Siemens PXC4.M16-2 Automation Station

The PXC4.M16-2 is a compact automation station designed for HVAC and building control systems, featuring 16 programmable inputs/outputs, BACnet MS/TP communication, and integration capabilities for Modbus and M-bus devices. It supports various functions such as alarming, scheduling, and IT security, and can be mounted on standard rails or walls. The device is suitable for a range of applications with customizable options for expansion through I/O modules and KNX PL-Link devices.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
234 views18 pages

Siemens PXC4.M16-2 Automation Station

The PXC4.M16-2 is a compact automation station designed for HVAC and building control systems, featuring 16 programmable inputs/outputs, BACnet MS/TP communication, and integration capabilities for Modbus and M-bus devices. It supports various functions such as alarming, scheduling, and IT security, and can be mounted on standard rails or walls. The device is suitable for a range of applications with customizable options for expansion through I/O modules and KNX PL-Link devices.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Desigo™

Automation stations
PXC4.M16-2

For the control of primary plants


● Compact automation station for HVAC and building control systems,
freely programmable using graphical programming interface
● Communication BACnet MS/TP (BTL certified)
● Integration of Modbus data points via RTU
● 16 inputs/outputs: 12 universal inputs/outputs, 4 relay outputs
Extendable via I/O modules TXM…
● KNX PL-Link bus to connect RDG2..KN room thermostats, sensors, and operator
units (including bus power)
● Integration of M-bus energy meters via RS485 level-converter
● WLAN interface for engineering and commissioning
● Operating voltage AC or DC 24 V
● Mounted on standard rails or on the wall
● Plug-in screw terminal blocks

A6V14651900_en--_b Smart Infrastructure


2025-01-27
Functions
Optimized, flexible automation station for HVAC and building automation and control
systems
● System functions (alarming, scheduling, trending, access protection with individually
definable user profiles and categories)
● Integrates data points and/or subsystems via Modbus RTU
● Integration of wired M-bus meters via RS485 level-converter:
– Offline and/or online engineering with ABT Site. No additional M-bus tool required
– Primary and/or secondary device addressing
● The following functions are available with KNX PL-Link bus:
– Communication with RDG2..KN room thermostats, sensors, and operator units
– Plug-and-play connection of Siemens field devices with KNX PL-Link
● Engineering and commissioning with the ABT Site Tool using graphical function charts
● Freely programmable. All function blocks, available in libraries, can be graphically
connected.
● BTL tested BACnet communication on MS/TP, in compliance with the BACnet standard
including B-BC profile (Rev. 1.20*)
● IT security including HTTPS, IEC-62443 4-2 (Security Level 2**), and BACnet Secure
Connect
● Generic operation via embedded web interface
● WLAN interface for engineering and commissioning
● Operating voltage AC 24 V or DC 24 V
● Direct connection of field devices
● DIN rail or screw mounting
● Plug-in screw terminal blocks

* BTL certification will be updated to Rev. 1.20 once the certification process is completed.
** For details about network and physical setup, refer to the Desigo Products Cybersecurity
Guidelines (A6V14142297).

Type summary

PXC4.M16-2 variants 1) PXC4.M16S-2 PXC4.M16-2


Order number S55375-C153 S55375-C151
Number of inputs and outputs (Onboard) 16 16
Number of universal inputs and outputs (UIO) 12 12
Number of relay outputs (DO) 4 4
Number of inputs and outputs (Onboard + TXM) up to 40 up to 40
Number of integration data points 0 up to 40
(Modbus RTU)
Total number TXM-I/Os and integration DPs 40 2) 80 2)
Number of KNX PL-Link devices 0 up to 64 2)
Number of configurable RS485 interfaces for Modbus RTU 0 1
integration
Number of M-bus meters wired via level converters (RS485) 3) 0 up to 250

1)
For details on engineering, see PXC4, PXC5 & PXC7 Planning overview (A6V13054435).
2)
KNX PL-Link data points do not count as integration points. For KNX PL-Link, only the limits on BACnet objects
are considered.
3)
The limitation is given by the maximum number of integration data points and maximum number of BACnet
objects.

