Chapter 2 Two Way Slab
Chapter 2 Two Way Slab
Bedar R.Hassan
Halabja University
Bedar R.Hassan
Civil Engineering Department
• 1. Introduction:
• Slabs are supported in such a way that two-way action results.
• When loaded, at any point the slab is curved in both principal directions.
• Moments also exist in both directions.
• To resist these moments, the slab must be reinforced in both directions.
1
10/8/2024
• This result is approximate because the actual behavior of a slab is more complex
than that of the two intersecting strips.
• Because the moments in the long direction are the smaller ones, it is economical to
place the steel in that direction on top of the bars in the short direction.
• The total load on the slab is carried not only by the bending moments in two
directions but also by the twisting moments.
2
10/8/2024
3
10/8/2024
• 2. Design of slabs with beams in all sides (Direct design method DDM):
• Is the semi-empirical method used for design of Two-way slabs based on ACI
code.
• Procedure: Assume thickness of the slab (150mm-220mm)
• 1. Conditions:
• Moments in two-way slabs can be found using the semiempirical direct design
method, subject to the following restrictions:
• A. There must be a minimum of three continuous spans in each direction.
• B. The panels must be rectangular and L/B< 2.
• C. The successive span lengths in each direction must not differ by more than one
third of the longer span.
• D. Columns may be offset a maximum of 10 percent of the span in the direction of
the offset from either axis between centerlines of successive columns.
• E. Loads must be due to gravity only, and the unfactored LL ≤ 2 unfactored DL.
• F. If beams are used on the column lines, the relative stiffness of the beams in the
two perpendicular directions;
𝛼𝑓1 𝑙22 𝐸𝑐𝑏 𝐼𝑏
• 0.2 ≤ ≤5 𝛼𝑓 =
𝛼𝑓2 𝑙12 𝐸𝑐𝑠 𝐼𝑠
• Where:
• 𝑙1 is defined as the span in the direction of the moment analysis.
• 𝑙2 is the span in the lateral direction measured center to center of the support.
• αf is the relative stiffness of the beams and slabs.
• Ecb and Ecs are the moduli of elasticity of the beam and slab concrete.
• Ib and Is are the moments of inertia of the effective beam and the slab.
• Subscripted parameters αf1 and αf2 are used to identify α computed for the
directions of ℓ 1 and ℓ 2.
• Note: The flexural stiffnesses of the beam and slab may be based on the gross
concrete section, neglecting reinforcement and possible cracking, and variations
due to column capitals and drop panels may be neglected.
4
10/8/2024
• For exact calculation of moment of inertia of the beam: Two methods are
applicable:
• First (ACI 8.4.1.8): In the case of monolithic construction, beams are defined to
include that part of the slab on each side of the beam extending a distance equal to
the projection of the beam above or below the slab h w (whichever is greater) but
not greater than 4 times the slab thickness
• Second: By using Simplified method
𝑏ℎ3
• 𝐼𝐿−𝑏𝑒𝑎𝑚 = 1.5
12
𝑏ℎ3
• 𝐼𝑇−𝑏𝑒𝑎𝑚 = 2.0
12
5
10/8/2024
6
10/8/2024
7
10/8/2024
8
10/8/2024
• 8. Summarize moments:
• Summarize moments in the critical locations, then determine the moments per one
meter length based on the width of C.S and M.S.
• 9. Check for minimum effective depth required for flexure:
𝑓𝑐′ 𝜀𝑢
• Assume 𝜌 = 𝜌0.005 = 0.85𝛽1 ( ) to ensure ∅ = 0.9
𝑓𝑦 𝜀𝑢 +0.005
𝑓𝑦
• Determine required (d): 𝑀𝑢 = ∅𝜌𝑏𝑑 2 𝑓𝑦 (1 − 0.59𝜌 ′ )
𝑓𝑐
• Must be: 𝑑𝑟𝑒𝑞. ≥ 𝑑𝑝𝑟𝑜𝑣𝑖𝑑𝑒
• 10. Determine required flexural reinforcement:
𝑓𝑦
• 𝑀𝑢 = ∅𝜌𝑏𝑑 2 𝑓𝑦 (1 − 0.59𝜌 ′ )
𝑓𝑐
• Note: For design of steel reinforcement of slabs taken average effective depth.
