Proheat Control Manual 8000
Proheat Control Manual 8000
8000series
NOTE:
It is strongly recommended that a process should incorporate a
LIMIT CONTROL which will shut down the equipment at a
preset process condition in order to preclude possible damage
to products or system.
Select the
parameters for
view in the user
menu by using
v
L1
120V
L2
Fuse
High Limit
Contactor
Coil
Solid state
Relay
6000-201-00 L91-4110
Proheat Control Limit Control
Alarm
1 7 Heater 1 6
2 8
2 7
3 9
4 10 3 8
4 9
Quick Reference Guide
5 11 Process Limit
Sensor Sensor 5 10
6 12
vi
vii
L1
120V
L2
Fuse
High Limit
Contactor
Coil
Mercury
6000-101-00 Relay L91-4110
Proheat Control Limit Control
Alar
1 7 Heater 1 6
2 8
2 7
3 9
4 10 3 8
5 11 Process Limit 4 9
Quick Reference Guide
Sensor Sensor 5 10
6 12
Chapter 3 Programming
3-1 Lockout -----------------------31
3-2 Signal Input ------------------31
3-3 Control Outputs --------------32
3-4 Alarm ---------------------------37
3-5 Configure User Menu -----38
3-6 Ramp -------------------------39
3-7 Dwell Timer ------------------40
3-8 PV Shift -----------------------41
3-9 Digital Filter -------------------41
3-10 Failure Transfer -------------42
3-11 Auto-tuning ------------------43
3-12 Manual tuning -------------44
3-13 Manual Control -------------45
3-14 Data communication -----47
3-15 PV Retransmission----- -----47
3
Chapter 1 Overview
1-1 General
The Fuzzy Logic plus PID microprocessor-based controller series,
incorporate two bright, easy to read 4-digit LED displays, indicating
process value and set point value. The Fuzzy Logic technology
enables a process to reach a predetermined set point in the
shortest time, with the minimum of overshoot during power-up or
external load disturbance.
SERIES 6000 is a 1/16 DIN size panel mount controller. SERIES 4000
is a 1/4 DIN size panel mount controller. SERIES 8000
is a 1/8 DIN size panel mount controller. These units are powered by
11-26VAC/VDC or 90-250 VAC supply, incorporating a 2 amp. control
relay output as standard. The second output can be used as cooling
control, or an alarm. Both outputs can select triac, 5V logic output,
linear current or linear voltage to drive external device. There are
six types of alarm plus a dwell timer can be configured for the third
output. The units are fully programmable for PT100 and thermocouple
types J,K, T, E, B, R, S, N, L with no need to modify the unit. The input
signal is digitized by using a 18-bit A to D converter. Its fast sampling
rate, 5 scans/second, allows the unit to control with greater accuracy
and response time.
4
PID control with properly tuned
Temperature PID + Fuzzy control
Set
point
Figure 1.1
Fuzzy Control
Advantage
Time
High Accuracy
This Series controllers are manufactured with custom designed
ASIC(Application Specific Integrated Circuit ) technology which
contains a 18-bit A to D converter for high resolution measurement
( true 0.1 F resolution for thermocouple and PT100 ) and a 15-bit
D to A converter for linear current or voltage control output. The
ASIC technology provides improved operating performance,
low cost, enhanced reliability.
Fuzzy Control
The function of Fuzzy control is to adjust PID parameters from time to
time in order to make manipulation output value more flexible and
adaptive to various processes. The results is to enable a process to
reach a predetermined set point in the shortest time, with the minimum
of overshoot and undershoot during power-up or external load
disturbance.
Digital Communication
The units are equipped with RS-485 or RS-232 interface card to
provide digital communication. By using the twisted pair wires there
are at most 247 units can be connected together via RS-485 interface
to a host computer.
5
Programming Port
A programming port is used to connect the unit to a hand-held
programmer or a PC for quick configuration, also can be connected
to an ATE system for automatic testing & calibration.
Auto-tune
The auto-tune function allows the user to simplify initial setup for a
new system. A sophisticated algorithm is provided to obtain an optimal
set of control parameters for the process, and it can be applied
either as the process is warming up (cold start) or as the process
has been in steady state (warm start).
Lockout Protection
According to your security requirements, one of four lockout levels
can be selected to prevent unauthorized changes.
Bumpless Transfer
Bumpless transfer allows the controller to continue to control by
using its previous values if a sensor fails.
Soft-start Ramp
The ramping function is performed during power up as well as any
time the set point is changed. It can be ramping up or ramping down.
The process value will reach the set point with a predetermined
constant rate.
Digital Filter
A first order low pass filter with a programmable time constant is used
to improve the stability of process value. This is particularly useful in
certain application where the process value is unstable.
SEL Function
The units have the flexibility to select parameters which are most
significant so as to put these parameters in the front of display
sequence. There are 8 parameters that can be selected to allow the
user to build a custom display sequence.