2
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Onboard inputs and outputs

UIO Universal inputs and outputs support the following signal types:
● Passive sensors LG-Ni 1000, 2x LG-Ni1000, Pt 1000 (375, 385), NTC 10k (Type II / Beta (0-50 °C) =
3892 K), NTC 100k
● Resistance sensors 1000 Ohm, 2500 Ohm, 1000...1175 Ohm (for setpoint shift)
● Voltage input analog DC 0…10 V
● Current measurement analog DC 0...20 mA or 4...20 mA, (inputs U1, U2, U7, U8)
● Binary potential-free contacts for signaling functions
● Counter to 25 Hz (electronic switch to 100 Hz)
● Analog outputs DC 0…10 V
DO Relay outputs for binary controls, changeover contact
(NO, NC, pulse)

Equipment combinations

TXM I/O modules

Description Type 1) Data sheet


Digital input module 8 or 16 I/O points TXM1.8D, TXM1.16D CM2N8172
Universal module without / with local operation and LCD TXM1.8U, TXM1.8U-ML CM2N8173
Super universal module without / with local operation and LCD TXM1.8X, TXM1.8X-ML CM2N8174
Relay module without / with local operation TXM1.6R, TXM1.6R-M CM2N8175
Resistance measuring module (for Pt100 4-wire) TXM1.8P CM2N8176
Triac module TXM1.8T CM2N8179
Digital input and relay module TXM1.4D3R CM2N8188
Power module TXS1.12F10 CM2N8183
Bus connection module TXS1.EF10 CM2N8183
Island bus extension module [Link] CM2N8184

1)
Module series B and higher. In following use cases only series D can be used (available as of 2012):
● I/O bus communication mode "Event"

PXC4-2 can power TXM extensions modules. For further details see PXC4, PXC5 & PXC7 Planning overview
(A6V13054435) and data sheets.

3
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
KNX PL-Link devices

Description Type Data sheet


Wall-mounted temperature sensor QMX3.P30 CM2N1602
Wall-mounted temperature and humidity sensor QMX3.P40
Wall-mounted temperature, humidity, and CO2 sensor QMX3.P70
Wall-mounted temperature sensor and room operator unit QMX3.P34
Wall-mounted temperature and humidity sensor and room operator QMX3.P44
unit
Wall-mounted temperature, humidity, and CO2 sensor and room QMX3.P74
operator unit
Wall-mounted temperature sensor and room operator unit QMX2.P33 A6V10733768
Wall-mounted temperature and humidity sensor and room operator QMX2.P43
unit
Flush-mounted room sensors base and front modules: CE1N1411
● Base module for temperature and / or humidity measurement 1) ● AQR2570
● Base module for CO2 measurement 1) ● AQR2576
● Front module for base module without sensor ● AQR2530NNW
● Front module for base module with temperature sensor ● AQR2532NNW
● Front module for base module with humidity and temperature ● AQR2535NNW
sensor ● AQR2535NNWQ
● Front module for base module with humidity, temperature
sensor, and CO2 indicator LED
Passive infrared presence detector UP 258D12 A6V10489489
Presence detector WIDE with temperature sensor UP 258D31 A6V11894530
Presence detector WIDE with temperature and humidity sensor UP 258D41
Presence detector WIDE with temperature, humidity, and CO2 UP 258D51
sensor
Presence detector WIDE with temperature sensor and ultrasound UP 258D61
Room thermostat with temperature and humidity sensor RDG200KN A6V11545853
RDG260KN
Room thermostat with temperature, humidity, and CO2 sensor RDG204KN
RDG264KN

1)
Physical data points on the base module AQR257.. for use in HVAC functions:
- 2 x Binary potential-free contacts (NO, NC)
- 1 x Passive sensor NTC10K (Type II / Beta (0-50 °C) = 3892 K)
For details see PXC4, PXC5 & PXC7 Planning overview (A6V13054435) and data sheets.

