active energy consumed by an installation. They allow the user to understand the
real cost of an installation and to identify the consumption between the different loads.
Characteristics:
- Complies with EN 50470-3.
- Class B
- Energy readout: 7 digits.
- Backlit display.
- Indication of instantaneous power consumption.
- Total / partial counter.
ECN140D - Storage of energy values.
- LED flashes according to consumption.
- Display indication in case of incorrect wiring.
- Voltage 230V a.c. 50Hz.
- Direct connection.
- Current = 40A.

Note:
Modular Devices

- Use of heat dissipation inserts (cat ref. LZ060) are recommended on each side of direct connection meters.
& Connection

Width
Description (1 Mod =17.5mm) Cat ref.
Total counter, non resettable counter 1 Mod ECN140D

Single Phase kWh Meters - Direct 40A & 80A

Description:
- Energy meters are used to measure the active energy consumed by an installation. They allow the user to understand and
control the real cost of an installation and to divide the consumption between the different loads.

Characteristics:
- Fully compliant with the European standard EN 50470-3.
- Class B
- Accuracy ±1%.
- Energy readout: 7 digits.
- Backlit display.
ECP140D - Indication of instantaneous power consumption.
- Total / partial counter.
- Unlimited saving of measurements.
- LED flashes according to consumption.
- Tariff 1/ tariff 2 options.
- Display indication in case of incorrect wiring.
- Voltage 230V a.c. 50/60Hz.
- Max cable size = 16mm.
- MID approved.
SMC120R - Pulsed output/modbus available.
- Sealable terminal cover.

Note:
- Use of heat dissipation inserts (cat ref. LZ060) are recommended on each side of direct connection meters.
Width
Description (1 Mod =17.5mm) Cat ref.
Single phase kWh meter direct 40A MID SO 1 Mod ECP140D
Single phase kWh meter direct 40A MID Modbus 1 Mod ECR140D
Single phase kWh meter direct 80A MID SO 2 Mod ECP180D
Single phase kWh meter direct 80A MID Modbus 2 Mod ECR180D
120 Ohm end resistor for Modbus RTU - SMC120R

Single Phase kWh Meters - Multi Tarriff

Width
Description (1 Mod =17.5mm) Cat ref.
Single phase kWh meter direct 3 x 80A SO 4 Mod ECP180T
Single phase kWh meter direct 3 x 80A Modbus 4 Mod ECR180T
120 Ohm end resistor for Modbus RTU - SMC120R

ECP180T

2.3 Data is subject to errors and technical modifications.


Metering & Monitoring
kWh Meters

Three Phase kWh Meters - Direct

Description:
- Energy meters are used to measure the active energy consumed by an installation. They allow the user to understand and
control the real cost of an installation and to divide the consumption between the different loads.
Characteristics
- Fully compliant with the European standard EN 50470-3
- Class B
- Accuracy ±1%
- Energy readout: 7 digits
- Backlit display
- Indication of instantaneous power consumption
- MID approved ECP380D
- Pulsed output/modbus available
- Unlimited saving of measurements
- LED flashes according to consumption
- Option: tariff 1/ tariff 2
- Three phase energy meters are adapted to all kind of networks
- Display indication in case of incorrect wiring
- Voltage 230/400V a.c. 50/60Hz

Modular Devices
- Operating Current: 250mA to 125A

& Connection
- Max cable size = 16mm
- Sealable terminal cover.

Note:
- Use of heat dissipation inserts (cat ref. LZ060) are recommended on each side of direct connection meters.

Width
Description (1 Mod =17.5mm) Cat ref.
Three phase kWh meter direct 80A MID SO 4 Mod ECP380D
Three phase kWh meter direct 80A MID Modbus 4 Mod ECR380D
Three phase kWh meter direct 125A MID SO 6 Mod ECP310D
Three phase kWh meter direct 125A MID Modbus 6 Mod ECR310D
120 Ohm end resistor for Modbus RTU - SMC120R

Data is subject to errors and technical modifications. 2.4


Metering & Monitoring
kWh Meters

Three Phase kWh Meters - Connection via Current Transformers

Description:
- Energy meters are used to measure the active energy consumed by an installation. They allow the user to understand and
control the real cost of an installation and to divide the consumption between the different loads.
Characteristics
- Fully compliant with the European standard EN 50470-3
- Class B
- Accuracy ±1%
- Energy readout: 7 digits
- Backlit display
- Indication of instantaneous power consumption
ECP300C - MID approved
- Pulsed output/modbus available
- Unlimited saving of measurements
- LED flashes according to consumption
- Option: tariff 1/ tariff 2
- Three phase energy meters are adapted to all kind of networks
- Display indication in case of incorrect wiring
- To be connected to CT with 5A on the secondary
Modular Devices

- Voltage 230/400V a.c. 50/60Hz


& Connection

- Starting current = 1mA


- Max current on CT secondary = 6A
- Sealable terminal cover

Note:
- Use of heat dissipation inserts (cat ref. LZ060) are recommended on each side of direct connection meters.

Width
Description (1 Mod =17.5mm) Cat ref.
Three phase kWh meter via CT, 1A or 5A, MID SO 4 Mod ECP300C
Three phase kWh meter via CT, 1A or 5A, MID Modbus 4 Mod ECR300C
120 Ohm end resistor for Modbus RTU - SMC120R

KNX Interface for Energy Meters

Description:
- The KNX interface for TXF121 energy meters allows remote reading of data and values from single phase and three phase
hager energy meters.

Width
Description (1 Mod =17.5mm) Cat ref.
KNX Interface for Energy Meter 1 Mod TXF121

TXF121

2.5 Data is subject to errors and technical modifications.


Metering & Monitoring
Current Transformers

Current Transformers (CT)

Characteristics:
- Current transformers are used to feed analogue and digital ammeters and kilowatt hour meters.
- The current on the secondary circuit (0 - 5A) is proportional to the current on primary circuit class: 1.
- Suitable for use with copper bar or cable.
- Can be mounted on a DIN rail (up to 600A CT).
- For complete list of dimensions see page 2.44.

Description Ratio Cat ref.


DIN Rail Mountable CT, 50A 50:5 SRA00505
DIN Rail Mountable CT, 100A 100:5 SRA01005 SRA00505
DIN Rail Mountable CT, 150A 150:5 SRA01505
DIN Rail Mountable CT, 200A 200:5 SRA02005
DIN Rail Mountable CT, 250A 250:5 SRA02505
DIN Rail Mountable CT, 300A 300:5 SRI03005
DIN Rail Mountable CT, 400A 400:5 SRC04005

Modular Devices
& Connection
DIN Rail Mountable CT, 600A 600:5 SRC06005
CT, 800A 800:5 SRD08005
CT, 1000A 1000:5 SRD10005
CT, 1500A 1500:5 SRD15005
CT, 2000A 2000:5 SRE20005
DIN Rail Mounting for CTs up to 600A. - SRZH01

Data is subject to errors and technical modifications. 2.6


Switching
Switch Disconnectors

Switch Disconnectors

- For use as a switch disconnector in all types of circuits.


- Complies with: IEC 60947-3 for all ratings and to EN60669 for ratings from 16A to 63A
Features
- All switches have a green / red indication on the toggle giving positive contact indication.
Technical data
- Utilisation category AC22A 230V / 400V
- In: 16A to 32A frame size 1. Connection capacity: 16mm² - rigid conductor, 10mm² - flexible conductor
- In: 32A to 63A frame size 2. Connection capacity: 25mm² - rigid conductor, 16mm² - flexible conductor
- In: 63A to 125A frame size 3. Connection capacity: 50mm² - rigid conductor, 35mm² - flexible conductor

SBN140
Description Frame size Mod. width Pack qty. Cat ref.
Single pole switch disconnectors
1 x 16A - 230V AC 1 1 12 SBN116
1 x 25A - 230V AC 1 1 12 SBN125
1 x 32A - 230V AC 1 1 12 SBN132
Modular Devices

1 x 32A* - 230V AC 2 1 12 SBN133


& Connection

1 x 40A - 230V AC 2 1 12 SBN140


1 x 63A - 230V AC 2 1 12 SBN163
1 x 63A* - 230V AC 3 1 12 SBN164
1 x 80A - 230V AC 3 1 12 SBN180
1 x 100A - 230V AC 3 1 12 SBN190
1 x 125A - 230V AC 3 1 12 SBN199

Description Frame size Mod. width Pack qty. Cat ref.


Double pole switch disconnectors
2 x 16A - 230V AC 1 1 12 SBN216
2 x 25A - 230V AC 1 1 12 SBN225
2 x 32A - 230V AC 1 1 12 SBN232
2 x 32A* - 230V AC 2 2 6 SBN233
2 x 40A - 400V AC 2 2 6 SBN240
2 x 63A - 400V AC 2 2 6 SBN263
2 x 63A* - 400V AC 3 2 6 SBN264
2 x 80A - 400V AC 3 2 6 SBN280
SBN240
x 2 x 100A - 400V AC 3 2 6 SBN290
2 x 125A - 400V AC 3 2 6 SBN299

Description Frame size Mod. width Pack qty. Cat ref.


Three pole switch disconnectors
3 x 16A - 400V AC 1 2 6 SBN316
3 x 25A - 400V AC 1 2 6 SBN325
3 x 32A - 400V AC 1 2 6 SBN332
3 x 32A* - 400V AC 2 3 4 SBN333
3 x 40A - 400V AC 2 3 4 SBN340
3 x 63A - 400V AC 2 3 4 SBN363
3 x 63A* - 400V AC 3 3 4 SBN364
3 x 80A - 400V AC 3 3 4 SBN380
SBN340
3 x 100A - 400V AC 3 3 4 SBN390
3 x 125A - 400V AC 3 3 4 SBN399

Description Frame size Mod. width Pack qty. Cat ref.


Four pole switch disconnectors
4 x 16A - 400V AC 1 2 6 SBN416
4 x 25A - 400V AC 1 2 6 SBN425
4 x 32A - 400V AC 1 2 6 SBN432
4 x 32A* - 400V AC 2 4 3 SBN433
4 x 40A - 400V AC 2 4 3 SBN440
4 x 63A - 400V AC 2 4 3 SBN463
4 x 63A* - 400V AC 3 4 3 SBN464
4 x 80A - 400V AC 3 4 3 SBN480
SBN440
4 x 100A - 400V AC 3 4 3 SBN490
4 x 125A - 400V AC 3 4 3 SBN499

2.7 Data is subject to errors and technical modifications.


Switching
Switch Disconnectors

Switch Disconnectors

- For use as a switch disconnector in all types of circuits.


- Complies with: IEC 60947-3 for all ratings and to EN60669 for ratings from 16A to 63A.
Features
- All switches have a green / red indication on the toggle giving positive contact indication.
Technical data
- Utilisation category AC22A 230V / 400V
- In: 16A to 32A frame size 1.
- Connection capacity: 16mm² - rigid conductor, 10mm² - flexible conductor
- In: 32A to 63A frame size 2.
- In: 80A to 125A frame size 3.
- Connection capacity: 50mm² - rigid conductor, 35mm² - flexible conductor SBR163

Description Frame size Mod. width Pack qty. Cat ref.


Single pole switch disconnectors
1 x 40A - 230V AC 2 1 12 SBR140
1 x 63A - 230V AC 2 1 12 SBR163

Modular Devices
1 x 80A - 230V AC 3 1 12 SBR180

& Connection
1 x 100A - 230V AC 3 1 12 SBR190
1 x 125A - 230V AC 3 1 12 SBR199

Description Frame size Mod. width Pack qty. Cat ref.


Double pole switch disconnectors
2 x 40A - 400V AC 2 2 6 SBR240
2 x 63A - 400V AC 3 2 6 SBR263
2 x 80A - 400V AC 3 2 6 SBR280
2 x 100A - 400V AC 3 2 6 SBR290
2 x 125A - 400V AC 3 2 6 SBR299

SBR263

Description Frame size Mod. width Pack qty. Cat ref.


Three pole switch disconnectors
3 x 40A - 400V AC 2 3 4 SBR340
3 x 63A - 400V AC 2 3 4 SBR363
3 x 80A - 400V AC 3 3 4 SBR380
3 x 100A - 400V AC 3 3 4 SBR390
3 x 125A - 400V AC 3 3 4 SBR399

SBR399

Description Frame size Mod. width Pack qty. Cat ref.


Four pole switch disconnectors
4 x 63A - 400V AC 2 4 3 SBR463
4 x 100A - 400V AC 3 4 3 SBR490
4 x 125A - 400V AC 3 4 3 SBR499

SBR499

Data is subject to errors and technical modifications. 2.8


Switching
Switch Disconnectors with Indicator Light

Switch Disconnectors with Indicator Light

- For use as a switch disconnector in all types of circuits.


- Complies with:
- IEC 60947-3 and EN60669
Features
- Orange LED indicator light.
- LED life time: 100 000 h.
- All switches have a green / red indication on the toggle giving positive contact indication
Technical data
- Utilisation category AC22A 230V / 400V
- In: 16A to 32A frame size 1.
SBT116 - Connection capacity: 16mm² - rigid conductor, 10mm² - flexible conductor

Description Frame size Mod. width Pack qty. Cat ref.


Single pole switch disconnectors with indicator light top
1 x 16A - 230V AC 1 1 12 SBT116
1 x 25A - 230V AC 1 1 12 SBT125
Modular Devices

1 x 32A - 230V AC 1 1 12 SBT132


& Connection

Description Frame size Mod. width Pack qty. Cat ref.


Single pole switch disconnectors with indicator light bottom
1 x 16A - 230V AC 1 1 12 SBB116
1 x 25A - 230V AC 1 1 12 SBB125
1 x 32A - 230V AC 1 1 12 SBB132

Description Frame size Mod. width Pack qty. Cat ref.


Double pole switch disconnectors with indicator light top
2 x 16A - 230V AC 1 1 12 SBT216
2 x 25A - 230V AC 1 1 12 SBT225
2 x 32A - 230V AC 1 1 12 SBT232

Description Frame size Mod. width Pack qty. Cat ref.


Double pole switch disconnectors with indicator light bottom
2 x 16A - 230V AC 1 1 12 SBB216
2 x 25A - 230V AC 1 1 12 SBB225
2 x 32A - 230V AC 1 1 12 SBB232

Description Frame size Mod. width Pack qty. Cat ref.


Double pole switch disconnectors with indicator light top & bottom
2 x 16A - 230V AC 1 1 12 SBM216
2 x 25A - 230V AC 1 1 12 SBM225
2 x 32A - 230V AC 1 1 12 SBM232

2.9 Data is subject to errors and technical modifications.


Switching
Auxiliaries & Accessories

Auxiliaries & Accessories

Auxiliary contact
- The auxiliary contact is common to the whole range of switch disconnectors from 16A to 125A with or without indicator light
Features
- The auxiliary contact have a mechanical indicator to show the position of the contact
Technical data
- Utilisation category AC12A 230V / 400V
- Connection capacity: 10mm² - rigid conductor, 6mm² - flexible conductor
Sealable terminal shrouds
- The sealable terminal shrould is compatible with switch disconnectors ratings from 32A to 63A frame size 2.
- For ratings from 63A to 125A frame size 3 switch disconnector, only the disible part is compatible to protect the front screw
heads. ESC080
Phase barrier shield
- The phase barrier shield is compatible with switch disconnectors ratings ratings from 32A to 125A frame size 2&3.
Padlocking kit
- Allows to lock the device in the OFF and ON positions.
- Will accept two padlocks with hasps of 4.75mm diameter max. (supplied without padlock).

Modular Devices
Description Mod. width Pack qty. Cat ref.

& Connection
Auxiliary contact 1NO + 1NC
Compatible with disconnector switches from 16 to 125A 0.5 1 ESC080

Description Pack qty. Cat ref.


Terminal shroud Compatible with switch disconnector from 32A to 63A frame size 2
To shroud the connection terminal and screws. The screw cover can be sealed. 4 MZN120

MZN120

Description Pack qty. Cat ref.


Phase barrier shield
Phase barrier shield 3 MZN121

MZN121

Description Pack qty. Cat ref.


Padlocking kit
Padlocking kit 2 MZN175

MZN175

Data is subject to errors and technical modifications. 2.10


Switching
Changeover Switches

Switch Disconnectors

- For use as a switch disconnector in all types of circuits.


- Complies with: IEC 60947-3 for all ratings and to EN60669 for ratings from 16A to 63A
Technical data
- Utilisation category AC22A 230V / 400V
- In: 16A to 40A frame size 1.
- Connection capacity: 16mm² - rigid conductor, 10mm² - flexible conductor

Description Frame size Mod. width Pack qty. Cat ref.


Centre OFF changeover switch I-0-II and common point on top
SFT232 1 x 25A - 230V AC 1 1 12 SFT125
1 x 32A - 230V AC 1 1 12 SFT132
1 x 40A - 230V AC 1 1 12 SFT140
2 x 25A - 230V AC 1 2 6 SFT225
2 x 32A - 230V AC 1 2 6 SFT232
2 x 40A - 230V AC 1 2 6 SFT240
Modular Devices
& Connection

3 x 40A - 400V AC 1 3 4 SFT340


4 x 40A - 230V AC 1 4 3 SFT440

Description Frame size Mod. width Pack qty. Cat ref.


Centre OFF changeover switch I-0-II and common point on bottom
1 x 16A - 230V AC 1 1 12 SFB116
1 x 25A - 230V AC 1 1 12 SFB125
1 x 32A - 230V AC 1 1 12 SFB132
2 x 16A - 230V AC 1 2 6 SFB216
2 x 25A - 230V AC 1 2 6 SFB225
2 x 32A - 230V AC 1 2 6 SFB232

SFB125

Description Frame size Mod. width Pack qty. Cat ref.


Changeover switch I-II and common point on top
1 x 25A - 230V AC 1 1 12 SFH125
1 x 32A - 230V AC 1 1 12 SFH132
2 x 25A - 230V AC 1 2 6 SFH225
2 x 32A - 230V AC 1 2 6 SFH232

SFH125

Description Frame size Mod. width Pack qty. Cat ref.


