The SKP15… electro-hydraulic actuator is designed for use with VG… series gas valves to provide safety shut-off control in industrial and commercial applications. It features a modular design, visual position indication, and operates on 110 to 240 Vac power, with a quick response time for closing. The actuator is UL listed and available in various configurations, including options for proof of closure and auxiliary switches.

Uploaded by

Harsh Dhawan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
54 views5 pages

Siemens SKP15

The SKP15… electro-hydraulic actuator is designed for use with VG… series gas valves to provide safety shut-off control in industrial and commercial applications. It features a modular design, visual position indication, and operates on 110 to 240 Vac power, with a quick response time for closing. The actuator is UL listed and available in various configurations, including options for proof of closure and auxiliary switches.

Uploaded by

Harsh Dhawan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Technical Instructions

Document No. 155-751


SKP15…U..
November 1, 2005

SKP Series
SKP15…U.. Gas Valve Actuator with
Safety Shutoff Function

Only when assembled to Series VG… Gas valves


Description SKP15… electro-hydraulic actuators are used in combination with VG… series gas
valves to provide safety shut-off control for industrial and commercial burner
applications.

The compact SKP15… actuator opens slowly and closes immediately when power is
interrupted. The modular design allows the SKP15… to be used in combination with all
VG… series gas valves bodies from 1/2-inch to 6 inches in size. The actuator is easily
mounted on the square flange of any VG… valve with four pre-mounted screws. A
visible position indicator on the front of the actuator displays the entire stroke of the
valve. A light indicates when the actuator is powered.

Features • UL listed, FM approved, CSA certified for USA and Canada, IRI approvable, and
ISO 9001 certified. European, Australian and Japanese approved versions
available.
• Proof of Closure with Over Travel (POC) versions are available.
• Optional NEMA 4 protection.
• Visual position indication.
• "Power on" indication light
• Quick connect wiring terminals
• Optional adjustable auxiliary switch available.
• Modular design with 360o actuator rotation for easy field wiring and installation.
• Low, 13.5 VA power consumption.

Application SKP15… series actuators are combined with 1/2-inch to 6-inch VG… series gas valve
bodies. VG… series gas valves must be ordered separately (See VG…U... Technical
Instructions, P/N 155-512P25).

Siemens Building Technologies, Inc.


Technical Instructions SKP15...U Electro-hydraulic Actuators
Document Number 155-751
November 1, 2005

Product Numbers Table 1.

Product Number1 Operating Proof of Closure Auxiliary Type of Switch


Voltage Switch 2 Switch 2
SKP15.013U1 – – –
SKP15.012U1 110 to 120 Vac X X SPDT SPDT
SKP15.011U1 X – SPDT
SKP15.013U2 – – –
220 to 240 Vac
SKP15.012U2 X X SPDT SPDT
Note:
1. European, CE certified models are available (see data sheet 7643)
2. Proof of closure and auxiliary switches cannot be field installed.

Accessories
AGA66 Sealing gasket to provide NEMA 3, 3R, and 4 protection (for VGG…/VGD…valves)

Specifications As safety shut-off valve UL/429, FM/7400, ANSI Z21.21/CGA6.5 C/I


Agency marks apply only for [Link] actuators
Agency approvals with [Link] series gas valve bodies.

Power supply Operating voltage 110 to 120 Vac + 10% to -15%


220 to 240 Vac + 10% to -15%
Operating frequency 50 to 60 Hz + 6%
Power consumption 13.5 VA
Duty cycle continuous
Operating environment Ambient operating temperature 5°F to 140°F (–15°C to 60°C)
Mounting position Any position except upside down
Physical characteristics Weight 2.4 lb (1.1 kg)
Enclosure NEMA 1, 2, 5, and 12 for indoor use
NEMA 3, 3R, and 4 with optional AGA66 gasket
Dimensions See Figure 3
Specification for valve bodies See gas valve Technical Instructions,
P/N 155-512P25
Conduit connection Two 1/2-inch NPSM threaded knock-outs
Electrical connection Spring loaded terminals for 14 AWG wires
Operating characteristics Output force 100 lb (450 N)
Maximum stroke 1 inch (26 mm)
Opening time for maximum stroke Varies with valve size, 14 seconds for max. stroke
Closing time <0.8 seconds
Auxiliary features Proof of closure switch Non-adjustable
Setting range of auxiliary switch 40% to 100% of stroke
Switch rating 6A/250 Vac resistive; 3A/120 Vac pilot duty

Page 2 Siemens Building Technologies, Inc.


