Refrigerant Charging Techniques Guide
Refrigerant Charging Techniques Guide
AND
AIR-CONDITIONING
LAB MANUAL
CERTIFICATE
satisfactorily completed his/her term work for the subject Refrigeration and
Date :
INDEX
Objective:
To study different components of VCR system.
To determine C.O.P. of VCR System.
Refrigeration:
Theory:
Refrigeration may be defined as an art of producing and maintaining a temperature in a space
below the surrounding temperature. It also includes the process of removing heat from the substance
under controlled conditions. It is used for the manufacturing of ice and similar products. This is widely
used for cooling of storage chambers in which perishable foods, drinks and medicines are stored. The
refrigeration has also wide application in submarine ships, aircrafts.
Standard Vapour Compression Cycle: - (SVCC)
This cycle consists of following four processes:
(1) Reversible adiabatic compression from the saturated vapour to a superheated condition.
(2) Reversible heat rejection at constant pressure (de-superheating and condensation of the refrigerant)
(3) Irreversible is enthalpy expansion from saturated liquid to a low pressure vapour.
(4) Reversible heat addition at constant pressure.
System components and its function: -
(1) Compressor: - Compressor is most important part of the system. The compressor raises the measure
of incoming vapour from the evaporator to a high pressure. Different type of compressor are:
Reciprocating compressor
Rotary compressor
Screw compressor
Centrifugal compressor
The selection of the above mentioned compressor depends upon the usage. Usually domestic
refrigerator are installed with reciprocating compressor. A hermetic type compressor is one in which
the compressor and motor integral on one shaft and they are both contained in a pressure shield
housing. It is compact in size, quite, low in cost and no problem of refrigerant gas leakage. The motor in
a hermetic type compressor is cooled by refrigerant suction gas.
Fig. 1.1- Schematic diagram of Vapour Compression Refrigeration System
(2) Condenser: - The function of a condenser is to remove heat from the superheated high pressure
refrigerant vapour and to condense the vapour into a sub cooled high pressure liquid. This is
accomplished a cooling medium either air or water. The air cooled condenser may be of static cooled
type where natural convective motion of air surrounding heat is enough to cool the condenser or they
may be of fan cooled type. The static cooled condenser is used in domestic refrigerators. In commercial
appliances and windows air-conditioners usually fan cooled condensers are used. The water
condenser is normally used in large system firms 5 tons and above.
(3) Expansion Devices: -As the high pressure sub-cooled refrigerant liquid from the condenser passes
through the expansion device its pressure and temperature is reduced. And outlet refrigerant, mostly
in liquid stage.
Expansion device are of many types and are selected as per the requirement. For example, for constant
evaporator pressure requirement automatic expansion valve are used. If variation in cooling load is
high the thermostatic valves are best suited.
Hermetic compressor are almost invariably are used with capillary tube, through a few of them might
also be used with thermostatic expansion valves.
(a) Thermostatic expansion valve: -
Thermostatic expansion valve controls the mass flow rate of refrigerant by sensing evaporator
outlet temperature. Thus the valve is sensitive to the cooling load. If the load is more, the degree of super
hit of refrigerant coming out of the evaporator increases. To maintain the degree of super heat to preset
level, more liquid is fed to evaporator. When the load is low, valve closes and less liquid quantity is fed.
Selection of thermostatic expansion is done on the basis of refrigerant used in capacity.
(b) Capillary tube: -
It is the simplest and cheapest form of expansion device. It does not include any moving parts hence
no maintenance is required. Capillary tube is supposed to be a single point operation device in the sense
that the best control is achieved only at a given set of operating parameters.
Under varying loads the capillary tube does not function satisfactorily. For example at lower loads
than designed value capillary tube may overfeed the evaporator causing liquid to return to compressor.
Under higher loads than designed the capillary tube starves the evaporator, causing excessive return gas
superheat. Hence for variation in cooling loads, it is not suitable.
(4) Evaporator: -The function of evaporator is to remove heat from the product or the area to be cooled
and maintain it at any desired temperature. The liquid refrigerant inside the evaporator evaporates by
absorbing heat and converts into vapour refrigerant and then it returns back into the compressor.
Various types of constructions of the evaporator used in refrigerant system e.g.
a) Finned tube evaporator coil
b) Bare tube soldered/clamped to the tank
c) Bare tube dipped in the liquid to be cooled
d) Shell & coil type evaporator
The choice of particular construction depends on the type of appliance. However in every case the
heat capacity depends on these factors viz. temperature difference between the load and the refrigerant,
heat transfer co-efficient and areas of the heat transfer.
(5) Drier: - If by chance refrigerant is containing any water particle then in low temperature region (i.e. at
and after the expansion valve) it forms ice and chokes the valve or bends thereby preventing the
smooth passage of refrigerant through it. To prevent this drier is used to remove any water particles
carried into the refrigerant. It is used in between the evaporator and compressor.
(6) Accumulator: -It is fitted in between the evaporator and compressor. It prevents the liquid refrigerant
from entering the compressor.
Description of Setup:
The unit is equipped with compressor operate on 220V AC supply and works on R-134 a. The unit
is fitted on with compressor, air cooled condenser, condenser fan motor drier, thermostatic expansion
valve, solenoid valve, capillary tube, expansion valve refrigerant flow motor water calorimeter (cooling
coil), suction gauge, discharge gauge, digital temperature indicator with probe to measure different
temperatures, heater inside the calorimeter, cooling thermostat, one number charging valve provided to
charge the liquid refrigerant. The voltmeter and ampere meter for compressor have been provided which
are duly interlocked type writing for safety point of view.
