100 linear continuous
plaster-in/bezel
A 100mm continuous linear recessed downlight with minimal visual impact.
Can be specified to any desired length.
Applications:
-- Where the ceiling is to be plastered or re-plastered with a gypsum finish
(plaster-in) or where the ceiling is not able to accept a plaster finish
(bezel).
Features:
-- Twin lamp configuration.
-- Single tool second fix internal lamp cartridge.
-- Tool free lamp and gear maintenance.
-- Internal cartridges with pre-wired plug connectors for efficient
installation.
Control options:
-- Switched
-- Analogue (1-10v)
-- Digital (DSI)
-- DALI
code lamp type base watts lumen cut-out
TP100LDL-(Length) Twin fluorescent overlapped Twin T5 G5 48W per metre 4400 lm per metre 120 x (overall length + 20mm)
TB100LDL-(Length) Twin fluorescent overlapped Twin T5 G5 48W per metre 4400 lm per metre 120 x (overall length + 20mm)
Example:
TP100LDL-4200 (where 4200mm is the linear length) plaster in continuous
25 linear profile with high efficiency diffuser.
100
Notes:
-- Where mitred corners or applications other than straight runs are
required an indicative dimensional drawing is preferred.
-- Lamp configuration is dependent on luminaire length and layout.
-- Please specify control gear required when ordering.
-- LED options available, please contact us for detail
Other information:
145
Installation guide Page 160
Lamp configuration Page 161
Important information Page 181
Accessories Page 185
Whitegoods Lighting Limited Unit 19 Hiltongrove 14 Southgate Road London N1 3LY T +44 (0)20 7241 2032 F +44 (0)20 7241 2033 mail@[Link] [Link]
120
whitegoods
lamp removal
installation instructions /
100 linear plaster-in:
P100LDL6-214
P100LDL9-221
suction cup
cut-out:
2
length +20mm x 120mm
click
4
25 100/150
5
145
click
click
Registration number is WEE/FG0362QY
M6 full nut
M6 threaded M6 washer
bar
M6 full nut
150 150 M6 full nut
fluorescent
cut-out lamp
diffuser
TP150LDLHE-(mm) TP150LDLHO-(mm)
All linear flourescent luminaires require support from above as shown, supports to be spaced at 1.5m maximum intervals, ideally between 750-1000mm.
Care must be taken when plastering the housing that no excess plaster is applied on the inside of the luminaire as this is detrimental to the operation of the luminaire.
Mains power supply to enter through end plate grommit hole. During installation the aperture width of the luminaire must be maintained at 150mm.
M6 full nut
M6 threaded
bar M6 washer
M6 full nut
150 150 M6 full nut
fluorescent
lamp
cut-out
diffuser
TP100LDLHE-(mm) TP100LDLHO-(mm)
All linear flourescent luminaires require support from above as shown, supports to be spaced at 1.5m maximum intervals, ideally between 750-1000mm
Care must be taken when plastering the housing that no excess plaster is applied on the inside of the luminaire as this is detrimental to the operation of the luminair
Mains power supply to enter through end plate grommit hole. During installation the aperture width of the luminaire must be maintained at 100mm.
A,B,C,D only for continuous system CABLE MOUNTING (optional) to be installed in the 5.5mm hole
A B screw/ rod
side joiner
plate x 2 cable
thread the
suspension
cable holder cable back
screw + through the
M4 x 8 screws hole
shake proof washer
C D
geartray
1 cable clamp 2
open lock plaster fluorescent
lamp
push to
open
pull the suspension cable
until the luminare is fixed di f fuser
in the ceiling
diffuser spacing template
M4 x 8 screws
ballast
ballast
mains link cable
Lamps configuration
Do not remove the diffuser spacing template until the luminaire has been installed within the ceiling void. If during installation the template falls from luminaire recheck diffuser mouth dimension (150/100mm), and return
mouth to the required dimension. On completion of installation if diffuser spacing templates do not fit correctly/fall from luminaire then the luminaire will also not fit correctly resulting on the failure of the luminaire.
important information
Installation The installation of these products should only be carried out by a suitably qualified
electrician in accordance with the instructions supplied with the product. All
installation instructions can be downloaded from our website. We recommend that
they are included with construction issue drawings and specifications.
Ceiling void depths for recessed downlights and linear luminaires: The Ceiling void
depth should ideally be 25mm deeper than the overall height of the luminaire. When
a fire-hood and/or a remote emergency pack is to be used, the void depth and space
surrounding the luminaire will need to be increased.
Dimensions and specification The drawings, dimensions and finishes of the products in this catalogue and any
accompanying information are purely indicative. Great care is taken to provide up
to date information in this publication, however, due to a continuing programme of
design and development, we reserve the right to change these dimensions without
prior notice. Please check the website for most up to date information. If a dimension
is critical to the success of your project, please confirm it directly with the technical
department. Throughout this publication, cut-out sizes refer to the aperture
required when fittings are mounted in soft plasterboard. For fibrous tiles, timber,
metal tiles and cast-in construction, check dimensions on site, or ask for a sample.
Whitegoods reserves the right to discontinue any product in this publication at any
time without prior notice.
Performance All photometric data supplied is taken from a standard production luminaire tested
under ideal laboratory conditions and may vary from data taken in alternative
conditions. All calculated light levels and/or lighting plots provided are offered for
guidance only. The customer must satisfy themselves that luminaires proposed are
suitable for the application intended in all performance and physical criteria.
Temperature and physical environment All products are tested with stated lamp wattage. Incorrect lamp types and
wattages may effect efficiency, create glare and seriously overheat the luminaire.
Adequate ventilation and free air space around fittings (in accordance with the
installation instructions supplied with the product) will be necessary when used in
confined spaces where elevated temperatures will occur. All luminaires are designed
to operate in a maximum 30degree ambient temperature. Operating in ambient
temperatures above this can affect performance and the mechanical functionality of
the luminaire.
Intellectual property In order that we can continue to develop innovative quality products, we believe
it is of critical importance that we protect our ideas and visions. Therefore any
infringement of our intellectual property will be vigorously pursued.
Returns We cannot offer refunds on Custom or Tailored products, Standard product may
be eligible for re-stocking within 3 months of original purchase date, subject to a
30% handling charge. All original packaging and documentation must be present and
goods must be in original condition.
Service Whitegoods will endeavor to fulfill all orders as quickly as possible and treat all
customers with the highest regard. For further information about Whitegoods
products and services, please visit [Link].
WEEE directive The Waste Electrical and Electronic Equipment Directive (WEEE Directive) is the
European Community directive 2002/96/EC on waste electrical and electronic
equipment, together with the RoHS Directive 2002/95/EC which became European
Law in February 2003, setting collection, recycling and recovery targets for all
types of electrical goods. This imposes responsibility for the disposal of waste
electrical and electronic equipment (WEEE) on the manufacturers of such
equipment. To meet these targets Whitegoods has become a member of Lumicom
to allow us to meet the current and future directives. For further information on
the WEEE directive please contact our offices.
WEEE Registration number is WEE/FG0362QY
Whitegoods Lighting Limited Unit 19 Hiltongrove 14 Southgate Road London N1 3LY T +44 (0)20 7241 2032 F +44 (0)20 7241 2033 mail@[Link] [Link]