(TR-7A) TRANSFORMER TEST RESULT (AFTER OIL PURIFICATION AND REGASKETING)
CUSTOMER Western Digital
ADDRESS 109 Technology Ave, Laguna Technopark, Biñan, Laguna
BRAND AM SGB DATE TESTED September 27, 2022
kVA RATING 1500 WEATHER Sunny
SERIAL # 4012246 TEMP. RISE 65 ̊ C
PRIMARY VOLTAGE 6,600 CONNECTION Δ-Y
SECONDARY VOLTAGE 440 VECTOR SIGN Dyn11
PRI. AMPS 131.2 OIL CONTENT Silicone
SEC. AMPS 1968.2 OIL VOLUME 975 Liters
FREQUENCY 60 Hz COOLING ONAN
PHASE Three % IMP. ( @ ˚C) 4.71%
DATE MFD. 2016 UNIT LOCATION Energy Center
I. TURN RATIO TEST
TAP COMPUTED ACTUAL VALUE
3 VALUE PHASE PHASE B PHASE C
6,600/440 15 14.998 14.996 14.996
% ERROR 0.01% 0.02% 0.02%
EQUIPMENT USED TRANSFORMER TURN RATIO TEST SET (VANGUARD INSTRUMENTS CO., INC.)
Remarks PASSED
II. INSULATION RESISTANCE TEST
@ kV (D.C.)
TERMINALS 1 MINUTE 10 MINUTES P.I.
SETTING
PRI. TO GRD. 5 ∞ ∞ 2 ABOVE
SEC. TO GRD. 0.5 ∞ ∞ 2 ABOVE
PRI. TO SEC. 5 ∞ ∞ 2 ABOVE
EQUIPMENT USED HIGH VOLTAGE INSULATION TESTER (KYORITSU MODEL 3125)
Polarization Index Test (P.I.)
Good: 2 and above
Acceptable: 1 to 1.9
Poor: below 1
REMARKS PASSED
III. WINDING RESISTANCE TEST
PRIMARY H1-H2 H1-H3 H2-H3
Test Values Ω 260.5 mΩ 262.2 mΩ 262.8 mΩ
SECONDARY X1-X2 X2-X3 X1-X3
Test Values Ω 1.49 mΩ 1.71 mΩ 1.173 mΩ
SECONDARY X1-X0 X2-X0 X3-X0
Test Values Ω 0.666 mΩ 0.585 mΩ 0.6654 mΩ
EQUIPMENT USED DIGITAL LOW RESISTANCE OHMMETER , TELDAR MODEL TRM-10
REMARKS PASSED
IV. OIL DIELECTRIC STRENGTH TEST
TEST VALUES
TRIALS @ 2.5 mm GAP BREAKDOWN VOLTAGE
1 60 kV
2 50 kV
3 65 kV
[Link]. 58.3 kV
EQUIPMENT USED Oil tester (KEIHIN DENSUKI CO., LTD)
A suggested limit for service-aged insulating fluids (Mineral) is 27kV @
2.5 mm gap.
REMARKS PASSED
TEST CONDUCTED BY: WITNESSED :
Rod Adorable
EIS Inc. Technician/EHS OFFICER 2
PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@[Link] WEBSITE: [Link]
(SWBD-8A) TRANSFORMER TEST RESULT(AFTER OIL PURIFICATION)
CUSTOMER Western Digital
ADDRESS 109 Technology Ave, Laguna Technopark, Biñan, Laguna
BRAND ABB DATE TESTED September 27, 2022
kVA RATING 300 WEATHER Sunny
SERIAL # 12VN1910005617 TEMP. RISE 65 ̊ C
PRIMARY VOLTAGE 6,600 CONNECTION Δ-Y
SECONDARY VOLTAGE 440 VECTOR SIGN Dyn11
PRI. AMPS 26.2 OIL CONTENT Silicone
SEC. AMPS 753.1 OIL VOLUME 910 Liters
FREQUENCY 60 Hz COOLING KNAN
PHASE Three % IMP. ( @ ˚C) 3.92%
DATE MFD. 2019 UNIT LOCATION Energy Center
I. TURN RATIO TEST
TAP COMPUTED ACTUAL VALUE
3 VALUE PHASE PHASE B PHASE C
6,600/440 15 14.98 14.96 14.93
% ERROR 0.13% 0.27% 0.47%
EQUIPMENT USED TRANSFORMER TURN RATIO TEST SET (VANGUARD INSTRUMENTS CO., INC.)
