Fire Tender Load Calculation R1

The document outlines load considerations for fire tender paths at a hotel drop-off area, detailing the effective area under the wheels and the load intensity calculations for slab design. It specifies the maximum load of two fire tenders, which is 900 kN, and provides dimensions for various structural elements. Additionally, it includes diagrams and specifications for dispersion distances and typical sections for the slab design.

Uploaded by

Manoj Pandita
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views24 pages

Fire Tender Load Calculation R1

The document outlines load considerations for fire tender paths at a hotel drop-off area, detailing the effective area under the wheels and the load intensity calculations for slab design. It specifies the maximum load of two fire tenders, which is 900 kN, and provides dimensions for various structural elements. Additionally, it includes diagrams and specifications for dispersion distances and typical sections for the slab design.

Uploaded by

Manoj Pandita
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd

Fire Tender path: Load Consideration at Hotel Drop off : Level_01

15

3 4
BHE-XX-XX-DR-S-3002

BHE-XX-XX-DR-S-3001 BHE-XX-XX-DR-S-3001

1 2
3 4 5
6 7 8
9 10 11
12 13 14
15 16
1
2

wheel of fire tender


BHE-XX-XX-DR-S-3000 BHE-
XX-XX-DR-S-3000

4500 4500
4500 4500 4500
4500 4500 4500
4500 4500 4500
4500 4500 4500
600

PLANTING REFER TO SOFTSCAPE PLAN

RAISED PLANTER

2
1575
14900

210
6600

L2-006A
1400

1100

PA
1350

C1
C2 C3
C4
C5 C6
C7
(400 x 800)
(600 x 800) (600 x 800)
(600 x 800)
(600 x 800) (800 x 800)
(450 x 800)

300
B

45
1500

PLANTING REFER TO
SOFTSCAP PLAN

70

2850 x 550
2850 x 650

00

10200
400 x 1300
11800

14075
9750

300 THK R.C. SLAB

dispersion distance

MOUNTABLE KERB 3
=210+270

3000 x 550 L5-003


3000 x 650

2
C8
C9 C10
C11
C12

1 3

C13 C14
C15

=480 mm
(400 x 800)
(400 x 1000) (500 x 700)
(500 x 700)
L2-006B

(500 x 700) L2-006B L2-008B

(500 x 700) (500 x


700) (400 x 800)
C

HOTEL DROP-OFF
5870 3325
Typical section for the dispersion through slab
1200
PA
FL +5.425 m

C16 C17
C18 C19
C20 C21
C22

PA
PA
C23

7500

(400 x 600) (400 x 600)


(500 x 500) (450 x 450)
500 x 800 (500 x 500) 500 x 800
(500 x 500) 500 x 800 (500 x 500)
500 x 800
C15A
(400 x 600)

HH
8250

(400 x 800)

250 THK R.C. SLAB


400 x 1300

300 x 800

1V

400 x 800

250 THK R.C. SLAB


400 x 700

300 x 600

C28
HOTEL DRO
6000 1200
(500 x 500)
D
C25
WALL

300 x 800

(400 x 700) C26


C27 C29

(800 x 1200)
C32
C33

(400 x 800) (450 x 450)


(800 x 1200)
(400 x 600)
RAMP DOWN TO GROUND LEVEL
300 x 800
JJ
C24
(400 x 800)

400 x 1500
9000

250 THK R.C. SLAB

300 x 800

300 x 800
0 x 1300
0 x 800

0 x 700

0 x 800

Fire Tender Load Consideration for slab


Load intensity to consider by this method

1
2

Effective area diagram for the fire tender wheels


Fire Tender path: Load Consideration at Hotel Drop off : Level_01

15

3 4
BHE-XX-XX-DR-S-3002

BHE-XX-XX-DR-S-3001 BHE-XX-XX-DR-S-3001

1 2
3 4 5
6 7 8
9 10 11
12 13 14
15 16
1
2

wheel of fire tender


BHE-XX-XX-DR-S-3000
BHE-XX-XX-DR-S-3000

4500
4500 4500
4500 4500 4500
4500 4500 4500
4500 4500 4500
4500 4500 600

PLANTING REFER TO SOFTSCAPE PLAN

RAISED PLANTER

2
1575
14900

210
6600

L2-006A
1400

1100

PA
1350

C1
C2 C3
C4
C5 C6
C7
(400 x 800)
(600 x 800) (600 x 800)
(600 x 800)
(600 x 800) (800 x 800)
(450 x 800)

300
B

45
1500

PLANTING REFER TO
SOFTSCAP PLAN

70

2850 x 550
2850 x 650

00

10200
400 x 1300
11800

14075
9750

300 THK R.C. SLAB

dispersion distance

MOUNTABLE KERB 3
=210+270

3000 x 550 L5-003


3000 x 650

2
C8
C9 C10
C11
C12

1 3

C13 C14
C15

=480 mm
(400 x 800)
(400 x 1000) (500 x 700)
(500 x 700)
L2-006B

(500 x 700) L2-006B L2-008B

(500 x 700) (500 x


700) (400 x 800)
C

HOTEL DROP-OFF
5870 3325
Typical section for the dispersion through slab
1200
PA
FL +5.425 m

C16 C17
C18 C19
C20 C21
C22

PA
PA
C23

7500

(400 x 600) (400 x 600)


(500 x 500) (450 x 450)
500 x 800 (500 x 500) 500 x 800
(500 x 500) 500 x 800 (500 x 500)
500 x 800
C15A
(400 x 600)

HH
8250

(400 x 800)

