Fit 3F

The FIT 3F is a programmable floor temperature controller that requires a remote temperature sensor for accurate temperature measurement. It offers various features including pre-set programs, manual operation, and holiday modes, allowing users to customize their heating schedules. The device must be installed by a qualified electrician and complies with safety regulations, operating within specified temperature ranges and conditions.

Uploaded by

liiva.annus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views2 pages

Fit 3F

The FIT 3F is a programmable floor temperature controller that requires a remote temperature sensor for accurate temperature measurement. It offers various features including pre-set programs, manual operation, and holiday modes, allowing users to customize their heating schedules. The device must be installed by a qualified electrician and complies with safety regulations, operating within specified temperature ranges and conditions.

Uploaded by

liiva.annus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

468 931 003 484 Connecting the remote sensor Remote Sensor F 193 720

User and
installation guide
 The FIT 3F needs a remote temperature sensor. This sensor
should be mounted in such a way that the temperature which
has to be controlled, can be measured correctly. Lay sensor
Floor Temperature Controller FIT 3F inside a protective tube (simplifies replacement). The sensor
lead can be extended up to 50 m by using a cable and con-
nections suitable for 230 V. Avoid laying sensor cable along-
Actual Day
side power cables, for example inside a conduit.
Actual
floor Caution!
Temperature 8. Pre-set programs
The sensor is at mains voltage.
There are 3 pre-set time/temperature programs in the con-
Calling for Heat
troller. Pre-set program 1 (as shown below) is the default.
(Blinks if
Therefore, if pre-set program 1 is the best program to suit the
detached from
application, there will be no need to change the time/tem-
power module
perature settings on the device.
or there is no
mains power) 6 Technical Data To select another program see 9. G1.

Order Type FIT 3F Program 1


Helping text Supply voltage 230 V AC 50 HZ (195…253 V) Monday to Friday
Mode = AUTO
Temperature setting range 10°C to 40°C; in 0,5°C steps Events 1 2 3 4
Time = 14:31
Temperature resolution 0,1°C steps Time 6:00 8:00 19:00 22:00
Output Relay NO contact Temperature °C 28,0 18,0 28,0 15,0
Switching current 10mA ... 16(4)A *;
Output signal PWM (Pulse Width modulation)
Saturday and Sunday
or ON/OFF Events 1 2 3 4
Time 8:00 10:00 19:00 22:00
1 Principle of operation PWM cycle time adjustable
Temperature °C 28,0 18,0 28,0 15,0
Minimum programmable time 10 Min
The programmable temperature controller FIT 3F allows
Power consumption ~ 1,2 W 28
programming switching events (up to 9) and temperatures 27
Accuracy of clock < 4 Min / year
according the personnel needs. After installation the device 26
Power reserve ~ 10 Years 25
shows automatically the actual time of the day and the floor
Remote sensor F 193 720, length 4m, 24
temperature. In AUTO mode, the heater will be activated 23
can be extended up to 50m
automatically according to programmed time and tempera- 22
Ambient temperature without condensation 21
ture. Program 1 is activated see 8. The floor temperature will Operating 0°C … 40°C 20
be controlled according to the temperature measured by the Storage –20°C … 70°C 19
18
remote sensor. The heater will be switched on when the Rated impulse voltage 4 kV 17
temperature drops below the current set-point. Ball pressure test 115°C 16 Mon - Fri
Sat - Sun
15
Voltage and Current for 14
the purposes of 6:00 h 8:00 h 10:00 h 12:00 h 14:00 h 16:00 h 18:00 h 20:00 h 22:00 h
2 Installation
Interference measurements 230V, 0,1A
Degree of protection IP 30 Program 2
Protection class of housing II (see Caution) Monday to Friday
Caution! Pollution degree 2 Events 1 2 3 4 5 6
This device must be installed by a qualified electrician, Software class A Time 6:00 8:00 12:00 14:00 19:00 22:00
according to the wiring diagram on the device and in com- Weight (with remote sensor) ~280 g Temperature °C 28,0 18,0 28,0 18,0 28,0 15,0
pliance with all applicable safety regulations. To maintain
compliance with Protection Class II, user access to the rear
* For current > 14 A do not loop the N-wire through the Saturday and Sunday
of the device must be prevented... This device, is used to
control the temperature only in dry rooms, under normal controller, use a separate terminal. Events 1 2 3 4 5 6
environmental conditions. This electronic device conforms Time 8:00 10:00 12:00 14:00 19:00 22:00
to EN 60730, It is an “independently mounted control” and Temperature °C 28,0 18,0 28,0 18,0 28,0 15,0
works according to operating principle 1C. 7 Wiring Diagram / Dimensions
28
27
26
25
24
23
3 Use 22
21
The electronic Floor Temperature Controller FIT 3F can be 20
used to control the floor temperature in conjunction with: 19
18
• direct floor heating 17
16 Mon - Fri
• floor temperature conditioning systems Sat - Sun
15
14
6:00 h 8:00 h 10:00 h 12:00 h 14:00 h 16:00 h 18:00 h 20:00 h 22:00 h

