Assessment of Damper Performance in Controlling Cable Vibrations Using A Reliability-Based Framework
Assessment of Damper Performance in Controlling Cable Vibrations Using A Reliability-Based Framework
1, 2017
Abstract: Owing to their long flexible nature and low intrinsic damping, bridge
stay cables are prone to various types of wind-induced vibrations, among which
the rain-wind-induced vibration is most frequently observed on site. External
dampers are widely used to control such unfavourable cable oscillations and
their effectiveness in suppressing large-amplitude cable vibrations was
addressed in many studies using deterministic approaches. However, the
mechanical and/or physical properties of cables and the attached dampers could
not only deviate from their respective nominal design values at a given design
point, but also vary considerably during the lifetime of a cable-stayed bridge
and thus affect damper efficiency. Hence, for a realistic damper performance
assessment, these uncertainties should be taken into account. The objective of
this paper is to present a time-variant reliability-based framework model to
assess how uncertainties in the structural parameters of a cable-damper system
would influence the time specific reliability performance of an external damper
yielded from the current design practice.
1 Introduction
where m is the cable mass per unit length, ζ is the damping ratio of the cable, ρ is the air
density, and D is the cable diameter. Consider an example of a typical bridge stay cable
having D = 20 cm and m =100 kg/m, this is equivalent to a structural damping
requirement of approximately 0.5%. The criterion is not only supported by experience in
Japan (Saito et al., 1994; Yamada, 1997) and France (Virlogeux, 1998), but also
confirmed by recent field monitoring program in China (Chen et al., 2004). In addition,
when revising design guideline of bridge stay cables, this criterion is recommended by
the Post-Tensioning Institute (PTI publication, 2001) to be used in practical design to
predicate the required damping in a stay cable to mitigate RWIV.
Besides modifying cable surface configuration and adding cross-ties, external
dampers are commonly used to suppress unfavourable cable motions on site. The
effectiveness of a damper design in controlling cable vibrations has been studied by many
researchers in terms of the structural modal damping level achieved by a stay cable when
attached with an external damper. Kovacs (1982) identified the existence of an optimal
damping in a taut cable-damper system, which was confirmed by a number of researchers
(Yoneda and Maeda, 1989; Uno et al., 1991; Pacheco et al., 1993; Krenk, 2000). In
particular, Pacheco et al. (1993) simplified the procedure of designing viscous dampers of
stay cables by deriving a universal damping estimation curve, which allowed relating the
modal damping level of a damped taut cable directly to the size and the location of a
damper. By solving the same problem using complex mode shapes, Krenk (2000)
developed an analytical form of this universal curve. Further, Mehrabi and Tabatabai
(1998), as well as Krenk and Nielsen (2002) presented a refined solution to a typical
cable-damper system by including the influence of cable sag and cable bending stiffness
in the formulation. The accurate asymptotic formula of the structural modal damping
ratio of a general cable-damper system was analytically derived by Fujino and Hoang
(2008). The study resulted in an explicit evaluation of reductions in the damper
effectiveness due to influential parameters such as the sag and the bending stiffness of a
cable and the stiffness of a damper support. Recently, Cheng et al. (2010) proposed an
energy-based method to evaluate the dynamic behaviour of a cable-damper system. A set
of damping estimation curves were developed for the practical parameter ranges of bridge
stay cables. These curves can be utilised to relate a specific damper design to the
corresponding equivalent structural modal damping of a damped stay cable.
At present, when an external damper is used to control RWIV of a stay cable, upon
considering the limitations of its installation location, the size of the damper is typically
selected using either the damper design curve or the design formula proposed in the
above mentioned studies so that the resulted equivalent structural damping ratio of the
damped cable would satisfy the damping requirement for suppressing RWIV proposed by
Irwin (1997). However, it is worth noting that most existing studies are based on the
assumption that the parameters of a cable-damper system are deterministic; whereas in
practice, it is expected that the system properties could not only deviate from their
respective nominal design values at a given design point, but also vary over time due to
changes in ambient conditions. For example, tension in a stay cable may increase or
decrease during its lifetime because of creep and shrinkage in concrete deck and/or pylon
and cable slacking (Au and Si, 2012). Thermal expansion or contraction of the fluid in a
viscous damper may result in excessive internal pressure in a damper or the formation of
a vacuum inside the damper, which would change the fluid properties or even cause
leakage and thus affect the damper capacity and degrade its efficiency. Therefore, the
assumption underlying deterministic approaches does not comply with the most common
Assessment of damper performance in controlling cable vibrations 35
Figure 1 A schematic model of an inclined sag cable with a transverse linear viscous damper
The sagging effect in a real cable due to its self-weight is usually considered in terms of a
sag d at the cable mid-span. The sag is given by d = mgL2cosθ/(8H), where H is the cable
tension component along its chord direction, and g is the gravitational acceleration. A
non-dimensional sag parameter is defined by Irvine and Caughey (1974) as:
2
⎛ 8d ⎞ L
λ2 = ⎜ ⎟ (2)
⎝ L ⎠ [ e ( EA)]
HL /
where EA is the axial rigidity of the cable, and Le = L[1 + 8(d/L)2] is the static (stretched)
length of the cable. It should be noted that, as indicated by equation (2), the
non-dimensional sag parameter λ2 does not only include the effect of cable sag, but also
that of the cable axial stiffness and inclination. For simplicity, it is assumed that the
variation of λ2 is associated with the variation of the sag level. For example, λ2 = 0
represents physically the case of a taut cable, and larger λ2 values correspond to more
flexible cables. In practice, stay cables on cable-stayed bridges typically have λ2 values in
the order of ten or smaller (Johnson et al., 2002). This range will be considered in the
current study.