9
10/8/2024
350(500)3
• F. For Edge beam: 𝐼𝐸.𝐵𝑒𝑎𝑚 = 1.5 = 5.468 × 109 𝑚𝑚4
12
350(500)3
• For Interior beam: 𝐼𝐼.𝐵𝑒𝑎𝑚 = 2 = 7.291 × 109 𝑚𝑚4
12
• I for slab:
6000(200)3
• For 7.5m span: 𝐼𝑆 7.5𝑚 = = 4 × 109 𝑚𝑚4
12
• For 6m span:
7.5 0.35 3925(200)3
• Exterior face ( + = 3.925𝑚): 𝐼𝑆−𝐸 6𝑚 = = 2.616 × 109 𝑚𝑚4
2 2 12
7500(200)3
• Interior face: 𝐼𝑆−𝐼 6𝑚 = = 5 × 109 𝑚𝑚4
12
10
10/8/2024
𝐼𝑏 5.468
• 𝛼𝑓𝐴 = = = 2.09
𝐼𝑠 2.616
𝐼𝑏 7.291
• 𝛼𝑓𝐵 = = = 1.45
𝐼𝑠 5
𝐼𝑏 7.291
• 𝛼𝑓𝐶 = = = 1.82
𝐼𝑠 4
• May be moment analysis in two-directions:
• For span 6m:
2.09 7.52
• 0.2 ≤ = 1.79 ≤ 5
1.82 62
1.45 7.52
• 0.2 ≤ = 1.24 ≤ 5
1.82 62
• For span 7.5m:
1.82 62
• 0.2 ≤ = 0.55 ≤ 5
2.09 7.52
1.82 62
• 0.2 ≤ = 0.80 ≤ 5
1.45 7.52
11
10/8/2024
12
10/8/2024
13
10/8/2024
14
10/8/2024
15
10/8/2024
• Case (2):
𝑥 𝑥3𝑦
• 𝐶 = σ 1 − 0.63
𝑦 3
200 2003 (300) 350 3503 (500)
• 𝐶 = 1 − 0.63 + 1 − 0.63
300 3 500 3
• 𝐶 = 464,000,000 + 3,994,520,833 = 𝟒, 𝟒𝟓𝟖, 𝟓𝟐𝟎, 𝟖𝟑𝟑𝒎𝒎𝟒
6000(200)3
• 𝐼𝑆 7.5𝑚 = = 4 × 109 𝑚𝑚4
12
𝐸𝑐𝑏 𝐶 𝐶 4,458,520,833
• 𝛽𝑡 = = = 0.557
2𝐸𝑠𝑏 𝐼𝑆 2𝐼𝑆 7.5𝑚 2(4×109 )
• 0 ≤ 𝛽𝑡 ≤ 2.5 from Table:
𝑙 0.9−1 𝑥−1
• When ( 2 = 0.5): = →∴ 𝑥 = 0.97772
𝑙1 2.5−0 0.557−0
𝑙2 0.75−1 𝑦−1
• When ( = 1.0): = →∴ 𝑦 = 0.9443
𝑙1 2.5−0 0.557−0
𝑙2 0.9443−0.97772 𝐹𝑎𝑐𝑡𝑜𝑟−0.97772
• When ( = 0.8): = →∴ 𝐹𝑎𝑐𝑡𝑜𝑟 = 0.957
𝑙1 1.0−0.5 0.8−0.5
• C.S=0.957
• C.S=0.957(104.04)=99.56 kN.m
• C.S (Beam portion)=0.85(99.56)=84.62 kN.m
• C.S (Slab portion)=0.15(99.56)=14.93 kN.m
• M.S=1-0.957=0.043
• M.S=0.043(104.04)=4.47 kN.m
16
10/8/2024
17
10/8/2024
• 8. Summarize moments:
• For 6m span:
• *1.325m came from ((1.5m (C.S)-(0.35/2)=1.325m)
Mu(kN.m)/1
Face Location Moments Mu’ (kN.m) Width (m)
m length
Exterior Negative 17.48 1.325* 13.19
C.S
face Positive 9.42 1.325* 7.11
3.925m Negative 56.11 4.5/2=2.25 24.93
width M.S
Positive 30.21 4.5/2=2.25 13.42
Negative 33.4/2=16.7 1.325* 12.60
Interior C.S
Positive 17.98/2=8.99 1.325* 6.78
face 7.5m
width Negative 107.22/2=53.61 4.5/2=2.25 23.82
M.S
Positive 57.73/2=28.86 4.5/2=2.25 12.82
• 8. Summarize moments:
• For 7.5m span:
• **The design moments must be based on the slab width only without beams.
