Technical Specifications
Technical Specifications
Proposed by: John Paul Bonus, John Kennedy Manio, and John Paul Opiana
Location: San Rafael, Tarlac City, Philippines
TECHNICAL SPECIFICATIONS
SPECIFICATIONS
These specifications outline the methods of construction and the types of
materials to be used in the execution of the proposed Two-Storey Residential
Building, as illustrated in the architectural and engineering plans and detailed
drawings.
The plans, detailed drawings, and this specification document shall be
interpreted as mutually complementary. Any requirement or detail indicated in
either the plans or the specifications—though not explicitly mentioned in the
other—shall be deemed as included in both and is therefore binding for
execution.
GENERAL CONDITIONS
All phases of construction shall be executed with first-class workmanship
and in strict accordance with the intent and requirements of the plans and these
specifications. The finished work shall reflect the quality standards expected of
a well-executed residential building project.
The construction works shall strictly comply with the provisions of the
National Building Code of the Philippines, as well as all applicable local
ordinances and regulations enforced by the City/Municipality of Tarlac,
Philippines and other relevant authorities.
All works described herein shall conform to the generally accepted
standards and practices prescribed by current building codes, rules, and
technical regulations, including but not limited to:
• ASTM (American Society for Testing and Materials)
• ACI (American Concrete Institute)
• Philippine National Standards (PNS)
• National Building Code of the Philippines
• National Structural Code of the Philippines
• Philippine Electrical Code
• Philippine Plumbing Code
• Philippine Mechanical Code
• And all other applicable national standards and local ordinances
governing construction, safety, and environmental compliance.
DIVISION 1 – GENERAL REQUIREMENTS
1.1 Permits and Legal Requirements
The Contractor shall be solely responsible for securing all permits,
clearances, licenses, and certificates necessary for the lawful commencement
and execution of the works. These shall include, but are not limited to:
• Building Permit
• Excavation Permit
• Electrical Permit
• Plumbing and Sanitary Permit
• Mechanical Permit
• Occupancy Permit
Additionally, the Contractor shall obtain and maintain the following
insurance policies for the full duration of the project:
• Contractor’s All Risk Insurance (CARI)
• Third-Party Liability Insurance
• Workmen’s Compensation Insurance
• Any other insurance policies as may be required by the Local Government
Unit (LGU) or other regulating agencies.
All fees, charges, and associated costs for the procurement of permits and
insurances shall be shouldered by the Contractor. Proof of compliance, including
copies of approved permits and insurance policies, shall be submitted to the
Public-Private Partnership (PPP) Center prior to mobilization and as part of
project documentation.
2.1 CLEARING
The Contractor shall clear the entire project site, including a buffer zone
of at least 10 meters from the edge of the outermost project component, unless
otherwise directed by the Architect.
Clearing includes the complete removal of all trees, roots, shrubs,
vegetation, topsoil, organic and unsuitable materials, surface obstructions,
rubbish, existing structures, and other debris. Special care shall be taken to
preserve any elements designated to remain.
Cleared materials shall be hauled, transferred, or stockpiled in designated
areas within the site as approved by the architect. Materials not approved for
reuse shall be properly disposed of off-site in compliance with environmental
and municipal regulations.
2.3 EXCAVATION
Excavation works shall include removal of soil, rock, or existing fill to the
required depths and profiles shown in the drawings. Excavation shall only
proceed with prior authorization and shall not exceed indicated levels unless
instructed by the PSG.
All excavation faces shall be supported with proper shoring, bracing, or
sheeting to prevent collapse, subsidence, or injury. Blasting or hazardous
methods of excavation are strictly prohibited.
Should unauthorized over-excavation occur, the void shall be filled with
lean concrete (Class B) or engineered fill, subject to approval and at no cost to
the Owner. A coordination meeting shall be conducted immediately to
document and resolve the incident.