Changeover switch I-II and common point on bottom
1 x 16A - 230V AC 1 1 12 SFL116
1 x 25A - 230V AC 1 1 12 SFL125
1 x 32A - 230V AC 1 1 12 SFL132
2 x 16A - 230V AC 1 2 6 SFL216
2 x 25A - 230V AC 1 2 6 SFL225
2 x 32A - 230V AC 1 1 6 SFL232

Description Frame size Mod. width Pack qty. Cat ref.


Changeover switch I-II
1 x 25A - 230V AC 1 1 12 SFM125
1 x 32A - 230V AC 1 1 12 SFM132

Description Cat ref.


Centre-off changeover double pole
2 pole changeover switch 63A I-0-II SF263

2.11 Data is subject to errors and technical modifications.


Switching
Light Sensitive Switches

Light Sensitive Switch

Characteristics
- A photo-electric cell measures the light level and in conjunction with the relay provides on/off control of a circuit.
- This device controls lighting circuits in relation to ambient light, based on user settings.
- Sealable front cover.
- Outputs: 1 changeover AC1 contact 16A - 230V a.c.
- Maximum distance: 50m between photocell and controller
Application Example:
- Street lighting, display lighting, illuminated signs etc.
Connection
- Capacity: Rigid: 1.5 to 10mm², Flexible: 1 to 6mm².
- On board LED shows status of changeover contact. EEN100
Technical Data
- 4 position override switch allowing: auto, on, off, test
- 2 sensitivity ranges: 5 to 50 lux, 50 to 2000 lux.
- Supplied with a separate surface-mounted photo-electric cell EE003.
- Must be used in conjunction with a suitably rated contactor where load conditions demand.
- For technical data, see page 2.47.

Modular Devices
& Connection
Width
Description (1 Mod =17.5mm) Cat ref.
Light Sensitive SwitchEFMJWFSFEXJUIBTFQBSBUFTVSGBDFQIPUPFMFDUSJDDFMM&&/ 1 Mod EEN100
Light Sensitive Switch - delivered with: a separate GMVTI photo electric cell EEN00 1 Mod EEN101
Two Channels Light Sensitive Switch EE200
Two Channels Light Sensitive Switch EE200 delivered with surface cell EE003 EE201
Two Channels Light Sensitive Switch for Cascading EE202
Two Chnls. Light Sens. Sw. for Cascading EE202 delivered with surface cell EEN003 EE203
Compact light switch IP 55 / integrated cell, basic 8A (without settings) EE701
Compact light switch IP 55 / integrated cell, enhanced 16A (with settings) EE702

Light Sensitive Programmer

Characteristics
- To control the lighting installation in relation to time and ambient light.
- A weekly programmer associated with a light sensitive switch.
- Outputs: 1 changeover AC1 contact 16A - 230V a.c.
- Maximum distance: 50m between photocell and controller.
Working Principle
- The user programmes both on/off periods and a desired light level. The cell measures the light level within the on period.
Depending on the light level (below or above the programmed threshold) the output will be switched on/off.
- 20 program steps, 1 minute switching increments.
Programming Function
- Programming by keys and display on LCD screen. EE171
- On/off override facility, permanent working.
- Display and control of the programme.
- Test setting for easy adjustment.
- 2 sensitivity ranges: 5 to 50 lux, 50 to 2000 lux.
- Supplied with a separate surface-mounted photo-electric cell EE003.
- Must be used in conjunction with a suitably rated contactor where load conditions demand.
- For technical data, see page 2.47.

Description Width Cat ref.


Light Sensitive Programmer with Surface Cell 3 Mod EE110
Light Sensitive Programmer 3 Mod EE171

Astronomical Time Switch

Characteristics
- Astronomical time switches must be used in conjunction with a suitable rated contactor. Weekly cycle. Delivered with key
EG005. Protected cable clamps capacity: rigid : 1.5 to 10mm2, flexible : 1 to 6mm2

Description Cat ref.


1 Channel 230V~50 Hz, Changeover Contact 16A AC1, Operating Reserve Lithium Battery 5 years EE180
2 Channels 230V~50 Hz, 2 Changeover Contacts 16A AC, Operating Reserve Lithium Battery 5 years EE181
EE180

Replacement Photo Electric Cell

Description For Cat ref. Pack qty. Cat ref.


Flush-mounted Photo Electric Cell EEN100, EE171 1 EE002
Surface-mounted Photo Electric Cell EEN100, EE171 1 EE003

Data is subject to errors and technical modifications. 2.12


Switching
Universal Dimmers

Universal Dimmers

EVN011 EVN012 EVN002 EVN004 EV100 EV102 EV106 EV108


Supply voltage 230 V +/- 10 %
Frequency 50/60 Hz 50 Hz
Load consumption 0,2 W 3W
Load control type direct through dimmer
Remote power 300 W 500 W 20 to 1000 W contact 10A - 230V
Compatible load types :
- Incandescent 230 V 300 W 500 W 1000 W -
EVN011 - Halogen 230 V 300 W 500 W 1000 W -
- VLV halogen with transformer 300 VA 500 VA 1000 VA -
- Dimmable fluocompact 60 W 100 W - -
- Fluocompact & LED not dimmable - - - -
- Dimmable LED 230 V 60 W 100 W - -

1/10 V control - 1 input 1 input/ 1 output


Modular Devices

output
& Connection

1/10 V control status - slave slav./mast. master


I max. authorized for PB light 5 mA - 5 mA -
max. PB-dimmers distance 50 m
or 1-10 V control
EVN004 dim PB and ON/OFF on module no yes
Number of preset lighting levels - 1 - 2 - 3
Preset lighting levels control entry - 1 - 2 - 2
Min. and max. dim lighting setting - yes
On/Off status indication output - 1 contact O -
Values digital display - yes
Max. power dissipation 2,1 W 4,5 W 15 W 6W
IP IP 20
Operating temperature - 10°C to + 45°C
EV100 Storage temperature - 25°C to + 70°C - 20°C to + 60°C
Rigid connection 1,5 to 6 mm2 1,5 to 10 mm2
Flexible connection 1 to 6 mm2 1 to 6 mm2

Characteristics
- Controls the lighting level of all types of light source: incandescent, LV halogen, ELV halogen with electronic or ferromagnetic
transformer, LED lamps, ELV LED lamps with electronic transformer, fluorescent with electronic ballast.
- The EVN 300W and 500W dimmers also allow lighting level adjustment for dimmable CFL and dimmable LED lamps.
- Dimming controlled by push button: start / stop by short press, increasing / decreasing by maintaining pressure.
- Automatic load recognition.
- Soft start (progressive start) to increase the working life of lamps.
EV108 - Remembers previous dimming level.
- Protection against overheating.
- 3 modes for load learning: auto, advanced, expert (comfort version).
- Can replace a latching relay, with light level function.
- Push button (line or neutral).
- Comfort version includes scene setting by two short presses on the push button, progressive switch-off & night light.

Width
LZ060 Description (1 Mod =17.5mm) Pack qty. Cat ref.
300W Standard Version 1 Mod 1 EVN011
300W Comfort Version 1 Mod 1 EVN012
500W Standard Version 2 Mod 1 EVN002
500W Comfort Version 2 Mod 1 EVN004
1000W Standard Version 5 Mod 1 EV100
1000W Advanced Version 5 Mod 1 EV102
1/10V Pilot Dimmer Standard Version 4 Mod 1 EV106
1/10V Pilot Dimmer Advanced Version 4 Mod 1 EV108
Heat Dissipation Insert 0.5 Mod 12 LZ060

2.13 Data is subject to errors and technical modifications.


Contactors
Overview

Description 230V 110/127V


Standard Contactors Hum-free Contactors Standard Contactors
1 Normally Open ESC125 (25A-250V)
1 Normally Closed ESC126 (25A-250V)
2 Normally Open ESC225 (25A-250V) ESC225S (25A-250V) ESM225 (25A-250V)
ESC240 (40A-440V) ESC240S (40A-440V)
ESC263 (63A-440V) ESC263S (63A-440V)
2 Normally Closed ESC226 (25A-250V)
ESC241 (40A-440V)
ESC264 (63A-440V)

1 NO & 1 NC ESC227 (25A-250V) ESM227 (25A-250V)


3 Normally Open ESC325 (25A-440V) ESC325S (25A-440V)
ESC340 (40A-440V) ESC340S (40A-440V)
ESC363 (63A-440V) ESC363S (63A-440V)
4 Normally Open ESC425 (25A-440V) ESC425S (25A-440V) ESM440 (40A-440V)

Modular Devices
ESC440 (40A-440V) ESC440S (40A-440V)

& Connection
ESC463 (63A-440V) ESC463S (63A-440V)
4 Normally Closed ESC426 (25A-440V) ESC426S (25A-440V)
ESC441 (40A-440V)
ESC464 (63A-250V)
2 NO & 2 NC ESC427 (25A-440V) ESC427S (25A-440V)
ESC442 (40A-250V)
ESC465 (63A-440V)
3 NO & 1 NC ESC428 (25A-440V) ESC428S (25A-440V)
ESC443 (40A-440V)
ESC466 (63A-440V)

Description 24V 12V 8/12V


Standard Contactors Hum-free Contactors Standard Contactors Hum-free Contactors Standard Contactors

1 Normally Open ESD125 (25A-250V) ESL125 (25A-250V)


1 Normally Closed
2 Normally Open ESD225 (25A-250V) ESD225S (25A-250V) ESL240 (40A-440V) ESL225S (25A-250V) ESL225 (25A-250V)
ESD240 (40A-440V) ESD240S (40A-440V) ESL263 (63A-440V) ESL240S (40A-440V)
ESD263 (63A-440V) ESD263S (63A-440V) ESL263S (63A-440V)
2 Normally Closed ESD226 (25A-250V) ESL241 (40A-440V) ESL226 (25A-250V)
ESD241 (40A-440V) ESL264 (63A-440V)
ESD264 (63A-440V)

1 NO & 1 NC ESD227 (25A-250V) ESL227 (25A-250V)


3 Normally Open ESD325S (25A-440V)
4 Normally Open ESD425 (25A-440V) ESD425S (25A-440V) ESL425 (25A-440V) ESL425S (25A-440V)
ESD440 (40A-440V) ESD440S (40A-440V) ESL440 (40A-440V) ESL440S (40A-440V)
ESD463 (63A-440V) ESD463S (63A-440V) ESL463 (63A-440V) ESL463S (63A-440V)
4 Normally Closed ESD426 (25A-250V) ESD426S (25A-440V) ESL426 (25A-440V) ESL426S (25A-440V)
ESD464 (63A-250V)
2 NO & 2 NC ESD427 (25A-440V) ESD427S (25A-440V) ESL427 (25A-440V) ESL427S (25A-440V)
3 NO & 1 NC ESD428 (25A-440V) ESD428S (25A-440V) ESL428 (25A-440V) ESL428S (25A-440V)

Data is subject to errors and technical modifications. 2.14


Contactors
Contactors

Contactors

- Contactors are essential powerdevices to control heating, lighting or ventilation systems.


- They are recommended in association with control and energy management devices (thermostats, delay timers,
programmers...)
- Standard 1 module and 2 module versions are recommended for applications where a reduced consumption and heating
dissipation are needed.
- Complies to IEC 61095.
- The contactors can be associated with the auxiliary contact ESC080 for remote signalling.
- It is recommended to use a heat dissipation insert LZ060 between each 3 products.

Coil AC In power circuit


ESC225 Description Type 50 Hz AC7-a / AC1 Width Pack qty. Cat ref.
Contactor 1NO 230 V 25A-250V 1 Mod 12 ESC125
24V 25A-250V 1 Mod 1 ESD125
8/12V 25A-250V 1 Mod 1 ESL125

1NC 230V 25A-250V 1 Mod 1 ESC126


Modular Devices
& Connection

2NO 230V 25A-250V 1 Mod 12 ESC225


40A-440V 3 Mod 1 ESC240
63A-440V 3 Mod 1 ESC263

ESD263 2NO 24V 25A-250V 1 Mod 12 ESD225


40A-440V 3 Mod 1 ESD240
63A-440V 3 Mod 1 ESD263

2NO 12V 40A-440V 3 Mod 1 ESL240


63A-440V 3 Mod 1 ESL263

2NO 8/12V 25A-250V 1 Mod 1 ESL225

2NO 110/127V 25A-250V 1 Mod 1 ESM225

2NC 230V 25A-250V 1 Mod 12 ESC226


ESC325
40A-440V 3 Mod 1 ESC241
63A-440V 3 Mod 1 ESC264

2NC 24V 25A-250V 1 Mod 1 ESD226


40A-440V 3 Mod 1 ESD241
63A-440V 3 Mod 1 ESD264

2NC 12V 40A-440V 3 Mod 1 ESL241


63A-440V 3 Mod 1 ESL264

2NC 8/12V 25A-250V 1 Mod 1 ESL226


ESC425

1NO+1NC 230V 25A-250V 1 Mod 12 ESC227


24V 25A-250V 1 Mod 1 ESD227
8/12V 25A-250V 1 Mod 1 ESL227
110/127V 25A-250V 1 Mod 1 ESM227

3NO 25A-440V 2 Mod 6 ESC325


40A-440V 3 Mod 4 ESC340
63A-440V 3 Mod 1 ESC363

4NO 230 V 25A-440V 2 Mod 6 ESC425


ESC463
40A-440V 3 Mod 4 ESC440
63A-440V 3 Mod 4 ESC463

4NO 24V 25A-440V 2 Mod 2 ESD425


40A-440V 3 Mod 3 ESD440
63A-440V 3 Mod 3 ESD463

2.15 Data is subject to errors and technical modifications.


Contactors
Contactors

Coil AC In power circuit


Description Type 50 Hz AC7-a / AC1 Width Pack qty. Cat ref.
Contactor 4NO 12 V 25A-250V 2 Mod 1 ESL425
40A-440V 3 Mod 1 ESL440
63A-440V 3 Mod 1 ESL463

4NO 110/127V 40A-440V 3 Mod 1 ESM440

4NC 230V 25A-440V 2 Mod 1 ESC426


40A-440V 3 Mod 1 ESC441
63A-250V 3 Mod 1 ESC464

4NC 24V 25A-250V 2 Mod 1 ESD426


63A-250V 3 Mod 1 ESD464

Modular Devices
4NC 12V 25A-440V 2 Mod 1 ESL426

& Connection
2NO+2NC 230V 25A-440V 2 Mod 1 ESC427
40A-440V 3 Mod 1 ESC442
63A-440V 3 Mod 4 ESC465

2NO+2NC 24V 25A-440V 2 Mod 1 ESD427

2NO+2NC 12V 25A-440V 2 Mod 1 ESL427

3NO+1NC 230V 25A-440V 2 Mod 6 ESC428


40A-440V 3 Mod 4 ESC443
63A-440V 3 Mod 1 ESC466

3NO+1NC 24V 25A-440V 2 Mod 1 ESD428

3NO+1NC 12V 25A-440V 2 Mod 1 ESL428

Data is subject to errors and technical modifications. 2.16


Contactors
Hum-free Contactors

Hum-free Contactors

- Contactors are essential power devices to control heating, lighting or ventilation systems.
- They are recommended in association with other control and energy management devices (thermostats, delay timers,
- programmers...)
- The hum-free versions are recommended for housing applications where silent operating is requested.
- Complies to IEC 61095.
- The contactors can be associated with the auxiliaries contact ESC080 for remote signaling, except the ESx225S.
- It is recommended to use a heat dissipation insert LZ060 between each product.

Coil AC In power circuit


Description Type 50 Hz AC7-a / AC1 Width Pack qty. Cat ref.
ESC225S Hum-free contactor 2NO 230 V 50/60 Hz 25A-250V 1 Mod 12 ESC225S
220V DC
40A-440V 3 Mod 4 ESC240S
63A-440V 3 Mod 4 ESC263S

2NO 24V 50Hz 25A-250V 1 Mod 1 ESD225S


Modular Devices

24V DC
& Connection

40A-440V 3 Mod 1 ESD240S


63A-440V 3 Mod 1 ESD263S

2NO 12V 50Hz 25A-250V 1 Mod 1 ESL225S


12V DC
ESC425S 40A-440V 3 Mod 1 ESL240S

63A-440V 3 Mod 1 ESL263S

3NO 230V 50/60 Hz 25A-440V 2 Mod 6 ESC325S


220V DC
40A-440V 3 Mod 1 ESC340S
63A-440V 3 Mod 1 ESC363S

3NO 24V 50Hz 25A-440V 2 Mod 1 ESD325S


24V DC

4NO 230V 50/60 Hz 25A-440V 2 Mod 6 ESC425S


ESC463S
220V DC
40A-440V 3 Mod 1 ESC440S
63A-440V 3 Mod 1 ESC463S

4NO 24V 50Hz 25A-440V 2 Mod ESD425S


24V DC
40A-440V 3 Mod ESD440S
63A-440V 3 Mod ESD463S

4NO 12V 50Hz 25A-440V 2 Mod 1 ESL425S


12V DC
40A-440V 3 Mod 1 ESL440S
63A-440V 3 Mod 1 ESL463S

4NC 230V 50/60 Hz 25A-440V 2 Mod 1 ESC426S


220V DC
24V 50 Hz 25A-440V 2 Mod 1 ESD426S
24V DC
12V 50Hz 25A-440V 2 Mod 1 ESL426S
12V DC

2NO+2NC 230V 50/60 Hz 25A-440V 2 Mod 1 ESC427S


220V DC
24V 50Hz 25A-440V 2 Mod 1 ESD427S
24V DC
12V 50 Hz 25A-440V 2 Mod 1 ESL427S
12V DC

3NO+1NF 230V 50/60 Hz 25A-440V 2 Mod 1 ESC428S


220V DC
24V 50Hz 25A-440V 2 Mod 1 ESD428S
24V DC
12V 50 Hz 25A-440V 2 Mod 1 ESL428S
12V DC

2.17 Data is subject to errors and technical modifications.


Contactors
Override Contactors, Night & Day Contactors

Override Contactors

- For the remote switching and control of power circuits.