Mu(kN.m)/1m
Location Moments Mu’ (kN.m) Width (m)
length
Ext. Negative 14.93 5.63
3-
C.S Positive 45.03 16.99
0.35=2.65m
Int. Negative 55.30 20.86
Ext. Negative 4.47 1.49
M.S Positive 70.42 3 23.47
Int. Negative 86.48 28.82
18
10/8/2024
• For 6m span:
𝑓𝑦 420
•𝑚= = = 23.53 , 𝐴𝑠 (𝑚𝑖𝑛.) = 0.0018𝑏ℎ =360mm2
0.85𝑓𝑐′ 0.85(21)
• 𝐴𝑠 (𝑚𝑎𝑥.) = 0.0135 1000 168 = 2268𝑚𝑚2
• All of the reinforcement smaller than maximum reinforcement.
Face Location Moments Mu(kN.m)/1m length Ru As (mm2)
Exterior Negative 13.19 0.52 211.12
C.S
face Positive 7.11 0.28 112.89
3.925m Negative 24.93 0.98 403.39
width M.S
Positive 13.42 0.53 215.24
Interior Negative 12.60 0.49 198.76
C.S
face Positive 6.78 0.26 104.76
7.5m Negative 23.82 0.93 382.23
width M.S
Positive 12.82 0.50 202.88
19
10/8/2024
20
10/8/2024
• Critical sections shall be located so that the perimeter bo is a minimum, but need
not be closer than d/2 (For square or rectangular column, Edges or corners of
columns, concentrated loads, or reaction areas)
• Note: For a circular or regular polygon-shaped column, critical sections for two-
way shear in accordance with (a) and (b) shall be permitted to be defined
assuming a square column of equivalent area.
• Take dav for calculation.
21
10/8/2024
2
• Size Factor: 𝜆𝑠 = ≤1
1+0.004𝑑
• (d) shall be the average of the effective depths
in the two orthogonal directions.
• (β) is the ratio of long to short sides of the
column, concentrated load, or reaction area.
• Note: For shapes other than rectangular, β is
taken to be the ratio of the longest overall
dimension of the effective loaded area to the
largest overall perpendicular dimension of the
effective loaded area as shown.
• The value of αs is 40 for interior columns, 30
for edge columns, and 20 for corner columns.
22
10/8/2024
• Procedure:
• 1. Conditions:
• Moments in two-way slabs can be found using the semiempirical direct design
method, subject to the following restrictions:
• A. There must be a minimum of three continuous spans in each direction.
• B. The panels must be rectangular and L/B< 2.
• C. The successive span lengths in each direction must not differ by more than one
third of the longer span.
• D. Columns may be offset a maximum of 10 percent of the span in the direction of
the offset from either axis between centerlines of successive columns.
• E. Loads must be due to gravity only, and the unfactored LL ≤ 2 unfactored DL.
• F. Not included in the case of flat slabs and flat plate slabs.
23
10/8/2024
24
10/8/2024
25
10/8/2024
26
10/8/2024
• Example (2): An interior flat plate slab (190mm) for the structure with three equal
spans in each direction as shown in the Figure below; Design this panel of slab,
when the slab subjected to service live load 3.75 kN/m2 and a service dead load
equal to 5.25 kN/m2 (including slab weight). fy=420 MPa, and fc’=21 MPa
(Normal-weight concrete), and column heights of 3.6m. Use #12mm as flexural
bars.
• 1. Limitations:
• All conditions included in the case of example.
• 2. Find the thickness of the slab:
• Flat plate slab without beams, drop panels, and column capital.
• fy=420 MPa
𝑙𝑛 6000
•ℎ= = = 181.81𝑚𝑚 < 190𝑚𝑚 ; Also >125mm (OK)
33 33
• 3. Check for Shear:
• A. One-Way shear:
• 𝑤𝑢 = 1.2 5.25 + 1.6 3.75 = 12.3 kN/m2
12
• 𝑑𝑠ℎ𝑜𝑟𝑡 = 190 − 20 − = 164𝑚𝑚
2
4.8 0.3
• 𝑉𝑢 @𝑑 = 12.3 − − 0.164 = 25.65𝑘𝑁/𝑚
2 2
• ∅𝑉𝑐 = 0.17 1 21 1000 164 10−3 = 127.76𝑘𝑁 ≥ 𝑉𝑢 = 25.65𝑘𝑁
• ∴ The thickness is safe for shear.