Technical Specifications:
Compressor : Hermetically sealed make
Agitator : Compatible capacity
Condenser : Air cooled compatible to compressor
Condenser cooling fan : Compatible capacity with permanent lubricating motor
Evaporator : Made of Stainless steel insulated with ceramic wool/P.U.F
Rotameter : Make Eureka
Expansion device : Capillary tube solenoid & thermostatic valve
Pressure gauges : 2 Nos.
Safety control : Time delay circuit
Temperature sensor : RTD PT-100 type
Control panel : Digital voltmeter (0-300V) and ammeter (0-10A)
Temp. Measurement : Digital temperature indicator with multi-channel switch
Experimental Procedure:
1. Switch in main board, check voltage. It should not be less than 180 V.
2. Start the condenser fan motor.
3. See that all the respective indication lights are on.
4. Put the water in the evaporative tank/calorimeter.
5. Switch on the compressor.
6. At the time of the start of the unit, note down the reading of voltage, ampere, suction and
discharge gauge- pressures reading for compressor.
7. Check and note down the reading of various temperature through digital temp. Indicator.
8. Always close the door of the evaporator.
9. Note down the reading of the pressure gauge. Absence of any reading will indicate the blockage or
leakage of gas.
10. After the gap of 15 minutes, start the agitator motor for two minute for equalization of water
temperature and note down all the readings.
11. Now if you want to provide or test load on our compressor, switch on the heater.
12. Check and note don the readings of temperature, pressure and energy.
13. Now let the unit run for at least 10-20 minutes.
14. Switch on the agitator motor for 2 minutes for equalization of water temperature.
15. Check the water temperature through Digital Temp. Indicator. It must not go ahead of 350C.
16. After taking the required readings, switch off the heating process if the unit runs with compressor
or cooling process.
17. While closing the unit, first switch-off the compressor, condenser, fan motor, and all the other
valves and switches on the unit.
18. Always check the indication lights provided on the board for each component.
Observation Table:
Sr. Volume of
P1 P2 T1 T2 T3 T4 T5 T6 V I
No water (W)
1
Calculations:
(1) C.O.P. theo :-
𝑅𝐸
COPth = 𝐶𝑊𝑡ℎ
𝑡ℎ
𝐻1 −𝐻3
COPth = (H3=H4)
𝐻2 −𝐻1
Nomenclature: -
T1 – Temperature of compressor inlet (suction) (0C)
T2 – Temperature of compressor outlet (discharge) (0C)
T3 – Temperature of condenser outlet (0C)
T4 – Temperature of evaporator inlet (0C)
T5 – Temperature of water inlet (0C)
T6 – Temperature of water outlet (0C)
H1 – Enthalpy at compressor inlet (KJ/kg)
H2 – Enthalpy at compressor outlet (KJ/kg)
H3 – Enthalpy of sub-cooling at condenser outlet (KJ/kg)
H4 - Enthalpy of refrigeration at evaporator inlet (KJ/kg)
P1 & P2– Pressure at compressor suction and discharge (kg/cm 2)
V & I – Voltmeter and ammeter reading
Conclusion:
Exercise:
1 Why in practice a throttle valve is used in vapour compression refrigerator rather than an
expansion cylinder to reduce pressure between the condenser and the evaporator?
2 Explain Construction and working of simple vapour compression refrigeration system
with P-V, T-S and P-H diagram and derive equation of COP for Bell-Coleman cycle.
3
A 5 Tonne R-12 refrigeration plant has saturated suction temperature of -5°C. The condensation
takes place at 32°C and there is no undercooling of refrigerant liquid. Assuming isentropic
compression, find (i) COP of the plant, (ii) Mass flow rate of refrigerant (iii) Power required to run
the compressor in KW.
Take the following properties of R-12.
Objective:
To study different components of Electrolux VAR system.
To determine C.O.P. of Electrolux VAR System.
Theory:
Electrolux refrigeration is an absorption type refrigeration system. In absorption refrigeration system,
the vapour is drawn from the evaporator by absorption into liquid having high affinity for refrigerant.
The refrigerant is expelled from the solution by application of heat and its temperature is increased. This
refrigerant in the vapour form passes to the condenser gets liquefied where heat is rejected and the
refrigerant gets liquefied. This liquid again flows to the evaporator at reduced pressure and the cycle is
completed.
Absorber: -The main function of the absorber is the absorption of the refrigerant vapour by its weak or
poor solution in a suitable absorbent, forming a strong or rich solution.
Condenser: -It condenses the vapour refrigerant into the liquid by condenser fan and passes it into the
receiver tank for recirculation.
Evaporator: - It evaporates the liquid refrigerant by absorbing the heat into vapour refrigerant and
sends back to next run.
Vertical generator in which an aqua solution of ammonia can range itself from distilled water at
the bottom of the generator to strong ammonia vapour at the surface of liquid.
A water separator which is provided to remove water vapour so that they should not enter the
condenser, get condensed there and pass on to evaporator where chocking might occur due to its
freezing. The water vapour is formed in the boiler as some of the water may evaporator on application of
heat to the boiler. The separator is jacked with liquid ammonia at pressure of about 14 bar gauge for
which the saturation temperature is about 400C.
The dehydrate ammonia gas condensed to liquid in the condenser and gravitates to ‘U’ tube which
acts as seal for the gas to enter the evaporator or any gas passing from evaporator to condenser.
In the evaporator, ammonia liquid comes across an atmosphere of hydrogen at about 12 bar
pressure. The plant is charged to a pressure of about 14 bars. Hence due to Dalton’s law of partial
pressure. The pressure of ammonia gas should fall to about 2 bar gauge and the saturation temperature
corresponding to about 2 gauges is about -100C. The temperature surrounding the evaporator is much
high than this. Thus ammonia evaporates and produces the refrigerating effect i.e. absorbs the latent heat
of vaporization at 2 bar gauge and about -100C from the space to be refrigerated.
