The document provides detailed specifications for various low-tension (LT) panels and their associated circuit breakers, including incoming breaker sizes, load capacities, and cable sizes. It outlines the load distribution across different phases and includes future load considerations for several circuits. Additionally, it details the incoming cables and circuit configurations for multiple distribution boards (DBs) and sub-main distribution boards (SMDBs).

Uploaded by

Sreejesh Sree
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views28 pages

LV PANEL-28A02 Rev-01 Updated 16.07.2023

The document provides detailed specifications for various low-tension (LT) panels and their associated circuit breakers, including incoming breaker sizes, load capacities, and cable sizes. It outlines the load distribution across different phases and includes future load considerations for several circuits. Additionally, it details the incoming cables and circuit configurations for multiple distribution boards (DBs) and sub-main distribution boards (SMDBs).

Uploaded by

Sreejesh Sree
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

LT PANEL

LT PANEL-28A02 FED FROM :TRANS-28A02 INCOMING BREAKER SIZE : 2500 ATP ACB 50KA
REF :

LOC: FAC.-28A /LV ROOM LT PANEL SIZE : 10 WAYS INCOMING CABLE SIZE : 11x1C,630mm2 CU XLPE/AWA/PVC

CIRCUIT BREAKER PHASE LOAD (KW)


MDB
MDB LOAD
MCCB DIVERSIFIE DIVERSITY
CABLE SIZE (mm2) DESCRIPTION LOAD (KW) AFTER REMARKS
CIRCUIT NO RATING (A) R Y B D LOAD FACTOR
DIVERSITY
50KA (%)

1RYB 630 FUTURE LOAD FOR FP-2806 411.16 142.40 131.60 137.60 209.37 90 188.43

2RYB 400 4C, 300mm2 CU XLPE/SWA/PVC FP-28A07 226.96 82.04 69.64 75.29 142.40 90 128.16

3RYB 400 4C,300mm2 CU XLPE/SWA/PVC MDB-13A01 298.98 96.21 99.26 103.51 193.12 90 173.81

4RYB 630 FUTURE LOAD 500.00 166.67 166.67 166.67 250.00 90 225.00

5RYB 630 FUTURE LOAD 500.00 166.67 166.67 166.67 250.00 90 225.00

6RYB 630 FUTURE LOAD 500.00 166.67 166.67 166.67 250.00 90 225.00

7RYB 400 SPARE

8RYB 160 SPARE

9RYB 125 SPARE

2X4C, 150mm2 CU XLPE/SWA/PVC+2X 1C,


10RYB 630 C.B-28A02-(300 KVAR)
70mm2 CU.PVC

TOTAL LOAD(KW) = 2437.10 820.65 800.50 816.39 1165.41


INCOMING BREAKER
FP REF : FP-28A07 FED FROM : LT PANEL-28A02 400 ATP MCCB 50KA
SIZE :
OUT DOOR FP SIZE : 6 WAYS INCOMING CABLE SIZE : 4C, 300mm2 CU XLPE/SWA/PVC

CIRCUIT BREAKER PHASE LOAD (KW) MDB's CIRCUIT


DIVERSIFIE
DIVERSIFIE DIVERSITY DIVERSIFIED
MCCB CABLE SIZE (mm2) DESCRIPTION LOAD (KW) D LOAD
D LOAD FACTOR LOAD (KW)
CIRCUIT NO RATING (A) R Y B (KW)
(KW) (%)
35KA

1RYB 125 FUTURE LOAD FOR SMDB-14A01 41.50 17.47 13.37 14.67 24.68 90 22.21

2RYB 125 FUTURE LOAD FOR SMDB-15A01 41.50 17.47 13.37 14.67 24.68 90 22.21

3RYB 250 4C, 120mm2 CU XLPE/SWA/PVC ATS-16A01 134.34 47.10 41.30 45.95 107.76 90 96.99

4R 40 SPARE
4Y 25 3C, 10mm2 CU XLPE/SWA/PVC CU-27B01 1.60 1.60 1.10 90 0.99
4B 40 SPARE

5RYB 125 SPARE

6RYB 200 SPARE

TOTAL LOAD(KW) = 226.96 82.04 69.64 75.29 142.40


INCOMING BREAKER
SMDB REF : SMDB-16A01 FED FROM : ATS -16A01 / FP-28A07 250 A MCCB 35KA
SIZE :
LOC. : FAC.-16A/ G F / ELEC.RM SMDB SIZE : 14 WAYS INCOMING CABLE SIZE : 4C, 120mm2 CU XLPE/SWA/PVC

CIRCUIT BREAKER PHASE LOAD (KW) DB's


CIRCUIT DIVERSIFIE
DIVERSIFIE
MCCB CABLE SIZE (mm2) DESCRIPTION LOAD (KW) DIVERSITY D LOAD REMARKS
D LOAD
CIRCUIT NO RATING (A) R Y B FACTOR (%) (KW)
(KW)
25KA

4C, 16mm2 CU XLPE/SWA/PVC+1C, 16mm2


1RYB 63 DB-16A01 15.04 5.60 5.00 4.45 10.3 90 9.30
CU.PVC

4C, 50mm2 CU XLPE/SWA/PVC+1C, 25mm2


2RYB 125 DB-16A01/UPS 39.60 13.60 12.40 13.60 29.70 90 26.73
CU.PVC

4C,16mm2 CU XLPE/SWA/PVC+1C,16mm2
3RYB 63 TPN ISOLATOR FOR CCU-G1 (DUTY) 23.70 7.90 7.90 7.90 23.70 90 21.3
CU.PVC

4C,16mm2 CU XLPE/SWA/PVC+1C,16mm2
4RYB 63 TPN ISOLATOR FOR CCU-G1 ( STAND BY)
CU.PVC

4C,10mm2 CU XLPE/SWA/PVC+1C,10mm2
5RYB 40 TPN ISOLATOR FOR CCU-G2 (DUTY) 16.70 5.57 5.57 5.57 16.70 90 15.0
CU.PVC

4C,16mm2 CU XLPE/SWA/PVC+1C,16mm2
6RYB 63 TPN ISOLATOR FOR CCU-G3 (DUTY) 16.70 5.57 5.57 5.57 16.70 90 15.0
CU.PVC

4C,6mm2 CU XLPE/SWA/PVC+1C, 6mm2


7RYB 32 TPN ISOLATOR FOR AHU-1 1.50 0.50 0.50 0.50 1.50 90 1.4
CU.PVC

4C,6mm2 CU XLPE/SWA/PVC+1C, 6mm2


8RYB 32 TPN ISOLATOR FOR FAHU-1 1.10 0.37 0.37 0.37 1.10 90 1.0
CU.PVC

Page 1 of 2
INCOMING BREAKER
SMDB REF : SMDB-16A01 FED FROM : ATS -16A01 / FP-28A07 250 A MCCB 35KA
SIZE :
LOC. : FAC.-16A/ G F / ELEC.RM SMDB SIZE : 14 WAYS INCOMING CABLE SIZE : 4C, 120mm2 CU XLPE/SWA/PVC