27
10/8/2024
• B. Punching Shear:
• 𝑑𝑎𝑣. = 190 − 20 − 12 = 158𝑚𝑚
158 158 158 158
• 𝑏° = 2 300 + + + 2 400 + + = 2032mm
2 2 2 2
158 158 158 158
• 𝑉𝑢 = 12.3 (6 × 4.8) − ( 300 + + × 400 + + × 10−6 ) =
2 2 2 2
352.22𝑘𝑁
2
• 𝜆𝑠 = = 1.1 ≤ 1
1+0.004(158)
2
𝑞𝑢 𝑙2 𝑙𝑛
• 4. Ultimate static moments: 𝑀° =
8
• For span 6m and width (4.8m): 6-0.4=5.6m>(0.65×6m=3.9m)
12.3(4.8)5.62
• 𝑀° = = 231.44𝑘𝑁. 𝑚
8
• For span 4.8m and width (6m): 4.8-0.3=4.5m>(0.65×6m=3.9m)
12.3(6)4.52
• 𝑀° = = 186.81𝑘𝑁. 𝑚
8
• 5. Assignment of Moments to Critical Sections:
• For span 6m with width (4.8m): Interior span
• -M=0.65(231.44)=150.44 kN.m
• +M= 0.35(231.44)=81 kN.m
• For span 4.8m with width (6m): Interior span
• -M=0.65(186.81)=121.43 kN.m
• +M= 0.35(186.81)=65.38 kN.m
28
10/8/2024
• For span 4.8m (6m width): • For span 4.8m (6m width):
• -M=0.65(186.81)=121.43 kN.m • +M= 0.35(186.81)=65.38 kN.m
𝑙2 6 𝑙2 𝑙2 6 𝑙2
• = = 1.25 and 𝛼𝑓𝐵 =0 • = = 1.25 and 𝛼𝑓𝐵 =0
𝑙1 4.8 𝑙1 𝑙1 4.8 𝑙1
• C.S=0.75(121.43)=91.07kN.m • C.S=0.6(65.38)=39.23kN.m
• M.S=121.43-91.07=30.36 kN.m • M.S=65.38-39.23=26.15 kN.m
29
10/8/2024
• 8. Summarize moments:
Mu(kN.m)/1
Face Location Moments Mu’ (kN.m) Width (m)
m length
Negative 112.83/2=56.42 1.2 47.01
6m span C.S
Positive 48.6/2=24.3 1.2 20.25
with 4.8m
width Negative 37.61/2=18.81 1.2 15.67
M.S
Positive 32.4/2=16.2 1.2 13.5
4.8m span Negative 91.07/2=45.54 1.2 37.95
C.S
with 6m Positive 39.23/2=19.62 1.2 16.35
width Negative 30.36/2=15.18 1.8 8.43
M.S
Positive 26.15/2=13.08 1.8 7.26
30
10/8/2024
31
10/8/2024
32
10/8/2024
• Procedure:
• 1. Conditions:
• Moments in two-way slabs can be found using the semiempirical direct design
method, subject to the following restrictions:
• A. There must be a minimum of three continuous spans in each direction.
• B. The panels must be rectangular and L/B< 2.
• C. The successive span lengths in each direction must not differ by more than one
third of the longer span.
• D. Columns may be offset a maximum of 10 percent of the span in the direction of
the offset from either axis between centerlines of successive columns.
• E. Loads must be due to gravity only, and the unfactored LL ≤ 2 unfactored DL.
• F. Not included in the case of flat slabs and flat plate slabs.
33
10/8/2024
• A depth of the drop panel in a non-prestressed slab shall not less than 0.25hslab ,
and The drop panel shall extend in each direction from the centerline of support a
distance not less than one-sixth the span length measured from center-to-center of
supports in that direction.
• A shear cap, where used to increase the critical section for shear at a slab-column
joint, shall project below the slab soffit and extend horizontally from the face of
the column a distance at least equal to the thickness of the projection below the
slab soffit.
• 3. Check for One way and two ways shear:
• Based on the previous procedure.
• 4. Total static ultimate moments:
2
𝑞𝑢 𝑙2 𝑙𝑛
• 𝑀° =
8
• Note: The clear span is defined to extend from face to face of the columns,
capitals, brackets, or walls but is not to be less than 0.65ℓlong span C/C.
34
10/8/2024
35
10/8/2024
36
10/8/2024
37
10/8/2024
• Example(3):Design a
typical 7.2m × 6m interior
flat-slab panel with drop
panels only as shown in
Figure below. All panels are
supported by 500mm
square columns, 3.6m long.
The slab carries a uniform
service live load of 3.8
kN/m2 and a service dead
load of 1.15 kN/m2,
excluding self-weight. Use
fc’= 28 MPa and fy =400
MPa. Assume γconcrete=24
kN/m3. use #10mm as
flexural reinforcement.
