Indoor Switchgear Design Drawings
Indoor Switchgear Design Drawings
SHEET
TITLE REVISION DATE DESIGN CHANGE DESCRIPTION LEVEL DESCRIPTION LEVEL DESCRIPTION
NUMBER
A A
0 COVER SHEET 2 04/04/2008 REVISION 2 CHANGES INDICATED.
1 16
1 PANEL EQUIPMENT LAYOUT 2 04/04/2008 ADDITIONAL RACK MOUNTING HOLES ADDED TO FRONT PANEL TO PREVENT BOWING.
LABELLING ERRORS CORRECTED: TRIP AND CLOSE LABELS SWAPPED. 2 17 INDOOR SWITCHGEAR WITH REMOTE PROTECTION SCHEME
2 SCHEME LOGIC DIAGRAM 2 04/04/2008
MCB(AC) RATING CORRECTED TO 10A.
8 23
9 24
11 26
12 27
13 28
E E
14 29
15 30
NOTE
F AMP TRANSDUCER OPTION INCORPORATED INTO LEVELS 3, 5, 17, 18 & 19. DELETE IF NOT REQUIRED. F
G G
WORKSHEET: LEVEL 10
REVISION 2
J
OF 10
0
SHEET
K
TECHNICAL DRAWINGS
PROJECT APPROVED DESIGN APPROVED
S. TSHOBENI
M WHEN USING THIS SCHEME PLEASE MAKE SURE THAT DATE / / DATE 13/07/07
COVER SHEET
/ / DRAWN BY DRAWN BY
SET NUMBER SHEET NUMBER REVISION
REFERENCE FILE title4RF1100r2 IS ATTACHED ON ALL 2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
311.15mm (7U)
3 BACK PLATE
5
R1 1 MCB (VT) VOLTAGE TRANSFORMER MINIATURE CIRCUIT-BREAKER ( 2A ) G63(C02) GE
AREVA 001
2 MCB (H) MECHANISM BOX AC HEATER MINIATURE CIRCUIT-BREAKER ( 5A ) G61NC(C05) GE
3 DM DIODE MODULE KCH ELMEX
C C
D1, D2 DIODES WITHIN DIODE MODULE (2) DDSA9-16F ALSTOM
4 CL-X CLOSE AUXILIARY RELAY MK3P5-S 110/220Vdc OMRON
5 APT-X ANTI-PUMP TIMER AUXILIARY RELAY MK3P5-S 110/220Vdc OMRON
6 PNH-X PROTECTION NOT HEALTHY AUXILIARY RELAY MK3P5-S 110/220Vdc OMRON
8 9 10 7 AMP Tx SINGLE PHASE CURRENT TRANSDUCER ( OPTIONAL ) CA4 POWERCON
6 7 8 AS-1 TRIPPING CIRCUIT ARC SUPPRESSOR (SNUBBER CIRCUIT) SNUB CIRCUIT ALSTOM
9 AS-2 CLOSING CIRCUIT ARC SUPPRESSOR (SNUBBER CIRCUIT) SNUB CIRCUIT ALSTOM
D D
0.4830
E E
BACK PLATE
25 X 80 TRUNKING
R1
X1 F
F
4 5 6
1 2 3
3
4 5 6 7
G 1 2 G
40 X 80 TRUNKING
622.3mm (14U)
X2
REVISION 2
J
OF 10
1
SHEET
40 X 80 TRUNKING
SHT 10 CABLE BLOCK
K SHT 9 CABLING DIAGRAM
SHT 8 REFERENCE DIAG
SHT 7 SUPERVISORY KEY
8 9 TECHNICAL DRAWINGS
PROJECT APPROVED DESIGN APPROVED
S. TSHOBENI
2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
1 SvZ 28/08/2007 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - DATE / / DATE
13/07/07
WORKSHEET 10 1 0
REV AUTH DATE REVISION TO MASTER BY CHKD SCALE
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
FRONT VIEW A
F1 2.1 2.2
1 2
1 1 6
B 2 B
4
3 2 7
BUSBAR
4
3 8
5
3 6 Red
4 9 Green BUSBAR VT
P145
7
8 AREVA 5 10 5 001
BUSBAR ISOLATOR CB
TO BUSZONE PANEL
FAIL
C C
MANUAL/
SUP
D R PHASE W PHASE B PHASE SENS TRIP D
E/F
O/C O/C O/C E/F
0.4830
AMP Tx
SEF ON/
OFF
P1
E E
EMERGENCY
KIOSK TYPE
TRIP TRIP PB
CIRCUIT
BREAKER CLOSE
P1
FRONT VIEW
F1