Assessment of damper performance in controlling cable vibrations 37
For the cable-damper system shown in Figure 1, when damper location is selected,
the most influential factors that would affect the efficiency of a viscous damper include
the cable tension, T, and the damper capacity, c. As mentioned earlier, these two system
parameters could vary over the life time of a bridge due to change in the ambient
conditions such as creep and shrinkage in concrete deck and/or pylon, cable slacking, and
temperature-induced variation in damper fluid properties etc. Further, even at a given
time point, the actual cable tension and damper capacity in the system could deviate from
their respective nominal values. These facts lead us to consider cable tension and damper
capacity as time-dependent random variables in the current study, the uncertainties of
which are assumed to come mainly from the above two sources. The former type of
uncertainty can be included in the analysis by incorporating the time-varying
characteristics of cable tension and damper capacity over the bridge life time, which
typically can be collected from field monitoring program; whereas the latter type is
counted at a given point of time, by assuming that both the cable tension and the damper
capacity follow independent normal distributions, with mean values equal to their
respective nominal design values at the specific design point, and the standard deviations
defined by the specified coefficient of variations (COVs), as shown in Figure 2.
Figure 2 Schematic diagram showing uncertainty of cable tension and damper capacity
In the current study, the practical ranges of the non-dimensional parameters ξ and ψ are
selected based on the bridge stay cable database developed by Tabatabai et al. (1998).
The non-dimensional bending stiffness parameter ξ is limited to be no greater than 400,
whereas the damping parameter ψ is selected between 0 and 60.
g ( H (t ), c(t ) ) = g ( ξ ( H (t ) ) , ψ ( c (t ), H (t ) ) ) = ζ s (t ) − ζ r (3)
where g(∙) is the time-dependent LSF of the cable-damper system. Because only the
structural properties are expected to decay and the stochastic nature of the RWIV is
simplified, the time-variant reliability problem associated with equation (3) can be solved
as a series of classical time-independent reliability problems. The underlying assumption
is to consider failure events at any time of the bridge lifetime to be independent.
To develop the full expression for ζs(t), we consider the in-plane transverse vibration
of the cable-damper system shown in Figure 1 at a specific design point (H, c), which can
be described by the following partial differential equation (Fujino and Hoang, 2008):
∂ 2 η( X , t ) ∂ 2 η( X , t ) d 2Y ∂ 4 η( X , t )
H −m +h − EI = f c δ ( X − Ld ) (4)
∂X 2
∂X 2
∂X 2
∂X 4
where η(X,t) is the in-plane transverse displacement of the cable motion in the
Y-direction; m is the cable mass per unit length; H is the cable tension component along
its chord direction at the given design point; h(t) is the additional tension in the cable due
to vibration; EI is the bending stiffness of the cable; fc(t) is the in-plane damping force of
the damper and is a function of damper capacity c, and δ(X-Ld) is the Dirac delta
function. Fujino and Hoang (2008) proposed an asymptotic solution to equation (4), of
which the equivalent nth modal damping ratio, ζn, of a damped cable is identified directly
from the imaginary part of the complex natural frequency solution:
Assessment of damper performance in controlling cable vibrations 39
ζn η f ηsn ηn
= R f Rsn (5)
( η f ηsn ηn )
2
Ld / L
where X = {x1, x2,…,xn}T is the vector of the system design variables x1, x2,…,xn, Xk =
{x1,k, x2,k,…,xn,k}T is the vector X at the kth iteration, g(Xk) is the value of the nonlinear
LSF at Xk, xi,k is the ith element of X in the kth iteration, and n is the total number of
system random variables. In the current formulation, X = {x1 = H, x2 = c}T and n=2.
The solution uses an iterative process to minimise the discrepancy between the exact
nonlinear LSF and the approximate linearised LSF. The nonlinear index, r, can be
determined through a process called intervention method by using the values of LSF and
its gradients associated with the current and the last iterations as:
⎧⎪ n
∂g ( X k ) ⎫⎪
g ( X k −1 ) − ⎨ g ( X k ) +
1
r ∑x 1− r
i, k
∂xi
(x r
i , k −1 )
− xir, k ⎬ = 0 (9)
⎩⎪ i =1 ⎭⎪
However, the truncation error from the first-order Taylor series approximation used in
this method might be large. In particular, in the case of highly nonlinear LSFs associated
with large curvature failure surfaces, this approximation would reduce the accuracy of the
reliability assessment considerably. In addition, TANA method can only predict one MPP
in each iteration process. Hence, it is not capable of handling problems with multi-design
points in the LSF.