Dewatering shall be performed continuously as needed to maintain dry
and safe working conditions. Measures shall be taken to avoid disturbance or
removal of adjacent soils. Standing water shall not be allowed to accumulate at
the bottom of excavations.
Subgrade surfaces shall be cleared of loose soil, debris, and standing
water prior to pouring concrete. PSG inspection and approval shall be obtained
before proceeding with gravel bedding, reinforcement installation, or any
concrete works.
Temporary enclosures or warning barricades shall be placed around all
excavated areas. All excavations must be covered or protected when work is
not in progress to avoid accidents and ingress of debris or water.
2.4 GRADING, BACKFILLING, AND COMPACTION
Grading operations shall be limited to the areas designated on the
approved plans. No unauthorized cutting or grading shall occur outside
specified zones unless approved in writing by the PSG.
Backfill materials shall consist of common or approved on-site excavated
materials, free from organic matter, large rocks, debris, or perishable
components. Select fill shall be used where specified and shall consist of crushed
rock, gravel, or sand approved by the architect.
Before placement of fill, the base shall be scarified, cleared of all organic
or loose material, and moistened to ensure bonding with the new material.
Backfill shall be placed in uniform horizontal layers not exceeding 150 mm
(6") in loose thickness. Each layer shall be wetted and compacted by tamping
or mechanical rolling to not less than 90% of the maximum dry density in
accordance with ASTM D1557, Method D (Modified Proctor):
• Under building slabs on grade: minimum 90%
• Under paved or unpaved exterior areas: minimum 90%
• Subgrade for footings and structural members: minimum 90%
The Contractor shall perform field density tests (FDT) per lift to verify
conformance with compaction requirements. All results shall be submitted to
the PSG for approval prior to the next layer's placement.
Final fill layers under slabs shall consist of 50 mm (2") of fine granular
material (sand or crushed gravel), leveled and compacted.
A. MATERIALS
1. Cement
Portland Cement used for concrete shall conform to ASTM C150 Type I or
Type IP, and shall be sourced only from PSG-approved manufacturers. The
cement must be delivered in unopened, properly labeled bags, free from lumps
and moisture. Each batch delivered on-site shall be accompanied by a
manufacturer's Certificate of Compliance. Advance Cement shall be the
designated brand unless otherwise approved by PSG.
2. Water
Mixing water must be clean, potable, and free from injurious amounts of
oils, alkalis, salts, acids, organic matter, or other deleterious substances. Water
from potentially contaminated sources (e.g., surface runoff, seawater) shall not
be used unless tested and approved by PSG.
3. Fine Aggregates
Fine aggregates (sand) shall conform to PNS 18, Type 1 specifications.
Sand shall be composed of hard, dense, and durable natural or manufactured
particles, generally rounded or cubical in shape, free from clay lumps, soft
particles, organic matter, loam, or other foreign substances. The fineness
modulus shall be within the range of 2.3 to 3.1. Sand must be graded and washed
if required to meet gradation and cleanliness standards.
4. Coarse Aggregates
Coarse aggregates (crushed stone or gravel) shall comply with PNS 18,
Type 2 specifications and consist of clean, hard, durable, and uncoated particles
free from clay, silt, dust, or other deleterious substances.
o Use 1" maximum size for footings.
o Use 3/4" maximum size for beams, columns, and slabs.
Gradation shall conform to ASTM C33, and aggregates must be stockpiled
on clean platforms with adequate separation to prevent contamination or
intermixing.
5. Reinforcing Steel
Deformed steel bars shall be from Steel Asia or other PSG-approved
equivalent suppliers and must comply with ASTM A615 Grade 40 for billet steel
bars. Bars must be properly tagged for easy identification. Reinforcement bars
shall not be re-rolled or second-hand, and only new materials will be accepted.
6. Tie Wire
All intersections of reinforcing bars shall be tied using #16 galvanized iron
(G.I.) wire. Tie wire shall be of sufficient strength to ensure rebar stability during
concrete placement and vibration. Ends of tie wire must be bent away from
formwork to prevent surface blemishes.