Remarks PASSED
II. INSULATION RESISTANCE TEST
@ kV (D.C.)
TERMINALS 1 MINUTE 10 MINUTES P.I.
SETTING
PRI. TO GRD. 5 ∞ ∞ 2 ABOVE
SEC. TO GRD. 0.5 ∞ ∞ 2 ABOVE
PRI. TO SEC. 5 ∞ ∞ 2 ABOVE
EQUIPMENT USED HIGH VOLTAGE INSULATION TESTER (KYORITSU MODEL 3125)
Polarization Index Test (P.I.)
Good: 2 and above
Acceptable: 1 to 1.9
Poor: below 1
REMARKS PASSED
III. WINDING RESISTANCE TEST
PRIMARY H1-H2 H1-H3 H2-H3
Test Values Ω 1.678 Ω 1.685 Ω 1.633 Ω
SECONDARY X1-X2 X2-X3 X1-X3
Test Values Ω 1.438 mΩ 1.456 mΩ 1.372 mΩ
SECONDARY X1-X0 X2-X0 X3-X0
Test Values Ω 0.9473 mΩ 0.9451 mΩ 0.9485 mΩ
EQUIPMENT USED DIGITAL LOW RESISTANCE OHMMETER , TELDAR MODEL TRM-10
REMARKS PASSED
IV. OIL DIELECTRIC STRENGTH TEST
TEST VALUES
TRIALS @ 2.5 mm GAP BREAKDOWN VOLTAGE
1 72 kV
2 60 kV
3 75 kV
[Link]. 69 kV
EQUIPMENT USED Oil tester (KEIHIN DENSUKI CO., LTD)
A suggested limit for service-aged insulating fluids (Mineral) is 27kV @
2.5 mm gap.
REMARKS PASSED
TEST CONDUCTED BY: WITNESSED :
Rod Adorable
EIS Inc. Technician/EHS OFFICER 2
PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@[Link] WEBSITE: [Link]
TRANSFORMER TEST RESULT (AFTER OIL PURIFICATION)
CUSTOMER Western Digital
ADDRESS 109 Technology Ave, Laguna Technopark, Biñan, Laguna
BRAND ABB DATE TESTED September 27, 2022
kVA RATING 1000 WEATHER Sunny
SERIAL # 1LVN19005827 TEMP. RISE 65 ̊ C
PRIMARY VOLTAGE 6,600 CONNECTION Δ-Y
SECONDARY VOLTAGE 440 VECTOR SIGN Dyn11
PRI. AMPS 87.5 OIL CONTENT Silicone
SEC. AMPS 1312.2 OIL VOLUME 910 Liters
FREQUENCY 60 Hz COOLING KNAN
PHASE Three % IMP. ( @ ˚C) 4.71%
DATE MFD. 2014 UNIT LOCATION Energy Center
I. TURN RATIO TEST
TAP COMPUTED ACTUAL VALUE
3 VALUE PHASE PHASE B PHASE C
6,600/440 15 14.995 14.991 14.9997
% ERROR 0.03% 0.06% 0.03%
EQUIPMENT USED TRANSFORMER TURN RATIO TEST SET (VANGUARD INSTRUMENTS CO., INC.)
Remarks PASSED
II. INSULATION RESISTANCE TEST
@ kV (D.C.)