4 Features
• One line text display for simplified operation Program 3
• Back light (off, continuous, temporary after key pres) Monday to Friday
• Real time clock (setting of year, month, day, time) Events 1 2 3
Time 11:00 13:00 22:00
• Automatic Summer- Wintertime change over
Temperature °C 28,0 18,0 15,0
• Max 9 events per day (each day individually)
• Pre-set and adjustable programs Saturday and Sunday
• Optimum-Start 230V~ 50Hz Events 1 2 3 4
N
Time 8:00 10:00 19:00 22:00
• Arm chair programming (with removed display unit) L
Temperature °C 28,0 18,0 28,0 15,0
• OFF-Function, Key V to be pressed for 10 sec
• Holiday-Mode (date from – until can be set) 28
Load 27
• Timer (Party) specific temperature for some hours 26
25
• Energy consumption display (heating on time * cost) for last
24
2 days, -week, -month, -year 23
22
• Energy cost per hour adjustable
21
• Frost protection 20

• Range limits for adjusting max and min temperature N N L 19


18
• Access protection 17
16 Mon - Fri
• Operating language can be selected 15
Sat - Sun

• Control mode PWM or ON/OFF 14


Sensor 6:00 h 8:00 h 10:00 h 12:00 h 14:00 h 16:00 h 18:00 h 20:00 h 22:00 h
• Floor temperature can be read as number
Notes for Programming
Electric connection • Activated settings terminate automatically 3 Min after the
Caution! last key press, without saving. They return to the mode
Caution: disconnect electric circuit from supply which was active before entering the settings like AUTO,
Maximum length
MAN, etc.
of removed cable
Connecting according to Wiring Diagram • Entering a Code: change value with + – key then press OK
insulation 8 mm.
For solid wires 1 - 2,5mm2 • When going through User- or Installer settings the item
number used in the manual will be displayed, e.g. G1 for
"Program select one" or H2 for "Control Mode".
5. Mounting • There can be gaps in the sequence of numbers
The controller should be mounted in a location of the room
that is easily accessible for operation purposes. To insert or remove a Troubleshooting
flexible wire press pin 1. It is getting warm too late:
Fitting a. Are clock and program events set correctly?
b. Is the Optimum Start switched on? see H7
in a conduit box Ø 60 mm Did the controller have enough time (some days) to
• remove the display unit adapt to the room’s characteristics?
• remove the frame c. Is change between Summer-and Wintertime activated,
• Mount it following the reverse see G5
procedure 2. The controller does not accept any changes
Is the access protection switched on? see G6
Caution! The plastic tab must be in place 3. The range of temperature setting is limited.
Mounting in plastic wall boxes to provide insulation between the Are temperature limits set? See G7
only terminals/wires and the mount- 4. Temperature display don‘t change.
ing screw. Is display of set-temperature activated? See G10
9 Description of Functions and Operation 11. Batteries
How the FIT Temperature Controller can be used In compliance with the EU Directive
Change temperature until next switching event Set temperature for a specific date 2006/66/EC, the button cell battery located on
see keys, + – in AUTO see main menu, HOLIDAY the printed circuit board inside this product,
Controlling the temperature according to pre-set profiles Use a separate program for special days can be removed at the end of the product life,
see main menu, AUTO see main menu, AT-HOME by professional personnel only.
Set a constant temperature (manual operation) Adjust the controller to personal needs
see main menu, MAN see main menu, USER-SETTINGS
Set temperature for a number of hours Adjust the controller to application needs
see main menu, TIMER see main menu, INSTALLER-SETTINGS


Keys to confirm / activate

+ – in AUTO (-) Set temperature temporarily until next switching event. OK


Indication by "-" behind AUTO-. First key-press shows set value, following
ones change it.

+ – in menu Scroll through the menu

OK Accepts modification / selection

Info Show related details in AUTO, MAN, TIMER, HOLIDAY, AT-HOME. To cancel press key again

Menu Enter menus. + – Key to move

V Go one step back

V for 10 sec Switch off connected load. Display reads OFF. Details see G4


Main Menu to confirm / activate

A MENU Use + – in order to walk through the menu

B AUTO The temperature will be controlled automatically according to the time and temperature of the selected OK
program, see G1. Use + – keys to change temperature until next switching event.

