Pump Type Selection Guide
Pump Type Selection Guide
ra
Important Notices
1. This write-up intended to provide general guide for pump type selection. It has to be noted that
the actual selection depends on many factors including the specific application which will
tD
require proper engineering judgments, as well as commercial considerations which are beyond
the scope of this guide.
2. This write-up is intended to be the first draft and is intended to promote discussions and
comments. Comments are highly encourages from all stake holders and will be required to
ensure the universal acceptance and implementation.
rs
Fi
Page 1 of 25
1. INTRODUCTION
1.1 SCOPE
This write up presents guidelines and provides recommendations for the type selection
and basic design of pumps. It is intended for pumps in critical and essential duties.
It is intended for use in exploration and production facilities, oil refineries, chemical
plants, gas plants, and, where applicable, supply/marketing installations.
Excluded from the scope of this g u i d e are pumps i n c r y o g e n i c o r refrigerated
product service.
If C l i e n t , national and/or local regulations exist in which some of the requirements
ft
may be more stringent than in this g u i d e , t h e E n g i n e e r i n g Contractor shall
determine by careful scrutiny which of the requirements are the more stringent and
which combination of requirements will be acceptable as regards safety, environmental,
economic and legal aspects.
ra
1.2 DEFINITIONS
design and construction. The C l i e n t will generally specify the technical requirements
and is the party that has accountability for critical technical decisions.
Any service in which there is an expected wear rate of 0.1 mm per year or more, or
where particle sizes exist larger than 1.00 mm in quantities exceeding 100 mg/kg.
Examples:
• Specially engineered pumps, such as slurry pumps, vortex pumps, and self-priming pumps
• Firefighting pumps according to NFPA 20.
Category 1
• Liquids containing hydrogen sulfide in concentrations above 600 mg/kg (600 ppm wt.)
• Liquids consisting of or containing lethal or carcinogenic substance(s) as indicated on the
data/requisition sheets.
ft
Examples of lethal substances are c o n c e n t r a t e d s u l f u r i c a c i d , phenol,
ethylene oxide and HF acid.
Examples of carcinogenic substances are Benzene, Toluene and 1, 3-Butadiene.
ra
Category 2
• Liquids consisting of or containing very toxic substances as indicated on the
data/requisition sheet.
• Hydrocarbon liquids at an operating temperature above their auto-ignition temperature.
Category 3
tD
• Hydrocarbon liquids with a seal chamber vapor pressure, higher than 500 kPa (abs)
• Hydrocarbon services of butane or lighter.
ft
equipment
A service in which A service in which A service in which All other services.
failure of failure of failure of
equipment causes equipment renders equipment renders
an unsafe a plant or process a plant or process
ra
condition of the unit inoperable or unit inoperable or
Definition plant or installation reduces reduces
resulting in performance to a performance to a
jeopardy to life level unacceptable level unacceptable
and/or major to the Client. to the Client.
damage (fire,
explosion etc.).
tD
Equipment shall be A decision not to Installed spare Economic evaluation
adequately spared install spare equipment is required to justify
to ensure 100% equipment is based normally selected spared equipment.
availability of the upon economic where potential
service under all considerations and losses due to
circumstances proven equipment equipment outage
Selection availability. Non- greatly outweigh
Criteria spared equipment equipment Capex.
availability may be Sparing philosophy
upgraded by means shall be
rs
Page 4 of 25
2. GENERAL
ft
the pump Seller.
2.1.2 Seller selection
Typically, Client furnishes the project with a project specific “Suggested Manufacturers
and Fabricators List” (SMFL). The Engineering Contractor shall make a recommendation
ra
to the Client which Sellers the Contractor intends to procure pumps and seals, subject to
Client approval.
If the Client has supply agreements in place, they shall be applied as a first choice. If so, the
Client shall provide copies of these agreements to the Engineering Contractor. The
Engineering Contractor shall then comply with his responsibilities stated in the supply
agreements. The use of alternative Suppliers besides or instead of agreement holders is
tD
subject to the approval of the Client.
In all respects selected pumps shall be within the range of the Manufacturer's proven
experience and shall not involve the use of any prototype design or components. In
selecting equipment, care shall be taken to ensure that prospective Sellers do not exceed the
ratings of their design in their efforts to offer competitively.