38
10/8/2024
• B. Punching Shear:
• For edge of drop panel:
• 𝑑𝑎𝑣.−𝑠𝑙𝑎𝑏 = 200 − 20 − 10 = 170𝑚𝑚
170 170 170 170
• 𝑏° = 2 2400 + + + 2 2000 + + = 9480mm
2 2 2 2
−6
• 𝑉𝑢 = 13.38 (7.2 × 6) − ( 2570 × 2170 × 10 )
• 𝑉𝑢 = 503.39𝑘𝑁
2
• 𝜆𝑠 = = 1.09 ≤ 1
1+0.004(170)
2400
• αs is 40 for interior columns and 𝛽 = = 1.2
2000
−3
• 𝑉𝑐1 = 0.33 1 1 28 9480 170 10 = 2814.17𝑘𝑁
0.33
• 𝑉𝑐2 = 0.17 + 1 1 28 9480 170 10−3 = 3794.86𝑘𝑁
1.2
0.083 40 170
• 𝑉𝑐3 = 0.17 + 1 1 28 9480 170 10−3 = 1957.43𝑘𝑁 > 𝑉𝑢
9480
39
10/8/2024
• B. Punching Shear:
• For edge of column:
• 𝑑𝑎𝑣.−𝑠𝑙𝑎𝑏 = 250 − 20 − 10 = 220𝑚𝑚
• 𝑏° = 4 500 + 220 = 2880mm
• 𝑉𝑢 = 13.38 (7.2 × 6) − ( 720 × 720 × 10−6 )
• 𝑉𝑢 = 571.08𝑘𝑁
2
• 𝜆𝑠 = = 1.06 ≤ 1
1+0.004(220)
720
• αs is 40 for interior columns and 𝛽 = =1
720
−3
• 𝑉𝑐1 = 0.33 1 1 28 2880 220 10 = 1106.39𝑘𝑁 > 𝑉𝑢
0.33
• 𝑉𝑐2 = 0.17 + 1 1 28 2880 220 10−3 = 1676.35𝑘𝑁
1
0.083 40 220
• 𝑉𝑐3 = 0.17 + 1 1 28 2880 220 10−3 = 1420.24𝑘𝑁
2880
2
𝑞𝑢 𝑙2 𝑙𝑛
• 4. Ultimate static moments: 𝑀° =
8
• For span 7.2m and width (6m): 7.2-0.5=6.7m>(0.65×7.2m=4.68m)
13.38(6)6.72
• 𝑀° = = 450.47𝑘𝑁. 𝑚
8
• For span 6m and width (7.2m): 6-0.5=5.5m>(0.65×7.2m=4.68m)
13.38(7.2)5.52
• 𝑀° = = 364.27𝑘𝑁. 𝑚
8
• 5. Assignment of Moments to Critical Sections:
• For span 7.2m with width (6m): Interior span
• -M=0.65(450.47)=292.81 kN.m
• +M= 0.35(450.47)=155.61 kN.m
• For span 6m with width (7.2m): Interior span
• -M=0.65(364.27)=236.78 kN.m
• +M= 0.35(364.27)=127.49 kN.m
40
10/8/2024
41
10/8/2024
• 8. Summarize moments:
Mu(kN.m)/1
Face Location Moments Mu’ (kN.m) Width (m)
m length
Negative 219.61/2=109.81 1.5 73.21
7.2m span C.S
Positive 93.37/2=46.69 1.5 31.13
with 6m
width Negative 73.2/2=36.3 1.5 24.2
M.S
Positive 62.24/2=31.12 1.5 20.75
6m span Negative 177.59/2=88.8 1.5 59.2
C.S
with 7.2m Positive 76.49/2=38.25 1.5 25.5
width Negative 59.2/2=29.6 2.1 14.1
M.S
Positive 51/2=25.5 2.1 12.14
42
10/8/2024
43
10/8/2024
• Termination of reinforcement:
• Where a slab is supported on spandrel beams, columns, or walls, anchorage of
reinforcement perpendicular to a discontinuous edge shall satisfy (a) and (b):
• (a) Positive moment reinforcement shall extend to the edge of slab and have embedment,
straight or hooked, at least 150 mm into spandrel beams, columns, or walls
• (b) Negative moment reinforcement shall be bent, hooked, or otherwise anchored into
spandrel beams, columns, or walls, and shall be developed at the face of support
• Where a slab is not supported by a spandrel beam or wall at a discontinuous edge, or
where a slab cantilevers beyond the support, anchorage of reinforcement shall be
permitted within the slab.
• Termination of reinforcement:
• For slabs without beams:
• (a) Reinforcement lengths shall
be at least in accordance with
Figure, and if slabs act as
primary members resisting
lateral loads, reinforcement
lengths shall be at least those
required by analysis.
• (b) If adjacent spans are
unequal, extensions of negative
steel beyond the face of support
shall be based on the longer
span.
• (c) Bent bars permitted only
where the depth-to-span ratio
permits use of bends of 45
degrees or less.