6
1-2 Ordering Code
40 - -
60 Options
80
0: Panel mount IP50 standard
1: Panel mount IP65 water
Power Input resistant rubber installed
2: DIN Rail mount with IP50
0: 90 - 250 VAC, (for 9100 only)
50/60 HZ 3: DIN Rail mount with IP65
1: 11 - 26 VAC or (for 9100 only)
VDC
X: Special Order
Communications
Signal Input 0: None
1: RS-485 interface
0: Standard Input 2: RS-232 interface
Thermocouple: 3: Retransmit 4-20mA / 0-20mA
J, K, T, E, B, R, 4: Retransmit 1-5 V / 0-5V
S, N, L 5: Retransmit 0-10V
RTD: PT100 DIN, X: Special order
PT100 JIS
1: 0 - 60 mV
2: 0 -1 V Alarm
3: 0 - 5 V 0: None
4: 1 - 5 V 1: Form C relay 2A/240VAC
5: 4 - 20 mA 9: Special order
6: 0 - 20 mA Output 2
7: 0 - 10 V 0: None
X: Special Order 1: Form A relay 2A/240VAC
2: Pulsed voltage to
drive SSR, 5V / 30mA
3: Isolated 4 - 20mA / 0 - 20mA
Output 1 4: Isolated 1 - 5V / 0 - 5V
0: None 5: Isolated 0 - 10V
1: Relay rated 2A/240VAC 6: Triac output, 1A / 240VAC,
SSR
2: Pulsed voltage to drive SSR, 7: Isolated 20V/25mA
5V/30mA transducer power supply
3: Isolated 4 - 20mA / 0 - 20mA 8: Isolated 12V/40mA
4: Isolated 1 - 5V / 0 - 5V transducer power supply
5: Isolated 0 - 10V 9: Isolated 5V/80mA
6: Triac output 1A / 240VAC,SSR transducer power supply
C: Pulsed voltage to drive SSR, C: Pulsed voltage to drive SSR,
14V/40mA 14V/40mA
X: Special order X: Special order
7
1-3 Programming Port
Rear Front
Terminal Panel
Figure 1.2
Programming Port
6 4 2
Overview
5 31
Access Hole
6 4 2
5 31
The programming port is used for off-line automatic setup and testing
procedures only. Do NOT attempt to make any connection to these
pins when the unit is in normal operation.
8
1- 4 Keys and Displays
KEYPAD OPERATION
SCROLL KEY :
This key is used to select a parameter to be viewed or adjusted.
UP KEY :
This key is used to increase the value of selected parameter.
DOWN KEY :
This key is used to decrease the value of selected parameter.
RESET KEY : R
This key is used to:
1. Revert the display to display the process value.
2. Reset the latching alarm, once the alarm condition is
removed.
3. Stop the manual control mode , auto-tuning mode and calibration
mode.
4. Clear the message of communication error and auto-tuning error.
5. Restart the dwell timer when the dwell timer has been time out.
6. Enter the manual control menu during failure mode occurs.
9
Alarm Upper Display, to display process value,
Indicator menu symbol and error code etc.
Output 2 Process Unit Indicator
Indicator
Output 1 OP1 OP2 ALM
Indicator C F
R Figure 1.4
6000 Display of Initial Stage
10
1- 5 Menu Overview
User Setup Manual Auto-tuning Calibration
menu menu Mode Mode Mode
11
1-6 Parameter Descriptions
Parameter Parameter Description Range Default
Notation Value
25.0 C
SP1 Set point for output 1 Low: SP1L High :SP1H (77.0 F)
Set point for output 2
Low: -19999 High :45536 10.0 C
SP2 when output 2 performs (18.0 F)
alarm function
Set point for alarm or Low: -19999 High: 45536 10.0 C
SP3 dwell timer output (18.0 F)
0 : No parameter
is locked
1 : Setup data are
Select parameters to be locked
LOCK 0
locked 2 : Setup data and
User data except Set
point are locked
3 : All data are locked
0 : J type thermocouple
1 : K type thermocouple
2 : T type thermocouple
3 : E type thermocouple
4 : B type thermocouple
5 : R type thermocouple
6 : S type thermocouple
7 : N type thermocouple
8 : L type thermocouple
1
INPT Input sensor selection 9 : PT 100 ohms DIN (0)
curve
10 : PT 100 ohms JIS
curve
11 : 4 - 20 mA linear
NOTE; 12
current input
: 0 - 20 mA linear
Input Selection current input
11 - 17 13 : 0 - 60 mV linear
millivolt input
of Linear (ma/VDC) 14 : 0 - 1V linear voltage
Require input
special order 15 : 0 - 5V linear voltage
input
only See Matrix 16 : 1 - 5V linear voltage
Page 8. input
17 : 0 - 10V linear voltage
input
12
Parameter Parameter Description Range Default
Notation Value
0 : Degree C unit
0
UNIT Input unit selection 1 : Degree F unit
(1)
2 : Process unit
0 : No decimal
point
1 : 1 decimal digit
DP Decimal point selection 1
2 : 2 decimal digits
3 : 3 decimal digits
0 : 0 second time
constant
1 High: : 0.2 second time
constant
2 : 0.5 second time
constant
3 : 1 second time
constant
4 : 2 seconds time
Filter damping time constant
FILT 5 2
constant of PV : 5 seconds time
constant
6 : 10 seconds time
constant
7 : 20 seconds time
constant
8 : 30 seconds time
constant
9 : 60 seconds time
constant
13
Parameter Parameter Description Range Default
Notation Value
0 : Reverse (heating )
control action
OUT1 Output 1 function 0
1 : Direct (cooling)
control action
0 : Relay output
1 : Solid state relay
drive output
2 : Solid state relay
output
3 : 4-20 mA current
module
O1TY Output 1 signal type 4 : 0 - 20 mA current 0
module
5 : 0 - 1V voltage
module
6 : 0 - 5V voltage
module
7 : 1 - 5V voltage
module
8 : 0 - 10V voltage
module
Select BPLS ( bumpless
transfer ) or 0.0 ~ 100.0 % to
Output 1 failure transfer continue output 1 control
O1FT mode function as the unit fails, or 0
select OFF (0) or ON (1)
for ON-OFF control.
