SYMBOLS GENERAL NOTES AND SPECIFICATIONS
SINGLE LINE DIAGRAM DUPLEX RECEPTACLE OUTLET
ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE
WITH THE NATIONAL BUILDING CODE, PROVISIONS OF THE LATEST
TO SOLECO SPECIAL PURPOSE OUTLET APPROVED PHILIPPINE ELECTRICAL CODE, THE LAWS AND ORDINACES
220V, UTILITY POWER SUPPLY OF THE LOCAL CODE ENFORCING AUTHORITIES AND REQUIREMENTS OF
HANGING LIGHTINGS THE LOCAL ELECTRIC COMPANY AND BUILDING ADMINISTRATION
2- [Link] THHN Wire REQUIREMENTS
LED PIN LIGHTS
+ 1- [Link] THHN Wire 1. ALL ELECTRICAL WORKS HEREIN INCLUDED SHALL BE EXECUTED IN
TRANSFORMER BANKING ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE
c b M PHILIPPINE ELECTRICAL CODE, THE RULES AND REGULATION OF THE
CIRCUIT HOMERUN
LOCALITY AND THE REQUIREMENTS OF THE POWER COMPANY.
2- [Link] THHN Wire CURRENT TRANSFORMER
+ 1- [Link] THHN Wire 2. POWER SERVICE SHALL BE SINGLE PHASE 230V, 60HZ
CIRCUIT CONNECTION
3. ALL CONDUITS SHALL BE PROTECTED AGAINST DAMAGES BY THE
VOLTAGE TRANSFORMER
ENTRANCE OF WATER AND FOREIGN MATTER DURING CONSTRUCTION.
Sc Sb CIRCUIT HOMERUN ALL ENDS OF CONDUITS SHALL BE PROPERLY PLUGGED TO EXECUTE
MOISTURE AND DUST IMMEDIATELY AFTER THE CONDUITS ARE PLACED.
20AT CIRCUIT BREAKER
MAIN 4. WHENEVER NECESSARY PULLBOX OF PROPER SIZE AND DIMENSION SHALL
C1 M kW-HR METER READER BE PROVIDED ALTHOUGH NOT INDICATED IN THE PLAN, ALL JUNCTION BOXES
c1 SHALL BE PROVIDED WITH METAL PLATE COVER.
CIRCUIT RUN "CONTINUATION TO" 5. PANELBOARD SHALL BE PROVIDED WITH SOLID GROUNDING BUS WITH
C2
CIRCUIT RUN "CONTINUATION FROM" TERMINALS.
6. MOUNTING HEIGHTS OF DEVICES SHALL BE:
a MCB MAIN CIRCUIT BREAKER AS FOLLOWS
PANEL BOARD...................... 1.82m ABOVE FINISHED FLOOR TO TOP OF PANEL
c2 SCB(1-3) SUB DISTRIBUTION CIRCUIT BREAKET
WALL SWITCHES.................. 1.40m ABOVE FINISHED FLOOR TO CENTER DEVICE
DISTRIBUTION BOARD CONVENIENT OUTLET........ 0.30m ABOVE FINISHED FLOOR TO CENTER DEVICE
Sa GROUNDING BAR WITH LUG
0.15m ABOVE WORKING COUNTER TO CENTER OF DEVICE
7. THERE SHALL BE ADEQUATE AND EFFECTIVE EQUIPMENT GROUNDING, GROUND
RESISTANCE SHOULD BE NO MORE THAN 5 OHMS. IF GROUND RESISTANCE EXCEEDS
5 OHMS, ADDITIONAL GROUND ROD SHALL BE PROVIDED.