CIRCUIT BREAKER PHASE LOAD (KW) DB's


CIRCUIT DIVERSIFIE
DIVERSIFIE
MCCB CABLE SIZE (mm2) DESCRIPTION LOAD (KW) DIVERSITY D LOAD REMARKS
D LOAD
CIRCUIT NO RATING (A) R Y B FACTOR (%) (KW)
(KW)
25KA
9R 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CCU-G1(DUTY) 4.00 4.00 4.00 90 3.60

9Y 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CCU-G2 (DUTY) 4.00 4.00 4.00 90 3.60

9B 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CCU-G3 (DUTY) 4.00 4.00 4.00 90 3.60

10R 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CCU-G1 ( STAND BY)

10Y 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G1 ( STAND BY)

10B 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G1 ( STAND BY)

11R 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G1 (STAND BY)

11Y 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G1 ( STAND BY)

11B 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G2 (DUTY) 4.00 4.00 4.00 90 3.60

12R 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G2 ( DUTY) 4.00 4.00 4.00 90 3.60

12Y 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G1 ( STAND BY)

12B 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G2 ( STAND BY)

13R 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G2 ( STAND BY)

13Y 20 SPARE

13B 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G1 ( STAND BY)

14RYB 63 SPARE

TOTAL LOAD(KW) = 134.34 47.10 41.30 45.95 107.76

Page 2 of 2
DB REF : DB-16A01 FED FROM : SMDB -16A01 INCOMING BREAKER SIZE : 63 A MCCB 35kA

LOC: FAC-16A/ G F / ELEC.RM DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 16mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC
SECTION/RCD

CIRCUIT BREAKER LOAD (KW)


BUSBAR

EARTH TOTAL CIRCUIT DIVERSIFIE


WIRE SIZE LD/PNT
MCB WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY D LOAD
(mm2)(P & N) (KW)
CIRCUIT NO RATING (A) (mm2)(E) POINTS R Y B FACTOR (%) (KW)
10KA
LIGHTS IN OPERATOR AND BATTERY CHARGING + 2 EM
1R 10 2 x 2.5 2.5 0.05 8 0.40 75 0.30
LIGHTS
1Y 10 2 x 2.5 2.5 LIGHTS IN OFFICE + 1 EM LIGHT 0.05 7 0.35 75 0.26

1B 10 2 x 2.5 2.5 LIGHTS IN OFFICE + 1 EM LIGHT 0.05 7 0.35 75 0.26

2R 10 2 x 2.5 2.5 LIGHTS IN ELEC ROOM, & KITCHEN + 2 EM LIGHTS 0.05 5 0.25 75 0.19

2Y 10 2 x 2.5 2.5 LIGHTS IN LOBBY & CORRIDOR + 4 EM LIGHTS 0.05 9 0.45 75 0.34

2B 10 2 x 2.5 2.5 LIGHTS IN SMDF + 1 EM LIGHT 0.05 3 0.15 75 0.11

3R 10 2 x 2.5 2.5 LIGHTS IN SHERYAN & MDF ROOM + 3 EM LIGHTS 0.05 9 0.45 75 0.34
40A,(100mA) RCD 4P

3Y 10 2 x 2.5 2.5 EXTERNAL LIGHTS 0.05 3 0.15 75 0.11

3B 10 SPARE
13A FUSED SWITCHED SPUR OUTLET SOCKET WITH
4R 20 2x4 4.0 0.30 1 0.30 90 0.27
INDICATOR LAMP FOR VAV-1
13A FUSED SWITCHED SPUR OUTLET SOCKET WITH
4Y 20 2x4 4.0 0.30 1 0.30 90 0.27
INDICATOR LAMP FOR VAV-3
13A FUSED SWITCHED SPUR OUTLET SOCKET WITH
4B 20 2x4 4.0 0.30 1 0.30 90 0.27
INDICATOR LAMPFOR VAV-2
5R 10 SPARE
3C, 6mm2 CU
5Y 20 SPN ISOLATOR FOR REF1 0.25 1 0.25 90 0.22
XLPE/SWA/PVC
13A FUSED SWITCHED SPUR OUTLET SOCKET WITH
5B 20 2x4 4.0 0.25 1 0.25 90 0.22
INDICATOR LAMPFOR CAV-1
6R 20 SPARE
3C, 6mm2 CU
6Y 20 SPN ISOLATOR FOR REF2 0.50 1 0.50 90 0.45
XLPE/SWA/PVC
6B 20 SPARE

7R 32 2x4 4.0 13A S.SOCKETS IN OPERATOR ROOM 0.20 7 1.40 75 1.05

7Y 32 2x6 6.0 13A S.SOCKETS IN OFFICE ROOM 0.20 9 1.80 75 1.35

7B 10 2 x 2.5 2.5 LIGHTS IN TOILET + 1 EM LIGHT 0.05 4 0.20 75 0.15

Page 1 of 2
DB REF : DB-16A01 FED FROM : SMDB -16A01 INCOMING BREAKER SIZE : 63 A MCCB 35kA

LOC: FAC-16A/ G F / ELEC.RM DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 16mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC
SECTION/RCD

CIRCUIT BREAKER LOAD (KW)


BUSBAR

EARTH TOTAL CIRCUIT DIVERSIFIE


WIRE SIZE LD/PNT
MCB WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY D LOAD
(mm2)(P & N) (KW)
CIRCUIT NO RATING (A) (mm2)(E) POINTS R Y B FACTOR (%) (KW)
10KA