System controller

Description Type Data sheet


System controller to integrate Modbus and MS/TP devices PXC5.E003 A6V11646020
PXC7 A6V12505052

4
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Technical and mechanical design
The compact build allows for mounting the devices on a standard rail or a wall.
4 5 6
4 PXC4.M16-2: Plug-in terminal block with screw
terminals
KNX PL-Link
5 Plug-in terminal block with screw terminals
Power supply
6 Plug-in terminal blocks with screw terminals
3 1 Universal inputs/outputs, field device supply
7
2 7 Connector for I/O modules TXM
Date/Series
S/N 8 Plug-in terminal block with screw terminals
WLAN
Relay outputs
Default

9 PXC4.M16-2: Plug-in terminal block with screw


terminals
11 10 9 8 COM, Modbus RTU
15 16 12 13 14
PXC4.M16S-2: Plug-in terminal block with screw
terminals
MS/TP
10 PXC4.M16-2: Plug-in terminal block with screw
terminals MS/TP
11 DIP switch for bus termination and polarization
COM, MS/TP
12 Slider for mounting on DIN rails
13 Eyelets for cable ties
1 Plastic housing 14 Holes for wall mounting
2 Service button (identification in network and 15 Date / Series and Serial number
WLAN on/off)
3 LEDs for communication and state 16 QR code for default WLAN access (description
see Technical data)

5
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
LED displays

Activity LED Color Activity Function


RUN Green Continuously ON Device operational
Continuously OFF Device not operational
Flashing Start-up or program halted
Red Continuously OFF OK
Continuously ON HW or SW fault
Rapid flashing Firmware or application missing/corrupted
MSTP Yellow Flashing Communication BACnet MS/TP
Continuously OFF No communication
COM TX Yellow Flashing Communication
(PXC4.M16-2) Continuously OFF No communication to subsystem

COM RX Yellow
(PXC4.M16-2)
SVC Red Continuously OFF OK
Flashing Device is not configured
Flashing per wink Identification of device after receipt of wink
command command

5 Hz 5 Hz

2s 1s 2s 1s

WLAN Blue Steady OFF WLAN inactive


Steady ON WLAN active and at least one WLAN client
connected
Flashing WLAN active and no WLAN client connected
Service button Press 0.2 ... 1 s Identification in the network
Press 1 ... 3 s Enable/ disable WLAN
WLAN is disabled automatically after 10 min, if
no client is connected
As per description Do the following to reset the device to factory
state:
1. Power off the device.
2. Power on the device.
3. Wait until all LEDs light up and turn off
again, then press the Service button.
4. Keep the Service button pressed until all
LEDs light up, then release the button.
All LEDs go off, the device restarts.
5. Wait until the device has fully started –
unconfigured (green RUN LED and red
SVC LED are flashing)

Product documentation
Related documents such as the environmental declarations, declarations of conformity, etc.,
can be downloaded from the following Internet address:
[Link]/bt/download

6
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Notes
Safety

CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
● Observe national provisions and comply with the appropriate safety regulations.

Mounting position and ambient temperature


The devices can be snapped onto standard rails or screwed onto a flat surface.
Plug-in screw terminals connect power and interfaces.

Ambient temperature -5...50 °C (23...122 °F) Ambient temperature -5...45 °C (23...113 °F)
● Wall, horizontal ● Overhead
– From left to right ● Wall, vertically

– From right to left – From top to bottom


– From bottom to top
● On a horizontal surface

Installation

WARNING
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
● Adapt the line diameters as per local regulations to the rated value of the installed fuse.

WARNING
The relay outputs may be connected to mains voltage
Risk of electric shock! Incorrect installation of the device may lead to electric shock injuries
when touching the device!
● Install the device in a lockable cabinet or use terminal covers.
● Do not install the device in locations where children are likely to be present.
● Conductors with a cross-section of 0.5 mm2 (AWG24) or greater shall comply with the
requirements of IEC 60332-1-2 and IEC 60332-1-3 or IEC TS 60695-11-21.