TERMINALS 1 MINUTE 10 MINUTES P.I.
SETTING
PRI. TO GRD. 5 ∞ ∞ 2 ABOVE
SEC. TO GRD. 0.5 ∞ ∞ 2 ABOVE
PRI. TO SEC. 5 ∞ ∞ 2 ABOVE
EQUIPMENT USED HIGH VOLTAGE INSULATION TESTER (KYORITSU MODEL 3125)
Polarization Index Test (P.I.)
Good: 2 and above
Acceptable: 1 to 1.9
Poor: below 1
REMARKS PASSED
III. WINDING RESISTANCE TEST
PRIMARY H1-H2 H1-H3 H2-H3
Test Values Ω 385.4 mΩ 385.4 mΩ 386.5 mΩ
SECONDARY X1-X2 X2-X3 X1-X3
Test Values Ω 1.324 mΩ 1.344 mΩ 1.363 mΩ
SECONDARY X1-X0 X2-X0 X3-X0
Test Values Ω 0.7390 mΩ 0.7312 mΩ 0.7481 mΩ
EQUIPMENT USED DIGITAL LOW RESISTANCE OHMMETER , TELDAR MODEL TRM-10
REMARKS PASSED
IV. OIL DIELECTRIC STRENGTH TEST
TEST VALUES
TRIALS @ 2.5 mm GAP BREAKDOWN VOLTAGE
1 76 kV
2 67 kV
3 78 kV
[Link]. 73.6 kV
EQUIPMENT USED Oil tester (KEIHIN DENSUKI CO., LTD)
A suggested limit for service-aged insulating fluids (Mineral) is 27kV @
2.5 mm gap.
REMARKS PASSED
TEST CONDUCTED BY: WITNESSED :
Rod Adorable
EIS Inc. Technician/EHS OFFICER 2
PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@[Link] WEBSITE: [Link]
(TR-2F) TRANSFORMER TEST RESULT(AFTER OIL PURIFICATION)
CUSTOMER Western Digital
ADDRESS 109 Technology Ave, Laguna Technopark, Biñan, Laguna
BRAND AM SGB DATE TESTED September 27, 2022
kVA RATING 500 WEATHER Sunny
SERIAL # 727479 TEMP. RISE 65 ̊ C
PRIMARY VOLTAGE 6,600 CONNECTION Δ-Y
SECONDARY VOLTAGE 220 VECTOR SIGN Dyn11
PRI. AMPS 26.2 OIL CONTENT Silicone
SEC. AMPS 793.1 OIL VOLUME 465 Liters
FREQUENCY 60 Hz COOLING LNAN
PHASE Three % IMP. ( @ ˚C) 3.98%
DATE MFD. 2014 UNIT LOCATION Substation 2 EXTENSION
I. TURN RATIO TEST
TAP COMPUTED ACTUAL VALUE
3 VALUE PHASE PHASE B PHASE C
6,600/220 51.9000 50.679 50.683 50.649
% ERROR 0.15% 0.06% 0.09%
EQUIPMENT USED TRANSFORMER TURN RATIO TEST SET (VANGUARD INSTRUMENTS CO., INC.)
Remarks PASSED
II. INSULATION RESISTANCE TEST
@ kV (D.C.)
TERMINALS 1 MINUTE 10 MINUTES P.I.
SETTING
PRI. TO GRD. 5 48.3 GΩ 67.7 GΩ 1.40
SEC. TO GRD. 0.5 42.9 GΩ 56.3 GΩ 1.31
PRI. TO SEC. 5 71.0 GΩ 89.3 GΩ 1.25
EQUIPMENT USED HIGH VOLTAGE INSULATION TESTER (KYORITSU MODEL 3125)
Polarization Index Test (P.I.)