B. CONCRETE
B.1. Proportioning and Mixing of Concrete
1. Concrete Classes and Proportions
Concrete shall be proportioned by weight or volume according to the
following standard mix designs:
Class Compressive Strength (28 days)
A 1:2:4 3000 psi for columns, beams, footings, tie beams
walks, driveways, hollow blocks mortar,
filler, plastering, floor and slabs on fill.
B 1 : 2.5 : 5 2500 psi Pipe bedding, for filling unauthorized over-
excavation voids, and other PSG
authorized used.
C 1:3:6 2000 psi thin reinforced sections, railings, for
filler in steel grid floors, and other PSG
authorized used.
2. Design Strength
Unless otherwise indicated in structural drawings, all concrete for
structural components (footings, beams, slabs, columns, walls) shall have a
minimum 28-day compressive strength of 3000 psi.
3. Mixing
Concrete shall be machine mixed using batch mixers with accurate
measuring of materials. Mixing shall begin within 30 minutes of adding cement
to aggregates. In remote areas, hand mixing may be allowed with prior approval,
provided mixing is done under direct supervision and in watertight platforms.
Mix must be uniform and free from dry pockets or excess water.
B.4. Finishing
1. General Finish Requirements
No plastering of concrete surfaces unless otherwise specified. Exposed
concrete shall be smooth and formed using high-quality plywood. Minor defects
must be repaired using approved patching products (e.g., Buildrite) only after
notifying PSG. Cement paste application is prohibited for hiding defects.
2. Slab on Fill
Concrete slabs on fill shall be placed over compacted subgrade and granular
base (G1), 50 mm minimum thickness or as specified. Proper moisture barrier
and jointing must be provided.
3. Non-slip Finish
Ramps, rear garages, and walkways must have broomed or textured non-slip
finish for safety.
4. Rough Finish
Rough float finish shall be provided where tiling or other finishes are to be
applied, including wet areas and bathrooms.
5. Smooth Finish
Smooth, steel-trowelled finish is required for the elevator pit floor. This must be
monolithic and finished while concrete is still plastic.
C. REINFORCEMENT
GENERAL
All reinforcement works shall conform to the latest American Concrete
Institute (ACI 318) provisions, ASTM standards, and the Philippine Structural
Code. Reinforcing steel shall be accurately placed and adequately secured to
resist displacement during concrete placement.
Reinforcement shall be free of oil, dirt, loose rust, mill scale, paint, or other
coatings that may reduce bond between steel and concrete. Prior to concrete
pouring, all reinforcement shall be inspected and approved by the Project
Supervision Group (PSG).
C1. MATERIALS
All reinforcing bars (rebars) shall be deformed steel bars, hot-rolled,
meeting the specifications of ASTM A615 Grade 40 or Grade 60, or equivalent,
and must be certified by the manufacturer (e.g., Steel Asia or approved
equivalent). Mill certificates indicating physical and chemical properties shall be
submitted to PSG for evaluation and approval.
1. Bar Sizes and Applications:
• 16 mm diameter deformed bar
o Primary bars for:
▪ Columns (vertical main bars)
▪ Beams (top and bottom reinforcement near supports)
▪ Footings (main reinforcement for isolated and combined
footings)
▪ Tie Beams (longitudinal bars)
o Selected for its high tensile strength and appropriate for major load-
bearing members.
• 12 mm diameter deformed bar
o Used at beam mid-span top bars where bending moments are
greatest and tension reinforcement is necessary.
o Also suitable for secondary structural reinforcements as specified
in structural drawings.
• 10 mm diameter deformed bar
o Used for:
▪ Beam stirrups (shear reinforcement spaced at calculated
intervals)
▪ Column lateral ties (to resist buckling of vertical bars and
provide confinement)
▪ Concrete Hollow Block (CHB) Wall Reinforcement (vertical
and horizontal bars embedded within block cells and grout)
o Ensures structural integrity and crack resistance in confinement
zones.
