node-red-contrib-s7 3.1.0
A Node-RED node to interact with Siemens S7 PLCs
npm install node-red-contrib-s7
A Node-RED node to interact with Siemens S7 PLCs.
This node was created as part of the ST-One project.
Install
You can install this node directly from the "Manage Palette" menu in the Node-RED interface.
Alternatively, run the following command in your Node-RED user directory - typically ~/.node-red on
Linux or %HOMEPATH%\.nodered on Windows
npm install node-red-contrib-s7
NodeJS version 10 or greater and Node-RED version 1.0 or greater is required.
Usage
Each connection to a PLC is represented by the S7 Endpoint configuration node. You can configure the
PLC's Address, the variables available and their addresses, and the cycle time for reading the variables.
The S7 In node makes the variable's values available in a flow in three different modes:
Single variable: A single variable can be selected from the configured variables, and a message is sent
every cycle, or only when it changes if diff is checked. msg.payload contains the variable's value and
msg.topic has the variable's name.
All variables, one per message: Like the Single variable mode, but for all variables configured. If diff
is checked, a message is sent everytime any variable changes. If diff is unchecked, one message is sent
for every variable, in every cycle. Care must be taken about the number of messages per second in this
mode.
All variables: In this mode, msg.payload contains an object with all configured variables and their
values. If diff is checked, a message is sent if at least one of the variables changes its value.
Variable addressing
The variables and their addresses configured on the S7 Endpoint follow a slightly different scheme than
used on Step 7 or TIA Portal. Here are some examples that may guide you on addressing your variables:
https://flows.nodered.org/node/node-red-contrib-s7 1/6
14/3/23, 11:08 node-red-contrib-s7 (node) - Node-RED
Step7 JS Data
Address Description
equivalent type
DB5,X0.1 DB5.DBX0.1 Boolean Bit 1 of byte 0 of DB 5
DB23,B1 or
DB23.DBB1 Number Byte 1 (0-255) of DB 23
DB23,BYTE1
DB100,C2 or
DB100.DBB2 String Byte 2 of DB 100 as a Char
DB100,CHAR2
DB42,I3 or
DB42.DBW3 Number Signed 16-bit number at byte 3 of DB 42
DB42,INT3
DB57,WORD4 DB57.DBW4 Number Unsigned 16-bit number at byte 4 of DB 57
DB13,DI5 or
DB13.DBD5 Number Signed 32-bit number at byte 5 of DB 13
DB13,DINT5
DB19,DW6 or
DB19.DBD6 Number Unsigned 32-bit number at byte 6 of DB 19
DB19,DWORD6
DB21,R7 or
DB21.DBD7 Number Floating point 32-bit number at byte 7 of DB 21
DB21,REAL7
DB2,S7.10* - String String of length 10 starting at byte 7 of DB 2
I1.0 or E1.0 I1.0 or E1.0 Boolean Bit 0 of byte 1 of input area
Q2.1 or A2.1 Q2.1 or A2.1 Boolean Bit 1 of byte 2 of output area
M3.2 M3.2 Boolean Bit 2 of byte 3 of memory area
IB4 or EB4 IB4 or EB4 Number Byte 4 (0 -255) of input area
QB5 or AB5 QB5 or AB5 Number Byte 5 (0 -255) of output area
MB6 MB6 Number Byte 6 (0 -255) of memory area
IC7 or EC7 IB7 or EB7 String Byte 7 of input area as a Char
QC8 or AC8 QB8 or AB8 String Byte 8 of output area as a Char
MC9 MB9 String Byte 9 of memory area as a Char
II10 or EI10 IW10 or EW10 Number Signed 16-bit number at byte 10 of input area
QI12 or AI12 QW12 or AW12 Number Signed 16-bit number at byte 12 of output area
MI14 MW14 Number Signed 16-bit number at byte 14 of memory area
IW16 or EW16 IW16 or EW16 Number Unsigned 16-bit number at byte 16 of input area
QW18 or AW18 QW18 or AW18 Number Unsigned 16-bit number at byte 18 of output area
MW20 MW20 Number Unsigned 16-bit number at byte 20 of memory area
IDI22 or EDI22 ID22 or ED22 Number Signed 32-bit number at byte 22 of input area
QDI24 or ADI24 QD24 or AD24 Number Signed 32-bit number at byte 24 of output area
MDI26 MD26 Number Signed 32-bit number at byte 26 of memory area
ID28 or ED28 ID28 or ED28 Number Unsigned 32-bit number at byte 28 of input area
QD30 or AD30 QD30 or AD30 Number Unsigned 32-bit number at byte 30 of output area
MD32 MD32 Number Unsigned 32-bit number at byte 32 of memory area
IR34 or ER34 IR34 or ER34 Number Floating point 32-bit number at byte 34 of input area
QR36 or AR36 QR36 or AR36 Number Floating point 32-bit number at byte 36 of output area
MR38 MR38 Number Floating point 32-bit number at byte 38 of memory area
DB1,DT0 - Date** A timestamp in the DATE_AND_TIME format
DB1,DTZ10 - Date** A timestamp in the DATE_AND_TIME format, in UTC
DB2,DTL2 - Date** A timestamp in the DTL format
DB2,DTLZ12 - Date** A timestamp in the DTL format, in UTC
Unsigned 16-bit number at byte 4 of DB 57, interpreted as
DB57,RWORD4 DB57.DBW4 Number
Little-Endian
DB13,RDI5 or Signed 32-bit number at byte 5 of DB 13, interpreted as
DB13.DBD5 Number
DB13,RDINT5 Little-Endian
https://flows.nodered.org/node/node-red-contrib-s7 2/6
14/3/23, 11:08 node-red-contrib-s7 (node) - Node-RED
Step7 JS Data
Address Description
equivalent type
Unsigned 16-bit number at byte 20 of memory area,
MRW20 MW20 Number
interpreted as Little-Endian
*) Note that strings on the PLC uses 2 extra bytes at start for size/length of the string
**) Note that javascript's Date are always represented in UTC. Please use other nodes like node-red-
contrib-moment to properly handle type conversions
Notes on S7-1200/1500
These newer PLCs offer an "extended" version of the S7 Protocol, while we have only a "basic" version of it.