To overcome these limitations, second-order reliability methods (SORMs) are
selected. In these methods, when approximating the limit state function at MPP, the
original limit state surface is replaced by a second-order approximate one with the
addition of a second-order derivative term to the Taylor series expansion:
1
g (U ) ≈ g (U *) + ∇g (U *) (U − U *) + (U − U *) ∇ 2 g (U *)(U − U *)
T T
(10)
2
where the system variables are presented in a standard normalised U-space, U*is the
coordinate of the MPP, g (U ) is the approximate LSF, g(U*) is the LSF value at the
Assessment of damper performance in controlling cable vibrations 41
MPP, ∇g(U*) is the gradient of the LSF at the MPP, and ∇2g(U*) represents the second-
order derivatives of the LSF at the MPP.
Wang and Grandhi (1995) simplified the calculations of the failure probability Pf by
proposing an adaptive approximation method for the SORM. In this method, the
nonlinear approximate LSF, g ( X ) developed in the TANA method is used to calculate
the second order derivatives of the LSF at the MPP, which considerably reduces the
computation time. In addition, it improves the accuracy of failure probability calculations
compared to the first-order reliability methods. The failure probability Pf can be
computed by either the Breitung’s formulation or the Tvdet’s formulation (Choi et al.,
2007).
The SORM with adaptive approximations method is applied to the studied cable-
damper system in the current work due to its formulation simplicity.
on equation (6), the minimum required structural damping ratio for such a cable-damper
system to prevent RWIV is ζr = 0.717%. The value of the LSF of the current cable-
damper system is determined according to equation (7) as:
g ( X ) = g ( x1 = H = 3, 700 kN, x2 = c = 50 kN ⋅ s/m ) = 1.339%
The TANA method is applied first to compute the reliability index of the studied damped
cable, with the iteration results summarised in Table 1. The convergence tolerance is set
to be 0.001. As can be seen from the table, the reliability index converges after four
iterations at point H4 = 4,410.8 kN, c4 = 171.3 kN∙s/m. This point is the MPP with
corresponding reliability-index equals to β4 = 11.79, and the associated probability of
failure equals to Pf = 5.6 × 10–16.
Table 1 Summary of reliability analysis results by TANA
Iteration no. 1 2 3 4
H (kN) 3,700.0 5,230.8 4,730.2 4,410.8
c (kN∙s/m) 50.0 111.8 182.4 171.3
g(Xk) 0.00134 0.0188 0.0081 0.00013
(∂g/∂H)|μH –2.12 × 10–7 –9.52 × 10–8 –1.32 × 10–7 –6.18 × 10–7
(∂g/∂H)|μc 2.62 × 10–5 8.32 × 10–6 4.11 × 10–5 7.17 × 10–5
β 10.83 11.47 11.77 11.79
ε – 0.1099 0.0260 0.0009
⎡ ∂g (U *) / ∂H ∂g (U *) / ∂c ⎤
⎢ − ∇g (U *) − ∇g (U *) ⎥
⎢ ⎥
⎢⎣ 0 1 ⎥⎦
where ∂g(U*)/∂H and ∂g(U*)/∂c are the gradients of the limit state function g(∙)
evaluated at the MPP defined by H and c, and ⏐∇g(U*)⏐ is the magnitude of the gradient
function. The curvature corresponding to parameters H and c when the orthogonal
Y-space is used is calculated for the approximate LSF, g ( X ) at the MPP using the
method proposed by Wang and Grandhi (1995), which resulted in a reliability-index of
β = 11.79 and the corresponding probability of failure of Pf = 9.1 × 10–16.
To perform MCS, a set of 108 one-dimensional inputs are generated randomly for
each parameter and then the two variables H and c are combined together to generate a
total of 1016 runs. For each run, equation (5) is used to evaluate the equivalent first modal
damping ratio of the cable-damper system. The reliability-index is determined from the
ratio between the mean and the standard deviation of the limit state function, which is
β = 12.04. The corresponding probability of failure is Pf = 1.1×10–15. A comparison of
the reliability analysis results in terms of the probability of failure, Pf, shows that the
SORM with adaptive approximations method would yield more accurate reliability
evaluation results of the given cable-damper system than the TANA method. This is
mainly due to its capability of handling nonlinear LSF. In addition, it is computationally
more efficient than the MCS. Therefore, the SORM with adaptive approximations
method will be used in the rest of the paper to predict the performance of cable-damper
systems.