44
10/8/2024
• For two-way slabs with stirrups, the maximum value of Vc is taken as following
equation, because the reinforcement resist all the shear beyond that at inclined
cracking (which occurs at approximately half the capacity of a slab without shear
reinforcement (that is, 𝑉𝑐 = 0.5 × 0.33𝜆𝜆𝑠 𝑓𝑐′ 𝑏° 𝑑):
• 𝑉𝑐 = 0.17𝜆𝜆𝑠 𝑓𝑐′ 𝑏° 𝑑
𝑉𝑢 −∅𝑉𝑐
• 𝑉𝑠 = ≤ 𝑉𝑠 = 0.25 𝑓𝑐′ 𝑏° 𝑑
∅
• 𝑉𝑠 = 𝐴𝑣 𝑓𝑦 sin 𝜃
• With bars bent at 45 °, the next critical section is approximately 3/4 times the
effective depth, past the first critical section as shown.
45
10/8/2024
• Example (4): A flat plate floor has thickness h = 190mm and is supported by
450mm square columns spaced 6m on centers each way. The floor will carry a
total factored load of 14kN/m2. Check the adequacy of the slab in resisting
punching shear at a typical interior column, and provide shear reinforcement, if
needed, using bent-bar reinforcement. An average effective depth d = 150mm may
be used. Material strengths are fy = 420 MPa and fc’ = 28 MPa (Normal Concrete).
𝑑
• = 75𝑚𝑚; 𝑏° = 4 450 + 75 + 75 = 2400𝑚𝑚
2
• 𝑉𝑢 = 14 62 − 0.62 = 498.96𝑘𝑁
2 2 450
• 𝜆𝑠 = = = 1.12 ≤ 1 𝛽= = 1 and 𝛼𝑠 = 40
1+0.004𝑑 1+0.004(150) 450
• ∅𝑉𝑐 = ∅0.33𝜆𝜆𝑠 𝑓𝑐′ 𝑏𝜊 𝑑 = 0.75 × 0.33 28 2400 150 10−3 = 𝟒𝟕𝟏. 𝟒𝟕𝒌𝑵
0.33
• ∅𝑉𝑐 = ∅ 0.17 + 𝜆𝜆𝑠 𝑓𝑐′ 𝑏𝜊 𝑑
𝛽
0.33
• ∅𝑉𝑐 = 0.75 × 0.17 + 28 2400 150 10−3 = 714.35𝑘𝑁
1
0.083𝛼𝑠 𝑑
• ∅𝑉𝑐 = ∅(0.17 + )𝜆𝜆𝑠 𝑓𝑐′ 𝑏𝜊 𝑑
𝑏𝜊
0.083 40 150
• ∅𝑉𝑐 = 0.75 × 0.17 + 28 2400 150 10−3 = 539.34𝑘𝑁
2400
• The thickness is not adequate for punching shear and shear reinforcement is
required.
• Bars bent at 45° will be used in two directions. When shear strength is provided by
a combination of reinforcement and concrete, the concrete contribution is reduced
to (𝑉𝑐 = 0.17𝜆𝜆𝑠 𝑓𝑐′ 𝑏° 𝑑):
• ∅𝑉𝑐 = ∅0.17𝜆𝜆𝑠 𝑓𝑐′ 𝑏° 𝑑 = 0.75 × 0.17 28 2400 150 10−3 = 242.88𝑘𝑁
498.96−242.88
• 𝑉𝑠 = = 341.44𝑘𝑁 ≤ 0.25 𝑓𝑐′ 𝑏° 𝑑 = 0.25 28
0.75
2400 150 10−3 =476.24kN
46
10/8/2024
• 𝑉𝑠 = 𝐴𝑣 𝑓𝑦 sin 𝜃
341.44(103 )
• 𝐴𝑣 = = 1149.86𝑚𝑚2
420(0.707)
• A total of four bars will be used (two in each direction), and with eight legs
• 1149.86Τ8 = 143.73𝑚𝑚2
• So, use #16mm as bent bar.
3
• 𝑑 = 0.75 150 = 112.5𝑚𝑚
4
• 𝑏° = 4 825 = 3300𝑚𝑚
• 𝑉𝑢 = 14 62 − 0.8252 = 494.47𝑘𝑁
• ∅𝑉𝑐 = ∅0.33𝜆𝜆𝑠 𝑓𝑐′ 𝑏𝜊 𝑑
• ∅𝑉𝑐 = 0.75 × 0.33 28 3300 150 10−3 = 648.28𝑘𝑁 > 𝑉𝑢
• Confirming that no additional bent bars are needed.
• The No. 16 bars will be extended along the bottom of the slab the full
development length.