CYC1 Output 1 cycle time Low: 0.1 High: 90.0 sec. 18.0
OFST Offset value for P control Low: 0 High: 100.0 % 25.0
0 : No Ramp Function
1 : Use unit/minute as
RAMP Ramp function selection Ramp Rate 0
2 : Use unit/hour as
Ramp Rate
14
Parameter Parameter Description Range Default
Notation Value
0 : Output 2 No Function
0 : Relay output
Output 2 hysteresis
value when output 2 50.0 C 0.1 C
O2HY performs alarm Low: 0.1 High: (90.0 F) (0.2 F)
function
CYC2 Output 2 cycle time Low: 0.1 High: 90.0 sec. 18.0
15
Parameter Parameter Description Range Default
Notation Value
Heating-cooling dead
DB band (negative value= Low: -36.0 High: 36.0 % 0
overlap)
0 : Normal alarm
action
1 : Latching alarm
ALMD Alarm operation mode action 0
2 : Hold alarm action
0 : Alarm output ON as
Alarm failure transfer unit fails
ALFT mode 0
1 : Alarm output OFF as
unit fails
0 : No communication
Communication
COMM function 1 : Modbus RTU mode 1
protocol
2 : 4 - 20 mA
PV Retransmission
3 : 0 - 20 mA
PV retransmission
4 : 0 - 5 VDC
PV Retransmission
5 : 1 - 5 VDC
PV Retransmission
6 : 0 - 10 VDC
PV Retransmission
16
Parameter Parameter Description Range Default
Notation Value
Address assignment of
ADDR digital communication Low: 1 High: 255
0 : Even parity
Parity bit of digital 1 : Odd parity
PARI communication 0
2 : No parity bit
2
0 : No parameter selected
6 : PB is put ahead
7 : TI is put ahead
17
Prameter Parameter Description Range Default
Notation Value
8 : TD is put ahead
12 : RR is put ahead
Select 1'st parameter for
SEL1 user menu 13 : O2HY is put ahead 2
16 : DB is put ahead
18
Dangerous voltages capable of causing death are sometimes
present in this instrument. Before installation or beginning any
troubleshooting procedures the power to all equipment must be
switched off and isolated. Units suspected of being faulty must be
disconnected and removed to a properly equipped workshop for
testing and repair. Component replacement and internal adjustments
must be made by a qualified maintenance person only.
Upon receipt of the shipment remove the control from the carton
and inspect for any shipping damage. If any damage have
occured, report and claim with the shipping carrier. Write down
the model number, serial number, and date code for future
reference when corresponding with our service team. The serial
number (S/N) and date code (D/C) are labeled on the box and
the housing of control.
19
Figure 2.1 Mounting Dimensions
92 mm
Panel
92 mm
53 mm
3.62” 2.08”
Panel
92 mm
3.62”
Cutout 8000 Series
Panel
45 mm
1.77”
65 mm
2.55”
1.77” Panel
45 mm
1.77”
Panel
45 mm
104.8mm
4.12”
20
2 - 3 Wiring Precautions
Before wiring, verify the label for correct model number and
options.
Verify that the ratings of the output devices and the inputs as
specified in Chapter 5 are not exceeded.
21
3.2mm min. 7.0mm max.
Figure 2.2
Lead Termination for
4000 Series & 8000 Series
6.0mm max.
