0% found this document useful (0 votes)
64 views3 pages

CLP2EA1C115 Level Controller Specs

The document describes a conductive level controller (Type CL) designed for liquid level management, featuring adjustable sensitivity, low-voltage AC electrodes, and a dual relay output. It supports various operational voltages (24 VAC/DC, 115 VAC, 230 VAC) and is suitable for both filling and emptying applications. The device is easy to install on DIN rails or with a circular plug and includes LED indicators for output and power status.

Uploaded by

Walace Lanes
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views3 pages

CLP2EA1C115 Level Controller Specs

The document describes a conductive level controller (Type CL) designed for liquid level management, featuring adjustable sensitivity, low-voltage AC electrodes, and a dual relay output. It supports various operational voltages (24 VAC/DC, 115 VAC, 230 VAC) and is suitable for both filling and emptying applications. The device is easy to install on DIN rails or with a circular plug and includes LED indicators for output and power status.

Uploaded by

Walace Lanes
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Conductive Sensors

2-point level controller


Type CL with potentiometer
• Conductive level controller
• Sensitivity adjustment from 250 Ω to 500 KΩ
• For filling or emptying applications
• Low-voltage AC electrodes
• Easy installation on DIN rails or with 11 pin circular
plug
• Rated operational voltage:
24 VAC/DC, 115 VAC or 230 VAC
• Output 2 x 8A/250 VAC DPDT relay
• LED indication for: Output ON and Power ON

Product De­scrip­tion Ordering Key CLD2EA1CM24


µ-Processor based level Max./min. control of charging/ Conductive level
controller for liquids with a discharging. The sensitivity DIN rail or plug mounting
wide sensitivity range (like is adjustable by means of the No of inputs
sewage water, chemicals, salt potentiometer and the rotary Charge/discharge
water etc.). switch. Adjustment potentiometer
2 x 8A DPDT relay output. Output
Relay DPDT
Power supply

Type Selection
Mounting Relay Ordering no. Ordering no. Ordering no.
Supply: 24 VAC/DC Supply: 115 VAC Supply: 230 VAC

DIN-rail DPDT CLD2EA1CM24 CLD2EA1C115 CLD2EA1C230


11-p circular plug CLP2EA1CM24 CLP2EA1C115 CLP2EA1C230

Specifications
Rated operational voltage (UB) Ranges H (High sensitivity) 50 KΩ to 500 KΩ, CF* = 1.0 nF
Pin 2 & 10 230 195 to 265 VAC, 45 to 65 Hz Dielectric voltage >2.0 KVAC (rms)
115 98 to 132 VAC, 45 to 65 Hz (contacts / electronics)
Supply class 2 24 19.2 to 28.8 VAC/DC
Rated impulse withstand volt. 4 kV (1.2/50 µS) (contacts /
Rated insulation voltage <2.0 kVAC (rms)
electronics) (IEC 664)
Rated impulse withstand
voltage 4 kV (1.2/50 µs) (line/neutral) Operating frequency (f)
Relay output 0.5 HZ
Rated operational power
AC supply 5 VA Response time
AC/DC supply 5 VA / 5 W OFF-ON (ton) 1 s
ON-OFF (toff) 1s
Delay on operate (tV) < 300 mS
Environment
Outputs
Overvoltage category III (IEC 60664)
Rated insulation voltage 250 VAC (rms) (cont./elec.)
Degree of protection IP 20 (IEC 60529, 60947-1)
Relay Rating (AgCdO) µ (micro gap) Pollution degree 2 (IEC 60664/60664A,
Resistive loads AC1 8 A / 250 VAC (2500 VA) 60947-1)
DC1 1 A / 250 VDC (250 W)
Temperature
or 10 A / 25 VDC (250 W)
Operating -20º to +50ºC (-4º to + 122ºF)
Small induc. Loads AC15 0,4 A / 250 VAC
Storage -50º to +85ºC (-58º to +185ºF)
DC13 0,4 A / 30 VDC
Mechanical life (typical) ≥ 30 x 106 operations Housing material CLP NORYL PPO, light grey
@ 18’000 imp/h CLD ABS VO, light grey
Electrical life (typical) AC1 > 250’000 operations Screw type M3
Level probe supply Max. 5 VAC Tightening tourque min/max 0.4Nm/0.8Nm
Level probe current Max. 2 mA Weight
Sensitivity 250Ω to 500KΩ AC supply 200 g
Factory settings standard AC/DC supply 125 g
range “S” 100KΩ UL Approvals cURus UL508, UL325, CSA-C22.2
Ranges L (Low sensitivity) 250 Ω to 5 KΩ, CF* = 4.7 nF No.247
Ranges S (Standard sensitivity) 5 KΩ to 100 KΩ, CF* = 2.2 nF CE marking Yes
*CF = maximum Cable Capacitance
Specifications are subject to change without notice (14.12.2015) 1
CLD2EA1CM24

Mode of Operation
Connection cable electrodes are in contact of a non-conductive mater­ NB!
2, 3, or 4 conductor PVC with the liquid. ial, to an additional electrode. If only one level detection is
cable, normally screened. The reference (Ref) must be (To be connected to pin Y3). required - interconnect the
Cable length: max. 100 m. connected to the container (In the diagram this electrode two inputs Y1 and Y2.
The resistance between the or if the container consists is shown by the dotted line).
cores and the ground must
be at least 500k. Normally,
it is re­
commended to use
a screened cable between
probe and controller, e.g.
where the cable is placed Relay 1 Relay 2
in parallel to the load cables (PE)

(mains). The screen has to be


Ref
Lo
Hi
7 5 6 2 4 3 8 9
connected to Y3 (reference). Y3 Y2 Y1 A1 12 14 22 24

Example 1
The diagram shows the level A2 11 21
control connected as max. 10 1 11
and min. control. The re­lays
react to the low alternating
current created when the X Versión D X = Versión P

Filling Time
Power supply ON

H H Level
S S Y2
Y1
L L
Fill Empty
Y3

Relay ON [11-14] (1-3)


Emptying Time
Power supply ON

H H
Level
S S Y2
Y1
L L
Fill Empty
Y3

Relay ON [11-14] (1-3)


[D-version] (P-version)

2 Specifications are subject to change without notice (14.12.2015)


CLD2EA1CM24

Wiring Diagram
Din-rail version Plug version

HI LO REF
Y2 A1 11 12 14
6
5 7
4 8
5 6
4 7
3 8
2 9

Conductive Level Controller


1 10
Sensitivity

S
H H
S
3 9
L L
Dual Function

Fill Empty

2 10
1 11

Y3 Y1 22 A2 24 21
Supply

Bottom view

Dimension Drawings
Din-rail version Plug version

60,2
60,2

41,5
41,5

81

81

35,5 35,5

Accessories Delivery Contents


• 11 pole circular socket ZPD11 • Amplifier
• Retaining spring HF • Packaging: Carton box
• Manual

Specifications are subject to change without notice (14.12.2015) 3