Good: 2 and above
Acceptable: 1 to 1.9
Poor: below 1
REMARKS PASSED
III. WINDING RESISTANCE TEST
PRIMARY H1-H2 H1-H3 H2-H3
Test Values Ω 803.4 mΩ 802 mΩ 802.9 mΩ
SECONDARY X1-X2 X2-X3 X1-X3
Test Values Ω 0.8459 mΩ 0.9783 mΩ 0.9604 mΩ
SECONDARY X1-X0 X2-X0 X3-X0
Test Values Ω 0.5643 mΩ 0.5561 mΩ 0.5633 mΩ
EQUIPMENT USED DIGITAL LOW RESISTANCE OHMMETER , TELDAR MODEL TRM-10
REMARKS PASSED
IV. OIL DIELECTRIC STRENGTH TEST
TEST VALUES
TRIALS @ 2.5 mm GAP BREAKDOWN VOLTAGE
1 71 kV
2 67 kV
3 78 kV
[Link]. 72 kV
EQUIPMENT USED Oil tester (KEIHIN DENSUKI CO., LTD)
A suggested limit for service-aged insulating fluids (Mineral) is 27kV @
2.5 mm gap.
REMARKS PASSED
PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@[Link] WEBSITE: [Link]
TEST CONDUCTED BY: WITNESSED :
Rod Adorable NOTED BY:
EIS Inc. Technician/EHS OFFICER 2
DATE: 9/27/22
PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@[Link] WEBSITE: [Link]
(TR-15B) TRANSFORMER TEST RESULT( AFTER OIL PURIFICATION)
CUSTOMER Western Digital
ADDRESS 109 Technology Ave, Laguna Technopark, Biñan, Laguna
BRAND AM SGB DATE TESTED September 27, 2022
kVA RATING 1000 WEATHER Sunny
SERIAL # 990761 TEMP. RISE 65 ̊ C
PRIMARY VOLTAGE 6,600 CONNECTION Δ-Y
SECONDARY VOLTAGE 440 VECTOR SIGN Dyn11
PRI. AMPS 87.5 OIL CONTENT Silicone
SEC. AMPS 1312.2 OIL VOLUME 910 Liters
FREQUENCY 60 Hz COOLING KNAN
PHASE Three % IMP. ( @ ˚C) 4.71%
DATE MFD. 2014 UNIT LOCATION Substation 3
I. TURN RATIO TEST
TAP COMPUTED ACTUAL VALUE
3 VALUE PHASE PHASE B PHASE C
6,600/440 15 14.9997 14.9997 14.9997
% ERROR 0.02% 0.03% 0.03%
EQUIPMENT USED TRANSFORMER TURN RATIO TEST SET (VANGUARD INSTRUMENTS CO., INC.)
Remarks PASSED
II. INSULATION RESISTANCE TEST
@ kV (D.C.)
TERMINALS 1 MINUTE 10 MINUTES P.I.
SETTING
PRI. TO GRD. 5 3.44 GΩ 4.36 GΩ 1.26
SEC. TO GRD. 0.5 3.24GΩ 4.73 GΩ 1.45
PRI. TO SEC. 5 3.16GΩ 4.81GΩ 1.52
EQUIPMENT USED HIGH VOLTAGE INSULATION TESTER (KYORITSU MODEL 3125)
Polarization Index Test (P.I.)
Good: 2 and above
Acceptable: 1 to 1.9
Poor: below 1
REMARKS PASSED
III. WINDING RESISTANCE TEST
PRIMARY H1-H2 H1-H3 H2-H3
Test Values Ω 362.1 mΩ 362.4 mΩ 362.1 mΩ
SECONDARY X1-X2 X2-X3 X1-X3
Test Values Ω 1.671mΩ 1.653mΩ 1.682mΩ
SECONDARY X1-X0 X2-X0 X3-X0
Test Values Ω 0.5759 mΩ 0.5788 mΩ 0.5303 mΩ
EQUIPMENT USED DIGITAL LOW RESISTANCE OHMMETER , TELDAR MODEL TRM-10
REMARKS PASSED
IV. OIL DIELECTRIC STRENGTH TEST
TEST VALUES
TRIALS @ 2.5 mm GAP BREAKDOWN VOLTAGE
1 55 kV
2 50 kV
3 53 kV
[Link]. 52.67kV
EQUIPMENT USED Oil tester (KEIHIN DENSUKI CO., LTD)
A suggested limit for service-aged insulating fluids (Mineral) is 27kV @
2.5 mm gap.