Fi
3. TYPE SELECTION
ft
3.1 GENERAL
Process pumps in Critical service shall be of the heavy-duty type.
Process pumps in essential services may be of the light-duty type, if all the following
criteria are met:
ra
a. Discharge gauge pressure shall be not greater than 1,900 kPa.
b. Suction gauge pressure shall be not greater than 500 kPa.
0 0
c. Pumping temperature shall be between 0 C and 150 C.
d. Rotational speed shall be not greater than 3,000 rpm (3,600 rpm for 60 Hz locations).
e. Rated total head shall be not greater than 120 m.
tD
f. Maximum impeller diameter shall be not greater than 330 mm (13”).
g. Driver Nameplate power shall not exceed 55 kW (OH3), 75kW (OH1).
h. Specific gravity of the liquid shall not be less than 0.7.
All other process pumps in essential services shall be of the heavy duty type, except if this
type will not provide the required reliability and availability (24,000 hours continuous
operation). In such cases, an alternative design may be selected and the pump shall
always be spared.
Examples of such cases are:
• High capacity pumps, e.g., cooling water pumps
rs
ft
BB2.
NOTES:
1. Vertical, in-line rigidly coupled pumps, OH4, shall not be selected.
ra
2. OH3 pumps are preferred, where NEMA motors are applied and if the operating
conditions are within the following limits:
a. Driver power is not greater than 75 kW
b. Rotational speed is not greater than 3,000 rpm (3,600 rpm for 60 Hz locations).
c. Fluid temperature is between -25 0C and 200 0C
d. Maximum impeller diameter 330 mm (13”)
tD
e. Maximum head 200 m.
Single casing radially split (ring joint) pump, BB4, shall not be used.
1. VS4 type may not be preferred by some Clients and its selection may be subject to the
Client’s approval.
2. In considering the above pump type, the selection of horizontal self-priming
pumps shall also be evaluated.
Page 7 of 25
• Gear pumps.
• Lobe pumps.
• Sliding or flexible vane pumps.
ft
suction specific speed and NPSHA.
If more than one pump type is considered technically suitable, the final selection should
be based on a life cycle cost evaluation, taking into account standardization, efficiency,
suction specific speed, NPSH margin and minimum flow.
ra
3.4.1 Pressure
For design pressures above 7,000 kPa in hazardous service, or above 14,000 kPa in non-
hazardous service, an axial split casing pump, BB3, may be used if approved by the
Client.
3.4.2 Temperature
tD
Unless specifically requested by the Client, axially split casings shall not be used for
operating temperatures above 100 0C.
3.4.3 Flow
Rated flow shall be selected between 8 0% and 110% of best efficiency point (BEP) for
the rated impeller.
For pumps with high turn down requirements, preference shall be given with pumps having
their normal flow and rated flow straddle the BEP.
Pumps with rated capacities of 1,000 m3/h or greater shall be selected within 10% of the
rs
but alternative methods of accomplishing this may be acceptable. Back filing of impellers
for this purpose is not allowed for new pumps. The head increase capability is not
intended for expansion of the process unit. Rather, it is intended to cover changes in
hydraulic calculations between preliminary and final. Single stage overhung pumps (type
OH1, OH2 and OH3) with impellers 330 mm or larger in diameter at 3,000 rpm (3,600 rpm
for 60 Hz locations) may require Clients approval.
3.4.5 NPSH
The Net Positive Suction Head Required (NPSHR) shall be based on water [at a
temperature of less than 65 0C (150 0F) at the rated flow and rated speed; no reduction or
correction factors shall be applied for other liquids.
Page 8 of 25
The Net Positive Suction Head Available (NPSHA) shall exceed the Net Positive Suction
Head Required (NPSHR) by at least 1 m (3 ft.) throughout the range from minimum
continuous stable flow up to and including the rated capacity, and by 0.3 m (1 ft.) at 120%
of rated flow.
For pumps in the following service:
• Vacuum
• Low temperature
• Boiler Feed Water (BFW)
• Cooling Tower Water (CTW)
• LPG.
• Liquids containing dissolved gases
ft
To avoid cavitation damage due to vapor-induced flow path restrictions, NPSHA shall be
1.5 x NPSHR, with a minimum margin of 5 m (15 ft.) between NPSHA and NPSHR
throughout the range from minimum continuous stable flow up to and including the rated
capacity and 1.25 x NPSHR with a minimum margin of 2 m (6 ft.) at 120% of rated flow.
ra
The maximum impeller tip speed in sulfinol and carbonate service shall be 45 m/s; for
these services the S e l l e r shall provide evidence of successful applications in similar
duties and the Client’s approval of pump selection is required.