1 PNH-I PROTECTION NOT HEALTHY INDICATION PROTECTION NOT HEALTHY
2 P145 FEEDER MANAGEMENT RELAY
2.1 PROGRAMMABLE LEDs
1 CIRCUIT-BREAKER CLOSED INDICATION ( RED ) CB CLOSED
2 CIRCUIT-BREAKER OPEN INDICATION ( GREEN ) CB OPEN
3 CIRCUIT-BREAKER NOT HEALTHY INDICATION CB NOT HEALTHY
4 OVERCURRENT TRIP INDICATION O/C TRIP
G G
5 EARTH FAULT TRIP INDICATION E/F TRIP
6 SENSITIVE EARTH FAULT TRIP INDICATION SEF TRIP
7 CIRCUIT-BREAKER FAIL INDICATION CB FAIL TRIP P2
REVISION 2
10 CIRCUIT-BREAKER TRIP CONTROL ( GREEN ) TRIP*
3 ESD ELECTROSTATIC DISCHARGE POINT ESD
4 ETPB EMERGENCY TRIP PUSH BUTTON WITH COVER EMERGENCY TRIP
5 FC FAULT COUNTER FAULT COUNTER
6 CTTB CURRENT TRANSFORMER TEST BLOCK CURRENT TRANSFORMER TEST BLOCK
J
7 VTTB VOLTAGE TRANSFORMER TEST BLOCK VOLTAGE TRANSFORMER TEST BLOCK
8 DCI MCB (M) MAIN DC ISOLATE MINIATURE CIRCUIT-BREAKER MAIN DC SUPPLY MCB (16A)
OF 10
9 DCI MCB (SR) SPRING REWIND DC ISOLATE MINIATURE CIRCUIT-BREAKER SPRING REWIND DC MCB (20A)
10 MCB (AC) AC ISOLATE MINIATURE CIRCUIT-BREAKER AC SUPPLY MCB (10A)
* PRESS TWICE IN 3s TO OPERATE
2
SHEET
K
TECHNICAL DRAWINGS
PROJECT APPROVED DESIGN APPROVED
DATE
S.J. van ZYL
DATE
EXERCISE
/ / 13/07/07
PROJECT CHECKED DESIGN CHECKED
S. TSHOBENI
M
NOTE: DATE / / DATE 13/07/07
SCHEME LOGIC DIAGRAM
/ / DRAWN BY DRAWN BY
SET NUMBER SHEET NUMBER REVISION
1. DOWNLOAD THE *.PSL FILE FROM THE P145 RELAY FOR FULL SCHEME LOGIC. 2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
2. LED SHOWS RED FOR "ARC LOCK-OUT" AND GREEN FOR "ARC IN PROGRESS"
1 SvZ 28/08/2007 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - DATE / / DATE
13/07/07
WORKSHEET 10 2 0
REV AUTH DATE REVISION TO MASTER BY CHKD SCALE
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P145
A A
VW
VR
VB
C20
C22
C21
C19
E53
E73
E13
E33
B B
A76
A76
A76
A76
VTTB
1
P145
2
C C
NOTE 3
E12
E32
E52
E71
MCB(VT)
2/1
6/5
4/3
A32
A75
A73
A74
A52
A12
90
2A
X1.10
X1.6
X1.8
X1.7
RP
RP
RP
3/4
5/6
1/2
D D
AMP Tx
NOTE 2
A73
A72
E11
E31
E51
E71
-
CONTINUED ON
X1.13
X1.14
X1.12
X1.11
5
RP
RP
RP
RP
1
SHEET 7
=
2
6
RP
X1.9
+
E E
A32
A52
A72
A12
CTTB
D32
D72
NOTE 1
8
F F
90
90
A31
A51
A71
A11
X1.16
X1.18
X1.17
X1.15
X1.19
X1.3
X1.4
X1.2
X1.5
X1.1
RP
RP
RP
RP
RP
RP
RP
RP
RP
G G
MB
(CT)
MB
(CT)
MB
(CT)
MB
(CT)
BUSBAR
REVISION 2
CT
CT
CT
CT
R
R
J
W
OF 10
B
B
P2
P2
P1
P1
BUSBAR ISOLATOR
CLASS TPS/PX
CLASS TPS/PX
3
SHEET
SURGE ARRESTER
PROTECTION
PROTECTION
LINE ISOLATOR
CLASS 0.2
CLASS 0.2
METERING
METERING
CIRCUIT-BREAKER
CORE 3
CORE 2
CORE 4
CORE 1
K
W
R
KIOSK TYPE
1. FOR CONNECTION TO CORE 2. THE LINK BETWEEN X1.8 AND X1.10 3. THE P145 RELAY IS SUITABLE FOR 1A OR 5A RATED CTs (VIA DIFFERENT TERMINAL INPUTS).