SKP15…U Electro-hydraulic Actuators Technical Instructions
Document Number 155-751
November 1, 2005

Operation

Figure 1. SKP15… Operation.


The electro-hydraulic actuator consists of a cylinder filled with oil, a piston containing an
electric oscillating pump, and a relief system. When power is supplied to the actuator, the
relief system closes, and the pump moves oil from the reservoir into the pressure
chamber. This action causes the piston to move downward in the cylinder, opening the
gas valve. When power to the actuator is interrupted, the relief system opens and the gas
valve closes in less than 0.8 seconds.
A position indicator, visible through the transparent portion of the terminal cover, shows
the entire stroke range of the actuator. A light, which is visible through the lower left
transparent portion of the terminal cover, indicates when the actuator receives power. An
optional, non-adjustable SPDT proof of closure over travel switch signals the closed
position after the gas valve has closed. An optional SPDT auxiliary switch is adjustable
between 40% and 100% of the stroke. The adjustment screw and scale are located on
the right side in the terminal box, and are visible through the transparent portion of the
terminal cover.
Installation WARNING:
• Personal injury or loss of life may occur if procedures are not followed
as specified.
• All installations must be performed by qualified personnel only.
• Do not pull the actuator shaft.
• The AGA66 gasket must be installed between the actuator and the
gas valve body to provide NEMA 3, 3R, and 4 protection rating for
VGG… and VGD… valves.
• The SKP15… actuator is directly coupled to the VG… series valve body by four pre-
mounted 4 mm Allen key screws.
• The square mounting flange can be rotated in steps of 90o to provide four different
mounting positions. The SKP15… actuator can be mounted in any position except
upside down.
• The actuator can be mounted or replaced while the valve body is under pressure.
• The SKP15… actuator has two knock-outs for the installation of 1/2”-14 NPSM
conduit connections.
• When conduit routing is connected, flexible conduit must be used.
• Liquid tight conduit must be used in combination with AGA66 to provide NEMA 3, 3R,
and 4 protection.
• The terminal marked GND, located above the wiring terminals, must be connected to
the electrical ground.

Siemens Building Technologies, Inc. Page 3


Technical Instructions SKP15…U Electro-hydraulic Actuators
Document Number 155-751
November 1, 2005

Installation, NOTE: Wiring must meet all relevant electrical codes.


Continued
Wiring and Switch • The actuator is equipped with spring-loaded terminals for 14 AWG wires.
Adjustment • The actuator has two line and two neutral terminals.
(See Terminal • Insert one wire into the opening of the terminal while pressing the lever downward
Designations) with a screwdriver or hard object. Make sure that all strands insert into the opening.
• Adjust the auxiliary switch (if provided) according to the wiring diagram on the label
below the terminals (see Figure 2). The adjustment screw and scale are located on
the right side of the terminal box, and are visible through the transparent portion of
the terminal cover.
NOTES: 1. The auxiliary switch is adjustable between 40% and 100% of the stroke. The
factory setting is at 40%.
2. The auxiliary switch must not be used for proof of closure detection or other
safety interlock functions.
3. The Proof of Closure Switch is non-adjustable.

Service There are no serviceable parts on the SKP15… series actuators. If inoperative, replace
the entire actuator. Tag wires before servicing.

Terminal
Designations
GAS0049R1

SKP15.012U… SKP15.011U… SKP15.013U…


Figure 2. Terminal Designations.

Siemens Building Technologies, Inc. Page 4


SKP15…U Electro-hydraulic Actuators Technical Instructions
Document Number 155-751
November 1, 2005

Dimensions
(Dimensions in
inches;
millimeters in
parentheses)

7.40
(188)
1/2"-14
NPSM
3.15
(80)

3.82
(97)
GAS0051R1

2.16
(55)
3.20 3.39 SQUARE
(81) (86)

Figure 3. SKP15…U.. Dimensions.

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners.
© 2005 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc. Your feedback is important to us. If you have Document No. 155-751
1000 Deerfield Parkway comments about this document, please send Country of Origin: US
Buffalo Grove, IL 60089-4513 them to SBT_technical.editor@[Link] Page 5
U.S.A.

You might also like