In order to ensure continues action, hydrogen gas has to be removed from ammonia vapour. This is
done in the absorber where a descending spray of very dilute ammonia liquid moseys the ascending
mixture of ammonia vapour and hydrogen. Ammonia vapour is readily absorbed with evaluation of heat
so that absorber has to be water jacketed or air cooled, otherwise evaporation may take place in this unit
and the absorption may cease.
Heat exchanger: Liquid heat exchanger is placed between absorber and the generator. This weak liquid
gets cooled and strong liquid gets heated. Thus is economized and better thermal efficiency is obtained.
This heat exchanger is counter flow type. The strong solution from the absorber is preheated on its way
to generator or boiler and the dilute solution on its way to absorber is cooled. This cooling of weak liquid
also helps absorption and reduces the cooling of absorber by external source.
Working:
(1) Strong ammonia solution flows from the absorber vessel through heat exchanger to the generator.
(2) When the ammonia solution is heated in the generator by applying heat from the external source,
bubbles of ammonia gas raises from the generator and passes to condenser through rectifier.
(3) The ammonia vapour is removed from the solution and passes into the condenser. Weak ammonia
solution left behind in the generator flows to the absorber through the heat exchanger.
(4) Air circulating over the fins of the condenser, cool down the vapour, condensing it into liquid
ammonia, which flows under gravity to the evaporator where it meets the hydrogen gas.
(5) The hydrogen in the evaporator lowers the ammonia vapour pressure and makes it evaporate.
(6) This process extracts heat from the evaporator, which in turn extracts heat from the food storage
space. Thereby the temperature inside the refrigeration is lowered.
(7) The mixture of hydrogen and ammonia passes from the evaporator to the absorber. Weak ammonia
solution is fed from the generator system through heat exchanger.
(8) As it returns to the absorber vessel, it absorbs the ammonia from the ammonia/hydrogen mixture
and gets ready for another round in the generator.
Experimental Procedure:
1. Ensure that all ON/OFF switches given on the panel are at OFF position.
Observation Table:
SR. No. T1 T2 T3
Calculations:
𝑇3 (𝑇1 −𝑇2 )
COP=
𝑇1 (𝑇2 −𝑇3 )
Nomenclature: -
COP – Co-efficient of performance
T1 – Temperature of generator, K
T2 – Temperature of condenser, K
T3 – Temperature of evaporator, K
Conclusion:
Exercise:
What is basic principle of Vapour absorption refrigeration system? Write brief note on
1
Electrolux (NH3-H2) refrigerator.
Explain the significance of Hydrogen used in Electrolux Refrigerator system. In a 15 TR ammonia
refrigeration plant, the condensing temperature is 250C and evaporating temperature -100C. The
refrigerant ammonia is sub-cooled by 50 C before passing through the throttle valve. The vapour
leaving the evaporator is 0.97 dry. Find (1) Coefficient of performance and (2) power required.
Use the following properties of ammonia:-
Enthalpy, Entropy,
2 Saturation Specific heat,
kJ/kg kJ/kg K
temperature kJ/kg K
0C
Discuss the advantages of vapour absorption refrigeration system over vapour compression
3
refrigeration system.
What is the effect of sub-cooling on the performance of vapour compression refrigeration
4
system?
GOVERNMENT ENGINEERING COLLEGE, VALSAD
MECHANICAL ENGINEERING DEPARTMENT
Objective:
To study construction and working of reciprocating, rotary and centrifugal compressor
Theory:
The compressor is the heart of vapour compression system. The compressor is used to reclaim the
refrigerant vapour leaving the evaporator. The refrigerant must be compressed to the pressure
corresponding to a saturation temperature higher than the temperature of the naturally available air or
water. The compressor is also used to circulate the refrigerant through the system. The capacity of
compressor determines the capacity of refrigeration system as a whole. The refrigeration compressor and
gas or air compressor differs very much because the refrigerating compressor is integral part of the cycle
and it is coupled to other components.
Classification:
Classification of refrigeration compressors:
1. Reciprocating compressor.
2. Rotary compressor.
3. Centrifugal and scroll compressor.
1. Reciprocating Compressor:
The reciprocating compressors are available in sizes as small as 1/12 hp up to about 150 hp for large
capacity installation. The reciprocating compressors are of three types.
a) Open type compressor.
b) Hermetically sealed compressor.
a) Open type of compressor:
A compressor whose crankshaft extends through the compressor housing so that a motor can be
externally coupled to the shaft is called open type [Link] types of compressors adopt a
volumetric compression system using pistons and work much like an internal combustion engine. The
pistons run up and down inside cylinders, producing suction and compression of the refrigerant gas.
Each cylinder has a suction valve for the gas refrigerant and a discharge valve to deliver the gas to the
condenser after having been compressed. A disadvantage of the open type of compressor is that the
shaft seal is most vulnerable point for leakage of refrigerant.
Fig 3.1- Cross-Section of Open Type compressor
b) Hermetically sealed compressor:
In hermetic compressor there is no need for shaft seal. The compressor and motor are mounted on
single shaft and whole assembly is fixed in a steel shell, the joint of which are welded. The losses due to
drive package and shaft seal friction are also eliminated i.e. the power required per tone of refrigeration
is less then that of the open type.