Figure 2.3
Lead Termination
3.0mm min. for 6000 Series
90-250VAC 1 L 11
47-63 Hz
12VA 2 N 12
3 C TX1 TXD 13 +
+
RE RS-485
OP1 /Retransmission Ma
_ 4 NO TX2 RXD 14 - RE
RS-232
5 C COM 15
+
OP2
_ 6 NO 16
7 C 17
A
ALM 8 NO PTA 18
RTD
TC+, V+
9 NC PTB, mA+ 19 B
+
+
+
TC-, V- _ _V _
10 PTB, mA-
20 B
TC V mA RTD
Figure 2.4
Rear Terminal Connection
for 4000 Series & 8000 Series
22
PV Retrans + -
RS-232: TXD RXD COM
RS-485: TX1 TX2
13 14 15
1 NO L 7 90-250 VAC
47-63 Hz
12VA
ALM 2 NC
N 8
3 C C 9
+
OP1
A 4 PTA NO 10 _
RTD
TC+, V+
5 C 11
+
+
PTB, mA+
I V OP2
_ _ TC-, V-
B 6 PTB, mA- NO 12 _
Figure 2.6
Rear Terminal Connection for 6000 Series
23
The controller is supplied to operate at 11-26 VAC / VDC or 90-250
VAC. Check that the installation voltage corresponds with the power
rating indicated on the product label before connecting power to
the controller.
24
Proper sensor type is also a very important factor to obtain precise
measurements. The sensor must have the correct temperature range
to meet the process requirements. In special processes the sensor
might need to have additional options such as leak-proof, anti-
vibration, be un-grounded or have special sheath materials.
+
+
PTB, mA+ V
TC-, V- 20 TC-, V- 6 _ _ _ B
PTB, mA- PTB, mA-
TC V mA RTD
3 9 LOAD
4 10
120V/240VAC
Mains Supply
Figure 2.9
Output 1 Relay or Triac (SSR) to Drive Load External Device
25
2-7 Control Output 1 Wiring (Cont’d)
External device
+
3 9 Output
+
Output
4 _ 10 _ _
30mA / 5V 5V
Pulsed
Voltage 33 +
33
0V
External device
4000 Series
8000 Series 6000 Series
+
+
4000 Series
8000 Series 6000 Series External device
+
+
26
Control Output 2 Wiring
4000 Series
8000 Series 6000 Series
5 11 LOAD
6 12
120V/240VAC
Mains Supply
Figure 2.13 External device
Output 2 Relay or Triac (SSR) to Drive Load
+
5 11
+
5 VDC @ 30 ma
Pulsed Voltage
_
6 _ 12 _
120V /240V
Mains Supply
30mA / 5V 5V
Pulsed
Voltage 33 +
33
0V
5 0 - 20mA, 11 0 - 20mA,
Load
4 - 20mA 4 - 20mA
6 _ 12 _
Maximum
Load
500 ohms
Figure 2.15 Output 2 Linear Current
27
Control Output 2 Wiring (Cont’d)
4000 Series. External device
8000 Series 6000 Series
+
+
+
5 0 - 1V, 0 - 5V 11 0 - 1V, 0 - 5V
Load
1 - 5V, 0 - 10V 1 - 5V, 0 - 10V
6 _ 12 _
_
Minimum
Load
Figure 2.16 Output 2 Linear Voltage 10 K ohms
4000 Series
8000 Series 6000 Series
7 3 LOAD
8 1
9 2
120V/240VAC
Figure 2.17 Alarm Output to Drive Load Mains Supply
External device
Output to
Re+ 13 +0-20/4-20ma, Recorder,
PLC, Etc.
0-5/1-5VDC, 0-10VDC
Re - 14
-
Load Resistance : 0 - 500 ohms ( for current output )
10 K ohms minimum ( for voltage output )
Figure 2.18
Retransmission Output Wiring
28
2-10 Data Communication
4000 Series
6000 Series RS-485 to RS-232
8000 Series network adaptor
TX1
TX113 SNA10A or
SNA10B
TX2 14 TX2
RS-232
Twisted-Pair Wire
4000 Series
6000 Series
8000 Series
TX1
TX1 13
TX2 14
TX2
4000 Series
6000 Series
8000 Series
TX1
TX1 13
TX2
TX2 14 Terminator
220 ohms / 0.5W
29
RS-232
4000 Series
6000 Series
8000 Series
PC
TXD 13
RXD 14
COM 15 9-pin
RS-232
port
CC94-1
Figure 2.20
RS-232 Wiring
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable
must be modified according to the following circuit diagram.
Figure 2.21
Configuration of RS-232
30
Chapter 3 Programming
Press for 3 seconds and release to enter setup menu. Press
to select the desired parameter. The upper display indicates the
parameter symbol, and the lower display indicates the selected value
of parameter.
3-1 Lockout
There are four security levels that can be selected by using
the LOCK parameter.
If NONE is selected for LOCK, then no parameter is locked.
If SET is selected for LOCK, then all setup data are locked.
If USER is selected for LOCK, then all setup data as well as user data
(refer to section 1-5) except set point is locked to prevent from being
changed.
If ALL is selected for LOCK, then all parameters are locked to prevent
from being changed.