3.4.6 Suction specific speed
The suction specific speed (S) shall be calculated by the Manufacturer from the formulae
tD
in ISO 13709 Annex A and shall be stated in the proposal.
NOTES:
1. The SI units in the formula used to calculate suction specific speed are as follows:
• Rotational speed, expressed in revolutions per minute;
• Flow rate, expressed in cubic meters per hour;
• NPSHR, expressed in meters.
2. For S in US Customary units, multiply the value in SI units (as above) by 0.8607.
rs
In SI units, the value of S shall be 12,800 or less. Selection of pumps with S greater
than 12,800 shall be subject to the approval.
If applied, any pump, exceeding the above S limit, shall be subject to the following:
1. The Manufacturer shall indicate the stable operation range in which recirculation effect
is absent.
Fi
2. The pump shall be installed with appropriate low flow control and/or low flow
protection in order to maintain the pump in the stable operation range.
3. The pump shall be NPSH tested.
4. The presence of Suction and/or Discharge Recirculation shall be determined during the
shop performance test by monitoring the pressure pulsations in the suction and in the
discharge areas of the casing. Piezoelectric transducers installed as close to the impeller as
possible in the suction and in the discharge of the pump may be used to detect pressure
pulsations. The data shall be analyzed with a spectrum analyzer coupled to an XY plotter
to produce a record of the pressure pulsations versus the frequency for selected flows.
5. Shaft deflection shall be measured over the full pump operating range. During the pump
Page 9 of 25
performance test there shall be no sign of cavitation, suction or discharge recirculation
(either vibration or noise) in the full operating range of the pump from minimum
hydraulically stable flow to at least 110% of best efficiency point of the rated impeller
(BEP).
3.4.7 Physical characteristics of pumped liquid
Corrosive and abrasive services.
The impeller tip speed shall be restricted to minimize the corrosive/abrasive effects. The
advice of the pump Manufacturer, based on his experience, shall be sought in this respect.
Pumps with bearings lubricated by the pumped liquid shall not be selected.
ft
3.5 ALTERNATIVE DESIGNS (CENTRIFUGAL PUMPS)
If operating requirements and/or liquid properties preclude the economic application of a
heavy- duty or light-duty pump, alternative designs may be offered if they have a lower
life cycle cost. The Manufacturer shall provide sufficient evidence of successful
ra
application and the selection shall be subject to the approval of the Client.
Alternative designs shall follow API 610/ISO 13709 design principles as far as
possible.
Canned motor and magnetic drive pumps may be selected only if all the following are
satisfied:
• The product shall not contain any solid particles.
• The product cannot crystallize or polymerize.
• The product kinematic viscosity shall not be greater than 40 mm2/s.
• The temperature difference between boiling point and suction temperature shall be at least
Fi
20 0C (but, subject to pump cooling design, this may be reduced if approved by the
Client).
• A vapor pressure versus temperature curve is available for the full operating range.
• NPSH margin from 70% to 120% of flow shall be at least 2 m
• Maximum power, 55 kW.
4. DESIGN REQUIREMENTS
ft
The method of bearing lubrication shall be selected from the list below in descending order
of preference, taking due account of local site considerations:
• pure oil mist
• purge oil mist
ra
• Oil ring
• circulating oil system
• grease (not allowed for heavy duty pumps).
Vertical in line pumps, type OH3, shall preferably be supplied with pure oil mist.
If a circulating oil system is required the complete equipment train, consisting of pump,
driver and gearbox, if applicable, shall be lubricated by the system.
tD
Pump circulation oil systems shall not be shared between separate equipment trains.
Grease-lubricated bearings may be used only for light duty centrifugal pumps and only if
approved by the Client.
4.1.3 Mechanical seals
Mechanical seals and seal systems shall comply t h e a p p r o p r i a t e p r o j e c t
s p e c i f i c a t i o n a n d A P I 6 8 2 . Mechanical seals shall be selected and designed for
a guaranteed 3-year operating period. Mechanical seals shall be applied for all pumps
except firewater pumps and vertical cooling water pumps.
rs
Seals and seal systems shall be selected and engineered by the seal Manufacturer. Seals and
systems shall be evaluated and selected separate from the pump. The pump Manufacturer
is responsible for the co-ordination of engineering and installation of the selected seal and
seal system.