2. Rotary compressor:
As the name implies, the displacement and compression of the refrigerant vapour is achieved due to
circular or rotary motion instead of reciprocating motion. These compressors are very efficient because
the actions of taking in refrigerant and compressing refrigerant occur simultaneously. They have very
few moving parts, low rotational speeds, low initial and maintenance costs, and are forgiving in dirty
environments. However, they are limited to smaller volumes of the gas and produce less pressure than
other types of compressors. There are two types of rotary compressor.
a) Rolling or Stationary Single Blade type rotary compressor:
The main components of rotary compressor are cylinder, roller mounted eccentrically on motor shaft
and a spring loaded shaft. The roller moves eccentrically on the driver shaft inside a stationary cylinder.
The vane moves up and down in the slot. This vane is dividing line between the suction and discharge of
compressor.
3. centrifugal compressor
Centrifugal compressors are similar in construction to centrifugal pumps , the incoming fluid enters the
eye of the spinning impeller and is thrown by centrifugal force to the periphery of the impeller. Thus
the blades of the impeller imparts a high velocity to the gas and also build up the pressure. From the
impeller the gas goes either into diffuser blades or into a volute casing, where some of the kinetic
energy is converted into pressure.
Exercise:
Exercise:
where,
pw = Existing partial pressure of water vapour in bar
pwb = Saturation pressure in bar corresponding to wet bulb temperature, Twb
p = Total pressure of the environment in bar
Tdb = Dry bulb temperature
Tdp = Dew point temperature
Psychometric Properties:
A. By Observation:
All reading are taken on date ______________ at __________ pm
1) Dry bulb temperature Tdb = ____________ ˚C
2) Wet bulb temperature Twb = ____________ ˚C
3) Relative humidity by hair hygrometer RH = ____________%
4) Barometric pressure p = ____________ bar
B. By calculation:
1) Dew Point Temperature Tdp = ____________ ˚C
2) Relative Humidity RH = _____________%
3) Partial pressure of water vapour by Dr. Carrier’s Eq. = _____________bar
4) Specific Humidity = _____________kg/kg of dry air
5) Absolute Humidity = _____________for 100m3 of air
6) Enthalpy of air ha = _____________ KJ/kg of dry air
7) Specific volume of air = _____________ m3/kg of dry air
8) Amount of dry present in 100m3 of air = _____________ kg
C. By psychrometric chart:
1) Relative Humidity RH = _____________ %
2) Work done w = _____________ KJ/kg of dry air
3) Enthalpy of air ha = _____________ KJ/kg of dry air
4) Specific volume va = _____________ m3/kg
5) Dew point temperature Tdp = _____________ ˚C
Exercise:
1 Define following terms: (i) Saturated air (ii) Specific humidity (iii) Relative humidity (iv)
Absolute humidity (v) Dry bulb temperature (vi) Dew point temperature (vii) Wet bulb
depression.
2 The sling- psychrometer reads 35°C DBT and 25°C WBT calculate followings: (i) Specific
humidity (ii) Relative humidity (iii) Absolute humidity in air (iv) Dew point temperature
(v) Enthalpy of the mixture per kg of dry air. Assume atmospheric pressure to be 1.01 bar.
3 40 m3 of air at 35°C DBT and 50% R.H. is cooled to 25°C DBT maintaining its specific
humidity constant. Determine: (i) Relative humidity (R.H.) of cooled air ; (ii) Heat
removed from air.
4 The atmospheric air at 300C dry bulb temperature and 75 % relative humidity enters a
cooling coil at the rate of 200 m3/min. The coil dew point temperature is 140C and the by-
pass factor of the coil is 0.1. Determine: 1. The temperature of air leaving the cooling coil;
2. The capacity of the cooling coil in tonnes of refrigeration 3. The sensible heat factor for
the process.
GOVERNMENT ENGINEERING COLLEGE, VALSAD
MECHANICAL ENGINEERING DEPARTMENT
Objective:
To determine C.O.P. of air-conditioning test rig.
To determine apparatus dew point of air-conditioning test rig.
Theory:
Previously the air conditioning for human comfort was considered luxury in most of the
countries but now a days it is a necessity. Therefore air conditioning industry is growing fastly
throughout the world. Due to increase in population and industrialization the uncomfort may be
due to the inadequate supply of oxygen or unbearable temperature. Full air conditioning does
the automatic control of an atmospheric environment either for comfort of human being or
animals or for the proper performance of some industrial or scientific processes. The purpose of
air conditioning is to supply sufficient volume of clean air containing a specific amount of water
vapour and at a temperature capable of maintaining predetermined atmospheric conditions.
1. Temperature Control: You can enjoy a perfect constant temperature because of the control of
not only cooling but also heating.
2. Humidity Control: The room can be humidified or dehumidified.
3. Air Filtering, Cleaning and Purification: The room is cleaned by removing dust and dirt from
the air.
4. Air movement and Circulation: Air which is cleaned and controlled in temperature and
humidity is distributed throughout the room. As a result, room air can be maintained evenly.
Description of Setup:
The equipment consists of a hermetically sealed compressor, air cooled condenser, blower for air
circulation through a duct mounted on a frame, an evaporator is placed in the duct, also there are heaters
of suitable capacity in the duct. The refrigerant used in the system is R22. The mass flow rate of air
through duct can be varied by arrangement provided on the blower unit. The humidity of air is increased
by introducing steam generated in small boiler. The relative humidity of air at inlet and outlet can be
measured by noting dry / wet bulb temperatures. The duct is insulated from outside to avoid heat loss.
The control panel consists of switches, voltmeter, ammeter etc. as well as energy meter for measuring the
power consumption of compressor. The refrigeration circuit and duct are mounted on a fabricated frame.