47
10/8/2024
48
10/8/2024
• Example (5): The flat plate slab with 190mm total thickness and 150mm effective
depth is carried by 300mm square columns 4.6m on centers in each direction. A
factored load of 534kN must be transmitted from the slab to a typical interior
column. Concrete and steel strengths used are, respectively, fc’ = 28 MPa and fy =
420 MPa, and use #8mm as stirrups. Determine if shear reinforcement is required
for the slab; and if so, design integral beams with stirrups to carry the excess
shear.
𝑑
• = 75𝑚𝑚; 𝑏° = 4 300 + 75 + 75 = 1800𝑚𝑚
2
• 𝑉𝑢 = 534𝑘𝑁
2 2 300
• 𝜆𝑠 = = = 1.12 ≤ 1 𝛽= = 1 and 𝛼𝑠 = 40
1+0.004𝑑 1+0.004(150) 300
• ∅𝑉𝑐 = ∅0.33𝜆𝜆𝑠 𝑓𝑐′ 𝑏𝜊 𝑑 = 0.75 × 0.33 28 1800 150 10−3 = 𝟑𝟓𝟑. 𝟔𝒌𝑵
0.33
• ∅𝑉𝑐 = ∅ 0.17 + 𝜆𝜆𝑠 𝑓𝑐′ 𝑏𝜊 𝑑
𝛽
0.33
• ∅𝑉𝑐 = 0.75 × 0.17 + 28 1800 150 10−3 = 535.76𝑘𝑁
1
49
10/8/2024
0.083𝛼𝑠 𝑑
• ∅𝑉𝑐 = ∅(0.17 + )𝜆𝜆𝑠 𝑓𝑐′ 𝑏𝜊 𝑑
𝑏𝜊
0.083 40 150
• ∅𝑉𝑐 = 0.75 × 0.17 + 28 1800 150 10−3 = 478.62𝑘𝑁
1800
• The thickness is not adequate and shear reinforcement is required.
• The effective depth 150mm just satisfies the minimum allowed to use stirrup.
𝑉𝑚𝑎𝑥 = ∅0.5 𝑓𝑐′ 𝑏° 𝑑 = 0.75 × 0.5 28 1800 150 10−3 = 535.76 > 534kN
• This value satisfied the requirement of ACI Table 22.6.6.3.
• The required perimeter of the second critical section, at which the concrete alone
can carry the shear is:
• 534 103 = 0.75 × 0.33 28𝑏𝜊 150 → 𝑏𝜊 = 𝟐𝟕𝟏𝟖. 𝟐𝟗𝒎𝒎
0.33
• 534 103 = 0.75 × 0.17 + 28𝑏𝜊 150 → 𝑏𝜊 = 1794.07𝑚𝑚
1
0.083 40 150
• 534 103 = 0.75 × 0.17 + 28𝑏𝜊 150 → 𝑏𝜊 = 2347.27𝑚𝑚
𝑏𝜊
• 2718.29 = 4 300 + 𝑥 → 𝑥 = 379.57𝑚𝑚
50
10/8/2024
51
10/8/2024
52
10/8/2024
• Headed shear stud reinforcement location and spacing shall be in accordance with
Table below:
53
10/8/2024
• Example (6): The flat plate slab with 190mm total thickness and 150mm effective
depth is carried by 300mm square columns 4.6m on centers in each direction. A
factored load of 534kN must be transmitted from the slab to a typical interior
column. Concrete and steel strengths used are, respectively, fc’ = 28 MPa and fy =
420 MPa, and use #8mm as stirrups. Determine if shear reinforcement is required
for the slab; and if so, using headed stud reinforcement. The #16mm bars will be
used as negative flexural reinforcement. The yield strength is fyt = 350 MPa for
studs.
• Based on previous example (5), the thickness is not adequate and shear
reinforcement is required.
16
• 𝐻(𝑆𝑡𝑢𝑑)𝑚𝑖𝑛 = 190 − 20 𝐶𝑜𝑣𝑒𝑟 − 20 𝐶𝑜𝑣𝑒𝑟 − = 142𝑚𝑚
2
• A stud height of 150mm will be used, which is consistent with the effective depth
and exceeds the minimum requirement (142mm).
• 𝑉𝑚𝑎𝑥 = ∅0.66 𝑓𝑐′ 𝑏° 𝑑 = 0.75 × 0.66 28 1800 150 10−3 = 707.21𝑘𝑁 > 534
• This value satisfied the requirement of ACI Table 22.6.6.3.