31
process value
INHI
Figure 3.1
PV Conversion Curve for
Linear Type Process Value
INLO
input signal
SL S SH
S SL
Formula : PV = INLO + ( INHI INLO )
SH SL
Example : A 4-20 mA current loop pressure transducer with range
0 - 15 kg/cm is connected to input, then perform the
following setup :
INPT = 4 - 20 INLO = 0.00
INHI = 15.00 DP = 2-DP
Of course, you may select other values for DP to alter
the resolution.
Control
Modes OUT1 OUT2 O1HY O2HY CPB DB
Heat: PID
Cool: PID REVR COOL
32
Heat Only ON-OFF Control : Select REVR for OUT1, Set PB to 0,
O1HY is used to adjust dead band for ON-OFF control, The output 1
hysteresis ( O1HY ) is enabled in case of PB = 0 . The heat only
on-off control function is shown in the following diagram :
PV
SP1
SP1 O1HY
ON
OFF
Time
Figure 3.2 Heat Only
ON-OFF Control
The ON-OFF control may introduce excessive process oscillation even
if hysteresis is minimized to the smallest. If ON-OFF control is set ( ie.
PB = 0 ), TI, TD, CYC1, OFST, CYC2, CPB, DB will be hidden and have
no function to the system. The auto-tuning mode and bumpless
transfer will be disabled too.
33
then increase OFST 25 %, and vice versa. After adjusting OFST value,
the process value will be varied and eventually, coincide with set point.
Using the P control (TI set to 0), the auto-tuning is disabled.
Refer to section 3-12 "manual tuning" for the adjustment of PB and
TD. Manual reset (adjust OFST) is not practical because the load may
change from time to time and OFST would require repeated changes.
Selecting the PID option will prevent this issue.
Heat only PID control : Selecting REVR for OUT1, PB and TI should
not be zero. Operate auto-tuning for the new process, or set PB, TI
and TD with historical values. See section 3-11 for auto-tuning
operation. If the control result is still unsatisfactory, then use manual
tuning to improve the control . See section 3-12 for manual tuning. The
unit contains a sophisticated PID and Fuzzy algorithm to eliminate
overshoot when the control is properly tuned.
Other Setup Required : O1TY, CYC1, O2TY, CYC2, O1FT, O2FT O1TY
& O2TY are set in accordance with the types of OUT1 & OUT2
installed. CYC1 & CYC2 are selected according to the output 1 type (
O1TY ) & output 2 type ( O2TY ). Generally, selects 0.5 ~ 2 sec. for
CYC1, if SSRD or SSR is used for O1TY; 10 ~ 20 sec. if relay is used
for O1TY, and CYC1 is ignored if linear output is used. Use similar
selections for CYC2.
34
You can use the auto-tuning program for new processes or directly
set the appropriate values for PB, TI & TD according to historical
data for the repeated systems. If the control behavior is still
inadequate, then use manual tuning to improve the control. See
section 3-12 for manual tuning.
35
PV OUT2=DE.HI
SV+SP2
SV+SP2-O2HY
ON
OFF
PV
SP2+O2HY
SP2
ON
OFF
36
3-4 Alarm
The controller has one alarm output. There are 6 types of alarm
functions and one dwell timer that can be selected, and four kinds of
alarm modes (ALMD) that are available for each alarm function
(ALFN). Besides the basic alarm output, output 2 can also be
configured as an alarm. But output 2 only provides 4 kinds of alarm
functions and only the normal alarm mode is available for this alarm.
A process alarm sets two absolute trigger levels. When the process is
higher than SP3, a process high alarm ( PV.HI ) occurs, and the alarm
is off as the process is lower than SP3-ALHY. When the process is
lower than SP3, a process low alarm ( PV.LO ) occurs and the alarm is
off as the process is higher than SP3+ALHY. A process alarm is
independent of set point.
A deviation alarm alerts the user when the process deviates too far
from set point. When the process is higher than SV+SP3, a deviation
high alarm (DE.HI) occurs and the alarm is off as the process is lower
than SV+SP3-ALHY. When the process is lower than SV+SP3, a
deviation low alarm (DE.LO) occurs and the alarm is off as the process
is higher than SV+SP3+ALHY. Trigger level of deviation alarm is
moving with set point.
A deviation band alarm presets two trigger levels relative to set point.
The two trigger levels are SV+SP3 and SV - SP3 for alarm. When the
process is higher than ( SV+SP3 ) or lower than ( SV - SP3 ), a
deviation band high alarm ( DB.HI ) occurs. When the process is within
the trigger levels, a deviation band low alarm (DB.LO) occurs.
In the above descriptions SV denotes the current set point value for
control which is different from SP1 as the ramp function is performed.
There are four types of alarm modes available for each alarm function,
these are: Normal alarm, Latching alarm, Holding alarm and Latching/
Holding alarm. They are described as follows:
37
Normal Alarm : ALMD = NORM
When a normal alarm is selected, the alarm output is de-energized
in the non-alarm condition and energized in an alarm condition.
Latching Alarm : ALMD = LTCH
If a latching alarm is selected, once the alarm output is energized, it
will remain unchanged even if the alarm condition is cleared. The
latching alarm is reset when the RESET key is pressed, once the alarm
condition is removed.