Technical Specifications:
1. Compressor : Hermetically sealed type.
2. Condenser : Air cooled type, cooling fan driven by motor.
3. Rotameter : Eureka make, range 6.1-61 LPH, calibrated for R22
4. Thermostatic Expansion valve : Danfos make no
5. Evaporator : Evaporator fitted in the duct size 10” x 10” x 3 row.
6. Blower unit : To force air through the duct 1HP 3 phase motor.
7. Heater fitted in the duct after the evaporator: 2kw
8. Steam generator to generate steam with suitable piping for introducing steam in the duct- 8
litre capacity, with 2 kw heater.
a) Pressure gauges for measurement of pressures.
b) HP & LP cut outs:
c) Energy meter for compressor with EMC ______ R/kwh.
Experimental Procedure:
The demonstration of the following processes can be done on the test rig.
1. Cooling process.
2. Heating process.
3. Cooling with dehumidification process.
4. Heating with humidification. Process.
Cooling Process: (Sensible cooling)
It is cooling with out subtraction of moisture is termed as sensible cooling. The cooling can be achieved by
parsing the air over cooling coil like evaporating coil of refrigeration cycle.
Heating Process:
Heating of air without addition of moisture is termed sensible heating. The heating can be achieved by
passing air over heater in the duct. The process is represented as below in psychometric chart:
Cooling with Dehumidification:
In this process cooling along with humidification is carried out it is represented as below:
Heating with Humidification:
It is represented as given below.
for starting the test rig. Put ‘ON” the air condenser fan and run it for 2-3 minutes.
1. Then start blower with suction full open.
2. Now put ‘ON’ the compressor switch, so that refrigeration cycle may produce refrigeration effect.
3. Run the plant for achieving steady temperature at condenser and Evaporator.
4. Measure the air velocity in the duct by using anemometer.
5. Note down the following observations.
Observation Table:
Heo – Hei
1. Theoretical COP = (Hco = Hei)
Hcl − Heo
rev x 3600
6. Work done by compressor = watt .
T x EMC
Actual COP
7 . Relative COP = Theoretical COP
TL
8. Carnot COP = TH & TL = Saturation temperature of condenser and evaporator in K
TH – TL
Conclusion:
Exercise:
Objective:
To study different controls used in refrigeration and air conditioning.
Theory:
1. Flow control devices :
The major devices under this category air the expansion devices. The purpose of the expansion devices
is two fold : it must reduce the pressure of the liquid refrigerant, and it must regulate the flow of
refrigerant to the Evaporator. An expansion device offers a resistance to flow so that the pressure drops
Resulting in a throttling process. Basically there are two types of expansion devices.
I. Variable restriction type
II. Constant Restriction Type
I. Variable restriction type
In the variable restriction type the extent of opening or area of flow keeps on changing depending on
the type of control. There are two common types of such control devices viz,
A. Thermostatic expansion valve.
B. Automatic expansion valve.
A. Thermostatic Expansion value (TEV):
The name may give an impression that it is a temperature control device. It is not a temperature control
device and it cannot be adjusted and used to vary evaporator temperature. Actually TEV is a throttling
device which works automatically maintaining proper and correct liquid flow as per the dictates of the
load on the evaporator. Because of automatic operation, high efficiency and ability to prevent liquid
flood backs this value is extensively used.
P1 = Thermostatic Elements Pressure
P2 = Evaporator Pressure
P3 = Pressure Equivalent of the Superheat Spring Force
1 State the name of Different types evaporative devices used in refrigeration system
Explain Automatic expansion valve.
2 Explain construction, working, advantages and disadvantages of Thermostatic Expansion
valve with neat sketch
GOVERNMENT ENGINEERING COLLEGE, VALSAD
MECHANICAL ENGINEERING DEPARTMENT
Objective:
To determine C.O.P. of Heat pump.
Theory:
Now-a-days, energy conservation is becoming very important. Hence engineers have started using
heat pump systems for commercial and industrial buildings to save energy. The heat pump is a machine
that absorbs heat at one location and transfers it to another location at a different temperature. Heat
pump is the modern expression for a refrigeration system In which heat discharged at the condenser is of
prime importance. Thus heat pump is device which collects heat from one source and delivers it to
another source using refrigeration cycle. The medium being, cooled serves as heat source.
Heat is picked up by the refrigerant, which is pumped to another higher level by the compressor
and given to the medium cooling condenser so that it can be used practically. The heat pumps can be
operated on low temperature heat energy using winter air, a body of water or the ground as a reservoir
and rejecting heat at a higher temperature, not enough to energize heating systems.
Thus the basic heat sources that are normally used are air, water and earth. When heat pumps are
installed frequently provision is made for both heating and cooling services to be supplied simultaneously
to the separate zones of buildings.
Description of Setup:
Mechanical Heat Pump is a table mounted model which uses water as well as air as a heat source
and sink for both cooling and heating purposes. The experiments can be done as water to water heat
pump i.e. using water condenser and water evaporator and water to air heat pump i.e. using water
condenser and air evaporator.
On the unit, compressor is mounted centrally and both the water and air condensers are mounted
on either sides of the compressor. All the components are mounted on the main unit and the schematic
layout of the Mechanical Heat Pump Is sell-explanatory.
Technical Specifications:
1. Compressor : hermetically sealed, using R-12 refrigerant.
2. Condenser : Water cooled copper tube, Shell & Coil type.
3. Rotameter : Eureka make, range 6.1-61 LPH, calibrated for R22
4. Thermostatic Expansion valve : Thermostatic expansion valve having 1/2 ton of
Refrigerating Capacity.
5. Evaporator: (a) Water circulated copper tube, Shell and Coil type.
(b) Air circulated copper tube type.