Figure 3 Effect of uncertainty level of cable tension and damper size on the reliability response
of a cable-damper system
(a)
(b)
(c)
46 S.A. Mohammadi et al.
has been observed for a given damper location to achieve the maximum damping ratio of
a damped cable (e.g. Kovacs, 1982; Pacheco et al., 1993; Krenk, 2000; Cheng et al.,
2010). In addition, the damper size ψr,max, which corresponds to the most reliable system
performance identified in the current study, is found to agree well with the optimum
damper size ψopt reported in the literature. Therefore, in the design of an external damper
to suppress cable vibrations, upon the determination of damper location, the objective is
then to select a damper size which would produce the optimum vibration control effect
with the most reliable performance. For instance, for a stay cable with a damper located
at 0.06L [Figure 4(c)], if ξ = 200, the optimum damper size which gives the maximum
achievable damping ratio of 3.11% would be ψopt = 6.0 (Cheng et al., 2010), whereas that
would yield the most reliable performance of the damped cable is ψr,max = 6.05, with the
associated reliability-index equals to β = 10.2.
It should be pointed out that in the case of cable-supported structures such as
cable-stayed bridges and suspension bridges, cables (cables and hangers for suspension
bridges) play an important role in resisting loads and transferring them from bridge deck
to tower and foundation. Therefore, they are designed with larger safety factor as
compared to other structural elements. A reliability-based performance assessment of a
suspension bridge in Japan (Imai and Frangopol, 2001) reported that the reliability-
indices of main cables, hanger ropes, and stiffening girders are very different. The β
values of the main cables are around 15, whereas those of the stiffening girders are within
the range of 3 to 6. Similarly, a reliability-based optimum design analysis of glulam
cable-stayed footbridges performed by Simões and Negrão (2005) showed necessity of
having reliability-index of the studied cable-stayed system within the range of 15 to 20 to
resist excessive cable deflection.
In addition, it is worth noting that the proposed reliability-based damper design
curves can be used to identify the practical range of damper size ψ to satisfy the required
reliability-index β for a particular cable with a bending stiffness parameter ξ. Due to the
dependence of the formulated limit state function in equation (3) on the structural
damping ζs, a practical range of damping parameter ψ should be determined to ensure a
safe design. The limit level of the damping parameter ψmin for a safe design is the locus of
the points where g(H, c) = 0. In the case of Γd = 0.02, when a very stiff cable is selected,
i.e. ξ = 100, the obtained structural damping ζs for the range of selected damper size
(ψ ≤ 60) is not adequate to resist RWIV. Furthermore, a comparison of the β-ψ curves in
Figure 4 suggests that the impact of cable bending stiffness on the damper size decreases
when the damper moves further towards the cable centre.
4.1.1 Example 1
For the same cable discussed earlier, which has L = 150 m, m = 72 kg/m, D = 0.2 m,
EI = 5,420 kN∙m2, and H = 3700 kN, an external damper is restricted to be installed at
Γd = 0.04. We propose to use the reliability-based damper design curves given in Fig. 4 to
determine the minimum required damper size in order to prevent rain-wind-induced
vibration with a reliability index β ≥ 4.7, and calculate the corresponding equivalent first
modal damping ratio of the damped cable.
Based on the given cable properties, the non-dimensional cable bending stiffness
parameter is ξ = 123.9. From Figure 4(b), when β = 4.7, the damping parameters
correspond to ξ = 100 and 200 are ψ = 6.6 and 3.7, respectively. Thus, that corresponds to
48 S.A. Mohammadi et al.
ξ = 123.9 can be obtained using linear interpolation, which gives ψ = 5.9. The damper
size is then determined as c = ψ Hm = 5.9 × 3, 700 × 103 × 72 = 96.3 kN s/m.
The equivalent structural damping ratio ζs for the first mode can be computed
according to equation (5). The non-dimensional damper coefficient parameter for the first
mode of a corresponding horizontal non-flexural taut cable-damper system is found to be:
The reduction and modification factors are obtained from the numerical solution of the
formulation proposed by Fujino and Hoang (2008). They are Rs1 = 0.946, Rf = 0.913,
ηs1 = 1.020, and ηf = 0.700. Hence, the equivalent first modal damping ratio of the system
is ζs = ζ1 = 1.429%. On the other hand, the required damping ζr for such a cable-damper
system to prevent rain-wind-induced vibration is determined to be 0.717%.
4.1.2 Example 2
If the non-dimensional bending stiffness parameter of a stay cable is ξ = 250, and the
possible damper location is Γd = 0.028, we propose to determine the minimum required
damping parameter to satisfy the reliability index of the cable-damper system for
resisting rain-wind-induced vibration to be β ≥ 6.0.
Using Figure 4(a), along with linear interpolation for bending stiffness parameter
ξ = 200 and 300, the non-dimensional damping parameter corresponding to ξ = 250 at
Γd = 0.02 is 22.0. Similarly, ψ = 4.6 for ξ = 250 and Γd = 0.04 can be obtained from
Figure 4(b). Therefore, by assuming a linear interpolation between results of Γd = 0.02
and 0.04, for a cable with ξ = 250, if a damper is attached to it at Γd = 0.028, to ensure
β ≥ 6.0, the minimum required damping parameter would be ψmin = 15.4.
Figure 5 Variation of reliability-index with bending stiffness parameter for three different
damper sizes at Γd = 0.06
To ensure the performance of an external damper sustains at the desired safety level,
maintenance should be carried out during the bridge service stage to minimise the impact
of cable tension and damper capacity variation on the response of a damped cable.