BALANCE CT, LOOP:
X1.6 - X1.9
SHOULD BE INSTALLED IF A SEPARATE
CORE BALANCE CT IS USED.
THE STANDARD DRAWING INDICATES THE RELAY WIRED FOR 1A RATED CTs.
USE THE TABLE BELOW TO DETERMINE THE CORRECT WIRING FOR 5A RATED CTs.
TECHNICAL DRAWINGS
PROJECT APPROVED DESIGN APPROVED
X1.7 - CT SCHEMES ORDERED FOR 5A RATED CTs WILL BE WIRED AS SUCH IN THE FACTORY.
THERE SHOULD ONLY BE ONE EARTH
X1.8 - CT
POINT ON EACH CT CIRCUIT.
DATE
S.J. van ZYL
DATE
EXERCISE
P145 TERMINAL NUMBER / / 13/07/07
PROJECT CHECKED DESIGN CHECKED
REMOVE LOOPS WIRE FERRULE NUMBER 1A RATED 5A RATED
S. TSHOBENI
M
X1.6 - X1.7 A12
DATE / / DATE 13/07/07
AC KEY DIAGRAM
X1.8 - X1.9 A32
/ / DRAWN BY DRAWN BY
2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
A76
A73
1 SvZ 28/08/2007 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - DATE / / DATE
13/07/07
WORKSHEET 10 3 0
REV AUTH DATE REVISION TO MASTER BY CHKD SCALE
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
NOTE 2 P145
DCI MCB (M) DCI MCB (M)
- + RP DCB DCB RP - + RELAY R3
K101 J1 J1A J2A J2 K102
A MAIN DC SUPPLY A
3 4 X2.1 * * X2.2 2 1 H6 H5
Any Prot Trip
16 AMP 16 AMP
CONTINUED ON CONTINUED ON
SHEET 6 (X2.3) SHEET 6 (X2.4)
P145
OPTO L1
RP RP
CIRCUIT-BREAKER K101 K103 K103 K102
OPEN
B X2.5 X2.6 D2 D1 B
CBO
OPTO L2
RP RP
CIRCUIT-BREAKER K101 K105 K105 K102
CLOSED
X2.7 X2.8 D4 D3
CBC
OPTO L3
RP RP
K101 K107 K107 K102
SPRING DISCHARGED
C C
X2.9 X2.10 D6 D5
SLS Discharge
CIRCUIT-BREAKER
NOT HEALTHY
DCI MCB(SR)
OPTO L4 NOTE 3
SPRING REWIND K101 K109 K109 K109 K102
MCB TRIPPED
11 12 D8 D7
CB Not Health
D D
RP RP
CIRCUIT-BREAKER K101 K109
COMMON ALARM
X2.11 X2.12
OPTO L5
RP RP
CIRCUIT-BREAKER K101 K111 K111 K102
E MB HEATER ALARM E
X2.13 X2.14 D10 D9
CB HeaterFail
OPTO L6
RP RP
EXTERNAL TRIP K101 K113 K113 K102
& LOCK-OUT
X2.22 X2.23 DM D12 D11
Ext Trip & LO
C
D1
F F F
AS-1
K101 K115
RELAY CONTACT
PROTECTION MODULE + -
NOTE 1 NOTE 1
ETPB RP RP
K101 K115 K115 K102
EMERGENCY TRIP
13 14 X2.15 X2.16
G P145 G
PROTECTION, RELAY R10
K101 K115
LOCAL AND
SUPERVISORY TRIP G4 G3
Main CB Trip DM
D2
OPTO L7
H RP
TRIP CIRCUIT K101 K117 K117
SUPERVISION
D14 D13 X2.17
NOTE 4 TC Healthy