8R 32 2x4 4.0 13A S.SOCKETS IN BATTERY CHARGING 0.20 6 1.20 50 0.60

8Y 32 2x4 4.0 13A S.SOCKETS IN CORRIDOR 0.20 2 0.40 50 0.20

8B 32 2x4 4.0 13A S.SOCKETS IN OFFICE 0.20 10 2.00 75 1.50

9R 32 2x4 4.0 13A S.SOCKETS IN STORE, KITCHEN & WATER FILTER 0.20 7 1.40 50 0.70
2 x 4.0 FIRE 4.0 FIRE
40A,(30mA) RCD 4P

9Y 20 13A UNSWITCH SPUR OUTLET SOCKETS FOR FACP 0.30 1 0.30 75 0.23
RATED RATED
20A DOUBLE POLE SWITCH WITH FLEX OUTLET FOR
9B 20 2x4 4.0 1.20 1 1.20 50 0.60
WATER HEATER IN TOILET
10R 20 2x4 4.0 ELECTRICAL ROOM SOCKET 0.20 1 0.20 50 0.10

10Y 20 2x4 4.0 SWITCHED SPUR OUTLET FOR HAND DRIER 0.50 1 0.50 50 0.25

10B 32 SPARE

11R 32 SPARE

11Y 32 SPARE

11B 32 SPARE

12R 32 SPARE

12Y 32 SPARE

12B 32 SPARE

TOTAL LOAD(KW) = 15.04 5.60 5.00 4.45 10.34

Page 2 of 2
DB REF : DB-16A01/UPS FED FROM :SMDB -16A01 INCOMING BREAKER SIZE : 125 A MCCB 35kA

LOC: FAC-16A/ GF / ELEC.RM DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 50mm2 CU XLPE/SWA/PVC+1C, 25mm2 CU.PVC

CIRCUIT BREAKER LOAD (KW) CIRCUIT


SECTION/
BUSBAR

EARTH TOTAL DIVERSIFIE


WIRE SIZE LD/PNT DIVERSITY
RCD

MCB WIRE SIZE LOAD DESCRIPTION NO.OF D LOAD REMARKS


CIRCUIT NO RATING (A) (mm2)(P & N) (KW) R Y B FACTOR
(mm2)(E) POINTS (KW)
10KA (%)

1R 20 2x4 4.0 13A TWIN SOCKETS IN SHERYAN ROOM 0.40 2 0.80 75 0.60
16A SINGLE PHASE INDUSTRIAL SOCKET IN SHERIYAN
1Y 32 2x6 6.0 1.20 1 1.20 75 0.90
ROOM
16A SINGLE PHASE INDUSTRIAL SOCKET IN SHERIYAN
1B 32 2x6 6.0 1.20 1 1.20 75 0.90
ROOM
16A SINGLE PHASE INDUSTRIAL SOCKET IN SHERIYAN
2R 32 2x6 6.0 1.20 1 1.20 75 0.90
ROOM
2Y 20 2x4 4.0 13A UNSWITCHED SPUR OUTLETS FOR MSFD 0.10 4 0.40 75 0.30

2B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90
16A SINGLE PHASE INDUSTRIAL SOCKET IN SHERIYAN
3R 32 2x6 6.0 1.20 1 1.20 75 0.90
ROOM
3Y 20 2x4 4.0 13A TWIN SOCKETS IN MDF ROOM 0.40 2 0.80 75 0.60

3B 20 2x4 4.0 13A TWIN SOCKETS IN MDF ROOM 0.40 2 0.80 75 0.60

4R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN MDF ROOM 1.20 1 1.20 75 0.90

4Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN MDF ROOM 1.20 1 1.20 75 0.90

4B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN MDF ROOM 1.20 1 1.20 75 0.90

5R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90

5Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90

5B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90

6R 20 2x4 4.0 13A TWIN SOCKETS IN SHERYAN ROOM 0.40 1 0.40 75 0.30

6Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90

6B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90

7R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90

7Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90
(30mA) RCD 4P

7B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90

Page 1 of 2
DB REF : DB-16A01/UPS FED FROM :SMDB -16A01 INCOMING BREAKER SIZE : 125 A MCCB 35kA

LOC: FAC-16A/ GF / ELEC.RM DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 50mm2 CU XLPE/SWA/PVC+1C, 25mm2 CU.PVC

CIRCUIT BREAKER LOAD (KW) CIRCUIT


SECTION/
BUSBAR

EARTH TOTAL DIVERSIFIE


WIRE SIZE LD/PNT DIVERSITY
RCD
4P

MCB WIRE SIZE LOAD DESCRIPTION NO.OF D LOAD REMARKS


CIRCUIT NO RATING (A) (mm2)(P & N) (KW) R Y B FACTOR
(30mA) RCD

(mm2)(E) POINTS (KW)


10KA (%)

8R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN MDF ROOM 1.20 1 1.20 75 0.90

8Y 20 2x4 4.0 13A TWIN SOCKETS IN MDF ROOM 0.40 2 0.80 75 0.60

8B 20 2x4 4.0 13A TWIN SOCKETS IN SMDF 0.40 2 0.80 75 0.60

9R 20 2x4 4.0 13A TWIN SOCKETS IN SMDF 0.40 2 0.80 75 0.60


2 x 4.0 FIRE 4.0 FIRE
9Y 20 13A UNSWITCHED SPUR OUTLETS FOR FM200 PANELS 0.10 4 0.40 75 0.30
RATED RATED
9B 20 2x4 4.0 13A TWIN SOCKETS IN PABX ROOM 0.40 2 0.80 75 0.60

10R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90

10Y 20 2x4 4.0 13A TWIN SOCKETS IN PABX ROOM 0.40 2 0.80 75 0.60

10B 20 2x4 4.0 13A TWIN SOCKETS IN PABX ROOM 0.40 2 0.80 75 0.60

11R 20 2x4 4.0 13A TWIN SOCKETS IN PABX ROOM 0.40 2 0.80 75 0.60

11Y 20 2x4 4.0 13A TWIN SOCKETS IN SMDF ROOM 0.40 2 0.80 75 0.60

11B 20 2x4 4.0 13A TWIN SOCKETS IN SMDF ROOM 0.40 2 0.80 75 0.60

12R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90

12Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90

12B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90

13R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90

13Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90

13B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90

14R

14Y 63 SPARE

14B

TOTAL LOAD(KW) = 39.60 13.60 12.40 13.60 29.70

Page 2 of 2
INCOMING BREAKER
CU REF : CU-27B01 FED FROM : FP-28A07 25 A SPN ISO. + RCD
SIZE :

LOC: FAC.-X1 / OT CU SIZE : 6 WAYS INCOMING CABLE SIZE : 3C, 10mm2 CU XLPE/SWA/PVC
SECTION/RC

CIRCUIT BREAKER
BUSBAR

WIRE SIZE EARTH TOTAL CIRCUIT DIVERSIFIE


LD/PNT
(mm2)(P & WIRE SIZE LOAD DESCRIPTION NO.OF LOAD (KW) DIVERSITY D LOAD REMARKS
D

MCB (KW)
CIRCUIT NO RATING (A) N) (mm2) (E) POINTS FACTOR (%) (KW)
10KA
1C 10 2 x 2.5 2.5 LIGHTS IN OT 0.05 3 0.15 75 0.11
32A,(30mA) RCD 4P