4.2.1 Example 3
In this example, we consider a damped cable on a concrete cable-stayed bridge, of which
the cable tension and damper property vary with time. The time-dependent effects on the
reliability of this cable-damper system are evaluated using the proposed time-variant
reliability analysis framework model. The properties of the cable used in this example
are taken from a study by Tabatabai and Mehrabi (2000): L = 93 m, D = 0.225 m,
EI = 3,049 kN∙m2, and m = 114.09 kg/m. The initial specified cable tension along
its chord direction is H = 5017 kN (ξ = 119.3). To suppress rain-wind-induced
cable vibrations, a linear viscous damper is attached 3.72 m from the cable lower end
(Γd = 0.04). In this example, two different damper design cases are considered. Case 1
represents an optimum damper design case with a copt = 271.1 kN∙s/m (ψopt = 11.3),
whereas Case 2 assumes a design case using a smaller damper size, c = 90.4 kN∙s/m
(ψ = 3.8). The cable tension loss is estimated based on the field monitoring data of a
cable-stayed bridge over a period of 300 days (Au and Si, 2012), whereas a linear
degradation from its original design is assumed for the damper capacity. In addition, it is
assumed that the cable chord tension and the damper capacity are random variables with
independent normal distributions, and the time variation of their respective mean values
over a period of 300 days are shown in Figure 6. We are interested in developing a
maintenance plan for the studied cable-damper system over a period of 300 days to
ensure its performance remain at a desired safety level during this time period.
50 S.A. Mohammadi et al.
Figure 6 Time variation of cable tension and damper capacity over a period of 300 days,
(a) cable tension along the chord (b) damping coefficient of damper
(a)
Case1
(b)
The reliability response of the damped cable over this time period is portrayed in
Figure 7 as the time history of the relative reliability-index β(t)/β0 for cases 1 and 2. It
can be seen that as expected, the reliability index β(t) decreases with time, which
suggests a higher probability of failure associated with the loss in the cable tension and
damper capacity during the lifetime of the cable-damper system. Further, a higher
reduction of β value occurs within the first 50 days due to a rapid loss of cable tension
over this time period. As can be seen from Figure 6(a), within the first 50 days, the loss in
cable chord tension is 7.4%, whereas over the entire 300 days, the total loss in cable
chord tension is 12.2%. Based on Figure 7, the impact of cable tension and damper
capacity variation on the reliability of the system performance at any time within the
300 days can be obtained. Hence, the time-dependent reliability index, β(t), can be
expressed as a function of the damper coefficient and the cable chord tension, i.e., β(c(t),
H(t)).
Case 1
Notes: Case 1: c0 = copt = 271.1 kN∙s/m, β0 = 9.50; Case 2: c0 = 90.4 kN∙s/m, β0 = 2.24
For a more convenient identification of the effect of cable tension loss and damper
capacity degradation on the system reliability, this set of results are also plotted in
Figure 8 in terms of the relative reliability-index β(t)/β0 versus the percentage loss of
cable chord tension [Figure 8(a)] and damper capacity [Figure 8(b)].Though the
presentation of Figure 8 isolates the dependence of the reliability index reduction on the
loss in cable chord tension and damper capacity, it should be pointed out that in the
analysis, the variation of H and c are considered simultaneously according to the patterns
shown in Figure 6. For example, at day 180, when the cable chord tension and the
damper capacity are reduced by 11.3% and 3%, respectively, the corresponding relative
reliability-index in case 1 is β (t = 180 day) / β0 = 0.980, i.e. the reliability-index drops
2% from its initial value.
52 S.A. Mohammadi et al.
Comparing the relative reliability index results of case 1 and case 2, it can be seen
that case 2 is more critical. This implies that when the damper capacity c is different from
the optimum value, the system performance would be more sensitive and have greater
degradation due to uncertainty in system parameters. This can also be verified by
comparing the slope of each reliability curve at different damping parameters in
Figure 4(b). The slope is less steep when ψ is closer to ψr,max.
Figure 8 Relative reliability-index estimation due to loss of (a) cable chord tension and
(b) damper capacity
(a)
(b)
Assessment of damper performance in controlling cable vibrations 53
The integration of reliability analysis into the lifetime maintenance strategy for the
studied cable-damper system can be achieved by considering the time variation of the
system performance associated with the loss in cable chord tension and damper capacity.