FC
REVISION 2
RELAY R16
PROTECTION TRIP K101 K119 K119 K102
FAULT COUNTER
NOTE 2
G18 G17
Fault Counter
K101
K102
J
OF 10
CONTINUED ON CONTINUED ON
SHEET 5 SHEET 5
4
SHEET
K
3. THE P145 WILL NOT ISSUE A CLOSE COMMAND TO THE CIRCUIT-BREAKER IF OPTO L3 IS ASSERTED (SLS DISCHARGED) OR OPTO L7
DATE
S.J. van ZYL
DATE
EXERCISE
IS DE-ASSERTED (TRIP COIL FAILED). THE AUTO-RECLOSE LOGIC WAITS UNTIL THE END OF THE DEAD TIME BEFORE CHECKING THE / / 13/07/07
PROJECT CHECKED DESIGN CHECKED
SLS STATUS. IF THE SPRING IS DISCHARGED THE DEAD TIME IS EXTENDED UNTIL THE SPRING CHARGES, OR UNTIL A SETTABLE
S. TSHOBENI
M
TIMER EXPIRES. EXPIRY OF THE TIMER CANCELS ARC.
DATE / / DATE 13/07/07
DC KEY DIAGRAM
4. ALL CLOSE COMMANDS TO THE CIRCUIT-BREAKER ARE BLOCKED IN THE EVENT THAT THE TRIP CIRCUIT IS UNHEALTHY (OPTO L7 DE-ASSERTED). / / DRAWN BY DRAWN BY
SET NUMBER SHEET NUMBER REVISION
IT IS THUS IMPERATIVE THAT PROVISION IS MADE FOR TRIP CIRCUIT SUPERVISION WHILST THE CIRCUIT-BREAKER IS IN THE OPEN POSITION. 2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
IF THE CIRCUIT-BREAKER DESIGN DOES NOT CATER FOR THIS, WIRE A N/C (52b) STATUS CONTACT BETWEEN X2.16 AND X2.17. 1 SvZ 28/08/2007 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - DATE / / DATE
13/07/07
WORKSHEET 10 4 0
REV AUTH DATE REVISION TO MASTER BY CHKD SCALE
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
K102
K101
P145 CL-X
RELAY R13
K101 K121 K121 K102
G10 G9 2 10
CB Close
APT-X
B B
RELAY R14
K101 K123 K123 K102
G12 G11 2 10
APT Output
CL-X
3 1 1 4
C C
K127 K125 K135 K133
9 11 11 8
NOTE 1 NOTE 1
RP RP
CIRCUIT-BREAKER K127 K129 K129 K131 K133
CLOSE & ANTI-PUMP
7 6 X2.18 X2.19 6 5
P145
AS-2
D OPTO L9 D
CONTACT PROTECTION K101 K129 K129 K129 K102
( ARC SUPPRESSOR )
+ - F2 F1
AP Timer In
OPTO L10
ETPB
K101 K137 K137 K102
EMERGENCY TRIP
13 14 F4 F3
Emergcy Trip
E E
OPTO L11
RP RP
BUSBAR 1 K101 K139 K139 K102
ISOLATOR OPEN
X2.26 X2.27 F6 F5
Status 1
OPTO L12
RP RP
BUSBAR 2 K101 K141 K141 K102
ISOLATOR OPEN
X2.28 X2.29 F8 F7
Status 2
F OPTO L13 F
RP RP
LINE K101 K143 K143 K102
ISOLATOR OPEN
X2.30 X2.31 F10 F9
Status 3
OPTO L14
RP RP