Disposal

This symbol or any other national label indicate that the product, its
packaging, and, where applicable, any batteries may not be disposed of as
domestic waste. Delete all personal data and dispose of the item(s) at
separate collection and recycling facilities in accordance with local and
national legislation.
For additional details, refer to Siemens information on disposal.

7
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Warranty
The application-specific technical data is guaranteed only in combination with the Siemens
products listed in the 'Device combinations' section. If third-party products are used, any
guarantee provided by Siemens will be invalidated.

Technical data
Power supply

Operating voltage (24 V~, ⏊, ) AC 24 V -15 / +20 % (PELV)


AC 24 V Class 2 (US)
48…63 Hz
Operating voltage DC 24 V (24 V≃, ⏊, ) DC 24 V -15 / +20 % (PELV)
DC 24 V Class 2 (US)
Functional ground (US) The terminal for the functional ground must be
Functional earth connected on the installation side with the building
grounding system (PE).
Screw terminals for wire cross sections up to Max. 2.5 mm2 (14 AWG)
Internal fusing 4 A irreversible / non-replaceable
External supply line fusing (EU) Non-renewable fuse max. 10 A slow-blow
or
circuit breaker max. 13 A
Tripping characteristic B, C, D per EN 60898
or
Power supply with current limitation of max. 10 A
Protection Reverse connection protection for DC 24 V

Power consumption (for transformer planning)

Operating voltage PXC4.M16S-2 PXC4.M16-2


AC 24 V DC 24 V AC 24 V DC 24 V
Full load 76 VA / 3.2 A 65 W / 2.7 A 80 VA / 3.3 A 67 W / 2.8 A
Base load 8 VA / 0.33 A 5 W / 0.2 A 8 VA / 0.33 A 5 W / 0.2 A
PXC4.M16S-2: without loading by I/O
modules TXM and field devices
PXC4.M16-2: without loading by I/O
modules TXM, KNX PL-Link, and field
devices
Field device supply V+ (DC 24 V, 100 mA) 5 VA / 0.2 A 3 W / 0.13 A 5 VA / 0.2 A 3 W / 0.13 A
(terminals 8 and 19)
Field device supply V≃ 48 VA / 2 A 48 W / 2 A 48 VA / 2 A 48 W / 2 A
(terminals 18 and 29)
I/O modules TXM supply 15 VA / 0.6 A 8.5 W / 0.35 A 15 VA / 0.6 A 8.5 W / 0.35 A
KNX PL-Link supply 4 VA / 0.17 A 2.2 W / 0.09 A

Function data

Hardware information PXC4.M16-2, PXC4.M16S-2


Processor Texas Instruments AM335x, 600 MHz
Storage 512 MByte RAM
512 MByte Flash

Data backup in the event of power failure


Energy reserve (supercap) to support real-time clock (7 days).
Data available if stored to flash memory. Occurs every 5 minutes.
The interval of 5 minutes is only valid for change log but not for trending.
In case of a power failure, trend log data can be lost up to 30 minutes.

8
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Interfaces

BACnet MS/TP interface


Interface type EIA-485, electrically isolated
Baud rate 9600, 19200, 38400, 76800, 115200 (depending on the
configuration)
Internal bus termination 120 Ohm, switchable with DIP switch
Internal bus polarization 270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only) 3-wire cable, shielded
Distance between 2 devices Max. 500 m (1650 ft)
Length of the MS/TP line Max. 1000 m (3300 ft)
Protection Short-circuit proof
Protection against faulty wiring with AC 24 V and
DC 24 V