- They are equipped with a 3 position manual control button: permanent ON, automatic mode, permanent OFF.
- Can be associated with the auxiliary contact ESC080 for remote signaling.
- Complies to IEC 61095.
- Auxiliary contact
- Associated with a contactor, it allows remote signaling.
- It is recommended to use a heat dissipation insert LZ060 between each 3 products.

Coil AC In power circuit


Description Type 50 Hz AC7-a / AC1 Width Pack qty. Cat ref.
Override contactor 1NO 230V 25A-250V 1 Mod 12 ERC125 ERC225

2NO 230V 25A-250V 1 Mod 12 ERC225


40A-440V 3 Mod 4 ESC240
63A-440V 3 Mod 1 ERC263

Modular Devices
& Connection
2NO 24V 25A-250V 1 Mod 1 ERD225
40A-440V 3 Mod 1 ERD240
63A-440V 3 Mod 1 ERD263
8/12V 25A-250V 3 Mod 1 ERL225
40A-440V 3 Mod 1 ERL240
63A-440V 3 Mod 6 ERL263 ERC425

2NC 230V 25A-250V 1 Mod 12 ERC226

3NO 230V 25A-440V 2 Mod 6 ERC325

4NO 230V 25A-440V 2 Mod 6 ERC425


24V 25A-440V 2 Mod 6 ERD425
12V 25A-440V 2 Mod 1 ERL425

4NC 230V 25A-440V 2 Mod 1 ERC426

2NO+2NC 230V 25A-440V 2 Mod 1 ERC427

3NO+1NC 230V 25A-440V 2 Mod 1 ERC428

Night & Day Contactors

- Night & day contactors allows the functioning of electrical devices during off-peak hours, especially storage heaters
andwater-heaters.
- The manual override allows: temporary override with automatic return at next coil energization, permanent switch-off in case
of long leave.
- Standard 1z and 2z versions are recommended for applications where a reduced consumption and heating dissipation are
needed.
- The hum-free versions ETCx25S are recommended for housing applications where silent operating is requested.
- Hum-free operating is guaranteed in time, switching noise is reduced.
- Complies to NF EN 61095

In power circuit Mod Width


Description Type Coil AC AC7-a / AC1 17,5 mm Pack qty. Cat ref. ETC225
Night & Day Contactors 2NO 230V 50Hz 25A-250V 1 1 ETC225
2NC 230V 50Hz 25A-250V 1 1 ETC226
1NO+1NC 230V 50Hz 25A-400V 1 1 ETC227
3NO 230V 50Hz 25A-440V 2 1 ETC325
230V 50Hz 40A-440V 3 1 ETC340
230V 50Hz 63A-440V 3 1 ETC363
4NO 230V 50Hz 25A-440V 2 1 ETC425
230V 50Hz 40A-440V 3 1 ETC440
230V 50Hz 63A-440V 3 1 ETC463

Hum-free Night & Day Contactors 2NO 230V 0/60Hz 25A-250V 1 1 ETC225S
ETC425S
220V DC
3NO 230V 0/60Hz 25A-250V 2 1 ETC325S
220V DC
4NO 230V 50/60 25A-250V 2 1 ETC425S
Hz 220V DC

Data is subject to errors and technical modifications. 2.18


Contactors
Hum-free Override Contactors

Hum-free Override Contactors

- For the remote switching and control of power circuits.


- They are equipped with a 3 position manual control button: permanent ON, automatic mode, permanent OFF.
- The hum-free versions are recommended for housing applications where silent operating is requested.
- Complies to IEC 61095.
- Can be associated with the auxiliary contact ESC080, except 1 module hum-free contactors (ERC225S).
- It is recommended to use a heat dissipation insert LZ060 between each product.

Coil AC In power circuit


Description Type 50 Hz AC7-a / AC1 Width Pack qty. Cat ref.
Hum-free override contactor 2NO 230V 50/60 Hz 25A-250V 1 Mod 1 ERC225S
ERC225S 220V DC
40A-440V 3 Mod 1 ESC240S
24V 50Hz 40A-440V 3 Mod 1 ERD240S
24V DC
63A-440V 3 Mod 1 ERD263S
12V 50Hz 40A-440V 3 Mod 1 ERL240S
Modular Devices

12V DC
& Connection

63A-440V 3 Mod 1 ERL263S

3NO 230V 50/60 Hz 25A-440V 2 Mod 6 ERC325S


220V DC
4NO 230V 50/60 Hz 25A-440V 2 Mod 1 ERC425S
220V DC
ERC425S
24V 50Hz 25A-440V 2 Mod 1 ERD425S
24V DC
12V 50Hz 25A-440V 2 Mod 1 ERL425S
12V DC

2.19 Data is subject to errors and technical modifications.


Relays
Latching Relays

Latching Relays

- Latching relays - operate when impulsed by a signal voltage.


- The impulse can be provided via a pushbutton or pushswitch. The first pulse operates the relay and
- latches it to its set (opposite) state, the next operation of the pushbutton returns the relay to its reset (original) state.
- Auxiliary Contacts (EPN050, EPN051)
- Are available for remote signalling and centralised control applications and can be easily combined with the latching relays.
- Connection: 10mm2 flexible, 6mm2 rigid
- 1 Mod = 17.5mm, 2 Mod = 35mm, 3 Mod = 52.5mm, 4 Mod = 70mm

Power
Description Coil circuit AC1 Mod. Width Cat ref.
Latching Relay 1 NO 230V 50Hz 16A - 250V~ 1 EPN510 EPN510
24V 50Hz 16A - 250V~ 1 EPN513

Latching Relay 2 NO 230V 50Hz 16A - 250V~ 1 EPN520


24V 50Hz 16A - 250V~ 1 EPN524
12V 50Hz 16A - 250V~ 1 EPN521

Modular Devices
& Connection
Latching Relay 1 NC + 1NO 230V 50Hz 16A - 250V~ 1 EPN515
24V 50Hz 16A - 250V~ 1 EPN518
12V 50Hz 16A - 250V~ 1 EPN519

Latching Relay 2 NC + 2 NO 230V 50Hz 16A - 250V~ 2 EPN525


24V 50Hz 16A - 250V~ 2 EPN528
12V 50Hz 16A - 250V~ 2 EPN529

Latching Relay 4 NO 230V 50Hz 16A - 400V~ 2 EPN540


24V 50Hz 16A - 400V~ 2 EPN541

EPN540

Auxiliary Contacts

Mod. Width
Description Power circuit 8.75mm Cat ref.
Auxiliary Contact 2A - 250V~ 0.5 EPN051
Auxliary Contacts for Centralised Control 24A - 230V~ 0.5 EPN050

Data is subject to errors and technical modifications. 2.20


Relays
Relays, Hum-free, Interface

Relays, Hum-free, Interface

Relays
- To provide remote control of low power circuits max.16A.
- They are equipped with a 3 position manual control button: permanent ON, automatic mode, permanent OFF.
- Complies to IEC 61095.
- It is recommended to use a heat dissipation insert LZ060 between each 3 products.
Auxiliary contact
- Associated with a relay, it allows remote signaling.
- Mechanical status indicator
Interface relays
- Power contacts adapted to very low voltage circuits. It is operating silently.
ERD218 - A signal indicates when the coil is under voltage.
- These relays ensure a galvanic isolation between LV and VLV up to 4kV.

Coil AC Mod. Width


Description Type 50 Hz Power circuit AC7-a / AC1 17,5 mm Pack qty. Cat ref.
Relays 2NO 230V 16A - 250V~ 1 1 ERC216
24V 16A - 250V~ 1 1 ERD216
Modular Devices

8/12V 16A - 250V~ 1 1 ERL216


& Connection

2NC 230V 16A - 250V~ 1 1 ERC217


24V 16A - 250V~ 1 1 ERD217
8/12V 16A - 250V~ 1 1 ERL217

ERC418
1NO+1NC 230V 16A - 250V~ 1 12 ERC218
24V 16A - 250V~ 1 1 ERD218
8/12V 16A - 250V~ 1 1 ERL218

3NO 230V 16A-440V 2 1 ERC316

4NO 230V 16A-440V 2 1 ERC416

2NO+2NC 230V 16A-440V 2 1 ERC418


24V 16A-440V 2 1 ERD418
12V 16A-440V 2 1 ERL418
EN145

Hum-free Relays 2NO+2NC 24V AC/DC 16A-440V 2 1 ERD418S


12V AC/DC 16A-440V 2 1 ERL418S

A1 1 Interface relays VLV/LV coil voltage: EN145


10 to 26V AC/DC
output: 1 changeover contact
A2 1 4
max. 5A 230V AC
min. 10mA - 12V DC
A1 1
Interface relays LV/VLV coil voltage: EN146
230V AC
A2 1 4
output: 1 changeover contact
max. 5A 230V AC
min. 10mA - 12V DC

2.21 Data is subject to errors and technical modifications.


Contactors & Relays
Auxiliaries for Contactors and Relays

Auxiliaries for Contactors and Relays

Auxiliary contact
- Associated with a relay or a contactor, it allows to show the product status or remote signaling.
- Not compatible with 1 module hum-free contactors and EN145 / EN146.
Heat dissipation insert
- It is recommended to use a heat dissipation insert LZ060 between each 3 products.
Sealing covers
- Not compatible with EN145 / EN146.

Mod. Width
Description 17.5mm Pack qty. Cat ref.
Auxiliary contact In power circuit AC7-a / AC1 1NO+1NF 6A-250V 0.5 1 ESC080 ESC080
Sealing cover for 1 module contactors 1 10 ESC001
for 2 module contactors 2 10 ESC002
for 3 module contactors 3 10 ESC003
Heat dissipation insert 0.5 12 LZ060

Modular Devices
& Connection
ESC002

LZ060

Data is subject to errors and technical modifications. 2.22


Pushbuttons
Impulse & Latching

Impulse & Latching

Description
- Modular pushbuttons to actuate loads either directly or via contactors etc.
Terminal Capacity
- 10mm² rigid conductor.
- 6mm² flexible conductor.
- BS EN 60947-5-1

Width
Characteristics (1 Mod =17.5mm) Cat ref.
Pushbuttons (Impulse) 16A - 250V
SVN311 a.c. Without Indicator Light
Contacts: 1 NO 1 Mod SVN311
Contacts: 2 NO 1 Mod SVN331
Contacts: 2 NO, Double Pushbutton 1 Mod SVN371
Contacts: 1 NC 1 Mod SVN321
Contacts: 2 NC 1 Mod SVN341
Modular Devices
& Connection

Contacts: 1 NO + 1 NC 1 Mod SVN351


Contacts: 1 NO + 1 NC, Double Pushbutton 1 Mod SVN391
Contacts: 2 NO 1 Mod SVN371
Contacts: 2NO + Green Push Button 1 Mod SVN373

SVN411 Pushbuttons (Impulse) 16A - 250V


a.c. With Indicator Light
Contacts: 1 NO : Green 1 Mod SVN411
Contacts: 2 NO : Red 1 Mod SVN432
Contacts: 1 NC : Red 1 Mod SVN422
Contacts: 2 NC : Green 1 Mod SVN441
Contacts: 1 NO + 1 NC 1 Mod SVN452
Contacts: 2 NO : Green 1 Mod SVN461
Contacts: 2 NO : Red 1 Mod SVN462

Pushbuttons (Latching) 16A - 250V


a.c. Without Indicator Light
SVN312 Contacts: 1 NO 1 Mod SVN312
Contacts:1NC 1 Mod SVN321
Contacts: 2 NO 1 Mod SVN332
Contacts: 1 NC 1 Mod SVN322
Contacts: 2 NC 1 Mod SVN342
Contacts: 1 NO + 1 NC 1 Mod SVN352

Pushbuttons (Latching) 16A - 250V


a.c. With Indicator Light
Contacts: 1 NO : Green 1 Mod SVN413
Contacts: 2 NO : Green 1 Mod SVN433
Contacts: 2 NO : Green 1 Mod SVN463
SVN413
Contacts: 2 NO : Red 1 Mod SVN464

2.23 Data is subject to errors and technical modifications.


Indication
Indicator Lights, Transformers

Indicator Lights

Characteristics
- Available with red, green, orange, blue & transparent lens.
Light Technology
- LED.
Options
- DIN rail mountable.
Connection
- Cage terminals.
Capacity
- 10mm² rigid conductor, 6mm² flexible conductor, BS EN 62094-1.
SVN121
Description Width (1 Mod =17.5mm) Cat ref.
Indicator Lights 230V a.c.
Indicator Colour: Green 1 Mod SVN121
Indicator Colour: Red 1 Mod SVN122
Indicator Colour: Orange 1 Mod SVN123

Modular Devices
Indicator Colour: Blue 1 Mod SVN124

& Connection
Indicator Colour: Transparent 1 Mod SVN125
Indicator Colour: Red & Green (Double Indicator) 1 Mod SVN126
Indicator Colour: Red x3 (Triple Indicator) 1 Mod SVN127
Indicator Colour: Clear (Double Indicator) 1 Mod SVN128
Indicator Colour: Red/Orange/Green (Triple Indicator) 1 Mod SVN129 SVN127
Indicator Colour: Green (Triple Indicator) 1 Mod SVN221
Indicator Colour: Red/Orange/Blue (Triple Indicator) 1 Mod SVN222

Indicator Lights 12/48V


Indicator Colour: Green 1 Mod SVN131
Indicator Colour: Red 1 Mod SVN132
Indicator Colour: Orange 1 Mod SVN133
Indicator Colour: Blue 1 Mod SVN134
Indicator Colour: Clear 1 Mod SVN135
Indicator Colour: Green/Red 1 Mod SVN136

Safety Transformers

Characteristics
- Provide Separated Extra Low Voltage (SELV) 8, 12, 24V a.c.
Technical Data
- Secondary voltages: 8V, 12V, 24V a.c.
- Cable capacities: 6mm²

Note: The transformers have a higher no load voltage. The stated voltages correspond to the voltages on nominal load.

Description Width (1 Mod =17.5mm) Cat ref.


230V/12V a.c. 50Hz, 20VA 50/60 Hz 4 Mod ST309 ST313
230V/24V a.c. 50Hz, 20VA 50/60 Hz 4 Mod ST310
230V/12-24V a.c. 50Hz, 25VA 50/60 Hz 4 Mod ST312
230V/12-24V a.c. 50Hz, 16VA 50/60 Hz 4 Mod ST313
230V/12-24V a.c. 50Hz, 40VA 50/60 Hz 4 Mod ST314
230V/12-24V a.c. 50Hz, 63VA 50/60 Hz 6 Mod ST315

Bell Transformers

Characteristics
- Provide Separated Extra Low Voltage (SELV) 8, 12, 24V a.c.
Technical Data
- Secondary voltages: 8V, 12V, 24V a.c.
- Cable capacities: 6mm².
- Bell transformers are short-circuit protected.

Note: When a bell transformer is installed in an enclosure with mains voltage equipment, 230V cable should be used on the
secondary side of the transformer or extra low voltage cable should be sheathed within the enclosure.

Description Width (1 Mod =17.5mm) Cat ref. ST301

230V/8V a.c. 50/60 Hz, 8-12V, 4VA 2 ST301


230V/8-12V a.c. 50/60 Hz, 8-12V, 8VA 2 ST303
230V/8-12V a.c. 50/60 Hz, 8-12V, 16VA 3 ST305

Data is subject to errors and technical modifications. 2.24


Indication
Bells, Buzzers

Bells

Technical Data
- Cable capacities: 6mm²
- Bells: Max. continuous duty ≤ 30 minutes.
Output
- Bells: 85 dBA.

Width
Description (1 Mod =17.5mm) Cat ref.
8/12V a.c., 5VA - 0.33A 1 Mod SU212
230V a.c., 6.5VA - 0.03A 1 Mod SU213
SU212

Buzzers

Technical Data
- Cable capacities: 6mm².
Modular Devices

- Buzzers: Max. continuous duty ≤ 30 minutes.


& Connection

Output
- Buzzers: 78dBA.

Width
Description (1 Mod =17.5mm) Cat ref.
8/12V a.c., 4VA - 0.33A 1 Mod SU214
SU214 230V a.c., 6.5VA - 0.03A 1 Mod SU215

2.25 Data is subject to errors and technical modifications.


Timers
Electromechanical Time Switches

Electromechanical Time Switches

Characteristics
- For hourly, daily or weekly programming.
- To control lighting, heating, ventilation, household appliances etc. to save energy and to improve comfort.
Technical Data
- Programming by captive segments.
- Manual override for 1 module products: Automatic, Permanent ON.
- Manual override for 3 module products: Automatic, Permanent ON, Permanent OFF.
- Minimum Switching Time: 15 min for daily dial, 2h for weekly dial.
- Supply failure reserve where applicable 200 hours, after being connected for 120 hours.
- For a selection chart see page 2.56, for technical data see page 2.55.
Connection EH010
- 1-4mm².

Width
Description Voltage Supply (1 Mod =17.5mm) Cat ref.
1 Channel Time Switches without Supply Failure Reserve
Daily Dial, 1 NO Changeover Contact, 16A 250V AC1 230V a.c. 50Hz 1 Mod EH010

Modular Devices
Daily Dial, 1 NO Contact, 16A 250V a.c. AC1 230V a.c. 50Hz 3 Mod EH110

& Connection
Daily Dial, 1 NO Changeover Contact, 16A 250V AC1 230V a.c. 50Hz 2 Mod EH209
Daily Dial, 1 NO Changeover Contact, 16A 250V AC1 230V a.c. 50Hz 2 Mod EH210

1 Channel Time Switches with Supply Failure Reserve


Daily Dial, 1 Changeover Contact, 16A 250V AC1 230V a.c. 50/60Hz 1 Mod EH011
EH171
Weekly Dial, 1 NO Contact, 16A 250V AC1 230V a.c. 50Hz 1 Mod EH071
Daily Dial, 1 NO Contact, 16A 250V AC1 230V a.c. 50/60Hz 3 Mod EH111
Weekly Dial, 1 NO Contact, 16A 250V AC1 230V a.c. 50/60Hz 3 Mod EH171
Daily + Weekly Dial, 1 NO Changeover Contact, 16A 250V AC1 230V a.c. 50/60Hz 5 Mod EH191
Daily Dial, 1 NO Changeover Contact, 16A 250V a.c. AC1 230V a.c. 50/60Hz 2 Mod EH211
Weekly Dial, 1 NO Changeover Contact, 16A 250V a.c. AC1 230V a.c. 50/60Hz 2 Mod EH271

Accessories
Sealing Kit for 3 Mod Time Switch EH901
Wall Mounting Kit for 3 Mod Time Switch EH902

Data is subject to errors and technical modifications. 2.26


Timers
Digital Time Switches

Digital Time Switches

Characteristics
- For the control of lighting, heating, household appliances, shop windows, signage etc. to improve comfort and to save
energy.