K101 K145 K145 K102
SPARE INPUT
X2.32 X2.33 F12 F11
Spare
RP RP
G SF6 GAS K101 K102 K102 G
MONITORING SUPPLY
X2.20 X2.21
RP RP
K101 K102
X2.34 X2.35
REVISION 2
P145
PSU
PROTECTION RELAY K101 K102
POWER SUPPLY
J2 J1
OF 10
5
SHEET
K
TECHNICAL DRAWINGS
PROJECT APPROVED DESIGN APPROVED
DATE
S.J. van ZYL
DATE
EXERCISE
/ / 13/07/07
PROJECT CHECKED DESIGN CHECKED
S. TSHOBENI
2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
1. LINKS USED IN ORDER TO ALLOW TESTING OF COILS. 1 SvZ 28/08/2007 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - DATE / / DATE
13/07/07
WORKSHEET 10 5 0
REV AUTH DATE REVISION TO MASTER BY CHKD SCALE
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A A
1M Ohm
ESD
DCI MCB (SR) DCI MCB (SR) K83 90
- + RP RP - +
M3 M1 M2 M4
SPRING REWIND DC SUPPLY X2.42
3 4 X2.3 X2.4 2 1
20 AMP 20 AMP
RP RP
M3 M4
B X2.36 X2.37 B
10 AMP
10 AMP
PNH-X
PNH-I
PROTECTION NOT
H13 H15 H70
HEALTHY
D D
4 1
AMBER
P145
RELAY R1
H13 H15
LAMP CHECK
H2 Lamp Test H1
E E
MCB (H) MCB (H)
RP RP
CIRCUIT-BREAKER H13 H17 H73 H70
HEATER SUPPLY
1/2 2/1 X2.40 X2.41 N N
5 AMP
5 AMP
F F
P145
RP RELAY R4 RP
CIRCUIT-BREAKER FAIL P7 P17
G BUS STRIP OUTPUT G
X2.24 H8 H7 X2.25
CB Fail
REVISION 2
J
OF 10
6
SHEET
K
TECHNICAL DRAWINGS
PROJECT APPROVED DESIGN APPROVED
DATE
S.J. van ZYL
DATE
EXERCISE
/ / 13/07/07
PROJECT CHECKED DESIGN CHECKED
S. TSHOBENI
2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
1 SvZ 28/08/2007 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - DATE / / DATE
13/07/07
WORKSHEET 10 6 0
REV AUTH DATE REVISION TO MASTER BY CHKD SCALE
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A A
SUPERVISORY ALARMS PNT NAME DESCRIPTION/
SUPERVISORY CONTROLS
ALARM WORDING PNT NAME
NOTE 3 P145
P145
OPTO L17
RP RELAY R5 RP RP RP
CIRCUIT-BREAKER X101 X103 CIRCUIT-BREAKER W101 W102
OPEN OPEN
X3.1 H10 H9 X3.2 NOTE 1 X3.35 E2 E1 X3.36
SUP CB Open SIR CB Trip
CIRCUIT-BREAKER
B (CBP) B
RP RELAY R6 RP
CIRCUIT-BREAKER X105 X107
OPTO L18
BREAKER CLOSED RP RP
X3.3 H12 H11 X3.4 CIRCUIT-BREAKER W103 W104
SUP CB Closed
CLOSE
X3.37 E4 E3 X3.38
SIR CB Close
RP RELAY R7 RP
SUPERVISORY X109 X111 SUPERVISORY