To keep the cable-damper system operating at its designated performance, the lifetime
variation of the system reliability-index should remain zero, which means
∂β ( c(t ), H (t ) ) ∂β ∂c ∂β ∂H
= ⋅ + =0 (11)
∂t ∂c ∂t ∂H ∂t
in which the lifetime variation of the damper capacity and the cable chord tension are
considered by ∂c/∂t and ∂H/∂t, respectively. If we assume that the maintenance of the
studied cable-damper system can be achieved by adjusting cable chord tension to ensure
that the performance remains at the designed safety level, equation (11) can be rewritten
as:
∂H ∂β / ∂c ∂c
=− ⋅ (12)
∂t ∂β / ∂H ∂t
Thus, the required adjustment of cable tension at any time of interest can be obtained
from the tangents of the reliability index curves with respect to c and H, i.e.:
⎛ β (t ) ⎞ ⎛ β (t ) ⎞
∂⎜ ⎟ ⋅ β0 ∂⎜ ⎟
∂β ( c(t ), H (t ) ) ⎝ β0 ⎠ β ⎝ β0 ⎠
= = 0⋅ (13)
∂c ⎛ c − c(t ) ⎞ c0 ⎛ c − c(t ) ⎞
∂⎜ 0
c ⎟ ⋅ ( −c0 ) ∂⎜ 0 ⎟
⎝ 0 ⎠ ⎝ c0 ⎠
⎛ β (t ) ⎞ ⎛ β (t ) ⎞
∂β ( c(t ), H (t ) )
∂⎜ ⎟ ⋅ β0 ∂⎜ ⎟
= ⎝ β0 ⎠ β
= 0 ⋅ ⎝ β0 ⎠ (14)
∂H ⎛ H − H (t ) ⎞ H 0 ⎛ H 0 − H (t ) ⎞
∂⎜ 0 ⎟ ⋅ ( −H0 ) ∂⎜ ⎟
⎝ H0 ⎠ ⎝ H0 ⎠
where the lifetime variation of the relative reliability index β(t)/β0 versus the percentage
loss in cable chord tension and damper capacity can be computed from the results in
Figure 8.
In the current example, the initial design point in case 1 is H0 = 5,017 kN,
c0 = 271.1 kN·s/m and the initial reliability index equals to β0 = 9.50. For instance, at day
180, it can be deduced from equations (13), (14), and Figure 8 that ∂β/∂c = 3.7×10–5 and
∂β/∂H = 3.1 × 10–7. Hence, to ensure β180 = β0 = 9.50, the adjustment rate of the cable
tension, in terms of its chord component, can be obtained from equation (12) as
where the lifetime variation of damper capacity at day 180 can be obtained from Figure 6,
which is ∂c/∂t = –0.056 kN∙s/m per day.
By repeating the calculations for cable chord tension adjustment rate, ∂H/∂t, at
different time instants, a maintenance plan can be defined over the lifetime of the studied
cable-damper system. The required additional force after a certain time period can be
obtained by integrating the adjustment rates over the maintenance period, i.e.
54 S.A. Mohammadi et al.
∂H
t
Hm = ∫0 ∂t
dt (15)
where Hm is the amount of cable chord tension adjustment required at day t. Figure 9
shows the required Hm at different time to maintain the desired performance of the
studied cable-damper system. The results show that to keep the system perform at a level
corresponding to the designed reliability index β0 = 9.50, the required additional amount
of cable tension increases monotonically during the lifetime of the cable, which, at the
end of the studied 300-day period is 188.1 kN. This equals to 3.7% of the initial design
value.
Figure 9 Additional tension adjustment to maintain system reliable performance over the period
of 300 days
Case 2
Case 1
If conducting the same exercise for case 2, the required additional tension force over the
300-day period would be 11.2% of the initial design value. Comparison of the two curves
shown in Figure 9 indicates that more adjustment in cable tension is needed if the
selected damper size is different from the optimum one. Therefore, when an external
damper is applied to control cable vibrations, it is very important to select the optimum
size or a size as closer as possible to the optimum one. This is not only for a more
effective vibration control, but also to ensure a higher reliability of the system.
5 Summary
External dampers are commonly used on cable-stayed bridges to control various types of
large amplitude cable oscillations. In the case of RWIV, due to lack of thorough
understanding of its excitation mechanism, current prediction of the required damping to
effectively suppress it is mainly depending on a Scruton number-based empirical
criterion, and the damper is designed using tools derived by deterministic-based analysis
approaches. Therefore, the latent stochastic nature of the problem, including the
uncertainty of cable and damper properties with respect to their nominal design values
Assessment of damper performance in controlling cable vibrations 55
and their potential time variations over the service life of a bridge, is generally excluded
in the formulation. Nevertheless, these uncertainties would render the actual system
properties deviate from their assumed nominal design value and could have a
considerable impact on the performance of a damped cable. The current study aims at
developing a time-variant reliability-based framework model to evaluate how these
uncertainties in the structural parameters of a cable-damper system would affect the
performance of an external damper designed according to the current practice.
The problem has been formulated as a limit state up-crossing scenario to determine
the time specific system reliability due to rain-wind-induced cable vibrations. The time-
variant reliability analysis is conducted by combing the existing time-invariant reliability
methods with the time-varying system parameters. The general form of the time-
dependent LSF was proposed as the difference between the available time-varying
equivalent structural damping ratio in a cable-damper system and the minimum required
structural damping ratio of a damped cable to avoid RWIV. Results showed that
compared to the first-order reliability method, the SORM with adaptive approximations
method could improve the accuracy of failure probability prediction while retaining
simplicity in the problem formulation and efficiency in computation. Various
applications of the proposed time-variant reliability-based framework model, including
the development of reliability-based damper design curves and long-term structural
maintenance plan, have been demonstrated through numerical examples. It has been
found that the presence of uncertainty in the structural properties of a cable-damper
system at a given design point could have a sizable effect on its reliability response and
thus should be considered in design. In particular, the performance of a cable-damper
system was observed to be more sensitive to the uncertainty associated with damper size.