250 THK R.C. SLAB


400 x 1300

300 x 800

1V

400 x 800

250 THK R.C. SLAB


400 x 700

300 x 600

C28
HOTEL DRO
6000
1200
(500 x 500)
D
C25
WALL

300 x 800

(400 x 700) C26


C27 C29

(800 x 1200)
C32
C33

(400 x 800) (450 x 450)


(800 x 1200)
(400 x 600)
RAMP DOWN TO GROUND LEVEL
300 x 800
JJ
C24
(400 x 800)

400 x 1500
9000

250 THK R.C. SLAB

300 x 800

300 x 800
0 x 1300
0 x 800

0 x 700

0 x 800

Load intensity to consider by this method

Fire Tender Load Consideration for slab


Effective area of the the
region under fire tender
wheels

Effective area diagram for the fire tender wheels


Fire Tender path: Load Consideration at Hotel Drop off : Level_01

15

3 4
BHE-XX-XX-DR-S-3002

BHE-XX-XX-DR-S-3001 BHE-XX-XX-DR-S-3001

1 2
3 4 5
6 7 8
9 10 11
12 13 14
15 16
1
2

wheel of fire tender


BHE-XX-XX-DR-S-3000 BHE-
XX-XX-DR-S-3000

4500 4500
4500 4500 4500
4500 4500 4500
4500 4500 4500
4500 4500 4500
600

Length is 11.4 m.

Maximum two fire


A
Maximum 527 kN load
tender, partly can

on each column PLANTING REFER TO SOFTSCAPE PLAN


stay in a bay of

because of one fire


9mX9m. RAISED PLANTER

tender in a bay 2
1575
14900

210
6600
L2-006A
1400

1100

PA
1350

C1
C2 C3
C4
C5 C6
C7
(400 x 800)
(600 x 800) (600 x 800)
(600 x 800)
(600 x 800) (800 x 800)
(450 x 800)

300
B

45
1500

PLANTING REFER TO
SOFTSCAP PLAN

70

2850 x 550
2850 x 650
00

10200
400 x 1300

11800

14075
9750

300 THK R.C. SLAB

dispersion distance

MOUNTABLE KERB 3
=210+270

3000 x 550 L5-003


3000 x 650

2
C8
C9 C10
C11
C12

1 3

C13 C14
C15

=480 mm
(400 x 800)
(400 x 1000) (500 x 700)
(500 x 700)
L2-006B

(500 x 700) L2-006B L2-008B

(500 x 700) (500 x


700) (400 x 800)
C

HOTEL DROP-OFF
5870 3325
Typical section for the dispersion through slab
1200
PA
FL +5.425 m

C16 C17
C18 C19
C20 C21
C22

PA
PA
C23

7500

(400 x 600) (400 x 600)


(500 x 500) (450 x 450)
500 x 800 (500 x 500) 500 x 800
(500 x 500) 500 x 800 (500 x 500)
500 x 800
C15A
(400 x 600)

HH
8250

(400 x 800)

250 THK R.C. SLAB


400 x 1300

300 x 800

1V
400 x 800

250 THK R.C. SLAB

400 x 700

300 x 600

C28
HOTEL DRO
6000 1200
(500 x 500)
D
C25
WALL

300 x 800

(400 x 700) C26


C27 C29

(800 x 1200)
C32
C33

(400 x 800) (450 x 450)


(800 x 1200)
(400 x 600)
RAMP DOWN TO GROUND LEVEL
300 x 800
JJ
C24
(400 x 800)

400 x 1500
9000

250 THK R.C. SLAB

300 x 800

300 x 800
0 x 1300
0 x 800

0 x 700

0 x 800

Fire Tender Load Consideration for Punching in Column

Load of one fire tender = 45 Tonn = 450 kN

Total length of one fire fighting vehicle is 11.4 m so assuming


worst case of two fire tender in a bay of (9mX9m).

-Total Load of two fire tenders = 450X2


= 900 kN

Load Intensity of two fire tenders in 9X9 m grid= Total load of


two fire tenders
Total effective
area of 1 bay

= 900

9X9

=11.11 kN/m2
Fire Tender path: Load Consideration at Function drop off: Ground level

wheel of fire tender

285

350

45

dispersion distance

=285+320

=605 mm

Typical
section for the dispersion through slab

Load intensity of fire tender for the slab design


Load
intensity to consider by this method

1 2

Effective area diagram for the fire tender wheels


Fire Tender path: Load Consideration at Function drop off: Ground level

wheel of fire tender

285

350

45

dispersion distance

=285+320

=605 mm

Typical section for the dispersion through slab

Load intensity of fire tender for the slab design

Load intensity to consider by this method


Effective area of the the
region under fire tender
wheels

Effective area diagram for the fire tender wheels


Fire Tender path: Load Consideration at Ramp: Ground level to Level-1

wheel of fire tender


310 mm filling in this zone.

310

350

45

dispersion distance

=310+320

=630 mm

Typical section for the dispersion through slab

Load intensity of fire tender for the slab design

Load intensity to consider by this method


1 2
Effective area of the the
region under fire tender
wheels

Effective area diagram for the fire tender wheels


Fire Tender path: Load Consideration at Ramp: Ground level to Level-1

wheel of fire tender


310 mm filling in this zone.

310

350

45

dispersion distance

=310+320

=630 mm

Typical section for the dispersion through slab

Load intensity of fire tender for the slab design

Load intensity to consider by this method


Effective area of the the
region under fire tender
wheels

Effective area diagram for the fire tender wheels