EG103 and EG203 (Basic Version)


- Automatic change of summer / winter time.
EG103E/V and EG203E (Advanced Version)
- Automatic change of summer / winter time.
- Holiday mode: forcing ON or OFF between two dates, presence simulation with random switching.
- Backlit screen.
- Impulse programming capability (1s to 30 min).
EG071
Programming Key
- To allow easy back up and re-installation of the program to allow permanent program overrides.
- Programming per day or group of days.
- 56 ON / OFF programme steps.
- Permanent ON/OFF overrides.
- Temporary ON/OFF overrides bar graph indication showing the daily profile.
- Ability to disable device button controls with EG004.
Modular Devices

- Programming can be completed without the need to be energised.


& Connection

Connection
- EG010 / EG071: 0.5 to 4mm².
- EG103 and EG203/E: 1 to 6mm² Flexible, 1.5 to 10mm² Rigid.
Operating Voltage
- 230 a.c. 50/60 Hz (except EG103V - 12/24V AC/DC).

EG103 Width
Description (1 Mod =17.5mm) Cat ref.
1 Channel Digital Time Switch (not compatible with program key)
Daily Cycle, 5 Adjustable pre-recorded programs 1 Mod EG010
6 Switchings per day (3 on and 3 off), Output: 1 changeover contact
16A - 250V AC 1, 3 year reserve
Weekly Cycle, Capacity 20 program steps, 230V 50/60 Hz 1 Mod EG170
Weekly Cycle, Capacity 20 program steps 1 Mod EG071
Output: 1 changeover contact
16A - 250V AC 1, 3 year reserve

1 Channel Digital Time Switch


Weekly Cycle (Basic Version), Output: 1 changeover contact 2 Mod EG103
EG203 16A - 250V AC 1, Delivered with key EG005
Weekly Cycle (Advanced Version), Output: 1 changeover contact 2 Mod EG103E
16A - 250V AC 1, Delivered with key EG005
Capacity : 56 program steps, Output: 1 changeover contact, μ 16A - 250V~ AC1 2 Mod EG103B
Capacity: 56 program step, Output: 1 changeover contact, μ 16A - AC1 - 12/24 V 2 Mod EG103V
AC/DC, 50/60 Hz

2 Channel Digital Time Switch (not compatible with program key)


Capacity : 20 program steps to be divided between the 2 channels 230V 50/60 Hz 3 Mod EG210

2 Channel Digital Time Switch


Weekly Cycle (Basic Version), Output: 2 changeover contact 2 Mod EG203
16A - 250V AC 1, Delivered with key EG005
Weekly Cycle (Advanced Version), Output: 2 changeover contact 2 Mod EG203E
16A - 250V AC 1, Delivered with key EG005
Capacity: 56 program steps, Output: 2 changeover contacts, μ 16A - 250V~ AC1 2 Mod EG203B
Capacity: 20 program steps to be divided between the 2 channels 230v 50/60 Hz 3 Mod EG270
2 Channels Yearly Time Switch. Voltage Rating: 230V~ 50/60 Hz. 4 Mod EG293B
Output: 2 changeover contacts, 10A - 250V~ AC1

2.27 Data is subject to errors and technical modifications.


Timers
Time Switch Accessories, Astronomical Time Switches

4 Channel Digital Time Switches

Weekly and Annual Cycle


- In commercial premises timed programming often requires the use of multi-circuit equipment with large programming
capacities for a weekly or annual cycle.
Applications
- Command of lighting circuits, control of heating, ventilation control, bells, alarms.
Functions
- Summer/winter time pre-programmed.
- External input for override (permanent, temporary, timed)
- The output can be defined as ON/OFF, impulse or cycle.
- 4 different cycles can be defined.
- Calculates automatically all dates linked with Easter. EG493E
- Programming for holiday period, including random mode.
- 10 specific weekly programs.
- Hour counter on each channel.
- Ability to disable device button controls with PIN code.
Connection
- Quick connect terminals.
- Capacity: 0.75 to 2.5mm².

Modular Devices
- For a selection chart see page 2.56.

& Connection
Width
Description (1 Mod =17.5mm) Cat ref.
4 Channel Yearly Time Switch 4 Mod EG493E
Spare grey programming key for timers EG493E EG007
Interface between PC & key interface module, with software on CD EG003
Interface between PC & key interface module, with USB EG003U
4 Channel Weekly Time Switch. Voltage Rating: 230V~ 50/60 Hz, 4 Mod EG470
Output: 4 changeover contacts, 16A - 230V~ AC1
4 Channel Weekly Time Switch. Output: 2 changeover contacts + 2NO contacts, 4 Mod EG403E
10A - 250V ~ AC1. Delivered with programming key.

Astronomical Time Switches

Characteristics
- Programming of lighting loads, with automatic change of winter / summer time.
- Expert program with individual astronomical program steps.
- Programming for day or group of days.
- Weekly programming.
- Permanent or temporary override.
- Programming for holiday period.
- Can be programmed via the PC software and the associated interface (EG003).
- For technical information see page 2.59.

Width EE180
Description (1 Mod =17.5mm) Cat ref.
1 Channel Astronomical Time Switch
Weekly Cycle, 230V a.c., 50Hz Changeover Contact 16A AC1, 2 Mod EE180
Operating reserve lithium battery 5 years, Delivered with key EG005

2 Channel Astronomical Time Switch


Weekly Cycle, 230V a.c., 50Hz 2 Changeover Contact 16A AC1, 2 Mod EE181
Operating reserve lithium battery 5 years, Delivered with key EG005

EE181

PC Interface & Software Tools

Description Pack qty. Cat ref.


Interface between PC & key interface module, with software on CD EG003
Interface between PC & key interface module, with USB 1 EG003U
Yellow locking key to prevent unauthorised re-programming 1 EG004
of all EG time clocks (except EG010, EG071)
Spare grey programming key for timers EG103, EG103V,EG203, EG103E, EG203E 1 EG005
DIN rail storage module for EG004 or EG005 1 EG006

EG003U

Data is subject to errors and technical modifications. 2.28


Timers
Time Lag Switches

Time Lag Switches

Characteristics
- Provides control of lighting circuits with automatic switch-off after a pre-set time.
- Compact design with a 2 position switch, permanent / timed lighting control facility.
Basic Staircase Time Lag Switches
- Adjustable time delay setting 30 sec. to 10 minutes.
Multifunction Staircase Time Lag Switches
- Incorporates a pre-warning of switch OFF improving safety.
- Double delay function: 30 sec. to 10 min. 1 hour on override by pressing the push-button for more than 3 seconds. Double
delay with pre-warning mode.
- For technical data see page 2.60.
EMN001
Description Pack qty. Cat ref.
Basic Staircase Time Lag Switches
Supply voltage 230V a.c. 50/60Hz 16A - 250V AC1 1 Mod EMN001
2300W incandescent halogen and fluorescent
Modular Devices

Multifunction Staircase Time Lag Switches


& Connection

Supply voltage 230V a.c. 50/60Hz 16A - 250V AC1 1 Mod EMN005
2300W incandescent halogen and fluorescent

EMN005

Delay Timers

Characteristics
- For timing and automation in domestic and commercial premises. The input signal can be via various switching devices
(pushbutton, latching switch, timeclock etc.) and the timed output used to control the application.
Applications
- To provide all types of automatic control i.e. lighting, ventilation, watering, machine pre-heating, cycle control etc. with
automatic switch off / on after preset time.
Terminal Capacity
- 6mm² max flexible.
- 1.5 - 10mm² rigid.
Technical Data
EZN001 - Voltage range: 12 to 48V DC, 12 to 230V AC.
- Adjustable: Time delay from 0.1s to 10hrs.
- Complies with BS EN 60669-2-1.
- For technical data see page 2.61.

Description Pack qty. Cat ref.


Delay On
Cde
1 changeover contact 1 Mod EZN001
S 10A / 230V a.c. AC1
T Time delay T:0.1s to 10hr

Delay Off
Cde
1 changeover contact 1 Mod EZN002
EZN002 S 10A / 230V a.c. AC1
T
Time delay T:0.1s to 10hr

Adjustable Time On
Cde
1 changeover contact 1 Mod EZN003
10A / 230V a.c. AC1
S Time delay T:0.1s to 10hr
T

Timer
Cde
1 changeover contact 1 Mod EZN004
S 10A / 230V a.c. AC1
T
Time delay T:0.1s to 10hr

EZN004 Symmetrical Flasher


Cde
1 changeover contact 1 Mod EZN005
S 10A / 230V a.c. AC1
T
Time delay T:0.1s to 10hr

Delay On / Off, Adjustable Time On / Off, Timer, Symmetrical Flasher


1 changeover contact 1 Mod EZN006
10A / 230V a.c. AC1
Time delay T:0.1s to 10hr

2.29 Data is subject to errors and technical modifications.


Connection
Of Devices
Insulated busbars, junction blocks, distribution blocks, terminals… all
that is needed to quickly and efficiently mount devices in enclosures and
distribution boards.
Connection
Insulated Busbars

Prong Insulated Busbars

KB163P Characteristics
- Brown or blue insulated busbars
- For MCBs Ph+N and fuse carriers 1 module spacing.
- Single, double, three and four pole busbars
for multipolar MCB from 0,5 to 63A
KB163N
for multipolar, single pole fuse carriers and SB switches.

Description Section In Width Cat ref.


KB190C Single pole 63A to be equipped with protection profiles brown (phase) 10 mm2 63A 13 modules KB163P
Single pole 63A to be equipped with protection profiles blue (neutral) 10 mm2 63A 13 modules KB163N
Single pole 100A 20 mm2 100A 24 mod. KB190C
20 mm2 100A 57 mod. (1m) KB190B
KB263A Double pole 10 mm2 63A 12 mod. KB263A
10 mm2 63A 24 mod. KB263C
16 mm2 80A 56 mod. (1m) KB280B
Modular Devices

Three pole 10 mm2 63A 12 mod. KB363A


& Connection

KB363C 10 mm2 63A 24 mod. KB363C


16 mm2 80A 57 mod. (1m) KB380B
Four pole to be equipped with busbar ends 10 mm2 63A 12 mod. KB463A
10 mm2 63A 24 mod. KB463C
KB463A 16 mm2 80A 56 mod. (1m) KB480B

End Caps (to insulate ends of the busbars)

Description Cat ref.


KZ021 End caps for single busbars KZ021
End caps for double busbars KB263A, KB263C KZ022
End caps for double/three pole busbars for KB280B, KB363A, KDN263B, KB363C, KB380B, KDN363B KZ023A
End caps for four pole busbars KB463A, KB463C, KB480B, KDN463B KZ024

Protection profiles

Description Width Cat ref.


KZ059
Protection profiles to insulate the spare prongs 5 modules KZ059

Insulated Busbars & Accessories


KD190B
Characteristics
Fork insulated busbars
- For modular devices equipped with biconnect terminals; multipolar MCBs from 0,5 to 63A (without Ph+N), RCCBs
- Connection terminals KF83A, KF83C and KF83D are compatible with aluminium and copper conductors.
KDN263B

Description Section In Width Cat ref.


Fork insulated busbars single pole, 1 mod. step, insulated 20 mm2 100A 57 mod.(1m) KD190B

KDN363B Fork insulated busbars double pole, 2 mod. step, insulated 10mm2 63A 56 mod.(1m) KDN263B
Fork insulated busbars three pole, 3 mod. step, insulated 10 mm2 63A 57 mod.(1m) KDN363B
Fork insulated busbars 4 pole, 1 mod. step, insulated (L1,L2,L3,N …) 10 mm2 63A 56 mod.(1m) KDN463B
Fork insulated busbars 3 x (P + N) (L1 N,L2 N,L3 N,L1 N,L2 N,L3 N …) 16 mm2 80A 12 mod. KDN451D
KDN463B Fork insulated busbars 3 x (P + N) (L1 N,L2 N,L3 N,L1 N,L2 N,L3 N …) 16 mm2 80A 57 mod. (1m) KDN451E
Fork connection terminals for fork busbars terminals KF84A
cable incoming : lateral connection, capacity: 1 x 25 mm2, cable tightening with 2 screws
Prong connection terminals for devices with screw terminal KF82A
cable incoming : top connection, capacity: 2 x 16 mm2 cable tightening with 2 screws
Connection terminals for KB163P and KB83B KF83A
KF84A cable incoming : lateral, connection capacity: 1 x 25 mm2, cable tightening with 1 screw
Connection terminals for KB163P and KB83B KF83B
cable incoming : lateral, connection capacity: 2 x 25 mm2, cable tightening with 1 screw
Connection terminals for busbars KB190B for KB263 to KB463 KF83C
cable incoming : lateral or top,connection capacity: 1 x 25 mm2,(35 mm2 rigid)
Connection terminals for KBN663A to KBN663C KF83D
KF82A cable incoming : lateral or top,connection capacity: 2 x 25 mm2 flexible, (35 mm2 rigid)

2.31 Data is subject to errors and technical modifications.


Connection
Distribution Blocks

Distribution Blocks

Characteristics

Single Pole Distribution Blocks


- Monoblocs, insulated for copper conductor
- Ui: 500V
- Fixing on DIN rail, mounting plate and main devices plate kits.
4 x KJ02A
Stepped Distribution Blocks
- Modular, monobloc for copper conductors
- Removable front cover
- Ui: 500V
- Fixing on DIN rail

- Equipped with an insulated rear plate


- Complies with IEC 60 998-1 and IEC 60947-7-1.

Description Width mm Cat ref.

Modular Devices
Single pole distribution blocks 125A, Isc peak: 30kA, 27 mm KJ02D

& Connection
incoming: 1 x 35 + 1 x 16 mm2, outgoing: 6 x 16 mm2
160A, Isc peak: 50kA 35 mm KJ02C KJ02E
incoming: 1 x 70 mm2, outgoing: 6 x 16 mm2
250A, Isc peak: 50kA, incoming: 1 x 95 mm2, 45 mm KJ02A
outgoing: 2 x 25 + 5 x 16 + 4 x 10 mm2
400A, Isc peak: 50kA, incoming: 1 x 150 mm2 45 mm KJ02B
outgoing: 2 x 25 + 5 x 16 + 4 x 10 mm2
Modular distribution monobloc fixing on 100A - four pole, Isc peak: 20kA - Ui: 500V 98 mm, KJ02E
DIN rail, on mounting plate phase: 1 x 25 + 2 x 10 + 5 x 6 mm2 flexible (5.5 mod.)
neutral: 1 x 25 + 6 x 10 + 4 x 6 mm2 flexible
h. 74,5 x d. 45 mm
Modular distribution blocks Brass busbar terminal 4P 100A KJ100A
fixing on DIN rail, on mounting plate KJ100A
Brass busbar terminal 4P 125A KJ125B
Brass busbar terminal 4P 160A KJ160A
Supplementary Neutral Bar 100A, 7 connections KJ07NB
Supplementary Neutral Bar 125A, 12 connections KJ12NB
Supplementary Neutral Bar 125A, 15 connections KJ15NB

KJ125B

Multi-Connection Distribution Blocks

Characteristics

Four Pole Multi-Connection System 250A


KJ03A
- To supply 2, 3 and 4 pole devices.
- For Quadro enclosures 620 or 700 mm wide.
- Incoming connection with 4 screw lugs.
- Outcoming connection with insulated flexible connectors.

Delivered with KZ007


- 6 insulated blue cables (6 x 6 mm2),
- 12 insulated brown cables (12 x 6 mm2),
- 2 fixation lugs for Quadro system.

Description Cat ref.


Four pole multi-connection system 250A 60 outgoing connections: without KJ03A
- 25 neutral outgoings connectors
- 12 outgoings per phase
section: 6 and 10 mm2 withstand current under 40°C:
- per pole: 250A with KJ03B
- 40A with connector 6 mm2 connectors
-63A with connector 10mm2
Isc peak: 60kA, Un: 500 V AC - 50Hz
KZ001 / KZ002
Connector terminals to crimp flexible wire of 6 mm2 KZ007

Blue Brown
Cat ref. Cat ref.
Cables with connector for KJ03A 40A, 6 mm2 KZ001 KZ002
40A, 6 mm2 KZ051 KZ052
63A, 10 mm2 KZ004 KZ005
63A, 10 mm2 KZ074 KZ075

Data is subject to errors and technical modifications. 2.32


Connection
Junction Blocks

Junction Blocks

Characteristics
- For 16 to 35 mm2 copper conductors.
- In max: 125A
- To facilitate incoming cables connection and deviations in distribution boards and enclosures:
K018 fixing on DIN rail
for K024 and K025 blocks, the mounting can be horizontal or vertical.

Junction terminals
- For 25 to 150 mm2 copper or aluminium conductors.

Description Width Cat ref.