Further, at a specific damper location, the existence of a damper size which would result
in the most reliable performance of a damped cable has been identified. Results showed
that it agreed well with the optimum damper size reported in literature which can attain
the maximum damping ratio at the same damper location.
References
Au, F.T. and Si, X.T. (2012) ‘Time-dependent effects on dynamic properties of cable-stayed
bridges’, Structural Engineering and Mechanics, Vol. 41, No. 1, pp.139–155.
Casas, J.R. and Aparicio, A.C. (2010) ‘Rain-wind-induced cable vibrations in the Alamillo cable-
stayed bridge (Sevilla, Spain). Assessment and remedial action’, Structure and Infrastructure
Engineering, Vol. 6, No. 5, pp.549–556.
Chen, Z.Q., Wang, X.Y., Ko, J.M., Ni, Y.Q., Yang, G. and Hu, J.H. (2004) ‘MR damping system
for mitigating wind-rain induced vibration on Dongting Lake cable-stayed bridge’, Wind and
Structures, Vol. 7, No. 5, pp.293–304.
Cheng, S., Darivandi, N. and Ghrib, F. (2010) ‘The design of an optimal viscous damper for a
bridge stay cable using energy-based approach’, Journal of Sound and Vibration, Vol. 329,
No. 22, pp.4689–4704.
Choi, S.K., Grandhi, R.V. and Canfield, R.A. (2007) Reliability-Based Structural Design, Springer,
London.
Flamand, O. (2001) ‘An explanation of the rain-wind induced vibration of inclined stays’,
Proceedings of the 4th International Symposium on Cable Dynamics, Montreal, Canada,
28–30 May, pp.69–76.
Frangopol, D.M. and Maute, K. (2003) ‘Life-cycle reliability-based optimization of civil and
aerospace structures’, Journal of Computers and Structures, Vol. 81, No. 7, pp.397–410.
56 S.A. Mohammadi et al.
Frangopol, D.M., Maute, K. and Liu, M. (2007) ‘Optimization of structural and mechanical
systems’, in Arora, J.S. and Arora, J.S. (Eds.): Design Optimization with Uncertainty, Life-
Cycle Performance and Cost Considerations, pp.291–329, World Scientific Publishing,
London, England.
Fujino, Y. and Hoang, N. (2008) ‘Design formulas for damping of a stay cable with a damper’,
Journal of Structural Engineering, Vol. 134, No. 2, pp.269–278.
Geurts, C. and Staalduinen, P. (1999) ‘Estimation of the effects of rain-wind induced vibration in
the design stage of inclined stay cables’, in Larsen, Larose and Livesey (Eds.): Wind
Engineering into the 21st Century, pp.885–892, Balkema, Rotterdam.
Geurts, C., Vrouwenvelder, T., Staalduinen, P. and Reusink, J. (1998) ‘Numerical modelling of
rain-wind-induced vibration: Erasmus Bridge, Rotterdam’, Structural Engineering
International, SEI, Vol. 8, No. 2, pp.129–135.
Gu, M. and Lu, Q. (2001) ‘Theoretical analysis of wind-rain induced vibration of cables of cable-
stayed bridges’, The 5th Asia-Pacific Conference on Wind Engineering, Kyoto, pp.125–128.
Gu, M., Du, X.Q. and Li, S.Y. (2009) ‘Experimental and theoretical simulations on wind-rain-
induced vibration of 3-D rigid stay cables’, Journal of Sound and Vibration, Vol. 320,
Nos. 1–2, pp.184–200.
Hikami, Y. and Shiraishi, N. (1988) ‘Rain-wind induced vibrations of cables in cable-stayed
bridges’, Journal of Wind Engineering and Industrial Aerodynamics, Vol. 29, Nos. 1–3,
pp.409–418.
Imai, K. and Frangopol, D.M. (2001) ‘Reliability-based assessment of suspension bridges:
application to the Innoshima bridge’, Journal of Bridge Engineering, Vol. 6, No. 6,
pp.398–411.
Irvine, H.M. and Caughey, T.K. (1974) ‘The linear theory of free vibrations of a suspended cable’,
Proceedings of the Royal Society of London, Series A341, pp.299–315.
Irwin, P.A. (1997) ‘Wind vibrations of cables on cable-stayed bridges’, Building To Last:
Proceedings of Structural Congress XV, Portland, Oregon, 13–16 April, pp.383–387.
Johnson, E.A., Christenson, R.E. and Spencer, J.B. (2002) Flat-Sag Cables With Semiactive
Damping, Dept. of Civil and Env. Engrg. Los Angeles, University of Southern California.