6. Multichannel Digital temperature indicator with thermocouples: 0-3000 C. with 10 C least
count
7. Pressure gauges: Two Nos. for delivery and suction for measurement of pressures.
8. HP & LP cutouts: of suitable range.
9. Energy meter for compressor with EMC ______ R/kwh.
Experimental Procedure:
This experiment is performed by using water condenser and water evaporator. -
a) Start the water supply to both condenser and evaporator and adjust the flow rate to predetermine
value.
b) See that pressures in both the gauges are equal.
c) Put ‘ON’ the main switch.
d) Check the valve positions as per given diagram.
e) Now, start the compressor cooling fan first and then start the compressor. Within a short period,
clear liquid refrigerant flow will be seen in the rotameter.
f) After sometime the pressure of refrigeration cycle will become stable. Allow the plant to run for at
least half an hour.
g) During testing see that water flow rates are constant and not varying.
h) Allow the plant to attain steady state. Check tor steady state by taking the readings periodically.
i) Take all readings as mentioned in the observation table. Complete one set of observations.
By varying the water flow rate of condenser, effect of sub- cooling can be studied. Similarly by varying
water flow rate of evaporator, load on the plant can be varied.
Observation Table:
Where,
Tc = Time for 10 revolutions of energymeter disc sec.
Actual COP
5. Relative COP =
Theoretical COP
TL
6. Carnot COP = TH – TL
Exercise:
PRACTICAL 9: TO STUDY THE CHARGING, TESTING, EVACUATING, PUMPING DOWN AND LEAK
DETECTION TECHNIQUES IN A REFRIGERATION PLANT.
Objective:
To study the charging, testing, evacuating, and pumping down in a refrigeration plant.
To study leak detection techniques in a refrigeration plant.
Theory:
Charging and Evacuating Techniques:
Charging and evacuating techniques are the method of charging the plant with refrigeration. The
detailed procedure of charging the plant is as under:
Initially there may be air entrapped in the piping circuit of the plant. Thus before charging the
plant with the refrigerant, it is essential to remove entrapped air. For removing this air and thereby to
create a vacuum, a vacuum pump is used, which sucks the air.
A vacuum pump fitted with a compound gauge is connected to the suction line. As the air is
sucked the pointer on the compound gauge keeps on falling steady and vacuum is created. The pump is
run for a while till the compound gauge reads. The system is left as it is for some hours at a stretch and
the compound gauge reading is observed. If the pointer starts climbing towards zero there, it would be
ascertained that there is a leakage and if there is no change in the reading, then we can conclude that
the piping is leak proof.
If there is any leakage i.e. if the compound gauge reading slowly rises to higher values, then this
leakage has to be detected and plugged properly. For this the plant is pressurized with the air at high
pressure, so that the leakage may be removed. This completes the evacuating process.
Now the vacuum pump is disconnected and the suction line is connected to the cylinder
containing the refrigerant. There is a valve, provided at the suction line, which is closed before
disconnecting the vacuum pump. After connecting the cylinder to the suction line of the compressor, the
cylinder valve is opened and the nut joining the pipe to the suction is kept slightly loose. So that when
the valve is opened the refrigerant rushes out and forces the air entrapped in the pipe to the
atmosphere. Now the suction line is opened. There is vacuum inside, it sucks the refrigerant from the
refrigerant cylinder very rapidly. At the same time a pressure gauge indicates the pressure developed in
the compressors due to a charging of pipe attached to the suction line is disconnected and back
pressure is measured. The correct charging pressure is 175 to 200 lb/in 2 and the back pressure is about
20-25 Ib/in2. The correct charging pressure is of importance because if the pressure is more i.e. more
refrigerant is charged, then the handling of the refrigerant is not proper, thereby affecting the
performance of the plant.
Once the charging is over the plant is ready for service.
Testing :
When the refrigerant plant is newly set-up, the pipe joints and other connections of the system
have to be tested for leakage. For that in beginning CO 2 and N2 is passed through the system and
pressure gauge reading is noted. Then at the joint, some soap solution is applied. If no bubbles are
formed at the joint and pressure remains constants then we can conclude that the joints are free from
any leakage and if bubbles are formed then the joint has to be tightened more. The second method is
used to detect the leakage.
The system is completely evacuated after performing leakage test and this is done with the help of
a vacuum pump. Whether the system is completely evacuated or not is determined by the pressure
gauge readings. Then the plant will be evacuated and charged with refrigerant.
Pumping Down:
Pumping down means collecting all the refrigerant of the plant into its receiver tank. It is useful
when there is some minor repair of the plant is to be done. So refrigerant is not required to be removed
of the plant which is otherwise necessitates recharging.
For this the delivery valve of the receiver tank is closed and the plant is run for few minutes. After
some time all the refrigerant will be collected in the receiver tank and after rectifying the fault, by
opening the delivery valve of the plant refrigerant is charged in the line. If necessary, extra amount of
refrigerant should be added from the refrigerant cylinder.
Leak Detection:
If there is any leakage i.e. if the compound gauge reading slowly rises to higher values, then this
leakage has to be detected and plugged properly
Leak Test Methods :
Different leak testing methods one employed for different types of refrigerants.
1. Ammonia, R12, R22:
A. Sulphur Test Method:
Burning sulphur stick shows a dense white smoke if ammonia is present. The burning sulphur stick is
passed around all the joints and suspected leaky points for the appearance of smoke. This test is
applicable for tracing minute leaks only.
B. Soap Bubble Test:
This test may not be very effective to trace very minute ammonia leak as it is soluble in water.
Fortunately, ammonia is having plungent odor, a heavy leak can be easily detectable.
C. Litmus Test:
Wet litmus paper (Phenolpthalene paper) which turns red in contact with ammonia can also be used to
detect leaks.
