AQ-101 Arc Flash Protection Device

The AQ-101 arc flash protection device is a microprocessor-based unit designed to detect arc light and minimize damage from arcing faults by tripping circuit breakers. It features a wide power supply range, supports multiple sensors, and includes self-supervision for reliability. The device can operate independently or as part of a more complex arc protection system.

Uploaded by

drissa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
125 views6 pages

AQ-101 Arc Flash Protection Device

The AQ-101 arc flash protection device is a microprocessor-based unit designed to detect arc light and minimize damage from arcing faults by tripping circuit breakers. It features a wide power supply range, supports multiple sensors, and includes self-supervision for reliability. The device can operate independently or as part of a more complex arc protection system.

Uploaded by

drissa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

AQ-101 Arc flash protection device

AQ-101 Arc flash protection device

Description
The AQ-101 arc flash protection device is a sophisticated
microprocessor-based arc flash protection unit for arc light
detection. It is designed to minimize the damage caused by an
arcing fault (arc flash) by tripping the circuit breaker that
sources the fault current. The complete system self-supervision
function of AQ-101 provides the highest level of dependability
by continuously monitoring all internal system functions as
well as external connections.

The AQ-101 arc flash protection device can be used as a stand-


alone unit or as a part of a more complex arc protection system
via a binary bus.

Features:

A wide range for the power supply (18…72 V DC or 92…265


V AC/DC).
A maximum of 12 arc light point sensors (3 point sensors per
channel).
A maximum of 1 fiber loop sensor (optional).
4 trip relays (with 7 ms trip time).
1 system failure relay.
1 fast binary output.
2 fast binary inputs.
1 multifunction push button.
Non-volatile memory.
12 indication LEDs.

Learn more about how different protection techniques affect


the consequences of an arc flash:
“Arc flash comparison” by Arcteq Relays (https://youtu.be/EUlZ_a_rcIg)

Arcteq Relays Ltd


Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370
AQ-101 Arc flash protection device

Arcteq Relays Ltd


Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370
AQ-101 Arc flash protection device

Technical data
PROTECTION
Light (L>)
Light and pressure (L> / P>)
Circuit breaker failure protection (50BF/52BF)
Total trip time when using mechanical trip relays: 7 ms (only arc light signal from an AQ-110x
device)
Total trip time when using mechanical trip relays: 7 ms (both overcurrent and arc light signal
from an AQ-110x device)
Reset time (arc light stage): 2 ms

Arcteq Relays Ltd


Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370
AQ-101 Arc flash protection device

INPUTS AND OUTPUTS

Applicable sensors
AQ-01 light sensor (activation thresholds: 8 klx, 15 klx, 50 klx)
AQ-02 light and pressure sensor (activation thresholds: 8 klx, 15 klx, 50 klx)
AQ-06 plastic fiber sensor (3...40 m) (optional)
AQ-07 glass fiber sensor (3-50 m length) (optional)
AQ-08 glass fiber sensor (3...15 m) (optional)
Trip relays (T1, T2, T3, T4)
3 NO + 1 NC or 4 NO
Rated voltage: 250 V AC/DC
Continuous carry: 5 A
Make-and-carry for 3 s: 16 A
Make-and-carry for 0.5 s: 30 A
Breaking capacity DC (when L/R = 40 ms): 40 W; 0.36 A at 110 V DC
Contact material: AgNi 90/10
Binary output (BO1)
Number of outputs: 1
Rated voltage: +24 V DC
Maximum rated current: 20 mA
Binary inputs (BI1, BI2)
Number of inputs: 2
Threshold voltage: 24/110/220 V DC
Rated voltage: 250 V AC/DC
Rated current: 3 mA
Power supply
Auxiliary power supply: 92…265 V AC/DC
Auxiliary power supply: 18…72 V DC (optional)
Maximum interruption: 100 ms
Maximum power consumption: 5 W
Standby current: 90 mA

Arcteq Relays Ltd


Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370
AQ-101 Arc flash protection device

INTERFACE
12 indication LEDs
Multifunction push button (SET)
Autoconfiguration
Indication reset
System check

SELF-SUPERVISION
Sensors and wiring
Binary I/O
Trip coil
Power supply
Internal voltages
Settings

SYSTEM CONNECTIVITY
AQ 100 series
AQ 200 series
AQ 300 series

ACCESSORIES
AX016 Wall mounting bracket

Arcteq Relays Ltd


Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370
AQ-101 Arc flash protection device

Application Drawing

Arcteq Relays Ltd


Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370