AQ-101 Arc flash protection device
AQ-101 Arc flash protection device
Description
The AQ-101 arc flash protection device is a sophisticated
microprocessor-based arc flash protection unit for arc light
detection. It is designed to minimize the damage caused by an
arcing fault (arc flash) by tripping the circuit breaker that
sources the fault current. The complete system self-supervision
function of AQ-101 provides the highest level of dependability
by continuously monitoring all internal system functions as
well as external connections.
The AQ-101 arc flash protection device can be used as a stand-
alone unit or as a part of a more complex arc protection system
via a binary bus.
Features:
A wide range for the power supply (18…72 V DC or 92…265
V AC/DC).
A maximum of 12 arc light point sensors (3 point sensors per
channel).
A maximum of 1 fiber loop sensor (optional).
4 trip relays (with 7 ms trip time).
1 system failure relay.
1 fast binary output.
2 fast binary inputs.
1 multifunction push button.
Non-volatile memory.
12 indication LEDs.
Learn more about how different protection techniques affect
the consequences of an arc flash:
“Arc flash comparison” by Arcteq Relays (https://youtu.be/EUlZ_a_rcIg)
Arcteq Relays Ltd
Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370
AQ-101 Arc flash protection device
Arcteq Relays Ltd
Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370
AQ-101 Arc flash protection device
Technical data
PROTECTION
Light (L>)
Light and pressure (L> / P>)
Circuit breaker failure protection (50BF/52BF)
Total trip time when using mechanical trip relays: 7 ms (only arc light signal from an AQ-110x
device)
Total trip time when using mechanical trip relays: 7 ms (both overcurrent and arc light signal
from an AQ-110x device)
Reset time (arc light stage): 2 ms
Arcteq Relays Ltd
Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370
AQ-101 Arc flash protection device
INPUTS AND OUTPUTS
Applicable sensors
AQ-01 light sensor (activation thresholds: 8 klx, 15 klx, 50 klx)
AQ-02 light and pressure sensor (activation thresholds: 8 klx, 15 klx, 50 klx)
AQ-06 plastic fiber sensor (3...40 m) (optional)
AQ-07 glass fiber sensor (3-50 m length) (optional)
AQ-08 glass fiber sensor (3...15 m) (optional)
Trip relays (T1, T2, T3, T4)
3 NO + 1 NC or 4 NO
Rated voltage: 250 V AC/DC
Continuous carry: 5 A
Make-and-carry for 3 s: 16 A
Make-and-carry for 0.5 s: 30 A
Breaking capacity DC (when L/R = 40 ms): 40 W; 0.36 A at 110 V DC
Contact material: AgNi 90/10
Binary output (BO1)
Number of outputs: 1
Rated voltage: +24 V DC
Maximum rated current: 20 mA
Binary inputs (BI1, BI2)
Number of inputs: 2
Threshold voltage: 24/110/220 V DC
Rated voltage: 250 V AC/DC
Rated current: 3 mA
Power supply
Auxiliary power supply: 92…265 V AC/DC
Auxiliary power supply: 18…72 V DC (optional)
Maximum interruption: 100 ms
Maximum power consumption: 5 W
Standby current: 90 mA
Arcteq Relays Ltd
Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370
AQ-101 Arc flash protection device
INTERFACE
12 indication LEDs
Multifunction push button (SET)
Autoconfiguration
Indication reset
System check
SELF-SUPERVISION
Sensors and wiring
Binary I/O
Trip coil
Power supply
Internal voltages
Settings
SYSTEM CONNECTIVITY
AQ 100 series
AQ 200 series
AQ 300 series
ACCESSORIES
AX016 Wall mounting bracket
Arcteq Relays Ltd
Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370
AQ-101 Arc flash protection device
Application Drawing
Arcteq Relays Ltd
Kvartsikatu 2 A 1
65300 Vaasa, Finland
tel: +358 10 3221 370