Junction blocks, connection per pole: 1 pole, w. 40 x h. 55 x d. 40 mm 2.5 mod. K018
K024 incoming: 2 x 25 mm2, outgoing: 4 x 16 mm2
delivered with front protection covers
2 pole, w. 65 x h. 55 x d. 35 mm 4 modules K023
4 pole, w. 120 x h. 55 x d. 45 mm 7 modules K024
Modular Devices

5 pole,w. 150 x h. 55 x d. 45 mm 8.5 mod. K025


& Connection

K037
Junction blocks, connection per pole: 1 pole, w. 41 x h. 55 x d. 53 mm 2.5 mod. K037
incoming: 2 x 35 mm2, outgoing: 4 x 16 mm2
Junction terminals fixing on DIN rails can be mounted tighten by hexagonal wrench 25 to 95mm2 25 mm KR95P
in Univers and Quadro enclosures
tighten by hexagonal wrench 35 to 50mm2 31 mm KR15P
Connecting bars fixing on DIN rails 2 x 5 connecting for 2,5 mm2 cables K010
Grounding connection separate wedges section 50 mm2, delivered with 2 plates K085
equipped with 70 mm2 cable clamps

KR95P / KR15P

K010

2.33 Data is subject to errors and technical modifications.


Connection
Screw Terminals

Screw Terminals

Characteristics
- Screw terminals
- Tracking resistance KC > 600
- Temperature range 120°C
- For all rail dimensions according to DIN 50022
- Secure fit on all non-standardised, commercially available support profiles 35mm in width
- Mounting or removing transverse to rail possible in both directions
- Uniform dimensions reduce the required accessories
- Built-in, self-loosening protection; vibration and vibration proof KXA10LH
- Large clamping range; suitable for two conductors of the same cross section (for PE only 1 conductor)
- Guided control of conductor in the open terminals by conical insertion funnel
- Screwdriver guidance by arranged sunk clamping screws
- Retained screws when loosening, particularly important for mechanical screwdrivers
- All parts contained in terminal support
- Compact design with side wire entry
- Takes flexible conductors with ferrule to rated cross section
- Low contact resistance due to high contact forces

Modular Devices
Phase Feed Through Terminals

& Connection
Characteristics
- 400V or 800V
- Colour beige
- The following can be used with 1000V photovoltaic applications: KXA06LH, KXA10LH, KXA16LH, KXB35LH, KXB70LH, and
KXB150LH. A rated current of 1000V applies as long as the stripping length, the clearance and creepage distance comply
with VDE0110/01.89.

Description Dimensions Pack qty. Cat ref.


2.5² Through phase 800V/24A w. 5 x d. 48.5 x h. 44.5 mm 100 KXA02LH
4² Through phase 800V/32A w. 6 x d. 48.5 x h. 44.5 mm 100 KXA04LH
6² Through phase 1000V/41A w. 8 x d. 53.5 x h. 48 mm 100 KXA06LH
10² Through phase 400V/57A w. 10 x d. 51.5 x h. 58 mm 50 KXA10L
10² Through phase 800V/24A w. 10 x d. 55 x h. 53.8 mm 50 KXA10LH
16² Through phase 400V/76A w. 12 x d. 51.5 x h. 58 mm 50 KXA16L
16² Through phase 1000V/71A w. 12 x d. 57.5 x h. 59.3 mm 50 KXA16LH
35² Through phase 400V/125A w. 16 x d. 51.5 x h. 58 mm 20 KXA35L
35² Through phase 1000V/125A w. 16 x d. 67.6 x h. 70.6 mm 20 KXB35LH
70² Through phase 1000V/192A w. 24 x d. 81.2 x h. 76.8 mm 20 KXB70LH
150² Through phase 1000V/309A w. 28 x d. 98.6 x h. 96 mm 10 KXB150LH

Phase Terminal Blocks

Description Dimensions Pack qty. Cat ref.


2.5² Tiered phase 500V/24A w. 5 x d. 63.9 x h.65.8 mm 100 KXA02LX
4² Tiered phase 400V/32A w. 6 x d. 63 x h. 61.6 mm 100 KXA04LX
4² Earth tiered w. 6.2 x d. 63.2 x h. 59 mm 100 KXB04EX

Neutral Terminals

Characteristics
- 400V or 800V
- Colour blue
- Cross sectional area for solid conductors
- The following can be used with 1000V photovoltaic applications: KXA06NH, KXA10NH, KXA16NH, KXB35NH, KXB70NH,
and KXB150LH. A rated current of 1000V applies as long as the stripping length, the clearance and creepage distance
comply with VDE0110/01.89.

Description Dimensions Pack qty. Cat ref. KXA10NH


2.5² Through neutral 800V/24A w. 5 x d. 48.5 x h. 44.5 mm 100 KXA02NH
4² Through neutral 800V/32A w. 6 x d. 48.5 x h. 44.5 mm 100 KXA04NH
6² Through neutral 1000V/41A w. 8 x d. 53.5 x h. 48 mm 100 KXA06NH
10² Through neutral 400V/57A w. 10 x d. 51.5 x h. 58 mm 50 KXA10N
10² Through neutral 1000V/57A w. 10 x d. 55 x h. 53.8 mm 50 KXA10NH
16² Through neutral 400V/76A w. 12 x d. 51.5 x h. 58 mm 50 KXA16N
16² Through neutral 1000V/71A w. 12 x d. 57.5 x h. 59.3 mm 50 KXA16NH
35² Through neutral 400V/125A w. 16 x d. 51.5 x h. 58 mm 20 KXA35N
35² Through neutral 1000V/125A w. 16 x d. 67.6 x h. 70.6 mm 20 KXB35NH
70² Through neutral 1000V/192A w. 24 x d. 98.6 x h. 96 mm 20 KXB70NH
150² Through neutral 1000V/309A w. 28 x d. 98.6 x h. 96 mm 10 KXB150NH

Data is subject to errors and technical modifications. 2.34


Connection
Screw Terminals

Earth Terminals

Characteristics
- Colour yellow/green
- Cross sectional area for solid conductors

Description Dimensions Pack qty. Cat ref.


2.5² Protective conductor w. 5 x d. 48.5 x h. 48.6 mm 100 KXA02E
4² Protective conductor w. 6 x d. 48.5 x h. 51 mm 100 KXB04E
KXA10E
6² Protective conductor w. 8 x d. 53.5 x h. 54 mm 100 KXB06E
10² Protective conductor w. 10 x d. 51.5 x h. 58 mm 50 KXA10E
10² Protective conductor w. 10 x d. 55 x h. 54 mm 50 KXB10E
16² Protective conductor w. 12 x d. 57.5 x h. 57.5 mm 50 KXB16E
16² Protective conductor w. 12 x d. 51.5 x h. 58 mm 50 KXA16E
35² Protective conductor w. 16 x d. 67.6 x h. 63 mm 20 KXB35E1
35² Protective conductor w. 16 x d. 51.5 x h. 58 mm 20 KXB35E
Modular Devices
& Connection

Neutral Terminals

Characteristics
- Neutral separation 400V
- Colour blue
- The N disconnect terminal blocks can be used in cases with a degree of protection of at least IP54 according to IEC 60529
for photovoltaic applications 1000V can be used. It then applies 1000V/6kV/2

Description Dimensions Pack qty. Cat ref.


4² Neutral terminal 400V/25A w. 6 x d. 48.5 x h. 53.5 mm 100 KXA04ND
10² Neutral terminal 400V/45A w. 10 x d. 51.5 x h. 58 mm 50 KXA10ND
16² Neutral terminal 400V/62A w. 12 x d. 51.5 x h. 58 mm 50 KXA16ND

Three Conductor Terminal Blocks with Disconnect Slide

Characteristics
- 400V / 6kV / 3
- For phase-, N-, and PE
- With disconnect slide to neutral separation on busbars 10 x 3 mm

Description Dimensions Pack qty. Cat ref.


4²/1 x N- Disconnect L/ 1 x Through/1 x PE w. 6 x d. 51.5 x h. 90 mm 50 KXA04I3

Three Conductor Terminal Blocks

Characteristics
- N- isolation switching over separation
- For phase-, N-, and PE
- 400V/6kV/3
- Cannot be used with busbar
- Connect at either end of group of terminals

Description Dimensions Pack qty. Cat ref.


4²/1 x N Disconnect L/ 1 x Through/1 x PE w. 6 x d. 51.5 x h. 90 mm 50 KXA04I1

Three Wire Terminals without N- Separation

Characteristics
- Without neutral separation
- For phase-, N-, and PE
- 400V/6kV/3

Description Dimensions Pack qty. Cat ref.


4²/1 x Through N/1 x Through L/ 1 x PE w. 6 x d. 51.5 x h. 90 mm 50 KXA04I2

2.35 Data is subject to errors and technical modifications.


Connection
Screw Terminals

Supplementary Terminals

Characteristics
- Cannot be used with busbar
- Connect at either end of group of terminals

Description Dimensions Pack qty. Cat ref.


4²/2 x Through L w. 6 x d. 51.5 x h. 90 mm 50 KXA04I4
4²/1 x Through L w. 6 x d. 51.5 x h. 90 mm 50 KXA04I5
KXA04I5
4²/2 x Through L/1 x PE w. 6 x d. 51.5 x h. 90 mm 50 KXA04I6
4²/1 x Plug fuse/1 x Through L/1 x PE w. 6 x d. 51.5 x h. 90 mm 50 KXA04I7

Knife Disconnect Terminal Block

Characteristics
- Open or closed, sealed

Modular Devices
- Colour of release lever signals the open state

& Connection
- 800V/8kV/3

Description Dimensions Pack qty. Cat ref.


4² Knife disconnect terminal block, 800V/20A w. 8 x d. 49.5 x h. 48 mm 50 KXA04KD
KXA04KD

Fuse Terminals

Characteristics
- Open or closed, sealed
- Storage space for a spare fuse
- 800V/8kV/3

Description Dimensions Pack qty. Cat ref.


4² G Fuse terminals (5 x 30) Max. 63A w. 8 x d. 54.5 x h. 77.2 mm 50 KXB04F5
KXB04F5
4² G Fuse terminals (6.3 x 32) Max. 10A w. 10 x d. 54.5 x h. 77.2 mm 50 KXB04F6

Through Terminals, Vertically Bridged

Characteristics
- 400V/5kV/3
- Colour black
- Internal vertical bridged

Description Dimensions Pack qty. Cat ref.


2.5² Tiered internal bridged 500V/24A w. 5 x d. 63.9 x h. 65.8 mm 100 KXA02VB
4² Tiered internal bridged 400V/32A w. 6 x d. 70.5 x h. 61.6 mm 100 KXA04VB KXA02VB

Data is subject to errors and technical modifications. 2.36


Connection
Accessories for Screw Terminals

Endplates Through Terminals

Description Pack qty. Cat ref.


Endplate for KXA02LH, KXA04LH 10 KWE01G
Endplate for KXA02NH, KXA04NH 10 KWE01B
Endplate for KXA02E 10 KWE01GR
Endplate for KXA06NH 10 KWE02B
Endplate for KXA10L, KXA16L 10 KWE04G
KWE01B Endplate for KXA10N, KXA16N 10 KWE04B
Endplate for KXA10LH 10 KWE05G
Endplate for KXA10NH 10 KWE05B
Endplate for KXA10E, KXA16E 10 KWE04GR
Endplate for KXA16LH 10 KWE06G
Endplate for KXA16NH 10 KWE06B
Endplate for KXA35L 10 KWE03G
Endplate for KXA35N 10 KWE03B
Modular Devices
& Connection

Endplates Three Wire Terminals

Description Pack qty. Cat ref.


Endplate for KXA04I1 I2 I3 I4 I5 I6 10 KWE21G
Endplate for KXA04I7 10 KWE22G

Endplates N Disconnect Terminal Blocks

Description Pack qty. Cat ref.


Endplate for KXA16ND, KXA10ND 10 KWE17B
Endplate for KXA04ND 10 KWE24B

Endplate Tiered and Vertically Bridged Through Terminals

Description Pack qty. Cat ref.


Endplate for KXA02VB, KXA02LX 10 KWE25G
Endplate for KXA04VB, KXA04LX 10 KWE26G

Endplate Knife Disconnect Terminals

Description Pack qty. Cat ref.


Endplate for KXA04D 10 KWE27G

KWE27G

Non Insulated Cross Connector

Description Pack qty. Cat ref.


Connecting link 70mm², 2 fold 10 KWJ70C2
Connecting link 70mm², 3 fold 10 KWJ70C3
KWJ150C3
Connecting link 150mm², 2 fold 10 KWJ150C2
Connecting link 150mm², 3 fold 10 KWJ150C3

Marking Tags

Characteristics
- KW001: Box of 10 digits 0-9 to 50 individual labeling strips, KW002/03/04: numbered sequentially per 25 strips,
KW002: numbers 1-100, KW003: numbers 101-200, KW004: L1, L2, L3, N, PE

KWL001
Description Pack qty. Cat ref.
Designation clips box (0-9) 1 KWL001
Designation clips 0-100 (25 strips) 1 KWL002
Designation clips 101-200 (25 strips) 1 KWL003
Designation clips L1, L2, L3, N, PE (25 strips) 1 KWL004

2.37 Data is subject to errors and technical modifications.


Connection
Accessories for Screw Terminals

Insulated Cross Connector

Description Pack qty. Cat ref.


Insulated jumper bar 2.5², 2 fold 10 KWJ02B2
Insulated jumper bar 2.5², 3 fold 10 KWJ02B3
KWJ35A10
Insulated jumper bar 2.5², 4 fold 10 KWJ02B4
Insulated jumper bar 2.5², 5 fold 10 KWJ02B5
Insulated jumper bar 2.5², 10 fold 10 KWJ02B10
Insulated jumper bar 4mm², 2 fold 10 KWJ04A2
Insulated jumper bar 4mm², 3 fold 10 KWJ04A3
Insulated jumper bar 4mm², 4 fold 10 KWJ04A4
Insulated jumper bar 4mm², 5 fold 10 KWJ04A5
Insulated jumper bar 4², 10 fold 10 KWJ04A10
Insulated jumper bar 4², 12 fold 10 KWJ04A12
Insulated jumper bar 4², 2 fold 10 KWJ04B2
Insulated jumper bar 4², 3 fold 10 KWJ04B3

Modular Devices
Insulated jumper bar 4², 4 fold 10 KWJ04B4

& Connection
Insulated jumper bar 4², 5 fold 10 KWJ04B5
Insulated jumper bar 4², 10 fold 10 KWJ04B10
Insulated jumper bar 6², 2 fold 10 KWJ06B2
Insulated jumper bar 6², 3 fold 10 KWJ06B3
Insulated jumper bar 6², 4 fold 10 KWJ06B4
Insulated jumper bar 6², 5 fold 10 KWJ06B5
Insulated jumper bar 6², 10 fold 10 KWJ06B10
Insulated jumper bar 10², 2 fold 10 KWJ10B2
Insulated jumper bar 10², 3 fold 10 KWJ10B3
Insulated jumper bar 10², 10 fold 10 KWJ10B10
Insulated jumper bar 16², 2 fold 10 KWJ16A2
Insulated jumper bar 16², 3 fold 10 KWJ16A3
Insulated jumper bar 16², 10 fold 10 KWJ16A10
Insulated jumper bar 35², 2 fold 10 KWJ35A2
Insulated jumper bar 35², 3 fold 10 KWJ35A3
Insulated jumper bar 35², 10 fold 10 KWJ35A10

Non Insulated Cross Connector

Description Pack qty. Cat ref.


Connecting link 70mm², 2 fold 10 KWJ70C2
Connecting link 70mm², 3 fold 10 KWJ70C3
Connecting link 150mm², 2 fold 10 KWJ150C2 KWJ150C3
Connecting link 150mm², 3 fold 10 KWJ150C3

Busbar for N Disconnect Terminal Blocks

Description Pack qty. Cat ref.


N Busbar 1 KW1NBB

Busbar Terminals for Busbar 10 x 3mm

Description Pack qty. Cat ref.


Busbar terminal 16² 50 KW16ST
Busbar terminal 16² - 35² 20 KW35ST

KW16ST

End Clamp (material: plastic)

Description Pack qty. Cat ref.


End clamp 35mm² 100 KWB01
End clamp 150mm² 100 KWB02

KWB01

Data is subject to errors and technical modifications. 2.38


Connection
Brass Terminals

Brass Terminals

Characteristics
KM04L - Brass terminals
- For earth, neutral, phase copper conductors.
- In max: 60A

Version without base:


- Can be mounted using KZ bases or rail. Delivered with screws.
KM08L
Version with base:
- To be clipped on 12 x 2 mm rails.

- Earth: green/yellow base


- Neutral: blue base
KM07N
- Phase: beige base

With base With base With base Without


neutral earth phase base
Description Connection Section Cat ref. Cat ref. Cat ref. Cat ref.
Modular Devices

KM10B
Brass terminals with base 2x 6 + 2x10mm2 - - KM04L K140
& Connection

4 connections
plot length 30mm
4x16 + 4x10mm2 - - KM08L -
8 connections
KM10E 2 plot length 30mm
3x16 + 4x10mm2 KM07N KM07E KM07L K142
7 connections
plot length 49mm
5x16 + 5x10mm2 KM10A KM10B KM10C K143
KM13N 10 connections
plot length 67mm
5x16 + 6x10mm2 KM11N KM11E KM11L K144
11 connections
plot length 73mm
2x16 (dbl. drive)+ 8x10 mm2 KM10N KM10E KM10L K145
KM11B 10 connections
plot length 69mm
6x16 + 7x10mm2 KM13N KM13E - K148
13 connections
K151 plot length 85mm
1x25+5x16 + 5x10mm2 - KM11B - K151
11 connections
plot length 85mm
KM25N 1x25 + 8x16 + 8x10mm2 KM17N KM17E - K156
17 connections
plot length 121mm
1x25+11x16+13x10mm2 KM25N KM25E - K158
K158 25 connections
plot length 169mm
Brs. terminals without base 1x25 + 8x16 + 29x10 mm2, length 242mm K159
1x25 + 16x16 + 61x10 mm2, length 482mm K160
K159
1x25 + 33x16 + 129x10 mm2,length 992mm K162

Bases

Characteristics
KZ012
- Bases for brass terminals K140 to K162
- Insulated material
- M4 x 8 fixing screws

KZ014 Description Cat ref.