ISOLATED (SUP)
X3.5 H15 H14 X3.6
SUP SIS Off OPTO L19
RP RP
W105 W106
ARC ON
C RELAY R8 C
RP RP X3.39 E6 E5 X3.40
X113 X115 SEF
SEF OFF SIR ARC On
(SEFI)
X3.7 H18 H17 X3.8
SUP SEF Off
OPTO L20
RP RELAY R17 RP RP RP
X117 X119 AUTO RECLOSE W107 W108
ARC OFF ARC OFF
(ARC)
X3.9 B2 B1 X3.10 X3.41 E8 E7 X3.42
SUP ARC Off SIR ARC Off
RP RELAY R18 RP
D X121 X123 ARC LOCKED OUT D
ARC LOCKED OUT OPTO L21
(ARCL) RP RP
X3.11 B4 B3 X3.12 W109 W110
SUP ARC L/O SEF ON
X3.43 E10 E9 X3.44
SIR SEF On
RP RELAY R19 RP
X125 X127 PROTECTION TRIP
PROTECTION TRIP
(PT)
(OVERCURRENT & EARTH FAULT) X3.13 B6 B5 X3.14
SUP O/C&E/F OPTO L22
RP RP
W111 W112
SEF OFF
RP RELAY R20 RP
X129 X131 SEF TRIP X3.45 E12 E11 X3.46
E SEF TRIP SIR SEF Off E
(SEFT)
X3.15 B8 B7 X3.16
SUP SEF Trip
RP
X133
RELAY R21
X135
RP VT SUPPLY
SERIAL INTERFACE AND TIME SYNCHRONISATION
VT SUPPLY FAIL (VTSU)
X3.17 B10 B9 X3.18
SUP VT Fail
P145
+ RP
RP RELAY R22 RP Red Red
TRIP CIRCUIT X137 X139 TRIP CCT (TRIP CCT SUP)
Red
F SUPERVISION (TCT) J18 X3.47 F
X3.19 B12 B11 X3.20
SUP TC Fail
RP
RELAY R23
SERIAL SCADA COMMUNICATION COM 1 Blue Blue
INCOMING
RP RP -
CIRCUIT-BREAKER MB X141 X143 HEATER TERM. Blue
RS485 REAR PORT SUPPORTING DNP3 PROTOCOL X3.48
HEATER FAIL (HF) BLOCK
X3.21 B15 B14 X3.22 J17
SUP HeaterF CONN.
NOTE 4 RP
SCN
RP RELAY R24 RP
CIRCUIT-BREAKER X145 X147 CIRCUIT-BREAKER X3.49
PNH-X X3.50
RP RP
PROTECTION X149 X151 PROTECTION
RP
NOT HEALTHY (PNH) Blue
X3.25 5 6 X3.26 OUTGOING
X3.51 NOTE 5
NOTE 4 RP
H X3.52
RP RP
X3.27 X3.28
TXRXA RP
Red Red
Red
REVISION 2
4 X3.53
RP RP
REMOTE ENGINEERING ACCESS
X3.29 X3.30 RP
Blue Blue
RS232/RS485/K-BUS (SETTABLE) REAR PORT SUPPORTING COM 2 TXRXB INCOMING
Blue
COURIER PROTOCOL FOR APPLICATION WITH MiCOM S1 SOFTWARE DB9F X3.54
J SK4 7
RP RP
NOTE 4 RP
X3.31 X3.32
-0V
OF 10
X3.55
5
AMP Tx RP
Red
CONT. FROM SHT 3
SHEET7
X3.56
2
1
= RP
RP 6 RP Blue
K AMP TRANSDUCER W1 W2 OUTGOING
5
(OPTION) + - X3.57 NOTE 5
X3.33 X3.34
S. TSHOBENI
M
3. THE P145’s OPTO INPUTS ARE RATED FROM 19Vdc TO 265Vdc, WITH THE PICK-UP RANGE
DATE / / DATE 13/07/07
SUP ALARMS AND CONTROLS
OF EACH OPTO INDIVIDUALLY SELECTABLE BY SETTINGS.