Holding Alarm : ALMD = HOLD
A holding alarm prevents an alarm from power up. The alarm is
enabled only when the process reaches the set point value. Afterwards
, the alarm performs same function as normal alarm.
Latching / Holding Alarm : ALMD = LT.HO
A latching / holding alarm performs both holding and latching function.
The latching alarm is reset when the RESET key is pressed, once the
alarm condition is removed.
SEL1~SEL8 : Selects the parameter for view and change in the user menu.
Range : LOCK, INPT, UNIT, DP, SHIF, PB, TI, TD, O1HY, CYC1, OFST,
RR, O2HY, CYC2, CPB, DB, ADDR, ALHY
When using the up-down key to select the parameters, you may not obtain
all of the above parameters. The number of visible parameters is dependent
on the setup condition. The hidden parameters for the specific application
are also deleted from the SEL selection.
38
Example :
OUT2 selects DE.LO PB= 100.0 SEL1 selects INPT
SEL2 selects UNIT SEL3 selects PB SEL4 selects TI
SEL5~SEL8 selects NONE Now, the upper display scrolling becomes :
3 - 6 Ramp
The ramping function is performed during power up as well as any
time the set point is changed. Choose MINR or HRR for RAMP, the
unit will perform the ramping function. The ramp rate is programmed
by adjusting RR. The ramping function is disabled as soon as the
failure mode, the manual control mode, the auto-tuning mode or the
calibration mode occurs.
PV
200
C
100
C Figure 3.5 RAMP Function
30
C
Time
(minutes)
Note: When the ramp function is used, the lower display will show the
current ramping value. However it will revert to show the set point
value as soon as the up or down key is touched for adjustment. The
ramping value is initiated to process value either as power up or RR
and /or set point are changed. Setting RR to zero means no ramp
function at all.
39
3-7 Dwell Timer
The alarm output can be configured as dwell timer by selecting TIMR
for ALFN . As the dwell timer is configured, the parameter SP3 is used
for dwell time adjustment. The dwell time is measured in minutes
ranging from 0.1 to 4553.6 minutes. Once the process reaches the set
point the dwell timer starts to count down until zero ( time out ). The
timer relay will remain unchanged until time out. The dwell timer
operation is shown in the following diagram.
After time out the dwell timer will be restarted by pressing the RESET
key.
The timer stops to count during the manual control mode, failure mode,
calibration period and auto-tuning period.
PV
SP
Time
ALM power off or
SP3
touch RESET key
ON
OFF
Time
Timer starts
40
3 - 8 PV Shift
In certain applications it is desirable to shift the controller display value
from its actual value. This can be easily accomplished by using the PV
shift function.
3- 9 Digital Filter
In certain applications the process value is too unstable to be read.
To improve this a programmable low pass filter incorporated in the
controller can be used. This is a first order filter with time constant
specified by FILT parameter . The default value of FILT is 0.5 sec.
before shipping. Adjust FILT to change the time constant from 0 to 60
seconds. 0 second represents no filter is applied to the input signal.
The filter is characterized by the following diagram.
The output 1 and output 2 will perform the failure transfer functions
as the controller enters failure mode.
42
3 -11 Auto-tuning
The auto-tuning process is performed at set point.
The process will oscillate around the set point during tuning
process. Set the set-point to a lower value if overshooting
beyond the normal process value is likely to cause damage.
NOTE :
The ramping function, if used, will be disabled once auto-tuning
is proceeding.
The auto-tuning mode is disabled as soon as either failure mode
or manual control mode occurs.
43
Procedures:
The auto-tuning can be applied either as the process is warming
up ( Cold Start ) or as the process has been in steady state
( Warm Start ).
After the auto-tuning procedures are completed, the AT indicator
will cease to flash and the unit revert to PID control by using its
new PID values. The PID values obtained are stored in the
nonvolatile memory.
Auto-Tuning Error
If auto-tuning fails an ATER message will appear on the upper display
in cases of :
Solutions to
1. Try auto-tuning once again.
2. Don't change set point value during auto-tuning procedure.
3. Don't set zero value for PB and TI.
4. Use manual tuning instead of auto-tuning. ( See section 3-12 ).
5. Touch RESET key to reset message.
3 - 12 Manual Tuning
In some applications using auto-tuning to tune a process may be
inadequate for the control requirement. You should then try manual
tuning.
44
ADJUSTMENT SEQUENCE SYMPTOM SOLUTION
Slow Response Decrease PB
(1) Proportional Band ( PB )
High overshoot or
Increase PB
Oscillations
Slow Response or
Decrease TD
(3) Derivative Time ( TD ) Oscillations
High Overshoot Increase TD
45
PV PB too low
Ideal
Set point
P action
PB too high
Time
TI too high
PV
Set point
I action
Ideal
TI too low
Time
TD too low
PV
Ideal
Set point
D action
TD too high
Time
46
3 - 14 Data Communication
The controllers support RTU mode of Modbus protocol for data
communication. Other protocols are not available for the series.