Bases for brass terminals
K140 to K162 insulated material M4 x 8 fixing screws blue base, for neutral KZ012
green/yellow base, for earth KZ013
beige base, for phase KZ014

2.39 Data is subject to errors and technical modifications.


Connection
Bases & Rails for Terminals & Blocks

Bases & Rails for Terminals & Blocks B

A
Characteristics
A089
Bases for Brass Terminals
- For the mounting of the KM brass terminals without base.
B
- Material: flat bar 12 x 2 mm.

Mounting Rails A
- For the mounting of junction blocks and terminals into enclosures.
- Electro-zinc coated and bichromated. UT91A
- Length: 2m

Description Dimensions. Cat ref.


A090
Flat bar supports for terminal strips for brass terminals with base for one brass terminal A = 55 mm A089
B = 74 mm
Pinch carriers UT91A for brass terminals with base 1 span (250 mm) A = 205 mm UT91A
Brass terminals supports for brass terminals with base for mounting in all boards length: 2 m A090

Modular Devices
Rail fixing clips KZ060F to fix brass terminals on DIN rails with bases mounting on DIN rail width 20 mm KZ060F

& Connection
KZ012, KZ013 and KZ014 KZ060F

A099
horizontally vertically

Symmetrical rails, DIN 46277/3, width: 35 mm 1 span (250 mm) depth 7.5 mm A088

A088 A098 A099

depth 10 mm A098
depth 15 mm A099
Asymmetrical rails, DIN 46277/1 1 span (250 mm) depth 7.5 mm A050

Insulated Brass Terminals

Description Pack qty. Cat ref.


Brass terminals insulated green, earth, IP20 7 x 16mm2 1 KM07EF
Brass terminals insulated blue, neutral, IP20 7 x 16mm2 1 KM07NF KM07EF
2
Brass terminals insulated green, earth, IP20 12 x 16mm 1 KM12EF
Brass terminals insulated blue, neutral, IP20 12 x 16mm2 1 KM12NF

KM12NF

Data is subject to errors and technical modifications. 2.40


Connection
Quick Connect & Cage Terminals

Quick Connect & Cage Terminals

Characteristics
- For earth, neutral, phase copper conductors.
KN06P - The terminals are equipped with direct plug-in quickconnect terminals for 1,5 to 4 mm2 plug-in wires and cage terminals for
1,5 to 25 mm2 standard wires.
- Can be clipped on premounted bases for volta, vector, vega D, gala and gamma enclosures.
- Available as accessories.
- Complies with EN 60998. For technical information see page 2.59.

KN22N
Green/yellow
Cage Blue neutral Brown phase earth
2
Description Terminal qty. quick connect 1.5 to 4mm 1.5 to 25mm2 Cat ref. Cat ref. Cat ref.
Quickconnect and cage 5 1 KN06N KN06P KN06E
8 2 KN10N KN10P KN10E
11 3 KN14N KN14P KN14E
KN26E
14 4 KN18N KN18P KN18E
17 5 KN22N KN22P KN22E
Modular Devices

20 6 KN26N KN26P KN26E


& Connection

Accessories

Description Cat ref.


KN99P/N/E
Equipotential bridgings to connect 2 quickconnect terminals for neutral terminals (pack of 10) KN99N
for phase terminals (pack of 10) KN99P
for earth terminals (pack of 10) KN99E
VZ710 Bases for quickconnect terminals for volta, vector VZ711
vega 18 surface VZ710
gamma GZ30A
FW enclosure UZ00K1
VZ711 Universal bases for terminals to be fixed on 12 x 2 mm flat bars of length: 105 mm pre-cut base to fit with KN00A
DIN rails in Quadro and Univers enclosures the terminals dimensions
Incoming cage terminals allow the connection of cables up to 25 mm2 neutral terminals: 4 x 25 mm2 KN04N
Ui = 630V, 90A, can be clipped on quickconnect bases
GZ30A neutral terminals: 7 x 25 mm2 KN07N
phase terminals: 4 x 25 mm2 KN04P
phase terminals: 7 x 25 mm2 KN07P

KN00A

KN07N

KN04P

2.41 Data is subject to errors and technical modifications.


Engineered
solutions.
From pre-assembled standard distribution units to bespoke
composite TP&N boards and plug in distribution boards, we
can provide the solution.
kWh Meters
Electrical Characteristics

EC150 EC152 EC154M EC350 EC352 EC360 EC362 EC364M EC365B TE360 EC370 EC372 TE370
Electrical Characteristics
230V~ ±15%
Voltage 230V~ ±15%
400V~ ±15%
Frequency 50/60Hz 50/60Hz
Consumption < 10VA and 1W < 10 VA and 3W
Data
Connection Direct Via current transformer
Display Digital - 7 digits
Accuracy ± 1% - Class B according to EN 50470-3
I max 63A 100A 6A on CT secondary
I starting 40mA 80mA 10mA on CT secondary
Base current 10A 20A 5A
LED
1000 blinking per kWh 500 blinking per kWh 1000 blinking per kWh
Modular Devices
& Connection

Pulsed Ouput
1 pulse = 100Wh / 100ms / 27V DC max (excepted on KNX meters)
Tariff
1 2 2 1 2 1 2 2 1 2 1 2 2
Mechanical Characteristics
Width 3 Modules 4 Modules 7 Modules 4 Modules
Protection degree IP20 - IP51 (front part)
Temperature Storage temperature: -20ºC to +70ºC, Operating temperature: -10ºC to +55ºC
Connection Rigid: 1.5 to 16mm2 Rigid: 1.5 to 35mm2 Rigid: 1.5 to 10mm2
capacity Flexible: 1 to 16mm2 Flexible: 1 to 35mm2 Flexible: 1 to 6mm2

2.43 Data is subject to errors and technical modifications.


Current Transformers
Technical Data

Technical Data (to EN/IEC60044-1) Prim. Sec. Power Accuracy Dimensions Max. Busbar
[A] [A] [VA] class and cable
Size
Primary rated current 50 A - 2000 A
SRA01005 100 5 2.5 1 70 x 49,5 x 30 mm 30 x 10 mm
Rated secondary current 5A
25 x 15 mm
SRA01505 150 5 2.5 1
Rated frequency 50 - 60 Hz 20 x 20 mm
SRA02005 200 5 2.5 1
Highest voltage for equipment Um 720 V
SRA02505 250 5 2.5 1
Rated power-frequency withstand 3 kV
voltage (r.m.s.) SRC04005 400 5 5 1
Instrument security factor (FS) FS 5 SRC06005 600 5 5 1
Rated continuous thermal current 1,2 x In SRA00505 50 5 1.5 1 78 x 60 x 30 mm 20 x 10 mm
15 x 15 mm
current rating 120 %
Ø 20 mm
Rated short time thermal current Ith = 60 x In (max
SRI03005 300 5 5 1 78 x 60 x 30 mm 40 x 12 mm
50 kA)
Ø 28 mm
Rated dynamic current: Idyn = 2,5 x Ith
SRD08005 800 5 5 1 108 x 85 x 30 mm 60 x 10 mm

Modular Devices
(max 120 kA)
50 x 30 mm

& Connection
SRD10005 1000 5 5 1
Permissible ambient temperature -40 °C to + 40 °C Ø 45 mm
SRD15005 1500 5 5 1
Class of insulation in accordance E
with IEC 60085 SRE20005 2000 5 15 1 122 x 100 x 40 mm 80 x 10 mm
60 x 30 mm
Degree of protection DIN/EN 60529 IP 20
Ø 60 mm
/ VDE 0470 T1
Recommended tightening torque 1,5 - 2 Nm
secondary terminals

SRA01005, SRA01505, SRA02005,


SRA02505, SRC04005, SRC06005 SRA00505 SRI03005

SRD08005, SRD10005, SRD15005 SRE20005

Data is subject to errors and technical modifications. 2.44


Changeover Switches, Switch Disconnectors
Technical Data

Electrical Characteristics Changeover Switches


Family SF
Modular size 1 module 2 module 4 module
Cat ref. SFH125 SFM125 SFT125 SFH225 SFT225 SFT240 SF263
Thermal current Ith (40°C) 25A 25A 25A 25A 25A 40A 63A
Operational frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Rated operation voltage in AC 230V
Rated insulation voltage (Ui) 440V 440V 440V 440V 440V 440V 500V
Rated impulse withstand voltage Uimp 4 KV 4 KV 3 KV 6 KV 6 KV 6 KV 4 KV
Protection degree 2 2 2 3 2 2 2
Working temperature -20 to 50°C -20 to 50°C -20 to 50°C -20 to 50°C -20 to 50°C -20 to 50°C -20 to 50°C
Storage temperature -40 to 80°C -40 to 80°C -40 to 80°C -40 to 80°C -40 to 80°C -40 to 80°C -40 to 80°C
Operational Currents Ie
Load duty
Rated voltage
category
Modular Devices

400V AC AC 22A 25A 25A 25A 25A 25A 40A 63A


& Connection

400V AC AC 22B 25A 25A 25A 25A 25A 40A 63A


Short circuit characteristic
Rated short time withstand current 1s
IEC 60947-3 375A / 1sec 600A / 1sec 4.5kA cond.
Icw (rms)
Prospective short circuit current (rms) EN 60669 3kA 3kA 3kA 6kA 6kA n/a n/a
Mechanical characteristic
Rigid cable section 35 mm2 35 mm2 35mm2 25 mm2 25 mm2 25 mm2 25 mm2
flexible cable section 10 mm2 10 mm2 10 mm2 16 mm2 16 mm2 16 mm2 16 mm2
Tightening torque 1.8 Nm 1.8 Nm 1.8 Nm 1.8 Nm 1.8 Nm 1.8 Nm 1.8 Nm
IP protection degree 20 20 20 20 20 20 20
Mechanical endurance (number of
200,000 200,000 200,000 200,000 200,000 200,000 100,000
cycle)
Electrical endurance @ AC22 (number
25,000 25,000 25,000 5,000 5,000 2,500 5,000
of cyles)
Overall dimension
Width (mm) 17.5 17.5 17.5 35 35 35 71.5
Height (mm) 83 83 83 83 83 83 90
Depth (mm) 68 68 68 68 68 70 68

Electrical Characteristics Switch Disconnectors


Family SBx / SFx SBx SBx
Number of pole 1P - 2P - 3P - 4P
Frame size frame size 1 frame size 2 frame size 3
IEC 60947-3 ok ok ok
Comply to standard
IEC 60669-2-4 ok ok -
Thermal current Ith (40°C) 16A 25A 32A 32A 40A 63A 63A 80A 100A 125A
Operational frequency 50/60 Hz 50/60 Hz 50/60 Hz
Rated insulation voltage (Ui) 440V 440V 440V
Rated impulse withstand voltage Uimp 3kV 6 kV 6 kV
Protection degree 3 (SB) / 2 (SF) 3 3
Working temperature -20 to 50°C
Storage temperature -40 to 80°C
Operational Currents Ie
Rated voltage load duty category
AC 21-A(1) 16A 25A 32A 32A 40A 63A 63A 80A 100A 125A
400V AC AC 22-A(1) 16A 25A 32A 32A 40A 63A 63A 80A 100A 125A
AC 23-A(1) 10A 10A 10A 32A 40A 40A 40A 40A 40A 40A
Short circuit characteristics
Rated short time withstand current 1s Icw (rms) IEC 60947-3 240A 375A 480A 480A 600A 945A 945A 960A 1200A 1500A
Prospective short circuit current (rms) EN 60669-2-4 3kA 6kA n/a
Mechanical characteristics
Rigid cable section 16 mm2 25 mm2 50 mm2
2 2
Flexible cable section 10 mm 16 mm 35 mm2
Tightening torque 1.8 Nm 2.8 Nm 3.6 Nm
Busbar thickness n/a 1 to 1.5 mm 1.5 to 2 mm
IP protection degree 20
Mechanical endurance (number of cycles) 100000 30000 20000
Electrical endurance @ AC22 (number of cycles) 25000 5000 2500

(1)
A category: frequent operation

2.45 Data is subject to errors and technical modifications.


Light Sensitive Switches
Technical Data

Light Sensitive Switches Description


Using light sensitive switches can prevent the unnecessary use of lighting
circuits where sufficient daylight exists. The benefit of modular devices is the
facility to set the ambient lighting level at which the device will operate, and as
the device is fitted at the distribution point prevent unauthorised tampering.
The remote photocell unit can be mounted up to a distance of 50 metres from
the device. Two devices are available the standard EEN100 light sensitive test test
1 2
switch and an enhanced programmable version the EE171 that also allows
auto auto
time clock control. 1 2

Principle of Operation
Both devices control lighting systems according to natural illumination;
- The user sets the working level:
- The photo cell measures the external light level

The output of the EEN100 is:


- ON, when the measured level is lower than the pre-set light level
- OFF, when the measured level is higher than the pre-set light level

The output of the EE171 during the programmed ON time period is:

Modular Devices
- ON, when the measured level is lower than the pre-set light level 7 8 9 10 11 12

& Connection
- OFF, when the measured level is higher than the pre-set light level
10 11 12

The output of the EE171 during the programmed off time period is: m16A 250V AC1

- OFF, regardless of the lighting level


5
100
The light sensitive switches include a built in time delay which avoids Lux
50
2
2000
unnecessary switching due to temporary factors such as car headlight beams 3
etc... 6 4
auto
on/of f Prog
5 1
7 test

8 +
230 V 50 Hz

6E0585a
N L

Lux 1 2 5 6

1 2 3 4 5 6

The programmable light sensitive switch EE171 has two main


functions:
Light sensitive switch comprising
1. Override selector switch to allow permanent ON or OFF, auto or
test mode
T 2. Lighting range selector
3. Potentiometer to set light level
4. Indicator to show output switching status
6:00 8:00 17:00 23:00
A programmer to establish the automatic operating cycle
The programmer comprises 4 keys:
5. ON / OFF to choose whether the circuit is on or off.
6. Prog to set the program and scroll program steps
7. Reset
12 ON ON 8. + and - to change settings
11
10 OFF OFF OFF

L
N

10 11 12

1 2 5 6

Data is subject to errors and technical modifications. 2.46


Light Sensitive Switches
Technical Data

Mounting the Cell Technical Specification


To ensure correct operation of the light sensitive switch, the cell must not be
influenced by artificial light or direct solar radiation and should be sheltered
from dust and humidity. In case of disconnection of the link between the cell Electrical Specification
and the light sensitive switch, the output of the device will be switched on.
Make sure the light sensitive switch is unplugged before connecting the cell. Voltage Rating 230V +10 -15% 50Hz
Consumption 1.5VA Max
EE002 EE003 Output 1 Voltage Free Changeover Contact
Type Flush Mounting Surface Mounting Max Breaking Capacity AC1 16A 250V~
Dimensions (mm) 89 x 48 x 32 25 x 25 x 20 Incandescent Lamp 2000W 230V~
Hole 25mm Halogen Lamp 1000W 230V~
Connection Cable 1m 2 x 0.75mm2 0.75 to 4mm2 Fluorescent Lamp 1000W 230V~
Protection Class IP54 IP54 Uncompensated
Working & -30ºC to +60ºC -30ºC to +60ºC Compensated in Series (10μF) 1000W 230V~
Storage // Compensated (15μF) 200W 230V~
Temperature Duo 1000W 230V~
Functional Characteristics
Modular Devices

Adjustment of the Working Level Sensitivity Range 5 to 100 lux, 50 to 2000 lux
The test position of the override selector 1 makes setting the
& Connection

Cycle Weekly
preset level easier by removing the ON and OFF delay.
Programs 8 Pre-defined Program
Select the sensitivity range which suits your application (selector 1) Program Setting 1 Minute Increments*
5 to 100 lux (low light level) application examples; public lighting, shop Accuracy +6min / annum*
windows, signals...
Operating Reserve Lithium Battery Total of 3 Years
50 to 2000 lux (high light level) application examples; controls of shades Supply Failure*
On and Off Delay 15 to 60s
At the appropriate moment of the day, put the selector 1 in test Working Temperature -30ºC to +60ºC (cell)
position; turn the potentiometer 2 up to the switching point (the indicator 4 -10ºC to +50ºC (modular device)
lights); put the selector back to position ‘auto’ the normal operating mode of Storage Temperature -20ºC to +60ºC
the device.
Protection Class (cell) IP54
Insulation Class II
Connection Capacity
Modular Device 0.5 to 4mm2
Cell 0.75 to 2.5mm2
Max Length between Cell and 50m
Modular Device
Mounting of the Cell with 2 Screws 2.5mm
* EE171 only

2.47 Data is subject to errors and technical modifications.


Latching Relays
Technical Data

Technical Characteristics

EPN510 EPN513 EPN519 EPN525 EPN528 EPN529


EPN515 EPN518 EPN521 EPN540 EPN541
EPN520 EPN524
Voltage 230V 24V 12V 230V 24V 12V
Start Consumption 24VA 24VA 24VA 48VA 47VA TBC
Contact Rating AC1 - - 16A 250V~1 - - -
Electrical Endurace AC1 - 16A 150,000 Operations
Mechanical Endurance 500,000 Operations
Current in Open Position 8 mA
Max Duration of Voltage Supply to Coil 1h
Min Duration of Current Supply to Coil 0.1s
Working Temperature -5 to +40ºC
Storage Temperature -40 to +80ºC
Connections

Modular Devices
Coil:

& Connection
Flexible 0.5 to 4mm2
Rigid 1 to 6mm2
Power:
Flexible 1 to 6mm2
Rigid 1.5 to 10mm2
1 400~ for EPN540 and EPN541.

Auxiliary Contacts (EPN051)


The range of latching relays have been designed for use with an
auxiliary contact. The devices simply clip on the side of the relay.