4.1.4 Operating temperatures
Fi
For liquid temperatures below –25 0C, a vertical type pump with a dual mechanical seal and
an isolation chamber between the pump housing and sealing chamber shall be specified,
using methanol or another suitable fluid as the buffer/barrier medium.
Vertical high-speed pumps may be offered as an alternative provided proven experience
is available.
4.1.5 Cooling
Natural convection air-cooling is the preferred method.
The use of cooling water on the seal chamber jacket and/or bearing bracket is left to
the discretion of the pump and seal Supplier, but the ISO/API requirements for seal and
bearing life and prevailing oil sump temperatures shall be met (also for non-ISO/API
Page 11 of 25
pumps). If considered necessary by the pump Manufacturer, additional pump pedestal
cooling may be applied.
If cooling water is required for the bearing housing and the cleanliness of the cooling water,
as required by the pump Manufacturer, cannot be guaranteed, a circulating closed loop
cooling system with tank and cooler shall be applied.
The cooling water piping arrangement shall conform to API 682/ ISO 13709, Figures B.2,
B.4, B.5, B.6, B.8 and B.9.
For pumps not supplied with circulating oil systems, bearing cooling is generally required
where the pumping temperature exceeds 200 0C. When cooling is required the following
shall apply:
ft
• Use of water-cooled bearing housings requires approval.
• Oil cooling coils in the lube oil sump are preferred over jacketed, water-cooled bearing
housing. The coils (including fittings) shall be of nonferrous material or austenitic
stainless steel and shall have no internal pressure joints.
• Fan cooled bearing housings are acceptable for pumping temperatures to 250 0C where
ra
liquid cooling is not available.
• Individual flow indicators shall be provided on each pump's cooling system.
4.1.6 Baseplates
The pump and driver shall be mounted and delivered on a common baseplate. Base plate
drains shall be connected to the open drain system.
tD
4.1.7 Vibration Monitoring System
A shaft displacement vibration monitoring system shall be provided for the following pumps:
• All pumps in Critical service and un-spared pumps in essential service.
• Pumps with hydrodynamic thrust bearings
• Pumps with drivers greater than 1,500 kW
• Pumps with drivers greater than 550 kW and speeds greater than 3,000 rpm (greater than
3,600 rpm for 60 Hz locations).
Continuous vibration monitoring shall be considered in pumps in hazardous service.
Pump location, seal flush system, deluge system, etc. are items to be taken into
rs
consideration.
4.1.8 Pump Casing Vents
All centrifugal pumps require a vent on the casing and/or on the discharge line. In
most applications a vent on the discharge line is sufficient to prime the pump. Pumps that
require a casing vent are as follows:
Fi
• Vertical Inline (VI) pumps fitted with dry gas seals. The vent should come off the seal
chamber.
• Vertical Inline (VI) pumps that do not have an API seal flush Plan 13 (14 in some
arrangements) with the connection to the piping system above the level of the seal gland
plate. As long as the pump suction valve is open, this arrangement is self-venting
• Horizontal pumps with suction and discharge nozzles below the center line of the pump
• Horizontally split multi-stage pumps.
Page 12 of 25
Rotary positive displacement pumps shall conform to API 676.
Some additional requirements, which should be considered when specifying a rotary pump,
are specified below.
4.2.2 Bearings
In order to keep the number of shaft seals to a minimum, rotary pumps handling clean,
abrasive-free, non-corrosive liquids with lubricating properties shall be provided with internal
bearings lubricated by the pumped liquid.
In all other cases, pumps shall be provided with oil-lubricated bearings and timing gears in
separate housings. Constant level sight feed oilers shall be provided.
ft
Bearing selection shall be made according to para. (4.1.1) above.
4.2.3 Mechanical seals
See (4.1.3).
ra
4.2.4 Pressure relief
A separate pressure relief valve in the discharge piping, upstream of the discharge check and
the first block valves, shall be provided to protect the pump and its associated piping system.
4.2.5 Baseplates
See (4.1.6).
tD
4.3 RECIPROCATING AND METERING PUMPS
4.3.1 General
Reciprocating positive displacement pumps shall comply with the appropriate project
specification.