• The required perimeter of the second critical section, at which the concrete alone
can carry the shear is:
• 534 103 = 0.75 × 0.17 28𝑏𝜊 150 → 𝑏𝜊 = 5276.68mm
• 5276.68 = 4 300 + 𝑥 → 𝑥 = 1019.17𝑚𝑚
• For each side nearly 510mm is enough from the face of column. Also, for each
side extended to about d/2=75mm in both the end part and face of column which
equal to 660mm, and in first critical section equal to 585mm.
585 3𝑑
•𝑠= = 146𝑚𝑚 ≈ 140𝑚𝑚 < = 112.5𝑚𝑚 ≈ 110𝑚𝑚
4 4
• ∅𝑉𝑐 = ∅0.25𝜆𝜆𝑠 𝑓𝑐′ 𝑏° 𝑑=0.75 × 0.25 28 1800 150 10−3 = 267.88𝑘𝑁
• The maximum spacing between the stud rails must be less than 2d, so two lines of
studs are needed for a 300mm square column; a center-to-center spacing of
275mm.
54
10/8/2024
∅𝐴𝑣 𝑓𝑦 𝑑
• ∅𝑉𝑠 =
𝑠
(534−267.88)(110)(103 )
• 𝐴𝑣 = =
0.75×350×150
743.45𝑚𝑚2
• Use #12mm stud which have cross-
sectional area about 113mm2.
743.45
• 𝑁𝑜. 𝑜𝑓 𝑠𝑡𝑢𝑑 = = 6.58 ≈ 7.
113
• The first one placed at 50mm which
is smaller than d/2=75mm.
• Double Check:
• New 𝑏𝜊 = 4 275 + 785 2 =
5540𝑚𝑚 > 5276.68mm OK.
55
10/8/2024
56
10/8/2024
• Example (7): A flat plate slab 190mm thick is supported by interior 250mmm square
columns and is reinforced for negative bending with #16mm bars 125mm on centers in
each direction, with an average effective depth d of 150mm. The concrete strength fc’ is
21MPa. The slab must transfer a factored shear Vu of 475kN to the column. What special
slab reinforcement is required, if any, at the column to transfer the factored shear?
𝑑
• = 75𝑚𝑚; 𝑏° = 4 250 + 150 = 1600𝑚𝑚
2
2 2 450
• 𝜆𝑠 = 1+0.004𝑑
= 1+0.004(150)
= 1.12 ≤ 1 𝛽 = 450 = 1 and 𝛼𝑠 = 40
• A shear head will be used, fabricated from I-beam section (S100×11.5kg) with
100mm depth, fy = 345 MPa, S=50300mm3, Is=2.56(106), and A=1460mm2.
• 𝑉𝑚𝑎𝑥 = ∅0.58 𝑓𝑐′ 𝑏° 𝑑 = 0.75 × 0.58 21 1600 150 10−3 = 478.42𝑘𝑁 >
475𝑘𝑁
• 475 103 = 0.75 × 0.33 21𝑏° 150 → 𝑏° = 2792.01𝑚𝑚
• Note that the actual shear force to be transferred at the critical section is slightly
less than 475kN, because a part of the floor load is within the effective perimeter
bo ; however, the difference is small then use small shear head.
𝑐1 3 𝑐
• 𝑏° = 2792.01 = 4 2 + (𝑙𝑣 − 1 )
2 4 2
250 3 250
• 2792.01 = 4 2 + (𝑙𝑣 − )
2 4 2
• 𝑙𝑣 = 616.42𝑚𝑚 ≈ 620𝑚𝑚
• Assume αv=0.25
𝑉𝑢 𝑐
• 𝑀𝑝 = ℎ𝑣 + 𝛼𝑣 (𝑙𝑣 − 1 )
2∅𝑛 2
57
10/8/2024
475 250
• 𝑀𝑝 = 100 + 0.25(620 − ) 10−3 = 14.76𝑘𝑁. 𝑚
2(0.9)(4) 2
• 𝑀𝑟 = 50300 345 10−6 = 17.35𝑘𝑁. 𝑚
• Taking moments of the composite cracked section about the bottom surface:
200000 1 400 200000 𝑦
× ×201 ×150 + 1460 70 +(400𝑦 )
4700 21 0.125 1000 4700 21 2
•𝑦=
200000 1 400 200000
× ×201 + 1460 +(400𝑦)
4700 21 0.125 1000 4700 21
1 400 𝑦
9.28× ×201 ×150 + 9.28 1460 70 +(400𝑦 )
•𝑦= 0.125
1
1000
400
2
9.28× ×201 + 9.28 1460 +(400𝑦)
0.125 1000
5968.9×150 + 13549 70 +(200𝑦 2 )
•𝑦= → 𝑦 = 58.9𝑚𝑚
5968.9 + 13549 +(400𝑦)
58
10/8/2024
59