REMARKS PASSED
TEST CONDUCTED BY: WITNESSED :
PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@[Link] WEBSITE: [Link]
NOTED BY:
Rod Adorable
EIS Inc. Technician/EHS OFFICER 2
(TR-21B) TRANSFORMER TEST RESULT( AFTER OIL PURIFICATION)
CUSTOMER Western Digital
ADDRESS 109 Technology Ave, Laguna Technopark, Biñan, Laguna
BRAND AM SGB DATE TESTED September 27, 2022
kVA RATING 1000 WEATHER Sunny
SERIAL # 723761 TEMP. RISE 65 ̊ C
PRIMARY VOLTAGE 6,600 CONNECTION Δ-Y
SECONDARY VOLTAGE 230 VECTOR SIGN Dyn11
PRI. AMPS 87.5 OIL CONTENT Silicone
SEC. AMPS 2510 OIL VOLUME 910 Liters
FREQUENCY 60 Hz COOLING KNAN
PHASE Three % IMP. ( @ ˚C) 5.09%
DATE MFD. 2012 UNIT LOCATION Substation 3
I. TURN RATIO TEST
TAP COMPUTED ACTUAL VALUE
3 VALUE PHASE PHASE B PHASE C
6,600/230 28.695 28.682 28.685 28.688
% ERROR 0.04% 0.03% 0.02%
EQUIPMENT USED TRANSFORMER TURN RATIO TEST SET (VANGUARD INSTRUMENTS CO., INC.)
Remarks PASSED
II. INSULATION RESISTANCE TEST
@ kV (D.C.)
TERMINALS 1 MINUTE 10 MINUTES P.I.
SETTING
PRI. TO GRD. 5 3.56GΩ 4.64GΩ 1.30
SEC. TO GRD. 0.5 2.68GΩ 2.88GΩ 1.07
PRI. TO SEC. 5 3.42GΩ 4.78GΩ 1.39
EQUIPMENT USED HIGH VOLTAGE INSULATION TESTER (KYORITSU MODEL 3125)
Polarization Index Test (P.I.)
Good: 2 and above
Acceptable: 1 to 1.9
Poor: below 1
REMARKS PASSED
III. WINDING RESISTANCE TEST
PRIMARY H1-H2 H1-H3 H2-H3
Test Values Ω 365.1 mΩ 364.7 mΩ 364.6 mΩ
SECONDARY X1-X2 X2-X3 X1-X3
Test Values Ω 0.9683 mΩ 0.9675 mΩ 0.9670 mΩ
SECONDARY X1-X0 X2-X0 X3-X0
Test Values Ω 0.7334 mΩ 0.7339 mΩ 0.7337 mΩ
EQUIPMENT USED DIGITAL LOW RESISTANCE OHMMETER , TELDAR MODEL TRM-10
REMARKS PASSED
IV. OIL DIELECTRIC STRENGTH TEST
TEST VALUES
TRIALS @ 2.5 mm GAP BREAKDOWN VOLTAGE
1 71 kV
2 62 kV
3 76 kV
[Link]. 69.6 kV
EQUIPMENT USED Oil tester (KEIHIN DENSUKI CO., LTD)
A suggested limit for service-aged insulating fluids (Mineral) is 27kV @
2.5 mm gap.
REMARKS PASSED
PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@[Link] WEBSITE: [Link]
TEST CONDUCTED BY: WITNESSED :
Rod Adorable
EIS Inc. Technician/EHS OFFICER 2