The selected pumps shall be within the Manufacturer's actual field experience of
operating temperature, maximum working pressure, materials of construction, pump speed
and pumped liquid properties. Diaphragm pumps with direct mechanical actuation shall not
be selected.
rs
Plunger pumps shall at least three cylinders. On high-pressure applications, more cylinders
may be required to reduce pressure pulsations.
For metering pumps, provision shall be made in the pump suction piping to facilitate
capacity measurement and flow calibration.
Some additional factors, which should be considered when specifying reciprocating pumps,
Fi
ft
downstream of the bottle. The orifice shall be sized to provide a 170 kPa pressure drop at the
design flow.
For applications from 75 kW to 220 kW, consideration shall be given to conducting a
pulsation analysis and the use of Helmoltz filters.
ra
For applications of 220 kW and higher, a pulsation analysis shall be conducted. r shall
review the results.
Suction lines between the suction vessel and the pump shall be kept as short as possible to
minimize acceleration head loss.
4.3.4 Pressure relief
See (4.2.4). Diaphragm pumps shall have an internal relief valve on the hydraulic drive
tD
system; this valve shall not be used as a protection device for the process side of the pump.
All other reciprocating pumps shall have a separate external pressure relief valve in the
discharge, inside the first block valve, to protect the pump and its associated piping system.
4.3.5 Baseplates
See (4.1.6).
4.3.6 Diaphragms
Pump diaphragms shall be of the double diaphragm type. Diaphragm failure indication shall
be provided.
rs
5. ACCESSORIES
5.1 DRIVERS
Pumps may be driven by electric motors, steam turbines, gas turbines or internal
combustion engines according to application, location, fuel, availability and economics. The
Fi
ft
electric motor drivers should be capable of developing adequate starting torque to handle
such cases.
The sizing of driver power for operation on water during commissioning shall be specified
only, if this type of operation is imperative for plant pre-commissioning and start-up.
ra
For small, low power pumps seal losses assuming dual pressurized seal(s) shall be taken into
account.
Order of preference:
tD
• Direct drive shall be selected whenever possible Gearbox
• VFD or VSDS shall be selected if a variation in speed demand is specified for electric
motor drivers
• Belt drives shall not be used for centrifugal pumps in Critical or essential service.
5.3.1 Gear units
Gear units in essential unspared service above 750 kW shall comply with the relevant
project specification.
5.3.2 Couplings
rs
Couplings for pumps shall be of the forged steel, flexible disc/membrane or diaphragm
type with spacers, unless the Client approves alternative designs and/or materials.
Flexible membrane couplings for steam turbine drivers shall not lose transmission
capability upon membrane failure.
Fi
Page 15 of 25
APPENDIX-1 Pre-selected pump summary sheet
Table A-1.1
SELLER: PAGE
OF
Item No.
Spec. No.
ft
Service
Rated Capacity – m3/h
Diff. Head - m.
NPSHA - m.
Hyd Power - kW
ra
Pump type
Model No.
Flow at Best Efficiency
No. of stages
Speed – rpm
Imp. Dia-in - Rated / / / / / /
Imp. Dia-max/min
tD
NPSHR – m
Efficiency at rated point
Power - rated/max / / / / / /
Driver Nameplate Power
Driver Spec. No.
Mt’l code case/int / / / / / /
Seal
Seal code
Curve no.
Notes
rs
Page 16 of 25
APPENDIX-2 Pump selection checker board and description of acceptable pumps
ft
ra
tD
Pump Selection Guide
rs
Notes
1. Pump coverage chart based on normal ranges of operation of commercially available
types.
2. Solid lines, use left ordinate for head scale.
Fi
Page 17 of 25
The following guidelines are intended to indicate general limits within which these pumps
may be applied. Application of pumps beyond these limits needs to be evaluated with
proper engineering judgment.
ft
metallic pumps, which are not covered by this Appendix, shall be considered only when
metallic pumps are not suitable.
ra
Temperature to 150 0C
Suction Pressure to 500 kPa
Speed to 3000 (3600) rpm
Power at 3000 rpm (3600 rpm) to 75 kW
Max. Impeller Diameter 330 mm (13”)
tD
A-2.2 CHEMICAL PUMPS, VERTICAL IN LINE (OH3)
This includes single-stage centrifugal pumps with vertical shaft, having suction and
discharge nozzles in-line. Pumps manufactured in accordance with ASME B73.2 are
preferred.