/ / DRAWN BY DRAWN BY
SET NUMBER SHEET NUMBER REVISION
4. RS485 COMMUNICATION CIRCUITS TO BE EARTHED AT ONE POINT ONLY. 2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
5. INSERT 120 OHM TERMINATING RESISTOR BETWEEN + AND - IF DAISY CHAIN TERMINATES AT THIS RELAY PANEL.
1 SvZ 28/08/2007 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - DATE / / DATE
13/07/07
WORKSHEET 10 7 0
REV AUTH DATE REVISION TO MASTER BY CHKD SCALE
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
SHT 6
IA OPTO L24 2 1
TXRXA
A A PHASE 5A-C1 NOT SHT 7 A
SHT 3 SPARE 4
CURRENT 1A-C3 C2 USED E16 E15
IB COM 2 SHT 6
-0V 4 3
B PHASE 5A-C4 SK4 PORT SHT 7
SHT 3 POWER - = + 5
CURRENT 1A-C6 C5 SHT 5 DB9F
SUPPLY J1 = J2
IC
TXRXB SHT 4
C PHASE 5A-C7 SHT 7 12
SHT 3 + - 7
CURRENT 1A-C9 C8 48Vdc FIELD 11
J7 = J9 SPARE
IN SUPPLY 14
J8 J10 -
NEUTRAL 5A-C10 SHT 7
B SHT 3 B
CURRENT 1A-C12 C11 IRIG-B INPUT
DM
ISEF WATCHDOG SPARE BNC CONNECTOR
J11 J12 + D1
SENSITIVE 5A-C13 SHT 7
SHT 3 SHT 4
CURRENT 1A-C15 C14 F C
WATCHDOG SHT 5
J13 J14
VA D2
A PHASE ( OPTIONAL ) AMP TRANSDUCER SHT 4
SHT 3 E D
VOLTAGE C19 C22 SCN POWERCON CA4
SHT 7
VB J16
B PHASE SHT 3 ETPB
C C
VOLTAGE C20 RS485 PORT -
SHT 7
VC COM 1 J17 SHT 4
2 13 14
4
C PHASE 5 -
VOLTAGE C21 + SHT 7
SHT 7 =
J18 1 SHT 5
VS 6 13 14
4
+
SYNCH CHECK
SPARE
VOLTAGE C23 C24 RL1
LAMP
SHT 6 APT-X
TEST H1 H2 FC
D OPTO L1 D
RL2
CB VT/TCS SHT 5 SHT 4
SHT 4 SHT 5 2 10
OPEN D2 D1 OK H3 H4
OPTO L2 RL3
ANY PROT SHT 5
CB SHT 4 4
SHT 4 TRIP H5 H6
CLOSED D3 D3 1 MCB (AC)
RL4 3 10A
OPTO L3 CB
SHT 6
SPRING FAIL H7 H8 SHT 6
SHT 4 1/2 2/1
DISCHARGED D6 D5 SHT 5
E 5 E
RL5
SUP IND
OPTO L4 SHT 7 6
CB OPEN H9 H10
CB NOT 7 SHT 6
SHT 4 N N
HEALTHY D8 D7 RL6
SUP IND
SHT 7
OPTO L5 CB CLOSED H11 H12 SHT 5
8
CB HEATER
SHT 4 RL7 11
FAIL D10 D9 MCB (H)
9
H13 5A
OPTO L6 SHT 7
SUP IND H15
EXT TRIP SHT 6
F SHT 4 SIS OFF H14 AS-1 1/2 2/1 F
& L/O D12 D11
ALSTOM SNUB CIRCUIT
RL8
OPTO L7
TRIP COIL H16 SHT 6
SHT 4 SHT 7 SHT 4 N N
HEALTHY D14 D13 SUP IND H18
+ -
SEF OFF H17
OPTO L8
NOT RL9
SPARE NOT
USED D16 D15 SPARE AS-2 MCB (VT)
USED G1 G2
ALSTOM SNUB CIRCUIT 2A
OPTO L9
RL10
G APT TIMER MAIN SHT 3 G
SHT 5 SHT 4 1/2 2/1
INPUT F2 F1 TRIP G3 G4 SHT 5
+ -
OPTO L10 RL11
NOT
EMERGENCY SPARE SHT 3
SHT 5 USED G5 G6 3/4 4/3
TRIP F3 F3
CL-X
RL12
OPTO L11 NOT
SPARE
USED G7 G8 SHT 3
STATUS 1 SHT 5 SHT 5 5/6 6/5
F6 F5 2 10
RL13
OPTO L12 CB CLOSE SHT 5
H G9 G10