2C 10 2x4 4.0 SEARCHING LIGHTS + 1 EM LIGHT 1.05 2 1.05 75 0.79

3C 16 2x4 4.0 13A SOCKETS IN OT ROOM 0.20 2 0.40 50 0.20

4C 20 SPARE

5C 10 SPARE

6C 32 SPARE

TOTAL LOAD (KW) = 1.60 1.60 1.10

NOTES:-
CU-27A01 WILL BE FED FROM DB-30A01 & INCOMER CABLE WILL BE 3C, 10mm2 CU XLPE/SWA/PVC

CU-27B01 WILL BE FED FROM FP-28A07 & INCOMER CABLE WILL BE 3C, 10mm2 CU XLPE/SWA/PVC

CU-27C01 WILL BE FED FROM DB-02F01 & INCOMER CABLE WILL BE 3C, 16mm2 CU XLPE/SWA/PVC

CU-27D01 WILL BE FED FROM DB-07A01. & INCOMER CABLE WILL BE 3C, 35mm2 CU XLPE/SWA/PVC

CU-27E01 WILL BE FED FROM SMDB-08A201 & INCOMER CABLE WILL BE 3C, 25mm2 CU XLPE/SWA/PVC

Page 1 of 1
MDB REF : MDB-13A01 FED FROM : LT PANEL-28A02 INCOMING BREAKER SIZE : 400 A MCCB MAIN

LOCATION: GROUND FLOOR ELEC.ROOM-02 MDB SIZE : 6 WAYS INCOMING CABLE SIZE : 4C,300mm2 CU XLPE/SWA/PVC

CIRCUIT BREAKER PHASE LOAD (KW) SMDB & DB's CIRCUIT


MCCB DIVERSIFIED
CABLE SIZE (mm2) DESCRIPTION LOAD (KW) DIVERSIFIED DIVERSITY REMARKS
CIRCUIT NO RATING (A) R Y B LOAD (KW)
LOAD (KW) FACTOR (%)
35KA

4C, 50mm2 CU XLPE/SWA/PVC+ 1C,


1RYB 125 SMDB-13A01 78.35 26.00 25.35 27.00 51.75 90 46.58
25mm2 CU.PVC

4C, 95mm2 CU XLPE/SWA/PVC+ 1C,


2RYB 200 SMDB-13A11 119.29 37.05 40.70 41.54 84.58 90 76.12
50mm2 CU.PVC

4C, 95mm2 CU XLPE/SWA/PVC+ 1C,


3RYB 200 ATS-13A01 101.35 33.17 33.22 34.97 78.25 90 70.43
50mm2 CU.PVC

4RYB 100 SPARE

5RYB 80 SPARE

6RYB 63 SPARE

TOTAL LOAD(KW) = 298.98 96.21 99.26 103.51 193.12


SMDB REF : SMDB-13A11 FED FROM : MDB-13A01 INCOMING BREAKER SIZE : 200 A MCCB MAIN

LOCATION: FIRST FLOOR ELEC.ROOM-03 SMDB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 95mm2 CU XLPE/SWA/PVC+ 1C, 50mm2 CU.PVC

CIRCUIT BREAKER PHASE LOAD (KW) DB's


DIVERSITY DIVERSIFIED
MCCB RATING (A) CABLE SIZE (mm2) DESCRIPTION LOAD (KW) DIVERSIFIED REMARKS
CIRCUIT NO R Y B FACTOR (%) LOAD (KW)
25KA LOAD (KW)

1RYB 40 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC DB-13A11 12.35 3.95 4.20 4.20 9.34 90 8.40

2RYB 100 4C, 35mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC DB-13A12 50.50 16.90 16.30 17.30 32.80 90 29.52

3RYB 32 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC ISOLATOR FOR AHU-G1 ON ROOF 7.50 2.50 2.50 2.50 6.75 90 6.08

4RYB 32 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC ISOLATOR FOR AHU-G2 ON ROOF 7.50 2.50 2.50 2.50 6.75 90 6.08

5RYB 32 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC ISOLATOR FOR AHU-F1 ON ROOF 7.50 2.50 2.50 2.50 6.75 90 6.08

6RYB 32 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC ISOLATOR FOR AHU-F2 ON ROOF 7.50 2.50 2.50 2.50 6.75 90 6.08

7R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR REF-2 AT ROOF 0.656 0.66 0.66 90 0.59

7Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR REF-1 AT ROOF 0.042 0.04 0.04 90 0.04

7B 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR REF-1 AT ROOF 0.042 0.04 0.04 90 0.04

8R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR REF-1 AT ROOF 0.042 0.04 0.04 90 0.04

8Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR REF-2 AT ROOF 0.656 0.66 0.66 90 0.59

8B 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR BOOSTER PUMP AT ROOF 1.000 1.00 1.00 90 0.90

9RYB 40 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC DB-13A13 16.00 5.50 5.50 5.00 14.40 90 12.96

10R 20 SPARE

10Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G1 (STAND BY) AT ROOF FOR GF TEL RM 4.00 4.00 4.00 90 3.60

10B 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G1 (STAND BY) AT ROOF FOR GF SEC RM 4.00 4.00 4.00 90 3.60

11RYB 63 SPARE

12RYB 40 SPARE

TOTAL LOAD(KW) = 119.29 37.05 40.70 41.54 84.58


DB REF : DB-13A11 FED FROM :SMDB -13A11 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + 2 RCD

LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 11 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC

CIRCUIT BREAKER LOAD (KW)


WIRE SIZE EARTH TOTAL CIRCUIT
BUSBAR

LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
D

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)

1R 10 2 x 2.5 2.5 LIGHTS IN OFFICE 18 & 17 + 2 EM LIGHTS 0.05 12 0.60 75 0.45

1Y 10 2 x 2.5 2.5 LIGHTS IN OFFICE 16 & 15 + 2 EM LIGHTS 0.05 10 0.50 75 0.38


LIGHTS IN MANAGER-01& SECRETERY-01 +
1B 10 2 x 2.5 2.5 0.05 12 0.60 75 0.45
2 EM LIGHTS
LIGHTS IN MEETING ROOM 03 & OFFICE 08
2R 10 2 x 2.5 2.5 0.05 12 0.60 75 0.45
+ 2 EM LIGHTS
LIGHTS IN OFFICE 07 & 06 & MEETING
2Y 10 2 x 2.5 2.5 0.05 15 0.75 75 0.56
ROOM 01 + 3 EM LIGHTS
2B 10 2 x 2.5 2.5 LIGHTS IN OFFICE 03 & 01 + 2 EM LIGHTS 0.05 10 0.50 75 0.38