23

21
A1 1 3

A2 2 4

22

24

Technical Characteristics

EPN051 2
Voltage -
Contact Rating 2A / 250V
Imin / 230V 15mA

1 Voltage dependant on associated relay

3
1

4
3

Data is subject to errors and technical modifications. 2.48


Contactors
Contactor Selection

Heating Type of Load


The choice of the contactor depends on the mechanical endurance (number Loads are categorised into various AC ratings, (AC1, AC2, AC3 etc.) and the
of operations) and on the electrical heating load higher the AC rating the more inductive the load becomes.
i.e. resistive elements, infra-red element, convectors. All Hager contactor ratings are given at AC1, therefore they must be de-rated
if used on other types of AC load.
Choice of Contactors
The choice of contactor is dependant upon many parameters Heat Dissipation Inserts
i.e. operating voltage, size of contacts, number of operations, The ambient temperature around a contactor can affect its life
ambient temperature, type of load supplied etc. expectancy, therefore, we strongly recommend that heat
dissipation inserts (LZ060) are fitted between all contactors and
adjacent devices.

Single Phase Three Phase

U R

U R R U R
Modular Devices
& Connection

U R

Number of operations
100,000 150,000 200,000 500,000 1,000,000
16A 3 2.5 1.9 0.85 0.7
230V

25A 4.6 4 3 1.35 1


Max. load in kW

40A 7.3 6.3 4.7 2.2 1.6


63A 11.6 10 7.5 3.5 2.5
16A 8.9 8 5.8 2.8 2
400V

25A 13.8 12 8.6 4.3 3


40A 22 18.5 14.385 6.3 5
63A 35 30 22.6 10.2 7.6

Contactor selection when using with motors

Single Phase 230V (AC3 or AC7b) Three Phase 400V (AC3 or AC7b)

L1 U L1 U

L2 V M
M

L2 V L3 W

Choice of Contactor According to control diagram


Single Phase with Capacitor 230V Three Phase (AC3 or AC7) 400V 2 Wires 3 Wires
0.88 2 pole 25A
Maximum load

2.6 2 pole 40A


in kW

2.6 3 pole 25A


7.8 3 pole 40A
10 3 pole 63A

Requirements of Use Close Fitting


Influence of Working Temperature It is necessary to put a heat dissipation insert (reference LZ060) between each
Derating factor between 40°C and 50°C : 0.9 contactor.
Example: Heating with convector
The maximum load of ESC225 is 4.6kW for 50,000 operations and for
a temperature <40°C.
between 40°C and 50°C, the load is 4.6 x 0.9 i.e. 4.14kW

2.49 Data is subject to errors and technical modifications.


Contactors & Override Contactors
Technical Data

Auxiliary
Description Modular contact
contact
Standard conformity EN 61095
Approvals NF - VDE- IMQ - KEMA - RMC / CCC
Relay Contactor Relay Contactor Contactor Contactor Contactor
Number of modules 1 2 3 ½
Thermal current lth (40ºC) 16A 25A 16A 25A 40A 63A 6A
Rated frequency 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
Rated insulation voltage (Ui) 250V 250V 440V 440V 440V 440V 250V
Rated impulse withstand voltage (Uimp) 4kV 4kV 4kV 4kV 4kV 4kV 4kV
Protection Degree 2 2 2 2 2 2 2
Rated Operating currents and power ratings in AC
AC-1 / AC-7a Rated operational currents Ie 16A 16A 16A 25A 40A 63A -
Rated operational power 230V 3kW 4.6kW 3kW 4.6kW 7.3kW 11.6kW -
400V - - 8.9kW 13.8kW 22kW 35kW -
AC-3 / AC-7b Rated operational currents Ie 5.5A 8.5A 5.5A 8.5A 25A 32A -

Modular Devices
Rated operational power 230V 570W 880W 570W 880W 2.6kW 3.3kW -

& Connection
400V - - 1.7kW 2.6kW 7.8kW 10kW -
AC-12 Rated operational currents i.e. @ 230V - - - - - - 6A
AC-15 Rated operational currents i.e. @ 230V - - - - - - 2A
Mechanical and Electrical Endurances
Number of
Mechanical endurance 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000
operations
Electrical endurance @ Ie AC7a (AC12 for aux Number of
60,000 60,000 60,000 60,000 60,000 60,000 60,000
contact) operations
MCB Protected short-circuit withstand
Prospected short-circuit current rms 1kA 3kA 1kA 3kA 3kA 3kA 1kA
MCB C16- MCB C25- MCB C16- MCB C25- MCB C40- MCB C63- 6A 10x38
Associated protection
6kA 6kA 6kA 6kA 10kA 10kA gG Fuse
Power dissipation
Power dissipation per current path 1W 1.5W 1W 1.5W 3.2W 5W 0.4W
Magnetic system for Eco and standard contactor
Pick-up 2.2W 2.2W 2.8W 2.8W 5W 5W -
Coil consumption 2.2W 2.2W 2.8W 2.8W 5W 5W -
Closing delay 25ms 25ms 25ms 25ms 25ms 25ms -
Opering delay 15ms 15ms 15ms 15ms 20ms 20ms -
Connection
Main contact cable section Rigid 1...10mm2 1...10mm2 1...10mm2 1...10mm2 4...25mm2 4...25mm2 1...6mm2
2 2 2 2 2 2
Flexible 1...6mm 1...6mm 1...6mm 1...6mm 4...16mm 4...16mm 1...6mm2
Main contact connection screw Type M3.4 M3.4 M3.4 M3.4 M5 M5 M3.4
Posidrive PZ2 PZ2 PZ2 PZ2 PZ2 PZ2 PZ2
Max. tight.
1.2Nm 1.2Nm 1.2Nm 1.2Nm 2Nm 2Nm 1.2Nm
torque
2 2 2 2 2 2
Coil connection cable section Rigid 1...10mm 1...10mm 1...10mm 1...10mm 1...10mm 1...10mm -
Flexible 1...6mm2 1...6mm2 1...6mm2 1...6mm2 1...6mm2 1...6mm2 -
Coil connection screw Type M3.5 M3.5 M3.5 M3.5 M4 M4 -
Posidrive PZ2 PZ2 PZ2 PZ2 PZ2 PZ2 -
Max. tight.
1.2Nm 1.2Nm 1.2Nm 1.2Nm 1.5Nm 1.5Nm -
torque
Working temperature
-10ºC to +50ºC
Storage temperature
-40ºC to +80ºC

Data is subject to errors and technical modifications. 2.50


Contactors & Relays
Technical Data

Lighting systems with electronic ballasts cause inrush current peaks. Therefore we recommend you use the chart below to determinate the maximum amount of
lamps that can be connected to a Hager contactor: The chart gives the maximum amount of lamps per contact. In 2014 the performances of the contactors in
combination with lights increased. The products identified on the front face with the ‘+’ can accept a higher number of lamps. For these products, see the figures
in the column with the ‘+’ in the header.

Lamp Power 16A 25A 16A + 25A + 40A 63A


Compact fluo lamps
Compact fluo lamp with external electronic ballast 5W 11 15 17 27 49 76
7W 11 15 17 27 49 76
9W 9 13 16 26 40 63
11W 9 13 16 26 40 63
15W 7 11 14 22 36 57
18W 7 11 14 22 36 57
20W 7 11 14 22 36 57
23W 7 11 14 22 36 57
26W 7 11 14 22 36 57
Compact fluo lamp with integrated electronic ballast 5W 17 27 34 54 86 135
7W 17 27 34 54 86 135
Modular Devices

9W 17 27 34 54 86 135
11W 17 27 34 54 86 135
& Connection

15W 17 27 34 54 86 135
18W 13 20 25 40 63 100
20W 13 20 25 40 63 100
23W 13 20 25 40 63 100
26W 13 20 25 40 63 100
Incandescent lamps
Tungsten & halogen lamps 230V 40W 32 50 36 57 76 120
60W 21 33 28 45 67 105
75W 17 27 24 38 63 100
100W 13 20 17 28 41 65
150W 8 13 11 18 29 45
200W 6 9 8 14 22 35
300W 4 7 6 10 15 23
500W 2 3 3 6 9 14
1000W 0 0 1 2 4 7
Tungsten & halogen lamps 12 ou 24V 20W 13 20 25 40 139 218
35W 8 13 16 26 82 129
50W 6 9 11 18 60 94
75W 4 6 7 12 52 82
100W 2 3 3 6 35 55
150W 1 2 2 4 20 31
LED
LED 230V with integrated electronic ballast - non dimmable 4W 17 27 34 54 86 135
4.5W 17 27 34 54 86 135
6W 17 27 34 54 86 135
7W 17 27 34 54 86 135
8W 17 27 34 54 86 135
12W 17 27 34 54 86 135
17W 13 20 25 40 63 101
18W 13 20 25 40 63 101
22W 13 20 25 40 63 101
30W 9 14 17 28 44 70
34W 9 14 17 28 44 70
40W 9 14 17 28 44 70
50W 7 11 14 22 35 55
LED 230V with integrated electronic ballast - dimmable 4W 38 60 76 120 159 250
5.5W 38 60 76 120 159 250
6W 38 60 76 120 159 250
7W 38 60 76 120 159 250
8W 38 60 76 120 159 250
12W 38 60 76 120 159 250
17W 28 44 56 88 118 185
18W 28 44 56 88 118 185
22W 28 44 56 88 118 185
30W 20 31 39 62 82 130
34W 20 31 39 62 82 130
40W 20 31 39 62 82 130
50W 16 24 30 48 65 102
LED 230V headlight with integrated electronic ballast 100W - - 3 5 6 9
150W - - 1 3 4 6
200W - - 1 2 4 6
LED 12V with separated transformer - dimmable 1W 38 60 76 120 180 220
2.5W 38 60 76 120 180 220
4W 38 60 76 120 180 220
5W 38 60 76 120 180 220
7W 38 60 76 120 160 200
10W 38 60 76 120 160 200
15W 28 44 56 88 160 200

2.51 Data is subject to errors and technical modifications.


Contactors & Relays
Technical Data

Lamp Power 16A 25A 16A + 25A + 40A 63A


Fluorescent tubes
T5 double - uncompensated 2 x 18W 13 20 25 40 50 78
2 x 20W 12 19 24 38 50 78
2 x 36W 12 15 19 30 44 69
2 x 40W 10 13 16 26 40 63
2 x 42W 9 12 15 24 40 63
2 x 58W 7 9 11 18 27 42
2 x 65W 6 8 10 16 27 42
2 x 80W 5 7 8 14 22 35
2 x 115W 4 5 6 10 16 25
T5 double - serie compensation 2 x 18W 7 11 14 22 34 53
2 x 20W 7 11 14 22 29 45
2 x 36W 6 10 12 20 27 42
2 x 40W 6 10 12 20 27 42
2 x 42W 6 10 12 20 27 42
2 x 58W 6 10 12 20 25 39
2 x 65W 5 7 8 14 23 36

Modular Devices
2 x 80W 5 7 8 14 20 31
2 x 115W 4 5 6 10 17 25

& Connection
T5 single - electronic ballast 15W 7 11 14 22 36 57
18W 7 11 14 22 36 57
20W 7 11 14 22 36 57
36W 7 11 14 22 34 53
40W 7 11 14 22 29 45
42W 7 11 14 22 29 45
58W 6 10 12 20 27 42
65W 6 10 12 20 27 42
80W 6 10 12 20 27 42
115W 6 10 12 20 25 39
T5 double - electronic ballast 2 x 18W 7 11 14 22 34 53
2 x 20W 7 11 14 22 29 45
2 x 36W 6 10 12 20 27 42
2 x 40W 6 10 12 20 27 42
2 x 42W 6 10 12 20 27 42
2 x 58W 6 10 12 20 25 39
2 x 65W 5 7 8 14 23 36
2 x 80W 5 7 8 14 20 31
2 x 115W 4 5 6 10 17 25
Fluorescent tubes
T5 single - uncompensated 15W 13 20 19 30 70 100
18W 13 20 19 30 70 100
20W 12 19 19 30 70 100
36W 12 15 17 28 60 90
40W 10 13 16 26 60 90
42W 9 12 15 24 55 83
58W 7 9 10 17 35 56
65W 6 8 10 17 35 56
80W 5 7 9 15 30 48
115W 4 5 6 10 20 32
140W 3 5 6 10 16 26
T5 single - paralell compensation 15W 7 11 12 20 36 57
18W 7 11 12 20 36 57
20W 7 11 12 20 36 57
36W 7 11 12 20 34 53
40W 7 11 12 20 29 45
42W 7 11 12 20 29 45
58W 6 10 9 15 27 42
65W 6 10 9 15 27 42
80W 6 10 9 15 27 42
115W 6 10 9 15 25 39

Data is subject to errors and technical modifications. 2.52


Contactors & Relays
Technical Data

Lamp Power 16A 25A 16A + 25A + 40A 63A


Discharge lamps
High-pressure mercury-vapor lamps - without 50W 9 14 17 28 32 50
compensation 80W 6 9 11 18 24 37
125W 3 5 6 10 18 28
250W 2 3 3 6 10 15
400W 1 1 1 2 6 9
700W 0 0 0 0 4 5
High-pressure mercury-vapor lamps - paralell 50W 7 11 14 22 26 40
compensation 80W 5 8 10 16 22 34
125W 3 5 6 10 15 23
250W 2 3 3 6 9 14
400W 1 1 1 2 5 8
700W 0 0 0 0 3 5
1000W 0 0 0 0 2 3
Low pressure sodium lamps - without compensation 18W 8 10 8 12 17 23
35W 4 6 7 9 14 20
55W 3 6 7 9 14 20
Modular Devices

90W 2 4 5 6 9 14
135W 1 3 3 4 6 8
& Connection

180W 1 2 2 4 6 8
Low pressure sodium lamps - paralell compensation 18W 5 7 5 8 12 24
35W 4 6 4 7 10 23
55W 3 5 3 5 10 19
90W 2 3 3 4 8 16
135W 1 2 1 2 5 7
180W 1 2 1 2 5 6
High pressure sodium lamps - without compensation 35W 11 14 15 24 30 50
50W 9 12 10 15 22 34
70W 8 9 8 12 18 28
110W 6 8 6 10 14 22
150W 4 7 5 8 10 16
250W 2 4 3 5 6 10
400W 0 1 1 2 4 6
1000W 0 1 1 1 2 3
High pressure sodium-vapour lamps - electronic 35W 6 9 11 18 31 50
ballast or parallel compensation 50W 6 9 11 18 22 35
70W 4 6 7 12 16 25
110W 3 5 6 8 13 21
150W 3 5 4 6 8 13
250W 2 3 3 4 7 11
400W 1 1 1 2 5 8
1000W 0 0 0 1 2 3
Metal halide lamps - without compensation 35W 12 24 19 30 42 55
70W 10 15 12 17 26 36
150W 6 7 8 12 14 20
250W 3 5 5 8 9 14
400W 1 2 2 4 6 9
1000W 0 0 0 0 3 5
Metal halide lamps - electronic ballast or parallel 35W 6 10 12 18 22 39
compensation 70W 5 8 10 13 22 39
150W 3 5 6 8 12 22
250W 3 5 6 7 9 16
400W 1 1 1 2 5 7
1000W 0 0 0 1 2 3

2.53 Data is subject to errors and technical modifications.


Transformers
Technical Data

Safety Transformers
These transformers are designed to ensure personal safety, their
primary winding are electrically separated from their secondary 230 V 24 V
windings and they are intended to feed separated extra low voltage
circuits U ≤ 50V. A thermal overload, in the primary windings, ensures that if a
short circuit or an overload occurs in the output it will not damage the device.

Bell Transformers
Bell transformers are similar to safety transformers but the
secondary voltages do not exceed 24 volts, they are also similarly protected
against short circuits and overloads, by thermal protection in the primary
winding.