2. Halogenated Refrigerants:
Soap solution, Halogen leak detector, Halide torch and Electronic leak detectors are the methods used
to trace leaks in halogenated refrigerants
A. Halogen Torch:
A halogen torch can detect minute leaks, which are not possible to trace with soap solution. The presence
of trace of refrigerant can change the light blue colour of the detector flame to green or deep blue. The
end of the explorer tube of the detector is carefully passed over the joints and suspected leakage points. If
there is a leak, the refrigerant can be drained in with the suction effect at the end of the explorer tube to
the hot copper or brass portion of the burning torch. The
refrigerant reacts with the metal to form copper chloride, which produces the color change in the flame.
A well maintained halogen torch is claimed to detect leaks of the order of about 15 gram per year.
B. Electronic Leak Detector:
This is an electrical instrument. In this also an explorer tube is used to suck the refrigerant from the leaky
points to an instrument. A vibrator is provided to suck the refrigerant through the explorer tube. A filter
is also provided at the tip of the tube to prevent atmospheric dert entering the instrument. A heating
element in the tube heats the refrigerant drawn in and the refrigerant creates a variation in the current
flow of the instrument. The extent of variation of the current is an indication of the amount of leak. The
current variation is read on the dial of the instrument. The change of current actuates a relay which
operates an indicating light. These detectors are capable of detecting refrigerant leaks of the order of
about 0.3 gm per year. The electronic leak detector is a very sensitive instrument and should be handled
and stored carefully.
Exercise:
Objective:
To determine C.O.P. of an Ice-plant.
Theory:
Natural ice was used for preservation purpose for a very long time. But it has been replaced to a
large extent by manufactured ice since the beginning of twentieth century because of the uncertainly of
the natural supply and also because of the cost of transportation to the retail trade.
The manufacturer of ice is one of the principal needs of refrigeration and it will continue, as ice is
the cheapest means for short time preservation of food. A vast amount of research has been put in
developing a least expensive means of manufacture.
The quantity of ice required for different purpose is very large so that the manufacture of ice is one
of the principal applications of refrigeration. Ice factories are commonly installed now a day in every
small town of India to fulfill day-to-day requirements of the people.
The appearance of the ice plays important role for the sale in the retail trade. Therefore,
preliminary chemical treatment and filtration of water, agitation of water during freezing to issue
transparency, core sucking to remove impurities in the water supply and scoring of ice cakes in size
required for retail trade are important features of ice manufacturing.
In present day ice factories, all the operations mentioned above are automatically done to keep the
speed of production and distribution.
The vapour compression refrigeration cycle is based on a circulating fluid media viz. a refrigerant
having special properties of vaporizing at temperatures lower than the ambient and condensing back to
the liquid form, at slightly higher than ambient conditions by controlling the saturation temperature and
pressure.
When the refrigerant evaporates or boils at temperature lowers then ambient it extracts or
removes heat from the load and lowers the temperature consequently providing cooling.
The superheated vapour is increased to a level by the compressor to reach a saturation pressure so
that heat added to vapour is dissipated / rejected into the atmosphere, using operational ambient
conditions with cooling medians such as air or water. The vapour is condensed to liquid form and
recycled gain to form the refrigeration cycle.
Main components of refrigeration cycle: -
1. Compressor
2. Condenser
3. Throttling device
4. Evaporator
Compressor:
The compressor is known as the heart of the refrigeration system. It pumps the refrigerant vapour in
refrigeration cycle as the heart pumps blood in the body. The low temperature, pressure, superheated
vapour from the evaporator is conveyed through suction line and compressed by compressor to a high
pressure, without any change of gaseous state and the same is discharged into condenser. During this
process, heat is added to the refrigerant and is known as heat compression. The compressor should have
a compression ratio to raise the pressure of the refrigerant to such a level that the saturation temperature
of the discharged refrigerant is higher than the temperature of the available cooling medium, to enable
the superheated refrigerant to condenser at normal ambient condition.
Condenser:
The heat is added in the evaporator and compressor to the refrigerant is rejected in condenser at high
temperature. This superheated refrigerant vapors enters the condenser to dissipate its heat in three
stages. First on entering the refrigerant loses its superheat, it then loses its latent heat at which the
refrigerant is liquefied at saturation temperature pressure. This liquid loses its sensible heat, further and
the refrigerant leaves the condenser as a sub-cooled liquid.
The heat transfer from refrigerant to cooling medium takes place in the condenser. The sub-cooled liquid
from condenser is collected in a reservoir and is then fed through the throttling device by liquid line to
the evaporator.
There are several methods of dissipating the rejected heat into the atmosphere by condenser. These are
water-cooled, air cooled and evaporative cooled condensers.
Throttling device:
Throttling device is design to pass maximum possible liquid refrigerant to obtain a good refrigeration
effect. The line should be properly designed to have minimum pressure [Link] throttling device is a
pressure reducing device and a regulator for controlling the refrigerant flow. It also reduces the pressure
from the discharge pressure to the evaporator pressure without any change of state to the liquid
refrigerant.
Various types of throttling devices are:
a) Capillary tubes
b) Thermostatic valves
c) Hand expansion valves
d) Hand valves
Evaporator:
The liquid refrigerant from the condenser at high pressure is fed through a throttling device to an
evaporator at a low pressure. On absorbing the heat to be extracted from media to be cooled, the liquid
refrigerant boils actively in the evaporator and changes state. The refrigerant gains latent heat to
vaporize at saturation temperature /pressure and further absorbs sensible heat from media to be cooled
and gets fully vaporized and superheated.
Technical Specifications:
Compressor : Hermetically sealed along with its std. accessories
Condenser : Fins and tube type air cooled condenser
Condenser fan motor : one no.