Note: The use of this style of pump requires Oil Mist Lubrication or Sealed “Greased for
Fi
Life” Bearings. Oil sump lubrication with a pumping ring is not permitted.
ft
Speed to 3000 (3600) rpm
Power at 3000 rpm (3600 rpm) to 75 kW
Max. Impeller Diameter 330 mm (13”)
ra
A-2.4 Horizontal Single Stage Centerline Mounted (OH2)
Flow at 3000 rpm (3600 rpm) 340 m3/h
Head at 3000 rpm (3600 rpm) 200 m
Temperature to 425 0C
Suction Pressure to 1,725 kPa
tD
Speed to 3000 (3600) rpm
Power at 3000 rpm (3600 rpm) to 200 kW
Page 19 of 25
Suction Pressure to 3000 kPa
Power to 3,000 kW
ft
• multi-stage centrifugal, closed impellers, between bearings, radially split (double case,
or barrel); and,
• multi-stage centrifugal, closed impellers, between bearings, axially or axially split,
either volute or diffuser.
ra
A-2.8 VERTICAL TURBINE PUMPS
This includes vertical turbine pumps with one or more stages, either with or without
suction barrel. They are generally used where one or more of the following conditions exist:
• medium head, high flow conditions;
• limited NPSH available, so need to lower elevation of first stage impeller; and,
tD
• suction source liquid level is below the pump mounting elevation.
The actual limits of application are variable, depending upon such factors as temperature and
the materials of construction.
This type of pump is available for either process or ground water services and is available in a
wide range of sizes and number of stages.
suction, between bearings, closed impeller, axially split, normally foot-mounted pumps.
at up to 20,000 m3/h to 40 m
Temperature to 95 0C
Suction Pressure to 350 kPa
Speed to 1800 rpm
Power to 300 kW
ft
Diaphragm construction shall be specified if available. Flow shall be continuously adjustable
from pump maximum capacity to as close to no flow as possible.
ra
Discharge Pressure to 24,000 kPa
Temperature to 95 0C
Suction Pressure no limit, except must always be at least 140 kPa
less than discharge pressure
Speed Not higher than 80% of the Manufacturer's
tD
published maximum speed
Power to 7.5 kW
The previously noted guides cover the normal limits of simplex and duplex units, and will
cover most metering pump applications. Special metering pumps are available for higher
flows and for higher pressures.
For metering applications requiring flows above 2.0 m3/h at pressures less than 10,000
kPa where metering is automatically controlled by process, centrifugal pumps and control
valves shall be considered as an alternate.
rs
centrifugal pumps are required. For services which can be satisfied by both centrifugal and
reciprocating pumps, centrifugal pumps are preferred. Centrifugal pumps are normally less
expensive and require less maintenance.
ft
Flow to 1,000 m3/h
Discharge Pressure to 10,000 kPa
Temperature to 350 0C
Suction Pressure to 3,500 kPa
ra
Viscosity to 30,000 cSt
Speed to 1500 (1800) rpm
Power to 750 kW
The previously outline limits are only general guidelines, because of the parameters, and
the pump construction features such as bearing span, are interrelated. The Sellers must be
consulted for proper application.
tD
Single-rotor, triple-rotor, and other than heavy-duty, double rotor, externally timed screw
pumps are considered "special", and must have the concurrence of the owne r a n d t h e
e n g i ne er ing c ontractor before the solicitation of bids.