Kovacs, I. (1982) ‘Zur frage der seilschwingungen und der seildämpfung’, Bautechnik,
pp.325–332, in German.
Krenk, S. (2000) ‘Vibrations of a taut cable with an external damper’, Journal of Applied
Mechanics, Vol. 67, No. 4, pp.772–776.
Krenk, S. and Nielsen, S. (2002) ‘Vibrations of a shallow cable with a viscous damper’,
Proceedings of the Royal Society of London, Series A458, pp.339–357.
Kumarasena, S., Jones, N.P., Irwin, P. and Taylor, P. (2007) Wind-Induced Vibration Of Stay
Cables, U.S. Department of Transportation, Federal Highway of Administration,
FHWA-HRT-05-083, Boston.
Matsumoto, M. (1998) ‘Observed behaviour of prototype cable vibration and its generation
mechanism’, in Larsen and Esdahl (Eds.): Bridge Aerodynamics, pp.189–211, Balkema,
Rotterdam.
Matsumoto, M., Shirato, H., Yagi, T., Goto, M., Sakai, S. and Ohya, J. (2003) ‘Field observation of
the full-scale wind induced cable vibration’, Journal of Wind Engineering and Industrial
Aerodynamics, Vol. 91, Nos. 1–2, pp.13–26.
Mehrabi, A. and Tabatabai, H. (1998) ‘Unified finite difference formulation for free vibration of
cables’, Journal of Structural Engineering, Vol. 124, No. 11, pp.1313–1322.
Mohammadi, S., Cheng, S. and Ghrib, F. (2011) ‘Reliability assessment for damped bridge stay
cables under dynamic excitation’, Proceedings of the 8th International Conference on
Structural Dynamics, Leuven, Belgium, pp.2993–2999.
Mohammadi, S., Cheng, S. and Ghrib, F. (2013) ‘Assessment of dynamic behavior of an inclined
sag cable with a transverse linear viscous damper using reliability-based approaches’, General
Conference. 336, Montreal, Canada, Canadian Society of Civil Engineering, pp.1–9.
Assessment of damper performance in controlling cable vibrations 57
Pacheco, B.M., Fujino, Y. and Sulekh, A. (1993) ‘Estimation curve for modal damping in stay
cables with viscous damper’, Journal of Structural Engineering, Vol. 119, No. 6,
pp.1961–1979.
Pagnini, L. (2010) ‘Reliability analysis of wind-excited structures’, Journal of Wind Engineering
and Industrial Aerodynamics, Vol. 98, pp.1–9.
PTI Publication (2001) Recommendations For Stay-Cable Design, Testing and Installation, Fourth
Ed., Post-Tensioning Institute, USA.
Saito, T., Matsumoto, M. and Kitazawa, M. (1994) ‘Rain-wind excitation of cables on cable-stayed
Higashi-Kobe Bridge and cable vibration control’, Proceedings of the International
Conference on Cable-Stayed and Suspension Bridges (AFPC), 2, Deauville, France,
pp.507–514.
Simões, L.C. and Negrão, J.H. (2005) ‘Reliability-based optimum design of Glulam cable-stayed
footbridges’, Journal of Bridge Engineering, Vol. 10, No. 1, pp.39–44.
Tabatabai, H. and Mehrabi, A. (2000) ‘Design of mechanical viscous dampers for stay cables’,
Journal of Bridge Engineering, Vol. 5, No. 2, pp.114–123.
Tabatabai, H., Mehrabi, A.B., Morgan, B.J. and Lotfi, H.R. (1998) Non-Destructive Bridge
Evaluation Technology: Bridge Stay Cable Condition Assessment, Report prepared for Federal
Highway Admin. pSkokie, III: Construction Technology Laboratories.
Uno, K., Kitagawa, S., Tsutsumi, H., Inoue, A. and Nakaya, S. (1991) ‘A simple method of
designing cable vibration dampers of cable-stayed bridges’, Journal of Structural Engineering,
Japan Society of Civil Engineers, Vol. 6, No. 1, pp.167–178.
Virlogeux, M. (1998) ‘Cable vibrations in cable-stayed bridges’, in Larsen and Esdahl (Eds.):
Bridge Aerodynamics, pp.213–233, Balkema, Rotterdam.
Wang, L.P. and Grandhi, R.V. (1995) ‘Improved two-point function approximation for design
optimzation’, AIAA Journal, Vol. 32, No. 9, pp.1720–1727.
Yamada, H. (1997) ‘Control of wind-induced cable vibrations from a viewpoint of the wind
resistance design of cable-stayed bridges’, Proceedings of the 2nd International Seminar on
Cable Dynamics, Tokyo, pp.129–138.
Yamaguchi, H. (1990) ‘Analytical study on growth mechanism of rain vibration of cables’, Journal
of Wind Engineering and Industrial Aerodynamics, Vol. 33, pp.73–80.
Yoneda, M. and Maeda, K. (1989) ‘A study on practical estimation method for structural damping
of stay cable with damper’, Proceeding of Canada-Japan Workshop on Bridge Aerodynamics,
Ottawa, Canada, pp.119–128.
Notation