Therefore, some additional configuration steps on the PLC are necessary:
"Optimized block access" must be disabled for the DBs we want to access (image)
In the "Protection" section of the CPU Properties, enable the "Permit access with PUT/GET" checkbox
(image)
Notes on Logo! 8
On the newest Logo! 8.FS4 (and possibly 0BA8) Logic modules there is no need to set the Mode to TSAP
any more, instead the default Rack/Slot value of 0/2 works just fine.
The following table shows memory areas accessible without additional settings in the controller program:
Note: These memory areas seem to be read-only from outside the controller, as they are directly used by the
function blocks listed in "Logo Block" of the table
Logo Logo VM
example Node-RED address Description
Block Range
DB1,BYTE1024 or DB1,X1024.5 or
I 1024 - 1031 Reads input terminals 1...8 or 6 or 1...16
DB1,WORD1024
Reads analog input terminal 1. Always
AI 1032 - 1063 DB1,WORD1032
word sized.
DB1,BYTE1064 or DB1,X1064.5 or
Q 1064 - 1071 Reads output terminals 1...8 or 6 or 1...16
DB1,WORD1064
Reads analog output terminal 1. Always
AQ 1072 - 1103 DB1,WORD1072
word sized.
DB1,BYTE1104 or DB1,X1104.5 or
M 1104 - 1117 Reads bit flags M1...M8 or M6 or M1...16
DB1,WORD1104
AM 1118 - 1245 DB1,WORD1118 Reads analog flag 1. Always word sized.
DB1,BYTE1246 or DB1,X1246.5 or
NI 1246 - 1061 Reads network input 1...8 or 6 or 1...16
DB1,WORD1246
Reads analog network input 1. Always
NAI 1262 - 1389 DB1,WORD1262
word sized.
DB1,BYTE1390 or DB1,X1390.5 or
NQ 1390 - 1405 Reads network output 1...8 or 6 or 1...16
DB1,WORD1390
Reads network output 1. Always word
NAQ 1406 - 1469 DB1,WORD1406
sized.
On the other hand, Logo memory areas VM 0-849 are mutable from outside the controller, but they need to
be mapped into the Logo program. Without mapping, data written into these addresses will have no effect on
program execution. Used VM addresses in the range mentioned above can be read/written from/into in the
https://flows.nodered.org/node/node-red-contrib-s7 3/6
14/3/23, 11:08 node-red-contrib-s7 (node) - Node-RED
Logo program using the "Network" function blocks (in the function block setup use the "Local variable
memory (VM)" option to map VMs to the function block).
Some addressing examples:
Logo VM Example Node-RED address Description
0 DB1,BYTE0 R/W access
1 DB1,X1.3 R/W access Note: use booleans
2..3 DB1,WORD2 R/W access
4..7 DB1,DWORD4 R/W access
Bugs and enhancements
Please share your ideas and experiences on the Node-RED forum, or open an issue on the page of the project
on GitHub
Support
Community support is offered on a best-effort basis via GitHub Issues. For commercial support, please
contact us by sending an e-mail to [email protected].
License
Copyright: (c) 2016-2022, ST-One Ltda., Guilherme Francescon Cittolin [email protected]
GNU General Public License v3.0+ (see LICENSE or https://www.gnu.org/licenses/gpl-3.0.txt)
Node Info
Version: 3.1.0
Updated 1 year, 2 months ago
License: GPL-3.0-or-later
Rating: 4.5 20
View on npm
View on GitHub
View Scorecard 84
Actions
Rate:
Downloads
982 in the last week
Nodes
s7 endpoint
s7 in
s7 out
s7 control
https://flows.nodered.org/node/node-red-contrib-s7 4/6
14/3/23, 11:08 node-red-contrib-s7 (node) - Node-RED
Keywords
hardware
s7
logo
siemens
plc
profinet
node-red
Maintainers
daniel.michalichyn
gfcittolin
machadotiago
Report this module
If you have a concern about the contents of this module, please let us know. For example, if you believe it
contains unsuitable or inappropriate material.
This is not a way to get help with this module. For that, please contact its maintainers directly or post to
the Node-RED Forum.
Please provide some details about the module:
Cancel Report
Node-RED: Low-code programming for event-driven applications.
GitHub
npm
Documentation
APIs
Flow Library
About
Code of Conduct
Community
Blog
Twitter
Forum
Slack
https://flows.nodered.org/node/node-red-contrib-s7 5/6
14/3/23, 11:08 node-red-contrib-s7 (node) - Node-RED
Copyright OpenJS Foundation and Node-RED contributors. All rights reserved. The OpenJS Foundation has
registered trademarks and uses trademarks. For a list of trademarks of the OpenJS Foundation, please see our
Trademark Policy and Trademark List. Trademarks and logos not indicated on the list of OpenJS Foundation
trademarks are trademarks™ or registered® trademarks of their respective holders. Use of them does not
imply any affiliation with or endorsement by them.
The OpenJS Foundation | Terms of Use | Privacy Policy | OpenJS Foundation Bylaws | Trademark Policy |
Trademark List | Cookie Policy | Cookie Settings
https://flows.nodered.org/node/node-red-contrib-s7 6/6