Application Guide:
Flow to 1,000 m3/h
Discharge Pressure to 3,500 kPa (3.5 MPa)
Temperature to 350 0C
Suction Pressure to 1,500 kPa
Fi
Page 22 of 25
Table A-2.1 Design Limits for different styles of Centrifugal Pump
ft
FLOW POWER IMPELLER
PUMP PRESSURE HEAD TEMP SPEED
DUTY SP. GR DIAMETER COMMENTS
TYPE (Bar) (m) ( 0C) (m3/hr) (kW) (rpm)
(mm)
Light
ra
OH1 100
Latest edition
OH3 75 allows use of light
Any Ps <5 Pd<19 120 0 - 150 120 3000 330 duty pumps in
>0.7 (3600) hydrocarbon
service
Heavy
OH2
OH3
OH6
BB1
Any
Any
Any
Any
tD
70
200
1,500
425
-25 to
200
-25 to
200
100
340
2,000
200
300
75
2,000
3000
(3600)
3000
(3600)
330
rs
BB2 Any 2,000 2,000
BB3 Hazardous
Service 70 100
Non
BB3 Hazardous 140 100
Service
Fi
BB5 Any
3000 For Sump Pump
VS4/5 Any 40 150 35 37 330
(3600) Applications
Page 23 of 25
Table A-2.2 Pump Bearing and Lubrication System Selection
ft
Energy Density (d e )
< 4,000,000
(API 610 Table 10)
Pump Radial Bearing
ra
dm x N > 500,000
Pump Thrust Bearing If Driver has
dm x N < 500,000 X X Circulation
System
Energy Density (d e )
< 4,000, 000
(API 610 Table 10)
tD
Pump Radial Bearing
dm x N > 500,000
Pump Thrust Bearing
dm x N > 500,000 X X X
Energy density
< 4,000,000
(API 610 Table 10)
Energy Density (de)
rs
> 4,000,000 X X X
(API 610 Table 10)
ft
ra
tD
rs
Fi
Page 25 of 25
Heavy-duty centrifugal pumps must comply with the relevant project specifications, while light-duty centrifugal pumps need to adhere to applicable industry standards. Heavy-duty pumps often require more robust features such as more durable bearings and advanced lubrication systems like pure oil mist, which are not necessary for light-duty applications .
Canned motor and magnetic drive pumps are permissible if the product contains no solid particles, cannot crystallize or polymerize, has a kinematic viscosity not exceeding 40 mm²/s, the temperature difference between boiling and suction temperature is at least 20 °C (subject to client approval), maximum power does not exceed 55 kW, and a vapor pressure versus temperature curve is available for the full operating range .
Overhung, double-suction centrifugal pumps are not recommended due to potential bearing and shaft deflection issues that can arise, particularly in demanding applications. These design complications can lead to increased maintenance requirements and reduce the pump's operational reliability in critical service conditions .
Magnetic drive pumps are not recommended if the product temperature exceeds 150 °C, if the power requirement is greater than 55 kW, or if the service involves hazardous conditions. Additionally, these pumps should not be used if the product contains solid particles, can crystallize or polymerize, or if the product's kinematic viscosity is greater than 40 mm²/s .
A pressure relief valve in the discharge piping of rotary positive displacement pumps serves to protect the pump and its associated piping system from overpressure conditions by relieving excess pressure upstream of the discharge check and the first block valves .
A process pump in essential services can be classified as light-duty if the discharge gauge pressure is not greater than 1,900 kPa, suction gauge pressure is not more than 500 kPa, pumping temperature is between 0 °C and 150 °C, rotational speed does not exceed 3,000 rpm (or 3,600 rpm for 60 Hz locations), rated total head is not greater than 120 m, maximum impeller diameter does not exceed 330 mm, driver nameplate power is not more than 55 kW (for OH3 type) or 75kW (for OH1 type), and the specific gravity of the liquid is not less than 0.7 .
A vertical in-line pump with dry gas seals should be equipped with a casing vent when the pump does not incorporate an API seal flush Plan 13 or 14 with connections above the seal gland plate level. This venting is necessary to prevent trapping gases within the casing, thus ensuring proper pump operation and maintenance .
Fan-cooled bearing housings are acceptable for temperatures up to 250 °C as they provide necessary cooling to maintain the bearing performance without requiring a liquid cooling system. If liquid cooling is unavailable, alternative cooling methods like fan cooling can be used to lower the operational temperature effectively without the added complexity and maintenance of liquid cooling systems .
Noise control considerations include specifying equipment noise limits according to project specifications, which should be communicated unambiguously to the seller. The seller must supply guaranteed sound pressure and power levels for the overall unit, the pump, gearbox, driver, and any applicable auxiliaries .
For bearings in pump systems, the preferred lubrication methods are pure oil mist, purge oil mist, oil ring, and circulating oil systems, in that order. These methods ensure efficient lubrication and reduce maintenance needs. Grease is not allowed for heavy-duty pumps as it cannot provide sufficient lubrication under the demanding conditions these pumps face, which could lead to increased wear and risk of failure .