Setup
Enters the setup menu.
Select RTU for COMM . Set individual address as for those units
which are connected to the same port.
Set the Baud Rate ( BAUD ), Data Bit ( DATA ), Parity Bit ( PARI ) and
Stop Bit ( STOP ) such that these values are accordant with PC setup
conditions.
3 - 15 Process Retransmission
The controllers support a optional ma/VDC output (retransmit) of the
process variable. The program parameters to scale the ma/VDC
signal are RELO and REHI, respectively for low and high scale.
For example, using a 4/20 ma retransmission option to represent a
temperature of 0/200 F unit would be setup as;
RELO = 0 for 4 ma equals 0 F
REHI = 200 for 20 ma equals 200 F
This output would typically go to a recorder, PLC, indicator etc.
47
Chapter 4 Calibration
Do not proceed through this section unless there is a definite
need to re-calibrate the controller. Otherwise, all previous
calibration data will be lost. Do not attempt recalibration unless
you have appropriate calibration equipment. If calibration data is
lost, you will need to return the controller to your supplier who
may charge you a service fee to re-calibrate the controller.
48
Manual Calibration Procedures
Perform step 1 to enter calibration mode.
Step 1. Set the Lock parameter to the unlocked condition
( LOCK=NONE).
Press and hold the scroll key until appears on the
display, then release the scroll key.
Press the scroll key for 2 seconds then release,the display
will show and the unit enters calibration mode .
49
Step 4. Press scroll key until the display shows . Send a 100
ohms signal to the RTD input terminals according to the
connection shown below:
4000 Series
8000 Series 6000 Series
Step 5. Press scroll key and the display will show . Change
the ohm's value to 300 ohms .Press scroll key for at least 3
seconds. The display will blink a moment and two values are
obtained for RTDH and RTDL ( step 4 ). Otherwise, if the
display didn't blink or if any value obtained for RTDH and
RTDL is equal to -199.9 or 199.9 , then the calibration
failed.
50
Temperature
Calibrator 4000 Series
8000 Series 6000 Series
K-TC
51
Perform step 1 stated above , then press scroll key until the
display shows . Press the scroll key for at least 3
seconds. The display will blink a moment and a new value is
obtained. Otherwise , if the display didn't blink or if the
obtained value is equal to -199.9 or 199.9, then the calibration
failed.
Final step
Step 8. Set the LOCK value to your desired function.
52
Chapter 5 Specifications
Power
90 - 250 VAC, 47 63 Hz, 12VA, 5W maximum
11 - 26 VAC / VDC, 12VA, 5W maximum
Input
Resolution: 18 bits
Sampling Rate: 5 times / second
Maximum Rating: -2 VDC minimum, 12 VDC
maximum.
( 1 minute for mA input )
Temperature Effect: +/-1.5uV/ C for all inputs
except
mA input.
+/-3.0uV/ C for mA input
Lead Resistance Effect:
T/C: 0.2uV/ohm
3-wire RTD: 2.6 C/ohm of
resistance difference of two
leads.
2-wire RTD: 2.6 C/ohm of
resistance sum of two leads
Burn-out Current: 200 mA
Common Mode Rej: 120dB
Normal Mode Rej: 55dB
53
Characteristics:
Accuracy Input
Type Range
@ 25 C Impedance
-120 C 1000 C
J +/-2 C 2.2 M
( -184 F 1832 F )
-200 C 1370 C
K ( -328 F 2498 F ) +/- 2C 2.2 M
-250 C 400 C
T ( -418 F 752 F ) +/- 2C 2.2 M
E -100 C 900 C
( -148 F 1652 F ) +/- 2C 2.2 M
54
Output 1 / Output 2
Relay Rating : 2A/240 VAC, life cycles 200,000
for resistive load.
Linear Output
Resolution: 15Bits
Output Regulation : 0.02 % for full load change
Output Settling Time : 0.1 sec. ( stable to 99.9 % )
Isolation Breakdown Voltage : 1000 VAC
Temperature Effect: +/-0.01 % of SPAN / LC
55
DC Voltage Supply Characteristics ( Installed at Output 2 )
Type Tolerance Max. Output Ripple Isolation
Current Voltage Barrier
20 V +/-0.5 V 25 mA 0.2 Vp-p 500 VAC
12 V +/-0.3 V 40 mA 0.1 Vp-p 500 VAC
5 V +/-0.15 V 80 mA 0.05 Vp-p 500 VAC
Alarm
Alarm Relay : Form C Rating
2A/240VAC, 200,000 cycles for resistive load.
Alarm Functions : Dwell timer, PV High / Low Alarm,
Deviation High / Low Alarm,
Deviation Band High / Low Alarm
Alarm Mode : Normal, Latching, Hold, Latching / Hold.