3R 10 2 x 2.5 2.5 LIGHTS IN OFFICE 15 & 14 + 2 EM LIGHTS 0.05 10 0.50 75 0.38


LIGHTS IN MEETING-02 & OFFICE 20 & 19 +
3Y 10 2 x 2.5 2.5 0.05 15 0.75 75 0.56
3 EM LIGHTS
3B 10 2 x 2.5 2.5 LIGHTS IN OFFICE 11 & 12 + 2 EM LIGHTS 0.05 14 0.70 75 0.53
LIGHTS IN ELEC.03, , STORE-02 + 2 EM
4R 10 2 x 2.5 2.5 0.05 4 0.20 75 0.15
LIGHTS
40A, TPN (100mA RCD)

4Y 10 2 x 2.5 2.5 LIGHTS IN OFFICE 09 ,21,10+ 3 EM LIGHT 0.05 15 0.75 75 0.56


LIGHTS IN OFFICE 05 & 04 & 02 + 3 EM
4B 10 2 x 2.5 2.5 0.05 15 0.75 75 0.56
LIGHTS
5R 10 2 x 2.5 2.5 LIGHTS IN CORRIDOR + 5 EM LIGHTS 0.05 18 0.90 75 0.68

5Y 10 2 x 2.5 2.5 LIGHTS IN CORRIDOR + 9 EM LIGHTS 0.05 18 0.90 75 0.68

5B 10 2 x 2.5 2.5 LIGHTS IN CORRIDOR + 3 EM LIGHTS 0.05 10 0.50 75 0.38

6R 10 2 x 2.5 2.5 LIGHTS IN ROOF 0.05 1 0.05 75 0.04

6Y 10

6B 10

7R 10 SPARE

7Y 10 SPARE

7B 10 SPARE

Page 1 of 2
DB REF : DB-13A11 FED FROM :SMDB -13A11 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + 2 RCD

LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 11 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC

CIRCUIT BREAKER LOAD (KW)


WIRE SIZE EARTH TOTAL CIRCUIT
BUSBAR

LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
D

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)

8R 10 SPARE

8Y 10 SPARE

8B 10 SPARE
LIGHTS IN KITCHEN 01 & JAN 01 + 2 EM
9R 10 2 x 2.5 2.5 0.05 5 0.25 75 0.19
LIGHT
9Y 10 2 x 2.5 2.5 LIGHTS IN LADIES TOILET-01 + 1 EM LIGHT 0.05 4 0.20 75 0.15
LIGHTS IN KITCHEN 02 & JAN 02 + 2 EM
9B 10 2 x 2.5 2.5 0.05 5 0.25 75 0.19
LIGHT
10R 10 2 x 2.5 2.5 LIGHTS IN OFFICER TOILET-01 + 2 EM LIGHT 0.05 7 0.35 75 0.26

10Y 10 2 x 2.5 2.5 LIGHTS IN LADIES TOILET-02 + 1 EM LIGHT 0.05 4 0.20 75 0.15

10B 10 2 x 2.5 2.5 LIGHTS IN ORS TOILET-01 + 2 EM LIGHT 0.05 7 0.35 75 0.26

11R 10 2 x 2.5 2.5 LIGHTS IN OFFICER TOILET-02 + 2 EM LIGHT 0.05 7 0.35 90 0.32
40A, TPN (30mA RCD

11Y 10 2 x 2.5 2.5 LIGHTS IN DRESS 01& BATH 02 0.05 3 0.15 75 0.11

11B 10 2 x 2.5 2.5 LIGHTS IN ORS TOILET-02 + 2 EM LIGHT 0.05 7 0.35 75 0.26

12R 10 2 x 2.5 2.5 LIGHTS IN DRESS 02& BATH 03 0.05 3 0.15 90 0.14

12Y 10 SPARE

12B 10 2 x 2.5 2.5 LIGHTS IN BATH 01 + 1 EM LIGHT 0.05 4 0.20 75 0.15

13R 20 SPARE

13Y 20 SPARE

13B 20 SPARE

14R 10 SPARE

14Y 10 SPARE

14B 10 SPARE

TOTAL LOAD (KW) = 12.35 3.95 4.20 4.20 9.34 kW

Page 2 of 2
DB REF : DB-13A12 FED FROM :SMDB -13A11 INCOMING BREAKER SIZE : 100 A TPN ISOLATOR + RCD

LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 35mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC

CIRCUIT BREAKER LOAD (KW)


SECTION/RCD

WIRE SIZE EARTH TOTAL CIRCUIT


LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
BUSBAR

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)

1R 32 2x6 6.0 13A S.SOCKETS IN OFFICE 18 & 17 0.20 16 3.20 75 2.40

1Y 32 2x6 6.0 13A S.SOCKETS IN OFFICE 16 & 15 0.20 13 2.60 75 1.95


13A S.SOCKETS IN MANAGER-01&
1B 32 2x6 6.0 0.20 13 2.60 75 1.95
SECRETERY-01
13A S.SOCKETS IN MEETING ROOM 03 &
2R 32 2x6 6.0 0.20 13 2.60 75 1.95
OFFICE 08
13A S.SOCKETS IN OFFICE 07 & 06 &
2Y 32 2x6 6.0 0.20 20 4.00 75 3.00
MEETING ROOM 01
2B 32 2x6 6.0 13A S.SOCKETS IN OFFICE 03 & 01 0.20 11 2.20 75 1.65

3R 32 2x6 6.0 13A S.SOCKETS IN OFFICE 13 & 14 0.20 10 2.00 75 1.50


13A S.SOCKETS IN MEETING-02 & OFFICE
3Y 32 2x6 6.0 0.20 16 3.20 75 2.40
20 & 19
3B 32 2x6 6.0 13A S.SOCKETS IN OFFICE 11 & 12 0.20 16 3.20 75 2.40
13A S.SOCKETS IN ELEC.03 , STORE ROOM-
4R 32 2x4 4.0 0.20 8 1.60 75 1.20
02 & OFFICE 21
4Y 32 2x4 4.0 13A S.SOCKETS IN OFFICE 09 0.20 6 1.20 75 0.90