Compliance with the Standards


The bell and safety transformers conform with BS EN 61558.
Where transformers are to be used in a common enclosure with other devices U2
heat dissipation inserts LZ060 should be used.
U1 U3
Recommendation of Use
• To link only one secondary (never link both simultaneously)

Modular Devices
• Do not connect (in series or in parallel) secondaries of different

& Connection
transformers

Technical Specification

ST301 ST303 ST305 ST312 ST313 ST314 ST315


Nominal Power 4VA 8VA 16VA 25VA 16VA 40VA 63VA
Designation Bell Bell Bell Safety Safety Safety Safety
Primary Voltage 230 Volts 230 Volts 230 Volts 230 Volts 230 Volts 230 Volts 230 Volts
Secondary Voltage U2 8 Volts 8 Volts 8 Volts 12 Volts 12 Volts 12 Volts 12 Volts
In = 0.5A In =1A In = 2A In = 2.08A In = 1.33A In = 3.33A In = 5.25A
U3 12 Volts 12 Volts 12 Volts 24 Volts 24 Volts 24 Volts 24 Volts
In = 0.33A In = 0.67A In = 1.33A In = 1.04A In = 0.67A In = 1.67A In = 2.63A
No Load U2 12 Volts 15 Volts 12 Volts 14 Volts 16 Volts 14 Volts 14 Volts
Secondary Voltage U3 18 Volts 22 Volts 19 Volts 29 Volts 30 Volts 27Volts 27 Volts
Galvanic Insulation 4kV 4kV 4kV 4kV 4kV 4kV 4kV
Max Functional Temperature 35ºC 35ºC 35ºC 35ºC 35ºC 35ºC 35ºC
Overload and S/C Protection Thermal cut out in the primary winding
Insulation Class H H B B B B H

Data is subject to errors and technical modifications. 2.54


Electromechanical & Digital Time Switches
Technical data

Technical Specifications

EH011 EH010 EH111 EH110 EH171 EG103 EG103E EG203 EG203E EG493E
Version Daily Weekly Weekly & Annual
Voltage Supply 230V 230V 230V 230V 230V 230V AC 230V AC 230V AC 230V AC 230V AC
50/60Hz 50Hz 50/60Hz 50Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz
Consumption 0.5VA 0.5VA 0.5VA 0.5VA 0.5VA 6VA 6VA 6VA 6VA 6VA
Output 1 NO 1 NO 1 C/O 1 C/O 1 C/O 1 Volt 1 Volt 2 Volt 2 Volt 2 Volt Free 2 NO
Contact Contact Contact Contact Contact Free Free Free Free Changeover
Volt Free Volt Free Volt Free Volt Free Volt Free Change- Change- Change- Change- Contact
over over over over Contacts
Contact Contact Contacts Contacts
Switching Capacity
AC 1 16A / 16A / 16A / 16A / 16A / 16A AC 1 16A AC 1 16A AC 1 16A AC 1 10A AC 1
250V 250V 250V 250V 250V / 250V / 250V / 250V / 250V / 250V
4A DC 1 4A DC 1 4A DC 1 4A DC 1
/ 12V / 12V / 12V / 12V
Modular Devices
& Connection

Inductive Load cos 0.6 4A / 4A / 4A / 4A / 2.5A / 10A 10A 10A 10A 10A
250V 250V 250V 250V 250V / 250V / 250V / 250V / 250V / 250V
Incandescent Lamp 900W 900W 900W 900W 900W 2300W 2300W 2300W 2300W 1500W
Halogen Lighting 230V - - - - - 2300W 2300W 2300W 2300W 1500W
Compensated - - - - - 400W 400W 400W 400W 400W
Fluorescent Tubes
(max 45μF)
Non Compensated Fluorescent - - - - - 1000W 1000W 1000W 1000W 800W
Tubes
Compensated in Series
Compact Fluorescent Tubes - - - - - 500W 500W 500W 500W 400W
Minimum Current - - - - - 100mA / 100mA / 100mA / 100mA / 100mA / 250V
AC 1 250V 250V 250V 250V
Minimum Current - - - - - - - - - -
DC 1
Galvanic Insulation Between Power - - - - - < 4 kV < 4 kV < 4 kV < 4 kV < 4 kV
Supply and Output
Characteristics
Technology Quartz Quartz Quartz Quartz Quartz - - - - -
Dial 24hrs 24hrs 24hrs 24hrs 7 days - - - - -
Minimum Switching 5min 5min 5min 5min 2h - - - - -
Programming Capacity - - - - - 56 Steps 56 Steps 56 Steps 56 Steps 300 Steps
Minimum Time Between 2 Steps - - - - - 1min 1min 1min 1min 1min
Working Accuracy 1sec per 1sec per 1sec per 1sec per 1sec per ±1.5sec ±1.5sec ±1.5sec ±1.5sec ±0.2sec
day day day day day / 24h / 24h / 24h / 24h / 24h
Supply Failure Reserve 200hrs No 200hrs No 200hrs 5 years 5 years 5 years 5 years 5 Years Lithium
lithium lithium lithium lithium Battery
battery battery battery battery
Reached in 120h 120h 120h 120h 120h - - - - -
Manual Switch Type On Off Off Off Off - - - - -
Auto Auto Auto Auto Auto
On On On On On
Protection Degree - - - - - IP20 IP20 IP20 IP20 IP20
Environment
Working Temperature -10ºC to -10ºC to -10ºC to -10ºC to -10ºC to -5ºC to -5ºC to -5ºC to -5ºC to -10ºC to
+45ºC +45ºC +45ºC +45ºC +45ºC +45ºC +45ºC +45ºC +45ºC +45ºC
Storage Temperature -100ºC -100ºC -100ºC -100ºC -100ºC -20ºC to -20ºC to -20ºC to -20ºC to -20ºC to
to +50ºC to +50ºC to +50ºC to +50ºC to +50ºC +70ºC +70ºC +70ºC +70ºC +70ºC
Connection
Flexible 0.5 to 0.5 to 0.5 to 0.5 to 0.5 to 1.5 to 1.5 to 1.5 to 1.5 to 1 to 4mm2
4mm2 4mm2 4mm2 4mm2 4mm2 10mm2 10mm2 10mm2 10mm2
Rigid - - - - - 1 to 6mm2 1 to 6mm2 1 to 6mm2 1 to 6mm2 1.5 to 6mm2

EH010 / EH011 Ph EH110 / EH111 / EH171 Ph


N
N
230 VM ±10% 50/60Hz 230 VM ±10% 50/60Hz

3 M

2 4 1 2 3 4 5 6
1 3

2.55 Data is subject to errors and technical modifications.


Electromechanical & Digital Time Switches
Selection Chart

Time Clocks/Switches Selection Chart

Electromechanical Time Clocks Digital Time Clocks


1 Channel 1 Channel 2 Channels 4 Channels

1 Modules 3 Modules 1 Modules 2 Modules 2 Modules 4 Modules


EH010 EH110 EG071 EG103 EG203 EG493E
EH011 EH111 EG010 EG103E EG203E
EH171

Modular Devices
Programming Cycle Electromechanical Digital

& Connection
1 Channel 1 Channel 2 Channels 4 Channels
1 Module 3 Modules 1 Modules 2 Modules 2 Modules 4 Modules
EH010 EH110
24 Hours EG010
EH011 EH111
EG103 EG203
7 Days EH171 EG071
EG103E EG203E

Annual EG493E

Data is subject to errors and technical modifications. 2.56


1 Channel Digital Time Switch - EG010, EG071
Technical Data

Technical Characteristics - EG010 Product Presentation

Display
Electrical Characteristics 1. Time
2. Circuit Status
Voltage Supply 230V ±10% 50/60Hz 1 3. Program Selection
Consumption 1VA
Output 1 Changeover contact OFF 2 Buttons
16A - 250V AC 1 4. P to select the program to
3 apply
3A - 250V cosw = 0.6
1000W Incandescent lighting 5. Reset
6. to scroll program steps
Functional Characteristics P 7. + and - : to input time
Number of programs 5 Adjustable Pre-recorded Programs 4 5
Accuracy ±6min per year
Supply Failure Reserve Total of 3 years
6
Environment - +
Working Temperature -10ºC to +50ºC
7
Modular Devices

Storage Temperature -10ºC to +60ºC


& Connection

Cable Capacity 1 to 4mm2


Main Characteristics Easy to program: 5 programs are
pre-recorded. The user just has to select the Electrical Connection
program which corresponds to its use and
modify time switches if necessary. L
N

The 5 pre-registered programs are as follows:

5 6
P Prog

P0 OFF

P1 ON
EG 010
P2 6.00
1 2 3
23.00
3 4
P3 1 2
6.00 8.00 17.00 23.00

P4
6.00 8.00 11.00 13.00 17.00 23.00

Technical Characteristics - EG071 Product Presentation


Display
1. Time
Electrical Characteristics 2. Circuit Status
1 3. Days of the week
Voltage Supply 230V ±10% 50/60Hz
Consumption 1VA OFF 2 Buttons
Output 1 Changeover contact 4. ON / OFF : to select the circuit
16A - 250V AC 1 status
3A - 250V cosw = 0.6 3 5. Reset
1000W Incandescent lighting on/off Prog 6. Prog: to program the device and
4 5 scroll program
Functional Characteristics steps
Number of programs 20 Program Steps (each program step can be 6 7. To input time and day
applied to one of several days)
Accuracy ±6min per year
- +
Supply Failure Reserve Total of 3 years
Environment
Working Temperature -10ºC to +50ºC 7
Storage Temperature -10ºC to +60ºC
Cable Capacity 1 to 4mm2 Electrical Connection

5 6

EG 071
EG 010
3 4
1 2

2.57 Data is subject to errors and technical modifications.


Digital Time Switches
Technical Data

(EG103/EG103E) (EG203/EG203E)

+ A + B
2 2
1 1
ok menu ok menu

4 3 4 3

Modular Devices
& Connection
Keys Major Characteristics

1. Menu Selection of operating mode - Product delivered with current time and date set
Auto Mode of running according to the program selected - Automatic change of winter / summer time
Prog New for programming mode - Programming key
- For permanent waivers
Prog To modify an existing program
- For program copy or save
Checking of the program - Programming for day or group of days
Modification of time, date and selection of the winter/summer - 56 program steps On, Off
time change mode. - Impulses (1 sec to 30 min)*
Holidays - Permanent overrides On or Off ( permanent light on)
- Temporary overrides On or Off ( flashing)
2. +/- Navigation or setting of values
- Holiday mode : overrides On or Off between two dates*
In auto, mode, selection of overrides, waivers or - Simulation of presence *
random operation - Display bar graph of daily profile
3. OK To validate flashing information on display - Keyboard locking possible
4. To return to the previous step - Programmable with power off
- Back lit display*
You may return into auto mode at any moment using menu.
If no action is taken for 1 min, the switch returns to auto mode. * Evolution models E or V only

Connection Diagram EG103* Connection Diagram EG203*

L/+
N/- L
N

(EG 103E)

1 3 5 7 1 3 5 7

2 4 6 8
2 4 6 8

Data is subject to errors and technical modifications. 2.58


Astronomical Time Switches
Technical Data

Technical Characteristics

EE180 (1 Channel) EE181 (2 Channel)


Width in 17.5mm Modules 2 2
Supply Voltage 230V AC (+10 % / -15%, 50/60Hz
Number of Outputs 1 2
Characterisitics of Relay Change over contact 16A C 1 250V /10A cos phi = 0.6
Incandescent 2300W
230V Halogen 2300W
Standards CE + CTICK and CEI 60-669
Connection
Flexible 1 to 6mm2
Rigid 1.5 to 10mm2
Environment
Storage Temperature -20ºC to +60ºC
Modular Devices

Working Temperature -10ºC to +55ºC


& Connection

IP IP20
Functional Characteristics
Display LCD Without backlight screen
Operating reserve Lithium battery 5 years
Precision +/- 1.5s/day
Programming Key Yes
Automatic change of winter / summer
Yes
time
Functions available in free
Weekly programming / permanent override / temporary override
programming
Astro Functions
Independent programming for each
Astro mode Yes
channel
Programming of the lighting
Yes (if channel Astro)
interrution
Temporary override 15 / 30 / 60min
Maintained ON Adjustment common to the 2 channels
Anticipation ON Adjustment common to the 2 channels

Electrical Connection Product Presentation Keys


EE180 : 1 Channel 1. Menu Selection of operating mode
Auto Mode of running according to the program selected
Prog New for programming mode
Prog To modify an existing program
Checking of the program
Modification of time, date and selection of the winter/
1 3 5 7
summer time change mode
EE180
Astro Astronomical mode
+ Ì Indicated that the channel is in astronomical mode
A B 2 2. +/- Navigation or setting of values
2 4 6 8 A In auto, mode, selection of overrides, waiver or random
1 B
operation
ok menu
3. OK To validate flashing information on display
4. To return to the previous step
4 3
You may return into auto mode at any moment using menu.
If no action is taken for 1 min, the switch returns to auto mode.

EE181 : 2 Channels

1 3 5 7
EE180

2 4 6 8

2.59 Data is subject to errors and technical modifications.


Time Lag Switches
Technical Data

Time Lag Switches Wiring Diagrams


A common area where time delay devices are used is stairways and corridors in 4-Wire
multi occupancy buildings where they provide a level of energy efficiency. The
EMN001 device provides basic time lag control.

Technical Specification

EMN001 EMN002 EMN005


Electrical Characteristics
Supply voltage 230V +10 -15% 230V +10 -15% 230V +10 -15% N 3
50/60Hz 50/60Hz 50/60Hz
L 4
Consumption 1VA 0.5W Permanent 1VA
8W Max.
Size (Module) 1 - 1
Breaking Capacity 3-Wire
AC1 16A 230V AC 4A 230V~ 16A

Modular Devices
Incandescent 2300W 1000W 2300W

& Connection
Halogen 230V 2300W 1000W 2300W
Ferro Magnetic Transformer 1600W - -
Parallel Compensated Capacitor 112μF - -
Fluorescent Lamps 1000W 1000W
Series Compensated 3600W - 1000W
Electronic Transformer 2300W - - N 3
Compact Fluorescent 60 x 7W or - - L 4
Lamps with Electronic 40 x 11W or
Ballast 32 x 15W or
20 x 23W
23000W
with Conventional Ballast - -
Functional Characteristics Combination EMN002 with EMN001
Time Delay 30s to 10min 24s 30s to 10min
Retrigger Yes - -
Max. Current in Rest 100mA - -
Position
7
Automatic 3/4 Recognition Yes - - EM 002
Local Command Automatic / - Automatic /
Override On Override On
Environment N 3
Working Temperature -10 to +55ºC -15 to +55ºC -10 to +55ºC 8
L 4
Storage Temperature -20 to +60ºC -25 to +70ºC -20 to +60ºC
Connection
Flexible 1 to 6mm2 1 to 6mm2 1 to 6mm2
2 2
Rigid 1.5 to 10mm 1.5 to 10mm 1.5 to 10mm2
Connection EM001/EM002 - 2 wires 1.5 -

A: Basic Mode 230V


Press push button to switch ON the light. After a set time (Adjustable “T”, the 0V
light will switch OFF automatically.
A
B: Prewarning Mode
A signal (blink) will appear before the end of the lighting period. T T

C: Double delay mode


Press push button to switch light ON. After a set time (Adjustable “T”, the light
will switch OFF automatically. If you press the buton for more than 3 seconds,
a time lag of one hour begin.
230V

B 0V

T 10s 30s

230V
C 0V
>3 >3 >3

1h

T T

Data is subject to errors and technical modifications. 2.60


Delay Timers
Technical Data

Delay Timers Multifunction Timer - 6 Individual Functions


Delay timer devices are used to control a variety of processes where the A = Timer.
requirement is for switching circuits on, off or delaying the on or off switching B = Delay off (output relay opens either at end of command or after set time
for a pre-set period of time. Typical device types are: period - which ever is shorter).
C = Delay off.
- Delay on - intended to delay the starting or switching of a circuit for a set D = Delay on.
period of time following the command signal e.g. to delay the starting of E = Delay on (output relay closes either at end of command or after set time
motor loads where a large number of motors are to be started by the same period - which ever is shorter).
switch to reduce the effects of the starting currents. F = Symmetrical timer.
- Delay off - intended to delay the stopping or switching off of a circuit for a
set period of time following the removal of the command signal e.g. to On selection - contact permanently closed
overrun an extractor following the switching off of a process that creates Off selection - contact permanently open
fumes.
- Adjustable time on - intended to switch on for a set period, the command Output relay open - with no command
signal must remain on throughout the set period e.g. to switch on two sets
of heaters with one set (the boost) switching off after the set period. Output relay open - with command signal running
- Impulse timer - intended to switch on for a set period, the command
signal length is not important e.g. to boost a time clock controlled circuit Output relay closed - with command signal running
such as a water storage heater.
- Symmetrical timer - intended to toggle a circuit on and off in regular time Output relay close - with command signal removed
Modular Devices

patterns e.g. to run an extractor intermittently.


& Connection

Output relay closed (EZN005)

T T

T T T T T T

2.61 Data is subject to errors and technical modifications.


Delay Timers
Technical Data

Technical Specifications Functional characteristics


EZN001, EZN003, EZN005, EZ006
(functions D,E,F)
EZN001, EZN002, EZN003, EZN004, EZN005, EZN006 CD : Command.
Electrical Characteristics O : Output.
T : Time delay.
Supply Voltage 24-28 Vdc
12-48 Vdc (+10%) Terminals A1 & A2 Ph / +
12-230 Vac (+10%) Terminals A3 & A2 N/-

Output 1 Volt Free C/O Contact


A2
Life Expectancy
15
Max Load AC 1 8A / 230V~ 50,000 Cycles
Incandescent 450W~ 500,000 Cycles
18 16
Fluorescent Non Comp. 600W~ 50,000 Cycles
18 16
Inductive Load 0.6pf 5A / 230V~ 100,000 Cyles A1
15
Min Power
AC 100mA at 230V

Modular Devices
DC 100mA at 12V EZN002, EZN004, EZN006
(functions A,B,C)

& Connection
Galvanic Isolation 2kV
indicator light (for versions with NO
Standard / Norm BS EN 60669-2-1 contact).
Functional Characteristics ON
Timer Range 0.1s - 10 hours
OFF

Min. Command Period Ph / +


N/-
AC 50ms
A2 B1
DC 30ms
Operating Temperature 15

Working -20ºC to +50ºC


Storage -40ºC to +50ºC 18 16

Connection Capacity 18 16
A1
15
2
Flexible 1 to 6mm
Rigid 1.5 to 10mm2

Data is subject to errors and technical modifications. 2.62


Connection
Quick Connect & Cage Terminal Bases

Neutral, earth and phase terminals

Quick Connect Terminals Cage Terminals

KN06N KN10N KN14N KN18N KN22N KN26N KN04N KN07N


Modular Devices

KN06P KN10P KN14P KN18P KN22P KN26P KN04P KN07P


KN06E KN10E KN14E KN18E KN22E KN26E
& Connection

H 33 33 33 33 33 33 33 33

A 30 45 60 75 90 105 45 75

B 34 34 34 34 34 34 18 18

Terminal Supports

VZ711 GZ30A KN00A


VZ710
volta, vector gamma universal
vega, vega D
supports

H 32 35 30 35

A 240 315 195 105

B 42 42 42 42

Number 47 62 38 20

The number indicates the quantity of quickconnect terminals on the support.

2.63 Data is subject to errors and technical modifications.


Connection
Quick Connect & Cage Terminal Bases

Connection

Bridge for 2 terminals Quick Connect 1.5 to 4 mm2 Max. 25 mm2 wires in a cage Disconnecting with screwdriver
wires terminal

Modular Devices
& Connection
Mounting

Clipping on terminal bases Universal support :


and universal bases Horizontal mounting on DIN rail Vertical mounting on DIN rail Divisible universal support

Combinations: quantity of Quick Connect terminals on the bases

Quick Connect KN06N/P/E KN10N/P/E KN14N/P/E KN18N/P/E KN22N/P/E KN26N/P/E


terminals KN04N/P KN07N/P

Number of blocks 1 1.5 2 2.5 3 3.5

Quick Connect VZ710 GZ30A VZ711 vector, volta, KN00A


terminals bases Vega 18 surface, Vega D Gamma Gala, Vega 18 flush universal support

number of blocks 10.5 6.5 8 3.5


The bases above accept blocks combinations (neutral, phase and earth).
Connection between same terminals is done using equipotential bridgings (KN99x).

Data is subject to errors and technical modifications. 2.64