SHT 5
STATUS 2 SHT 5 4
F8 F7 RL14 PNH-I
1
ANTI-PUMP SHT 5
OPTO L13 G11 G12 3
SHT 6
REVISION 2
STATUS 3 SHT 5 RL15
F10 F9 AMBER
SHT 5
G13 5
OPTO L14 SPARE
NOT G15 6
SPARE PNH-X
SHT 5 USED G14 7
INPUT F12 F11
J
RL16
OPTO L15 SHT 5
SHT 5 2 10
NOT G16 8
OF 10
SPARE SHT 4
USED F14 F13 FAULT G18 11
COUNTER G17 9 SHT 6
OPTO L16 4
NOT RL17 1
SHEET 8
SPARE SUP IND
USED F16 F15 SHT 7 CTTB 3
ARC OFF B1 B2
IST PK2 4-WAY
OPTO L17
RL18
SUP SUP IND SHT 7
SHT 7 SHT 7 5
K CB OPEN E2 E1 ARC L/O B3 B4
8 7 6
OPTO L18 RL19 7
SUP IND
SUP SHT 7
SUP
OPTO L21 TCS FAIL B11 B12
DCI MCB (M) 8 7
TECHNICAL DRAWINGS
SHT 7 RL23 PROJECT APPROVED DESIGN APPROVED
SEF ON E10 E9 16A
OPTO L22
B13
SHT 7 SHT 4
6 5 DATE
S.J. van ZYL
DATE
EXERCISE
SUP IND B15 1 2 / / 13/07/07
SUP SHT 3 PROJECT CHECKED DESIGN CHECKED
SHT 7 HEATER FAIL B14
SEF OFF E12 E11 S. TSHOBENI
RL24
REFERENCE DIAGRAM
M OPTO L23 SHT 4 4 3 DATE / / DATE 13/07/07
3 4 / / DRAWN BY DRAWN BY
SPARE SHT 7 2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
USED E14 E13 SUP IND B18
CBNH B17 2 1
1 SvZ 28/08/2007 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - DATE / / DATE
13/07/07
WORKSHEET 10 8 0
REV AUTH DATE REVISION TO MASTER BY CHKD SCALE
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
REVISION 2
AC/DC DISTRIBUTION BOARD
OF 10
SHEET 9
K TERMINAL LOOPS (*)
NOTES:
STANDARD TERMINALS USED ARE ELMEX KULT1 10mm SPRING LOADED TERMINALS
DATE
S.J. van ZYL
DATE
EXERCISE
/ / 13/07/07
ELMEX KULTD6 8mm SPRING LOADED SLIDING LINK TEST TERMINAL PROJECT CHECKED DESIGN CHECKED
M
ENTRELEC D2.5/[Link] INSULATION DISPLACEMENT TERMINAL WITH DISCONNECT DATE / / DATE 13/07/07
PANEL CABLING DIAGRAM
ENTRELEC D6/[Link].1 INSULATION DISPLACEMENT TERMINAL / / DRAWN BY DRAWN BY
SET NUMBER SHEET NUMBER REVISION
ELMEX KUDF4 8mm TERMINAL WITH 1MOHM RESISTOR 2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A A
B B
C C
D D
E E
F F
G G
REVISION 2
J
SHEET 10 OF 10
K
TECHNICAL DRAWINGS
PROJECT APPROVED DESIGN APPROVED
DATE
S.J. van ZYL
DATE
EXERCISE
/ / 13/07/07
PROJECT CHECKED DESIGN CHECKED
S. TSHOBENI
2 SvZ 04/04/2008 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - S.J. van ZYL
1 SvZ 28/08/2007 CHANGES AS PER SHEET 0 - COVER SHEET SvZ - DATE / / DATE
13/07/07
WORKSHEET 10 10 0
REV AUTH DATE REVISION TO MASTER BY CHKD SCALE
SIZE
1 2 3 4 5 6 7 8 LEVELS 10 PANEL TYPE DESIGNATION 4RF-1100 GROOTTE A1L