The FIT 3F needs a remote temperature sensor. This sensor
should be mounted in such a way that the temperature which
has to be controlled, can be measured correctly. Lay sensor
Floor Temperature Controller FIT 3F inside a protective tube (simplifies replacement). The sensor
lead can be extended up to 50 m by using a cable and con-
nections suitable for 230 V. Avoid laying sensor cable along-
Actual Day
side power cables, for example inside a conduit.
Actual
floor Caution!
Temperature 8. Pre-set programs
The sensor is at mains voltage.
There are 3 pre-set time/temperature programs in the con-
Calling for Heat
troller. Pre-set program 1 (as shown below) is the default.
(Blinks if
Therefore, if pre-set program 1 is the best program to suit the
detached from
application, there will be no need to change the time/tem-
power module
perature settings on the device.
or there is no
mains power) 6 Technical Data To select another program see 9. G1.
4 Features
• One line text display for simplified operation Program 3
• Back light (off, continuous, temporary after key pres) Monday to Friday
• Real time clock (setting of year, month, day, time) Events 1 2 3
Time 11:00 13:00 22:00
• Automatic Summer- Wintertime change over
Temperature °C 28,0 18,0 15,0
• Max 9 events per day (each day individually)
• Pre-set and adjustable programs Saturday and Sunday
• Optimum-Start 230V~ 50Hz Events 1 2 3 4
N
Time 8:00 10:00 19:00 22:00
• Arm chair programming (with removed display unit) L
Temperature °C 28,0 18,0 28,0 15,0
• OFF-Function, Key V to be pressed for 10 sec
• Holiday-Mode (date from – until can be set) 28
Load 27
• Timer (Party) specific temperature for some hours 26
25
• Energy consumption display (heating on time * cost) for last
24
2 days, -week, -month, -year 23
22
• Energy cost per hour adjustable
21
• Frost protection 20
➔
Keys to confirm / activate
Info Show related details in AUTO, MAN, TIMER, HOLIDAY, AT-HOME. To cancel press key again
V for 10 sec Switch off connected load. Display reads OFF. Details see G4
➔
Main Menu to confirm / activate
B AUTO The temperature will be controlled automatically according to the time and temperature of the selected OK
program, see G1. Use + – keys to change temperature until next switching event.
C MAN The temperature will be controlled continuously according to the temperature set in this menu. OK
Use + – key to change temperature
D TIMER The temperature will be controlled temporarily according to the hours and temperature set in this menu. OK
On termination, AUTO will be re-started. HOLIDAY will be terminated.
E HOLIDAY The temperature will be controlled for the period of days and the temperature set in this menu. OK
Holiday starts at 0h of the first day, it ends at 24h of the last day, then going to AUTO.
In the period of time before HOL starts, AUTO will be active. TIMER will be terminated.
During this AUTO period of time, Temp can not be changed.
F AT HOME The temperature will be controlled automatically according to the time and temperature of the program OK
adjusted here (independent from AUTO). The program is the same for all days.
Pre-set is the program of Monday.
It needs to be terminated by user, e.g, by selecting AUTO. Usage: for holiday at home, illness etc.
H INSTALLER SETTINGS Customise the controller according to application needs (from installer only) OK
4 Off Heating Switch off the heater, the controller remains on power. Display reading OFF. NO
Permanent Frost protection may happen if selected. See H6.
Switching ON again by activating e.g. AUTO or by pressing key V for 10 Sec.
When re-activating via key V or this menu, AUTO will be activated.
6 Key Lock Protect controller against unauthorised use. Re-activate via code = 93 NO
7 Temperature limits Limits the temperature which can be set by the user, If both values are the same, no adjustment is 10; 40°C
min/max possible. This affects to AUTO, MAN, HOL, TIMER, AT-HOME, Programming.
The active program / mode will not be affected automatically.
8 Cost/Hr for Energy The assumed energy cost per hour (in cent/h) can be set. 10
9 Energy consumption Shows the approximate energy cost of the controlled area.
to date For the last: 2 days, week (7 days), month (30 days), year (365 days).
On the actual day, calculation is up to current time. In case of overflow 9999 will be displayed.
Calculation: On-Time of heater x cost per hour see above. Reset see H9
13 Backlight Continuously ON, Continuously OFF, temporarily illuminates after key press SHORT
16 Reset user settings Only USER SETTINGS will be set to factory settings NO
only The energy counter will not be re-set; to do this see H9)
CAUTION!
These settings should only be set-up by a qualified person. They can influence safety and the proper functioning of the system.
H INSTALLER Customise the controller according application needs (by installer only) default
SETTINGS
0 Code Enter Code (= 7) in order to access the menus. It is valid for 1 Hour
2 Control Mode PWM or ON/OFF can be selected. In case of PWM, the cycle Time can be set (in Minutes). PWM/10
Use short time for fast and longer time for slow reacting heating systems
6 Frost protection Set frost protection temperature. In OFF mode only, the Temperature will be controlled to that value. 10 °C
7 Optimum Start The set temperature will be reached at the time specified in the program. NO
During pre-heating time, AUTO_ will be displayd
11 Reset all All INSTALLER and USER settings will be set to its Factory setting NO
CONFIGURATION Display- and powermodule do not fit EXT SENSOR 1. Error of external sensor
g use only suitable parts g remove sensor
g switch off and on power supply 2. Over- or under run of valid display range
COMMUNICATION Communication between display- and power unit fails
g unplug and re-plug display unit
g switch off and on power supply