• #16 G.I. TIE WIRE (Gauge 16)
o To be used for securing all bar intersections, ensuring proper
placement during concrete pouring.
o Ties must be tight and ends shall be bent away from formwork to
prevent surface blemishes.
C4. SUBMITTALS
• Submit shop drawings for review and approval, showing:
o Bar bending schedules
o Splice locations
o Supports and clearances
• Submit mill certificates and material test reports from the supplier for all
steel bars.
• Provide a sample of each size of rebar to be used for approval before
procurement.
Actual removal timing may be adjusted based on field curing conditions and the
results of cylinder compression tests.
D2. SCAFFOLDING
All scaffolding used during construction activities shall:
• Comply with the Construction Occupational Safety and Health Standards
(COSH) of the Department of Labor and Employment (DOLE).
• Be rigid, stable, and properly anchored, capable of supporting all
expected live and dead loads.
• Include appropriate fall protection systems, toe boards, and guardrails as
required for safe access and work at height.
• Be erected by qualified personnel and inspected prior to use.
Temporary platforms shall provide safe working surfaces for all trades,
especially those involved in form setting, reinforcement installation, and
concrete placement.
All scaffolding that is no longer required shall be promptly dismantled and
removed from the construction site to ensure site safety and reduce
obstruction.
DIVISION 4 – MASONRY
A. MATERIALS
1. Concrete Hollow Blocks (CHB)
o Exterior Walls:
▪ Use 5” x 8” x 16” nominal size CHB (actual thickness: 150mm).
▪ Minimum face shell thickness: 25mm (1").
▪ Minimum compressive strength: 350 psi at 28 days.
▪ Used for all lower and upper floor exterior walls, including
parapets and exterior partitions.
o Interior Walls:
▪ Use 4” x 8” x 16” CHB (actual thickness: 100mm) for typical
interior partitions.
▪ Use 5” (150mm) thick CHB for walls accommodating
plumbing fixtures and piping.
▪ All CHBs shall be of uniform shape and size, free from cracks,
honeycombing, or visible defects.
Storage Requirements:
All CHBs shall be cured and stored for a minimum of twenty-eight (28)
days prior to delivery to site. CHBs that do not meet the required strength or
that show signs of defects shall be rejected. Submit physical samples and
manufacturer's certificate for approval.
2. Reinforcement for Masonry Walls
o Use 10 mm Ø deformed steel bars (No. 3, Grade 40) by Steel Asia
or equivalent approved brand.
o Reinforcement shall be embedded vertically and horizontally into
the block cells, anchored properly, and fully grouted.
o Submit mill certificates in accordance with Section TS-3.B for
compliance review.
3. Sand for Mortar and Plaster
o Sand shall be well-graded river sand, clean, hard, sharp, free from
silt, loam, clay, or other deleterious substances.
o Sand shall comply with the requirements of ASTM C144.
4. Cement
o Use only standard Portland cement complying with ASTM C150
Type I or Type IP. Refer to Section TS-3.B for additional
specifications.
o Advance Cement is the preferred brand, or approved locally
available equivalent.
5. Mortar and Plaster Mix
o Mortar shall be freshly mixed in batches for immediate use.
o Mixing shall not exceed 30–35 minutes per batch.
o Mortar shall be discarded if not used within one (1) hour or if
premature setting is observed.
o Re-tampering of mortar shall not be permitted unless an approved
admixture is used. Manufacturer’s data sheet for admixture must be
submitted for PSG approval.
D. SCAFFOLDING
• All scaffolding used for masonry and plastering works shall conform to
COSH (Construction Occupational Safety and Health) standards.
• Scaffolds shall be:
o Rigid, stable, and of sufficient capacity to carry expected loads.
o Properly braced and anchored against tipping or collapse.
o Inspected prior to use, and daily thereafter during active use.