Cooling coil : Water immersed type
Agitator with motor : Provided to circulate the brine
Brine tank cabinet : Inner and Outer surface of brine tank fabricated with S.S
Temperature measurement : RTD PT-100 type
Control panel : Digital voltmeter (0-300V) and ammeter (0-10A)
Temperature Indicator : Digital temperature indicator with multi channel switch
Description of Setup:
Primary refrigerant : R-22 refrigerant gas
Secondary refrigerant : Brine solution
Measuring controls : Suction pressure gauge for low pressure measurement
: Discharge pressure gauge for high pressure measurement
: Filter, drier, capillary tube type expansion device
: Main switch, Voltmeter, Amp-meter for compressor I/p
: Switches and indication lights
Temperature indicator : Digital temperature indicator provided with RTD sensors
Chemical Required : Sodium chloride ( Nacl ) – 15 kg
Experimental Procedure:
Starting procedure :
1. Give supply of 220V on the main switch of the rig.
2. Check the voltage.
3. Switch on the condenser fan switch.
4. After 2 minutes, switch on the compressor.
5. Check the compound and pressure gauge and note the readings.
6. Note down the pressure and temperature readings.
7. Put brine solution in the ice tank.
8. Note down the temperature of the brine tank from digital temperature indicator.
9. At the time of starting the apparatus note down the ampere & voltage reading.
10. Note down the reading of gauges, temperatures, ampere meter & voltmeter after running of the rig at
least 20 to 30 min. take 2 to 3 readings.
11. Start the agitator motor for 5 minutes only, after the gap of every 15 minutes.
12. Run the unit continuing at least 2-3 hours and note down the brine solution temperature, if the brine
temperature reaches up to 40C then put water in the ice can for freezing.
13. Now again check the temperature of suction pressure and discharge pressure.
14. Always close the door of ice tank and the door should be open at he time of putting ice cans of lifting
the same.
Closing procedure:
1. While closing the rig, first switch off the compressor.
2. Then close the condenser fan motor.
3. Then close all the other valves.
4. At last switch off the units.
5. After closing the unit, drain the brine solution from the tank in order to avoid the rusting of the
tank.
Observation Table:
Pressure
Sr. Temperatures (oC) V I
(kg/cm2)
no
P1 P2 T1 T2 T3 T4 T5 T6
Calculations:
𝑇ℎ𝑒𝑜𝑟𝑒𝑡𝑖𝑐𝑎𝑙 𝐶𝑂𝑃
Relative COP=
𝐴𝑐𝑡𝑢𝑎𝑙 𝐶𝑂𝑃
Conclusion:
Exercise:
Water-cooled condensers, typically used in large systems above 5 tons, are efficient for heat rejection due to high heat carrying capacity of water and promote better subcooling. Air-cooled condensers are used in smaller systems, like domestic refrigerators, where air with natural or fan-induced convection cools the condenser. While air-cooled systems are less efficient, they avoid water management concerns and are simpler to maintain .
The design of hermetic compressors, where both motor and compressor are encased within a single sealed unit, significantly prevents refrigerant gas leakage. As this integral design eliminates external shaft seals or connections, it creates a closed system, which not only simplifies the design but also enhances the containment of refrigerant, leading to improved system reliability and efficiency .
A thermostatic expansion valve controls the mass flow rate of refrigerant by sensing the evaporator outlet temperature. When the cooling load is high, the degree of superheat of refrigerant coming out of the evaporator increases, prompting the valve to feed more liquid to the evaporator. Conversely, when the load is low, the valve closes more to reduce the liquid quantity supplied, thereby preventing excessive superheat .
Relative humidity significantly impacts air conditioning performance since it determines the moisture content in the air that needs to be managed for comfort and system efficiency. High relative humidity can increase cooling loads and necessitates more dehumidification, thus increasing energy consumption. Conversely, low humidity might dry the air excessively, affecting comfort .
Hermetic type compressors, where the compressor and motor are integral on one shaft and contained in a pressure shield housing, offer several advantages. They are compact, quiet, low in cost, and have no problem with refrigerant gas leakage. Additionally, the motor is cooled by the refrigerant suction gas, enhancing efficiency .
Different expansion devices are suited for specific conditions. For constant pressure systems, automatic valves are suitable, while thermostatic valves fit variable loads due to their responsiveness to superheat changes. Capillary tubes, although low-maintenance and cost-effective, lack adaptability to load variations, thus potentially compromising efficiency unless conditions are stable .
The psychrometric chart visually represents various air properties and assists in calculating parameters like relative humidity, dew point temperature, and enthalpy of air. It helps deduce specific humidity and work done with changes in temperature, thus guiding the accurate adjustment of system controls for efficient moisture and temperature control .
Capillary tubes are simple and inexpensive expansion devices but are best suited for constant operating conditions. They lack the ability to self-adjust to load variations; thus, under lower loads than designed, capillary tubes may overfeed the evaporator, risking liquid return to the compressor. Under higher loads, they may starve the evaporator, causing excessive return gas superheat, making them unsuitable for varying cooling loads .
The evaporator is critical in the refrigeration cycle as it removes heat from the product or area to be cooled. Efficient heat exchange, therefore, depends on several factors like the temperature difference between the load and the refrigerant, the heat transfer coefficient, and the surface area available for heat transfer. Different evaporator constructions (e.g., finned tube, bare tube) are chosen based on these factors to optimize performance .
The drier is crucial for removing any water particles present in the refrigerant. In low temperature regions, especially after the expansion valve, water can freeze and form ice. This ice can block the valve or ducts, hindering refrigerant flow and reducing efficiency. Therefore, the drier ensures the smooth functioning of the refrigeration cycle by preventing ice formation .