WLAN interface
Interface type Wireless access point
Supported standards IEEE 802.11b/g/n
Frequency band 2.4…2.462 GHz
WLAN channels 1…11
Maximum radio-frequency power 16.4 dBm
Distance (unobstructed field) Min. 5 m (16 ft)
Device pairing Activation / deactivation with service button
Automatic switch off after 10 minutes if no WLAN-client
is connected.
Optionally, for cyber security reasons, the WLAN can be
permanently disabled via configuration.
Default SSID and WLAN password: Scan the QR code.
It will display something like WIFI:S:PXC4.M16-2_0000550;T:WPA;P:1400052738;;
Then SSID = PXC4.M16-2_0000550 and password = 1400052738
Determine manually: Use the information from the Date/Series/SN block It will display something like:
Date/Series: 20190423A0000550
S/N: 1400052738
SSID = <ASN>_<Running number after the series letter> and password = <S/N>

9
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
M-bus interface on COM interface (RS485)
Interface type EIA-485, electrically isolated
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400.
The maximum baud rate is depending on the
configuration of M-bus S-devices (subordinate devices)
and M-bus repeater.
Internal bus termination 120 Ohm, switchable with DIP switch
Internal bus polarization 270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only) 3-wire cable, shielded cable recommended (shield must
Cable length be connected to building earth in the mounting panel)
Max. 1000 m (3300 ft)
Protection Short-circuit proof
Protection against faulty wiring with AC 24 V and
DC 24 V
M-bus level converter including power supply (required) Configuration examples (simple M-bus loads à 1.5 mA):
● Up to 2 M-bus devices: STV Electronic, MPW-2 1
● Up to 6 M-bus devices: STV Electronic, MPW-6 1
● Up to 60 M-bus devices: Relay GmbH, PW60 1

1
For STV Electronic level converters, refer to [Link] For Relay GmbH level converters,
refer to [Link]
The use of these products is a recommendation only. Siemens cannot guarantee functionality nor take over any
warranty for third-party products. This information is subject to change without notice.

KNX PL-Link interface


Type KNX TP1 PL-Link, galvanic isolation
Baud rate: 9.6 kbps
Cabling (in-house cabling only) 2-wire cable, 0.75 mm2 / AWG20
or 1 mm2 / AWG18
Cable length With internal supply: Max. 80 m (262 ft)
With external supply: Max. 1000 m (3300 ft)
Internal bus power Max. 50 mA
When using external bus power for KNX PL-Link, switch
off the internal bus power via the ABT Site Tool.

I/O modules TXM bus interface


Nominal voltage DC 24 V
Supply current for I/O modules TXM Max. 300 mA
Connectable in parallel with DC 24 V power supply For details, see: TX-I/O- engineering and installation,
module TXS1.12F4 CM110562
Protection Short-circuit proof
TXM I/O module plug: No protection against faulty No electric protection.
wiring with AC 24 V Use cover

10
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Field device supply (I/O module TXM)
AC 24 V output current (terminal V~ on the TXM Max. 2 A, short-circuit proof 1)
module) If PXC4.M16-2 is powered by DC voltage, the field
device supply on terminal V~ of the TXM modules is
also DC voltage.

1)
Sum of onboard V~ and TXM module V~ current is max. 2 A.

Field device supply (Onboard)


AC 24 V output current (terminal V≃) Max. 2 A, short-circuit proof 1)
If PXC4.M16-2 is powered by DC voltage, the field
device supply on terminal V≃ is also DC voltage.
DC 24 V output current (terminal V+) Max. 100 mA, short-circuit proof, protected against
incorrect wiring with AC 24 V

1)
Sum of onboard V~ and TXM module V~ current is max. 2 A.

Screw terminals, plug-in


Cu-wire or Cu-strand with wire end sleeve 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.0 mm2 (22 to 18 AWG)
Cu-strand without wire end sleeve 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.5 mm2 (22 to 16 AWG)
Stripping length 6...7.5 mm (0.24...0.29 in)
Screwdriver Slot screws, screwdriver size 1 with shaft ø = 3 mm
Max. tightening torque 0.6 Nm (0.44 lb ft)

On PXC4.M16-2

Modbus RTU interface


Interface type EIA-485, electrically isolated
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600, 76800, 115200 (depending on the configuration)
Internal bus termination 120 Ohm, switchable with DIP switch
Internal bus polarization 270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only) 3-wire cable, shielded cable recommended (shield must
Cable length be connected to building earth in the mounting panel)
Max. 1000 m (3300 ft)
Protection Short-circuit proof
Protection against faulty wiring with AC 24 V and
DC 24 V