Dwell Timer : 0.1 - 4553.6 minutes
Data Communications
Interface: RS-232 ( 1 unit ), RS-485 ( up to 247 units )
Protocol: Modbus Protocol RTU mode
Address: 1 - 247
Baud Rate: 2.4 ~ 38.4 Kbits/sec
Data Bits: 7 or 8 bits
Parity Bit: None, Even or Odd
Stop Bit: 1 or 2 bits
Comm Buffer: 160 bytes
Analog Retransmission
Functions: Process Variable
Output Signal: 4-20 mA, 0-20 mA, 0 - 5V, 1 - 5V, 0 - 10V
Resolution : 15 bits
Accuracy : +/-0.05 % of span +/-0.0025 %/ C
Load Resistance : 0 - 500 ohms ( for current output )
10 K ohms minimum ( for voltage output )
Regulation: 0.01 % for full load change
Settling Time: 0.1 sec. (stable to 99.9 % )
Breakdown Volts: 1000 VAC min.
Linearity Error : +/-0.005 % of span
Temp Effect: +/-0.0025 % of span / C
Saturation Low : 0 mA ( or 0V )
Saturation High : 22.2 mA ( or 5.55V, 11.1V min. )
Output Range : 0-22.2mA(0-20mA or 4-20mA)
0-5.55V ( 0 - 5V, 1 - 5V )
0 - 11.1 V ( 0 - 10V )
56
User Interface
Display: Dual 4-digit LED Displays
Keypad: 4 keys
Programming Port: For automatic setup, calibration
and testing
Communication Port : Connection to PC for
supervisory control
Control Mode
Output 1: Reverse ( heating ) or direct ( cooling )
action
Output 2: PID cooling control, cooling P band
50~300% of PB, dead band -36.0 ~
36.0 % of PB
ON-OFF: 0.1 - 90.0 ( F ) hysteresis control
( P band = 0 )
P or PD: 0 - 100.0 % offset adjustment
PID: Fuzzy logic modified
Proportional band 0.1 ~ 900.0 F.
Integral time 0 - 1000 seconds
Derivative time 0 - 360.0 seconds
Cycle Time: 0.1 - 90.0 seconds
Manual Control: Heat (MV1) and Cool (MV2)
Auto-tuning: Cold start and warm start
Failure Mode: Auto-transfer to manual mode
while
sensor break or A-D converter damage
Ramping Control: 0 - 900.0 F/minute or
0 - 900.0 F/hour ramp rate
Digital Filter
Function: First order
Time Constant: 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60
seconds programmable
57
Environmental & Physical
Operating Temperature: -10 C to 50 C
Storage Temperature: -40 C to 60 C
Humidity: 0 to 90 % RH ( non-condensing )
Insulation Resistance: 20 Mohms min. ( at 500 VDC )
Dielectric Strengt : 2000 VAC, 50/60 Hz for 1 minute
Vibration Resistance: 10 - 55 Hz, 10 m/s for 2 hours
Shock Resistance: 200 m/s ( 20 g )
Moldings: Flame retardant polycarbonate
Dimensions:
4000 Series: 96mm(W) X 96mm(H) X 65mm(D),
53 mm depth behind panel
Agency Approvals
UL Pending
CSA Pending
Protective Class:
IP65 for panel with additional option
IP50 for panel without additional option
Ip20 for terminals and housing with protective cover.
EMC: EN61326
58
Table A.1 Error Codes and Corrective Actions
Error Display Error Description
Code Symbol Corrective Action
Illegal setup values have been Check and correct setup values of
used: Before COOL is used for OUT2, PB, TI and OUT1. IF OUT2
OUT2, DIRT ( cooling action ) has is required for cooling control, the
already been used for OUT1, control should use PID mode ( PB
or PID mode is not used for OUT1 = 0, TI = 0 ) and OUT1 should
4 ( that is PB = 0, and / or TI = 0 ) use reverse mode (heating action)
, otherwise, don't use OUT2 for
cooling control.
59
Warranty
Proheat Inc. makes no warranty or representations of any sort regarding the fitness for
use, merchantability, fitness for a particular purpose or the application of its products by
the purchaser. The selection, application or use of Proheat Inc. products is the
purchaser's responsibility.
Proheat Inc. controls are warranted to be free from functional defects in material and
workmanship for TWO YEARS after delivery to the first purchaser.
Proheat Inc.'s sole responsibility under the warranty, at Proheat Inc.'s option, is limited to
replacement or repair, free of charge, or refund of purchase price within the warranty
period specified. This warranty does not apply to damage resulting from transportation,
alteration, misuse or abuse.
No claims will be allowed for any damages or losses, whether direct, indirect, incidental,
special or consequential. Specifications are subject to change without notice. In addition,
Proheat Inc. reserves the right to make changes without notification to purchaser to
materials or processing that do not affect compliance with any applicable specifications.
There are no expressed or implied warranties extending beyond the warranty herein.
Proheat Inc.
117 East Adam Street
LaGrange, KY 40031
Main Office Phone: 502-222-1402
Fax: 502-222-0714
Technical Support
Phone: 502-222-1402
www.proheatinc.com
E-mail: [email protected]
60