• When masonry works requiring elevation are complete, scaffolding shall
be immediately dismantled and cleared from the site to ensure safety and
site organization.
DIVISION 5 – METALS
GENERAL
This section includes the supply, fabrication, delivery, and installation of
all metal components, including stainless steel railings, roof and ceiling framing,
and structural steel items as shown in the drawings and described in the
specifications.
All materials and workmanship shall comply with applicable ASTM
standards, NSCP (National Structural Code of the Philippines), and local building
regulations. Welding, bolting, and other joining methods shall conform to the
requirements of the American Welding Society (AWS) and Structural Steel
Code.
All steel materials shall be:
• Free from rust, scale, oil, paint, or other coatings unless specified.
• Straight, true, and without warping or deformity.
• Delivered with mill certifications, showing compliance with the required
specifications.
2. ROOF FRAMING
2.1 C-Purlins
• Material: Galvanized steel, high-tensile strength (minimum G550 grade).
• Dimensions: 2" x 4" (50mm x 100mm) with a minimum thickness of 1.5mm.
• Application: Used as roof rafters or purlins, spaced and supported in
accordance with structural calculations.
• Must be fastened using self-drilling screws (tekscrews) with neoprene
washers or bolt and nut assemblies, depending on load requirements.
2.2. Angle Bar Roof Trusses
• Chord Members: Use 2” x 2” x 3/16” thick mild steel angle bars.
• Web/Mid Members: Use 1-1/2” x 1-1/2” x 3/16” thick angle bars.
• Assembly:
o All members shall be fully welded at connections using 6013
welding rods, minimum three passes per joint.
o Welding shall be continuous unless otherwise detailed, and excess
spatter removed.
o Trusses shall be fabricated and installed plumb, level, and true to
alignment.
• Corrosion Protection: All members shall be wire-brushed, cleaned, and
painted with red oxide primer followed by two coats of epoxy enamel
(unless hot-dip galvanized).
3. CEILING FRAMING
3.1. Metal Furring System
• Material: Galvanized steel or aluminum furring channel, rust-resistant,
factory-rolled.
• Main Furring: 35mm x 70mm metal furring channel
• Cross Furring / Carrying Channels: Compatible sizes to support specified
ceiling board material (e.g., 1/4" Hardiflex).
• Spacing:
o Main channels: 0.60 to 1.20 meters on center depending on ceiling
span and load.
o Cross furring: As required to support ceiling board edges (typically
0.40 to 0.60m on center).
• Suspension System: Use GI suspension rods, adjustable hangers, and
approved anchors embedded in slab or beam ceiling.
• Must provide flat, level, and rigid support for the entire ceiling surface.
A. ROOFING SYSTEM
1. Roofing Panels
• Roofing shall be Long Span Rib-Type Pre-Painted GI Sheets, with the
following specifications:
o Material thickness: Gauge 26
o Profile: Rib-type (as shown in architectural and structural drawings)
o Finish: Factory pre-painted, oven-baked enamel coating with UV
and corrosion resistance
o Color: As approved by the Architect
2. Accessories and Flashing
• Flashing, Ridge Rolls, and Valley Rolls shall be:
o Material: Same as roofing (Pre-Painted GI)
o Thickness: Gauge 26
o Installation: Properly overlapped and sealed using neoprene
washers, fasteners, and approved sealant to ensure watertight
joints.
3. Gutter System
• Gutters shall be:
o Pre-formed Gauge 24 Pre-Painted GI Sheet
o Size and profile: As detailed in approved shop drawings and roof
plan
o Slope: Minimum 1/8” per foot to ensure proper drainage and prevent
water ponding
• Downspouts shall match the gutter material and shall be properly
supported and securely fastened to the structure.
4. Fasteners
• Use self-drilling, corrosion-resistant screws with EPDM washers.
• Screws shall be spaced in accordance with manufacturer’s
recommendations and local wind load calculations.
All door sizes and configurations shall be verified on site and coordinated with
architectural and structural openings.