4B 32 2x4 4.0 13A S.SOCKETS IN OFFICE 05 & 04 & 02 0.20 17 3.40 50 1.70

5R 32 2x4 4.0 13A S.SOCKETS IN CORRIDOR 0.20 3 0.60 50 0.30

5Y 20 2 x4 4.0 13A S.SOCKETS IN CORRIDOR 0.20 2 0.40 75 0.30


20A DOUBLE POLE SWITCH FOR W/H IN
5B 20 2x4 4.0 1.50 1 1.50 50 0.75
BATH 01
20A DOUBLE POLE SWITCH FOR W/H IN
6R 20 2x4 4.0 1.50 1 1.50 50 0.75
BATH-03
100A, TPN (30mA RCD

20A DOUBLE POLE SWITCH FOR W/H IN


6Y 20 2 x4 4.0 1.50 1 1.50 50 0.75
BATH-02
6B 32 2x4 4.0 13A S.SOCKETS IN KITCHEN 02 & JAN 02 0.20 7 1.40 50 0.70

7R 32 2x4 4.0 13A S.SOCKETS IN KITCHEN 01 & JAN 01 0.20 7 1.40 50 0.70
20A DOUBLE POLE SWITCH FOR W/H IN
7Y 20 2 x4 4.0 1.50 1 1.50 50 0.75
ORS TOILET-01
20A DOUBLE POLE SWITCH FOR W/H IN
7B 20 2x4 4.0 1.50 1 1.50 50 0.75
KITCHEN-02
20A DOUBLE POLE SWITCH FOR W/H IN
8R 20 2x4 4.0 1.50 1 1.50 50 0.75
OFFICER TOILET-02
8Y 32 2x4 4.0 13A S.SOCKETS IN OFFICE 10 0.20 7 1.40 75 1.05

8B 20 SPARE
20A DOUBLE POLE SWITCH FOR W/H IN
9R 20 2x4 4.0 1.50 1 1.50 50 0.75
KITCHEN 01
9Y 20 SPARE
HAND DRIER @ LADIES TOILET & ORS
9B 20 2x4 4.0 0.50 2 1.00 50 0.50
TOILET-2
HAND DRIER @ LADIES TOILET & ORS
10R 20 2x4 4.0 0.50 2 1.00 50 0.50
TOILET-1
9Y 32 2x4 4.0 HAND DRIER @ OFFICERS TOILET-02 0.50 1 0.50 50 0.25

Page 1 of 2
DB REF : DB-13A12 FED FROM :SMDB -13A11 INCOMING BREAKER SIZE : 100 A TPN ISOLATOR + RCD

LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 35mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC

CIRCUIT BREAKER LOAD (KW)


SECTION/RCD

WIRE SIZE EARTH TOTAL CIRCUIT


LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
BUSBAR

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)

10B 20 2x4 4.0 HAND DRIER @ OFFICERS TOILET-01 0.50 1 0.50 50 0.25

11R 32 SPARE

11Y 32 SPARE

11B 32 SPARE

12R 32 SPARE

12Y 32 SPARE

12B 32 SPARE

TOTAL LOAD (KW) = 50.50 16.90 16.30 17.30 32.80 kW

Page 2 of 2
DB REF : DB-13A13 FED FROM :SMDB-13A11 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + RCD

LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC

CIRCUIT BREAKER LOAD (KW)


SECTION/RCD

WIRE SIZE EARTH TOTAL CIRCUIT


LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
BUSBAR

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)

1R 20 2X4 4.0 13A S.SOCKET FOR VAV-1 0.50 1 0.50 90 0.45

1Y 20 2x4 4.0 13A S.SOCKET FOR VAV-2 0.50 1 0.50 90 0.45

1B 20 2x4 4.0 13A S.SOCKET FOR VAV-3 0.50 1 0.50 90 0.45

2R 20 2X4 4.0 13A S.SOCKET FOR VAV-4 0.50 1 0.50 90 0.45

2Y 20 2x4 4.0 13A S.SOCKET FOR VAV-5 0.50 1 0.50 90 0.45

2B 20 2x4 4.0 13A S.SOCKET FOR VAV-6 0.50 1 0.50 90 0.45

3R 20 2X4 4.0 13A S.SOCKET FOR VAV-7 0.50 1 0.50 90 0.45

3Y 20 2x4 4.0 13A S.SOCKET FOR VAV-8 0.50 1 0.50 90 0.45

3B 20 2x4 4.0 13A S.SOCKET FOR VAV-9 0.50 1 0.50 90 0.45

4R 20 2X4 4.0 13A S.SOCKET FOR VAV-10 0.50 1 0.50 90 0.45

4Y 20 2x4 4.0 13A S.SOCKET FOR VAV-11 0.50 1 0.50 90 0.45

4B 20 2x4 4.0 13A S.SOCKET FOR VAV-12 0.50 1 0.50 90 0.45

5R 20 2X4 4.0 13A S.SOCKET FOR VAV-13 0.50 1 0.50 90 0.45

5Y 20 2x4 4.0 13A S.SOCKET FOR VAV-14 0.50 1 0.50 90 0.45

5B 20 2x4 4.0 13A S.SOCKET FOR VAV-15 0.50 1 0.50 90 0.45

6R 20 2X4 4.0 13A S.SOCKET FOR VAV-16 0.50 1 0.50 90 0.45


40A, TPN (100mA RCD)

6Y 20 2x4 4.0 13A S.SOCKET FOR VAV-17 0.50 1 0.50 90 0.45

6B 20 2x4 4.0 13A S.SOCKET FOR VAV-18 0.50 1 0.50 90 0.45

7R 20 2X4 4.0 13A S.SOCKET FOR VAV-19 0.50 1 0.50 90 0.45

7Y 20 2x4 4.0 13A S.SOCKET FOR VAV-20 0.50 1 0.50 90 0.45

7B 20 2x4 4.0 13A S.SOCKET FOR VAV-21 0.50 1 0.50 90 0.45

8R 20 2X4 4.0 13A S.SOCKET FOR VAV-22 0.50 1 0.50 90 0.45

8Y 20 2x4 4.0 13A S.SOCKET FOR VAV-23 0.50 1 0.50 90 0.45

8B 20 2x4 4.0 13A S.SOCKET FOR VAV-24 0.50 1 0.50 90 0.45

9R 20 2X4 4.0 13A S.SOCKET FOR VAV-25 0.50 1 0.50 90 0.45

9Y 20 2x4 4.0 13A S.SOCKET FOR VAV-26 0.50 1 0.50 90 0.45

9B 20 2x4 4.0 13A S.SOCKET FOR CAV-1 0.50 1 0.50 90 0.45

10R 20 2X4 4.0 13A S.SOCKET FOR CAV-2 0.50 1 0.50 90 0.45

Page 1 of 2
DB REF : DB-13A13 FED FROM :SMDB-13A11 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + RCD

LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC

CIRCUIT BREAKER LOAD (KW)


SECTION/RCD

WIRE SIZE EARTH TOTAL CIRCUIT


LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
BUSBAR

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)

10Y 20 2x4 4.0 13A S.SOCKET FOR CAV-3 0.50 1 0.50 90 0.45

10B 20 2x4 4.0 13A S.SOCKET FOR CAV-4 0.50 1 0.50 90 0.45

11R 20 2X4 4.0 13A S.SOCKET FOR CAV-5 0.50 1 0.50 90 0.45

11Y 20 2x4 4.0 13A S.SOCKET FOR CAV-6 0.50 1 0.50 90 0.45

11B 20 SPARE

12R 20 SPARE

12Y 20 SPARE

12B 20 SPARE

TOTAL LOAD (KW) = 16.00 5.50 5.50 5.00 14.40 kW

Page 2 of 2
SMDB REF : SMDB-13A01 FED FROM : MDB-13A01 INCOMING BREAKER SIZE : 125 A MCCB MAIN

LOCATION: GROUND FLOOR ELEC.ROOM-02 SMDB SIZE : 4 WAYS INCOMING CABLE SIZE : 4C, 50mm2 CU XLPE/SWA/PVC+ 1C, 25mm2 CU.PVC

CIRCUIT BREAKER PHASE LOAD (KW)


DB's
MCCB DIVERSITY DIVERSIFIED
CABLE SIZE (mm2) DESCRIPTION LOAD (KW) DIVERSIFIED REMARKS
CIRCUIT NO RATING (A) R Y B FACTOR (%) LOAD (KW)
LOAD (KW)
25KA

4C, 10mm2 CU XLPE/SWA/PVC+1C,


1RYB 40 DB-13A01 14.10 4.80 4.60 4.70 10.58 90 9.52
10mm2 CU.PVC

4C, 35mm2 CU XLPE/SWA/PVC+1C,


2RYB 100 DB-13A02 48.30 15.70 15.30 17.30 32.58 90 29.32
16mm2 CU.PVC

4C, 10mm2 CU XLPE/SWA/PVC+1C,


3RYB 40 DB-13A03 15.95 5.50 5.45 5.00 14.35 90 12.92
10mm2 CU.PVC

4RYB 63 SPARE

TOTAL LOAD(KW) = 78.35 26.00 25.35 27.00 51.75


DB REF : DB-13A01 FED FROM :SMDB -13A01 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + 2 RCD

LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 14 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC

CIRCUIT BREAKER LOAD (KW)


WIRE SIZE EARTH TOTAL CIRCUIT
BUSBAR

LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY
D

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)

1R 10 2 x 2.5 2.5 LIGHTS IN OFFICE 16 & 17 + 2 EM LIGHTS 0.05 12 0.60 75 0.45

1Y 10 2 x 2.5 2.5 LIGHTS IN OFFICE 18 & 19 + 2 EM LIGHTS 0.05 10 0.50 75 0.38

1B 10 2 x 2.5 2.5 LIGHTS IN RECORD-01& MEETING-03 + 2 EM LIGHTS 0.05 10 0.50 75 0.38

2R 10 2 x 2.5 2.5 LIGHTS IN OFFICE 20 & 08 + 2 EM LIGHT 0.05 10 0.50 75 0.38

2Y 10 2 x 2.5 2.5 LIGHTS IN OFFICE 07 & 06 & MEETING-01 + 3 EM LIGHTS 0.05 15 0.75 75 0.56

2B 10 2 x 2.5 2.5 LIGHTS IN OFFICE 03 & 01 + 2 EM LIGHTS 0.05 10 0.50 75 0.38

3R 10 2 x 2.5 2.5 LIGHTS IN OFFICE 13 & 12 + 2 EM LIGHTS 0.05 10 0.50 75 0.38

3Y 10 2 x 2.5 2.5 LIGHTS IN MEETING-02 & OFFICE 15 & 14 + 3 EM LIGHT 0.05 15 0.75 75 0.56

3B 10 2 x 2.5 2.5 LIGHTS IN STORE-01& OFFICE 11 & 10 + 3 EM LIGHTS 0.05 14 0.70 75 0.53
LIGHTS IN ELEC.02 & TELECOM-02 & SECURITY & OFFICE 09 + 4
4R 10 2 x 2.5 2.5 0.05 17 0.85 75 0.64
EM LIGHTS
40A, TPN (100mA RCD)

4Y 10 2 x 2.5 2.5 LIGHTS IN OFFICE 05 & 04 & 02 + 3 EM LIGHTS 0.05 15 0.75 75 0.56

4B 10 2 x 2.5 2.5 LIGHTS IN CORRIDOR + 5 EM LIGHTS 0.05 17 0.85 75 0.64

5R 10 2 x 2.5 2.5 LIGHTS IN CORRIDOR + 5 EM LIGHTS 0.05 17 0.85 75 0.64

5Y 10 2 x 2.5 2.5 LIGHTS IN MAIN ENTRANCE HALL + 7 EM LIGHTS 0.05 18 0.90 75 0.68

5B 10 2 x 2.5 2.5 LIGHTS IN STAIR CASE-2 0.05 8 0.40 75 0.30

6R 10 2 x 2.5 2.5 LIGHTS IN STAIR CASE-3 + 1 EM LIGHT 0.05 9 0.45 75 0.34


EXTERNAL LIGHTS (CONTROLLED BY DAYLIGHT SENSOR +
6Y 10 2 x 2.5 2.5 0.05 9 0.45 75 0.34
TIMER + MANUAL SWITCH LOCATED AT DB)
6B 10 2 x 2.5 2.5 SPARE
EXTERNAL LIGHTS (CONTROLLED BY DAYLIGHT SENSOR +
7R 10 2 x 2.5 2.5 0.05 9 0.45 75 0.34
TIMER + MANUAL SWITCH LOCATED AT DB)
7Y 10 2 x 2.5 2.5 LIGHTING IN LIFT PIT 0.05 2 0.10 75 0.08