11
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Inputs
12 universal inputs / outputs U1...U12 with the following input functions (16-bit AD
converter):

Temperature measurement, analog


Type Range (over range) Resolution
AI NTC10K (Type II / Beta (0-50 °C) = 3892 K) -40...115 °C (-52.5...155 °C) 10 mK (25 °C)
-48...239 °F (-62.5...311 °F) 0.018 °F
AI NTC100K -40...125 °C (-52.5...155 °C)
-48...257 °F (-62.5...311 °F)
AI PT1K 385 (EU) 1) -50...600 °C (-52.5...610 °C) 20 mK
-58...1112 °F (-62.5...1130 °F) 0.036 °F
AI PT1K 375 (NA) 1) -50...180 °C (-52.5...185 °C) 10 mK
1) -58...356 °F (-62.5...365 °F) 0.018 °F
AI (LG-)Ni1000
AI 2x (LG-)Ni1000 1)

1)
A fixed value of 1 Ω is calibrated to correct line resistance.

Resistance sensor, analog


Type Range (over range) Resolution
1)
AI 1000 Ohm 0...1000 Ω (0...1050 Ω) 0.1 Ω
AI 2500 Ohm 1) 0...2500 Ω (0...2650 Ω) 0.1 Ω
1)
AI Pt1000 0...2500 Ω (0...2650 Ω) 0.1 Ω
1)
AI 1000-1175 Ohm for setpoint shift 1000...1175 Ω (900...1295 Ω) 0.1 Ω

1)
A fixed value of 1 Ω is calibrated to correct line resistance.

Voltage measurement, analog


Type Range (over range) Resolution
AI 0-10 V 0...10 V (-1.5...11.5 V) 1 mV
AI 0-10 V standard 0...100% (-10...110%) 0.01%
Open connection: Negative voltage -1.5 V (line failure detection)

Current measurement, analog (only inputs U1, U2, U7, U8)


Type Range (over range) Resolution Load
AI 4-20 mA 4...20 mA (1.6...22.4 mA) 1 µA 440 / 490 Ω
AI 0-20 mA 0...20 mA (-3...23 mA) 1 µA 440 / 490 Ω

Digital input
Contact query voltage 21.5...25 V
Contact query current 1 mA; 6 mA initial current
Contact resistance for closed contacts Max. 200 Ω
Contact resistance for open contacts Min. 50 kΩ
Counter memory (counter inputs 0 ... 4.3 x 109 (32-bit counter)
Min. closing/operating time [ms] Of which Max. counter frequency
including bounces Max. bounce time [ms] (symmetrical)
BI NO / BI NC 60 20
BI Pulse NO 30 10
CI Mech (25 Hz) 20 10 25 Hz
CI El (100 Hz) 5 0 100 Hz

12
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Outputs
12 universal inputs / outputs U1...U12 with the following output functions (10-bit DA
converter):

Voltage output, analog


Type Range (over range) Resolution Output current
AO 0-10 V 0...10 V (-0.05…10.6 V) 1 mV Max. 1 mA
AO 0-10 V 0...100% 0.01 % Max. 1 mA
standard 0% = 0 V, 100% = 10 V
(-0.05...10.6 V)

Relay output (outputs DO1...DO4)