C MAN The temperature will be controlled continuously according to the temperature set in this menu. OK
Use + – key to change temperature

D TIMER The temperature will be controlled temporarily according to the hours and temperature set in this menu. OK
On termination, AUTO will be re-started. HOLIDAY will be terminated.

E HOLIDAY The temperature will be controlled for the period of days and the temperature set in this menu. OK
Holiday starts at 0h of the first day, it ends at 24h of the last day, then going to AUTO.
In the period of time before HOL starts, AUTO will be active. TIMER will be terminated.
During this AUTO period of time, Temp can not be changed.

F AT HOME The temperature will be controlled automatically according to the time and temperature of the program OK
adjusted here (independent from AUTO). The program is the same for all days.
Pre-set is the program of Monday.
It needs to be terminated by user, e.g, by selecting AUTO. Usage: for holiday at home, illness etc.

G USER SETTINGS Customise the controller according to personal needs OK

H INSTALLER SETTINGS Customise the controller according to application needs (from installer only) OK

G USER Customise the controller according to personal needs default


SETTINGS

1 Program select Select one of the pre-defined programs, see 8. P1


(If another program is chosen, settings will not be saved)

2 Event Setting Modify Time and Temperature of active program, see 8. as


Each event can be reduced to the previous one or to 00:00h selected
Each event can be extended up to 23:50h, then ->>> is indicating that the event is in the next day. at G1
By pressing + or – key at ->>> a time can be adjusted. Max 9 events are possible.
The first digit indicates the actual event e.g. 3.12:00- 14:00 shows event 3.
Events can be set for day-blocks as well, when selecting days (Mon...Fri, Sat/Sun, Mon...Sun)
In order to finish programming, press V repeatedly.

3 Clock Settings Set Date and Time

4 Off Heating Switch off the heater, the controller remains on power. Display reading OFF. NO
Permanent Frost protection may happen if selected. See H6.
Switching ON again by activating e.g. AUTO or by pressing key V for 10 Sec.
When re-activating via key V or this menu, AUTO will be activated.

5 Summer/Winter time Select if automatic Summer/Winter-Time changeover YES


change over

6 Key Lock Protect controller against unauthorised use. Re-activate via code = 93 NO

7 Temperature limits Limits the temperature which can be set by the user, If both values are the same, no adjustment is 10; 40°C
min/max possible. This affects to AUTO, MAN, HOL, TIMER, AT-HOME, Programming.
The active program / mode will not be affected automatically.

8 Cost/Hr for Energy The assumed energy cost per hour (in cent/h) can be set. 10

9 Energy consumption Shows the approximate energy cost of the controlled area.
to date For the last: 2 days, week (7 days), month (30 days), year (365 days).
On the actual day, calculation is up to current time. In case of overflow 9999 will be displayed.

Calculation: On-Time of heater x cost per hour see above. Reset see H9

10 Set temperature to read Show set temperature instead of floor temperature NO

12 Number for floor Read the floor temperature as number. NO


temperature Instead of a temperature in °C a number will be displayed e.g. instead of 28,5 °C, 285 can be read.

13 Backlight Continuously ON, Continuously OFF, temporarily illuminates after key press SHORT

14 Language Select preferred operating language

15 Info Displays Controller-type and -version.

16 Reset user settings Only USER SETTINGS will be set to factory settings NO
only The energy counter will not be re-set; to do this see H9)

Change INSTALLER SETTINGS

CAUTION!
These settings should only be set-up by a qualified person. They can influence safety and the proper functioning of the system.

H INSTALLER Customise the controller according application needs (by installer only) default
SETTINGS
0 Code Enter Code (= 7) in order to access the menus. It is valid for 1 Hour

1 Application For this heating system the controller is suitable FLOOR

2 Control Mode PWM or ON/OFF can be selected. In case of PWM, the cycle Time can be set (in Minutes). PWM/10
Use short time for fast and longer time for slow reacting heating systems

6 Frost protection Set frost protection temperature. In OFF mode only, the Temperature will be controlled to that value. 10 °C

7 Optimum Start The set temperature will be reached at the time specified in the program. NO
During pre-heating time, AUTO_ will be displayd

9 Energy Counter Reset The energy counter will be set to 0 NO

11 Reset all All INSTALLER and USER settings will be set to its Factory setting NO

10. Error Indication


In case of errors, "Err" is blinking. The following errors can be displayed:

CONFIGURATION Display- and powermodule do not fit EXT SENSOR 1. Error of external sensor
g use only suitable parts g remove sensor
g switch off and on power supply 2. Over- or under run of valid display range
COMMUNICATION Communication between display- and power unit fails
g unplug and re-plug display unit
g switch off and on power supply

On all these errors, the relay will be off.