2. PAINTING WORKS
GENERAL
All surfaces to be painted shall be properly prepared prior to application.
Painting shall be executed in accordance with manufacturer instructions and
under the supervision of qualified personnel. Boysen paint products or their
approved equivalents shall be used throughout the project.
2.2 Surface Preparation Sequence
1. Surface Leveling: Remove protrusions and irregularities; sand surfaces to
achieve a smooth base.
2. Acid Neutralization: Apply concrete neutralizer to remove residual
acidity that may affect paint adhesion.
3. Primer Application: Use a primer-sealer to improve paint adhesion, block
efflorescence and water stains, and create a uniform base.
4. Lacquer or Seal Coat: Where applicable, apply a lacquer or hardening
base coat on wood or metal substrates.
5. Final Paint Coats: Apply two (2) full coats of the specified topcoat after
proper drying of undercoats.
2.3 Painting Specifications
• Exterior Masonry Surfaces:
o One (1) primer coat
o Two (2) coats of exterior latex paint (weather-resistant)
• Interior Masonry Surfaces:
o One (1) primer coat
o Two (2) coats of interior latex paint
• Exterior Wood Surfaces:
o One (1) primer coat
o Two (2) coats of exterior-grade enamel or house paint
• Interior Wood Surfaces:
o Application of putty coat to smoothen surfaces
o Two (2) coats of flat wall enamel
2.4 Additional Requirements
• Painting includes all surfaces of wood, concrete, metal, and drywall—
interior and exterior—unless noted otherwise.
• All paint materials must conform to Class “A” paint standards and relevant
provisions of the National Building Code.
• Color Scheme: All colors and finishes shall be subject to approval by the
Owner with final recommendation from the Project Architect. Paint
samples shall be submitted for final confirmation prior to implementation.
DIVISION 10 – SPECIALTIES
1.0 TOILET AND BATH ACCESSORIES
GENERAL
All toilet and bath accessories shall be selected from reputable brands
readily available in the local market, preferably from Wilcon Depot or similar
authorized distributors. Products must conform to relevant Philippine standards
and meet high-quality thresholds in terms of durability, aesthetic appeal, and
functionality.
All fixtures and accessories shall be:
• Installed by qualified tradesmen.
• Properly aligned, leveled, and secured.
• Compatible with the plumbing layout and wall/floor finishes.
• Accompanied by the manufacturer's installation and maintenance guides.
Shop drawings and product data sheets shall be submitted for approval prior to
procurement and installation.
1.2 Installation
• Accessories shall be installed after wall and floor finishes are completed
to avoid damage or misalignment.
• Floor drains shall be embedded flush with tile surfaces and provided with
traps where required.
• Anchors and fasteners used shall be non-corrosive and concealed
wherever possible.
• Final placement of accessories shall consider ergonomics and user
accessibility, and must conform to the plans and/or approved shop
drawings.
DIVISION 11 – EQUIPMENT
1. KITCHEN EQUIPMENT
GENERAL
All kitchen equipment to be provided and installed under this contract
shall be Panasonic brand or an approved equivalent, subject to evaluation and
acceptance by the Project Architect and Project Supervision Group (PSG).
Equipment shall be energy-efficient, space-saving, and in accordance with
current appliance safety standards.
1.1 Equipment Placement and Sizing
• Equipment dimensions, orientation, and model specifications shall strictly
follow the architectural and kitchen layout plans as indicated in the
construction drawings.
• Coordination with electrical and plumbing provisions is required to ensure
appropriate location of power outlets, water lines, and drainage.
• Ventilation or exhaust requirements must be verified during coordination
meetings.
1.2 Typical Kitchen Equipment (Indicative List)
The actual list may vary based on Owner preference and appliance availability.