External supply line fusing
Non-renewable fuse Max. 10 A, slow
Circuit breakers Max. 13 A, characteristic B, C, D as per EN 60898
Switching voltage AC/DC Max. AC 250 V / DC 30 V
Min. AC/DC 12 V
Current load AC NO contact: Max. 4 A resistive, 3 A inductive (cos phi
0.6)
NC contact: max. 2 A resistive, 1.5 A inductive (cos phi
0.6)
Min. 1 mA at AC 250 V
Min. 10 mA at AC 12 V
Current on make AC NO contact: Max. 10 A (1 s)
NC contact: Max. 3 A (1 s)
Current load DC NO contact: Max. 3 A resistive at DC 30 V
NC contact: Max. 1 A resistive at DC 30 V
Min. 10 mA resistive at DC 12 V
Response / release time 7 ms / 3 ms typical
Contact life at AC 250 V (reference values)
At 0.3 A resistive 5 x 105 switching cycles
NO contact at 3 A resistive 1 x 105 switching cycles
NC contact at 2 A resistive 1 x 105 switching cycles
Reduction factor for inductive load (cos phi = 0.6) 0.6
Insulating strength between relay contacts and system AC 3750 V, as per EN 60730-1
electronics (reinforced insulation).

CAUTION
No overvoltage protection is used when switching inductive loads
Risk of heavy electromagnetic disturbances and lower contact life when no overvoltage
protection is used when switching inductive loads.
● When switching inductive loads (e.g. contactors or electric motors) it is strongly
recommended to use suitable overvoltage protection devices to avoid heavy
electromagnetic disturbances and to ensure the specified contact life.

13
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Conformity

Ambient conditions and protection classification


Classification as per EN 60730
Automatic action Type 1
Control function Class A
Pollution degree 2
Overvoltage category III
Protection against electric shock Suitable for use in protection class I or II systems
Protection degree of housing to EN 60529
Front parts in DIN cut-out IP30
Terminal part IP20
Climatic ambient conditions
● Storage / Transport (packaged for transport) as per ● Class 1K22 / 2K12
IEC EN 60721-3-1 / IEC EN 60721‑3‑2 Temperature -25...70 °C (-13...158 °F)
Air humidity 5...95 % (non-condensing)
● Operation as per IEC/EN 60721-3-3 ● Class 3K23
Operation in enclosed dry locations, having no
temperature or humidity control
Temperature -5...50 °C (23...122 °F)
(for details see chapter Mounting)
Air humidity 5...95 % (non-condensing)
Mechanical ambient conditions
● Transport per IEC/EN 60721-3-2 ● Class 2M4
● Operation as per IEC/EN 60721-3-3 ● Class 3M11

Standards, directives, and approvals


Product standard IEC/EN 60730-1
Product family standards IEC/EN 63044-x
Electromagnetic compatibility (EMC) For residential, commercial, and industrial environments
EU conformity (CE) See CE declaration 1)
EAC conformity Eurasian compliance
RCM conformity See RCM declaration 1)
UL/cUL certification (US / Canada) UL916, [Link]
UL94, housing material meets classification V-0 2)
CSA certification C22.2, [Link]
listing
FCC CFR 47 Part 15C
BACnet Profile: B-BC
Revision: 1.20 3)
Detailed information on BACnet certificates, BTL
listings, and PICS can be found on the BACnet website
(filtered for Siemens products)
Environmental compatibility 1) The product environmental declaration 1) contains data
on environmentally compatible product design and
assessments (RoHS compliance, materials
composition, packaging, environmental benefit,
disposal).
OSHPD seismic certification Product meets OSHPD Special Seismic Certification
Preapproval under California Building Code 2022 (CBC
2022)4)

1)
Documents can be downloaded at [Link]/bt/download.
2)
Material level
3)
BTL certification will be updated to Rev. 1.20 once the certification process is completed.
4)
When installed within the following Siemens enclosures: PXA-ENC18, PXA-ENC19, or PXA-ENC34.

European Union conformity


Contact for regulatory topics: (EU) Siemens AG, Berliner Ring 23, DE-76437 Rastatt

14
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
FCC Statement
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
● Reorient or relocate the receiving antenna.
● Increase the separation between the equipment and receiver.
● Connect the equipment into an outlet on a circuit different from that to which the receiver
is connected.
● Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions:
1. This device may not cause harmful interference, and
2. this device must accept any interference received, including interference that may cause
undesired operation
FCC Caution: Changes or modifications not expressly approved by Siemens Switzerland
Ltd. could void user authority to operate the equipment. United States representative
[Link]

Industry Canada statement


This device complies with ISED’s license-exempt RSSs. Operation is subject to the following
two conditions:
1. This device may not cause interference, and
2. This device must accept any interference received, including interference that may cause
undesired operation.