Equipment Remarks
Refrigerator Panasonic, inverter-type preferred
Range or Cooktop Induction or gas type, built-in design
Built-in Oven Electric type, under-counter placement
Range Hood / Exhaust Fan Ducted or recirculating as applicable
Dishwasher (optional) Built-in or under-counter
1.3 Submittals
Submit product brochures, shop drawings, and technical specifications
for each piece of equipment for approval prior to purchase. Include installation
manuals and power/water requirements. Submit as-built kitchen layout
reflecting final equipment placement.
DIVISION 15 – MECHANICAL
1.0 PLUMBING SYSTEM
GENERAL
All plumbing works for this project shall be implemented in accordance
with the approved plumbing plans and under the direct supervision of a duly
licensed Sanitary Engineer or Master Plumber. The Contractor shall ensure full
compliance with:
• The National Plumbing Code of the Philippines
• Applicable local government regulations and ordinances
• Standards set by the Philippine Society of Sanitary Engineers (PSSE) and
other governing authorities
1.1 Installation Requirements
• All piping systems shall be properly graded and pitched to ensure
unrestricted flow and prevent the occurrence of water hammer, noise, and
trapped air.
• Adequate provisions must be made for cleanouts, access panels, and
ventilation as required by the code.
• All joints shall be securely and permanently connected using compatible
and approved materials.
• All embedded pipelines shall undergo flow and leak testing prior to
backfilling or enclosure.
1.2 Drainage, Waste, and Vent (DWV) System
• All DWV pipes shall use uPVC push-on type system, brand EMERALD or
approved equivalent.
• Pipes shall conform to the standards of ASTM D2729 or PNS 65-2, and be
properly supported at intervals not exceeding 1.5 meters.
• Elastomeric rubber gaskets shall be used for all joints. Use solvent cement
only where specifically allowed.
1.3 Water Supply System
• All in-house water supply piping shall be uPVC pipes and fittings from
NELTEX Series 1000 or approved equivalent.
• Pressure rating shall conform to PN 12/PN 20 standards, depending on
the demand per fixture unit and building height.
• Provide PPR gate and ball valves in key locations such as branch lines,
risers, and fixtures for future isolation and maintenance.
1.4 Fixture Connection and Supports
• Plumbing fixtures (e.g., lavatories, kitchen sinks, toilets) shall be
connected with flexible stainless braided hoses or as recommended by
the manufacturer.
• Pipes shall be supported with rigid galvanized iron (GI) straps, brackets,
or concrete saddles. No pipe shall be left hanging without proper
anchorage.
1.5 Testing and Commissioning
• Conduct the following tests before final acceptance:
o Leak Test: Apply pressure to water lines to check for leaks under
normal operating conditions.
o Flow Test: Observe the water flow at critical outlets to ensure
adequate pressure and delivery.
o 24-Hour Flood Test: For all embedded sanitary pipelines prior to
tiling or backfill.
• Submit a Test Certificate signed by the supervising licensed sanitary
engineer.
1.6 Submittals and Documentation
• Submit shop drawings, including:
o Piping layout, riser diagrams, fixture connections, valve locations
o Manufacturer specifications of all pipes, fittings, valves, and
accessories
• Submit as-built drawings upon completion of works
• Submit warranties and maintenance manuals for all installed plumbing
components
DIVISION 12 – ELECTRICAL
1. GENERAL
1.1 Scope of Work
The electrical works for this project shall include the complete supply,
installation, testing, and commissioning of all electrical systems in accordance
with the approved electrical plans, applicable codes and standards, and under
the direct supervision of a licensed Professional Electrical Engineer (PEE) or
Registered Master Electrician (RME).
1.2 Codes and Standards
All electrical materials and workmanship shall conform to the following:
• Philippine Electrical Code (PEC), latest edition
• National Electrical Code (NEC), where applicable
• National Building Code of the Philippines
• Requirements of the local electric utility provider (TEI / TARELCO)
• All relevant safety and quality regulations
3. MATERIAL SPECIFICATIONS
Component Approved Brand / Remarks
Circuit Breakers MEIJI Electric – bolt-on, industrial type