Radiofrequency radiation exposure statement


This equipment complies with FCC and IC radiation exposure limits set forth for an
uncontrolled environment. This equipment should be installed and operated with a minimum
distance of 20 cm between the radiator and your body.
This transmitter must not be co-located or operated in conjunction with any other antenna or
transmitter.
Housing

Color top / bottom 2003 Ti-Grey / 804 Black


Dimensions per DIN 43880, see dimensions
Weight without / with packaging 484 g / 554 g

15
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Connection terminals

8 9

3 4 5 6 7

AC/DC 24V

65 66 67 68 69 70

Terminal Symbol Description Module Channel


3, 4 KNX PXC4.M16-2: KNX PL-Link
5, 6 ≃, ⏊ Operating voltage AC 24 V or DC 24 V
7 Functional ground (must be connected on the installation
side with the building grounding system (PE)).
9 to 17 Ux Universal inputs / outputs 1…12 61 1…12
20 to 28
⏊ Measuring ground for Ux
8, 19 V+ DC 24 V power for field devices 2.4 W / 100 mA
18, 29 V≃ AC 24 V power for field devices 48 VA / 2 A
(If PXC4.M16-2 is powered by DC voltage, then the field
device supply on terminal V≃ is DC voltage, too)
65, 66, 67 MSTP PXC4.M16-2: Interface EIA-485 (BACnet MS/TP)
68, 69, 70 COM PXC4.M16-2: Interface EIA-485 (M-bus, Modbus RTU)
MSTP PXC4.M16S-2: Interface EIA-485 (BACnet MS/TP)
Term on, off Switch for bus termination
Polar on, off Switch for polarization
75 to 86 DOx Relay outputs 1…4 11 1…4

Wiring lines for field devices


Wiring length max. 300 m (1,000 ft), CU wire or CU strand.
Cross-section depending on the signal
30 m (100 ft) applies for signal types AI NTC10K and AI NTC100K
or 300 m (984 ft) with shielding

16
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Examples of connection diagrams for universal inputs/outputs
Digital inputs
S1 Feedback contact (NO)

Ux

S2 Feedback contact (NC)

Ux
Count inputs: Counter inputs, that count faster than 1 Hz and are laid with more than 10 meters using analog inputs in
the same cable duct, must be shielded.

Analog inputs
M B1 Temperature sensor LG-Ni 1000

Ux B

B2 Temperature sensor, general

Ux

B3 Resistance transmitter

Ux

B4 Active sensor with 0…10 V output powered by the


V+ V + automation station

Ux

B5 Active sensor with 0…10 V output with external


power
Ux V+ Do NOT ground external power (ground loops)

V+ + B6 Active sensors 0 ... 20 mA or 4 ... 20 mA (2-wire)


On U1, U2, U7, U8 only
Ux

Analog outputs
Y1 Device with input DC 0...10 V

Ux

Y2 General device with control input DC 0...10 V


V+ V+ powered by the automation station

Ux

Y3 General device with control input DC 0...10 V


Do NOT ground external power (ground loops)
Ux V+

17
Siemens Schweiz AG A6V14651900_en--_b
Smart Infrastructure 2025-01-27
Dimensions
All dimensions in mm and inches.

PXC4.M16-2
198 (7.80") 3 (0.12") 70.5 (2.78")

183 (7.20") 7 (0.28") 49 (1.91")

117 (41.61")

124 (4.88")

110 (4.33")
45 (1.77")

67 (2.64")
4.1 (0.16") 26.5 (1.04")

PXC4.M16-2 with TXM module


198 (7.80") 64 (2.52") 7 (0.28")

90 (3.54")

269 (10.59")

Issued by © Siemens 2023


Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
[Link]/buildingtechnologies

Document ID A6V14651900_en--_b
Edition 2025-01-27