7B 10 2 x 2.5 2.5 LIGHTS IN STAIR CASE-2 VOID 0.05 9 0.45 75 0.34

Page 1 of 2
DB REF : DB-13A01 FED FROM :SMDB -13A01 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + 2 RCD

LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 14 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC

CIRCUIT BREAKER LOAD (KW)


WIRE SIZE EARTH TOTAL CIRCUIT
BUSBAR

LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY
D

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)

8R 10 SPARE

8Y 10 SPARE

8B 10 SPARE

9R 10 2 x 2.5 2.5 LIGHTS IN KITCHEN 01 & JAN 01 + 2 EM LIGHTS 0.05 5 0.25 75 0.19

9Y 10 2 x 2.5 2.5 LIGHTS IN LADIES TOILET-01 + 1 EM LIGHTS 0.05 4 0.20 75 0.15

9B 10 2 x 2.5 2.5 LIGHTS IN KITCHEN 02 & JAN 02 + 2 EM LIGHTS 0.05 5 0.25 75 0.19

10R 10 SPARE

10Y 10 2 x 2.5 2.5 LIGHTS IN LADIES TOILET-02 + 1 EM LIGHTS 0.05 4 0.20 75 0.15

10B 10 2 x 2.5 2.5 LIGHTS IN ORS TOILET-01 + 2 EM LIGHTS 0.05 7 0.35 75 0.26

11R 10 2 x 2.5 2.5 LIGHTS IN OFFICER TOILET-02 + 2 EM LIGHTS 0.05 7 0.35 75 0.26
40A, TPN (30mA RCD

11Y 10 SPARE

11B 10 2 x 2.5 2.5 LIGHTS IN ORS TOILET-02 + 2 EM LIGHTS 0.05 7 0.35 75 0.26

12R 10 SPARE

12Y 10 SPARE

12B 10 2 x 2.5 2.5 LIGHTS IN OFFICER TOILET-01 + 2 EM LIGHTS 0.05 7 0.35 75 0.26

13R 20 SPARE

13Y 20 SPARE

13B 20 SPARE

14R 10 SPARE

14Y 10 SPARE

14B 10 SPARE

TOTAL LOAD (KW) = 14.10 4.80 4.60 4.70 10.58 kW

Page 2 of 2
DB REF : DB-13A02 FED FROM :SMDB -13A01 INCOMING BREAKER SIZE : 100 A TPN ISOLATOR + RCD

LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 35mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC

CIRCUIT BREAKER LOAD (KW)


SECTION/RCD

TOTAL CIRCUIT
WIRE SIZE (mm2) (P EARTH WIRE SIZE LD/PNT DIVERSIFIED
LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
BUSBAR

MCB & N) (mm2)(E) (KW) LOAD (KW)


CIRCUIT NO POINTS R Y B FACTOR (%)
RATING (A)

1R 32 2x6 6.0 13A S.SOCKETS IN OFFICE 16 & 17 0.20 13 2.60 75 1.95

1Y 32 2x6 6.0 13A S.SOCKETS IN OFFICE 18 & 19 0.20 12 2.40 75 1.80

1B 32 2x6 6.0 13A S.SOCKETS IN RECORD-01& MEETING-03 0.20 16 3.20 75 2.40

2R 32 2x6 6.0 13A S.SOCKETS IN OFFICE 20 & 08 0.20 10 2.00 75 1.50


13A S.SOCKETS IN OFFICE 07 & 06 &
2Y 32 2x6 6.0 0.20 18 3.60 75 2.70
MEETING-01 &
2B 32 2x6 6.0 13A S.SOCKETS IN OFFICE 03 & 01 0.20 11 2.20 75 1.65

3R 32 2x6 6.0 13A S.SOCKETS IN OFFICE 13 & 12 0.20 10 2.00 75 1.50


13A S.SOCKETS IN MEETING-02 & OFFICE 15
3Y 32 2x6 6.0 0.20 18 3.60 75 2.70
& 14
13A S.SOCKETS IN STORE-01& OFFICE 11 &
3B 32 2x6 6.0 0.20 21 4.20 75 3.15
09
4R 32 2x6 6.0 13A S.SOCKETS IN OFFICE 10 0.20 13 2.60 75 1.95

4Y 32 2x6 6.0 13A S.SOCKETS IN OFFICE 05 & 04 & 02 0.20 17 3.40 75 2.55

4B 32 2x4 4.0 13A S.SOCKETS IN MAIN ENTRANCE HALL 0.20 8 1.60 50 0.80

5R 32 2x4 4.0 13A S.SOCKETS IN CORRIDOR & ELEC-02 0.20 5 1.00 50 0.50
13A SPUR OUTLET SOCKETS IN MAIN
5Y 20 2 x4 FIRE RATED 4 FIRE RATED 0.30 1 0.30 75 0.23
ENTRANCE HALL FOR FACP
20A DOUBLE POLE SWITCH FOR W/H IN
5B 20 2x4 4.0 1.50 1 1.50 50 0.75
OFFICER TOILET-01
6R 32 2x4 4.0 13A S.SOCKETS IN KITCHEN 01 & JAN 01 0.20 7 1.40 50 0.70
100A, TPN (30mA RCD

20A DOUBLE POLE SWITCH FOR W/H IN


6Y 20 2 x4 4.0 1.50 1 1.50 50 0.75
KITCHEN-01
6B 32 SPARE

7R 32 2x4 4.0 13A S.SOCKETS IN KITCHEN 02 & JAN 02 0.20 7 1.40 50 0.70

7Y 32 SPARE
20A DOUBLE POLE SWITCH FOR W/H IN ORS
7B 20 2x4 4.0 1.50 1 1.50 50 0.75
TOILET-02

Page 1 of 2
DB REF : DB-13A02 FED FROM :SMDB -13A01 INCOMING BREAKER SIZE : 100 A TPN ISOLATOR + RCD

LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 35mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC

CIRCUIT BREAKER LOAD (KW)


SECTION/RCD

TOTAL CIRCUIT
WIRE SIZE (mm2) (P EARTH WIRE SIZE LD/PNT DIVERSIFIED
LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
BUSBAR

MCB & N) (mm2)(E) (KW) LOAD (KW)


CIRCUIT NO POINTS R Y B FACTOR (%)
RATING (A)
20A DOUBLE POLE SWITCH FOR W/H IN
8R 20 2x4 4.0 1.50 1 1.50 50 0.75
KITCHEN-02
8Y 20 SPARE

8B 20 2x4 4.0 HAND DRIER @ OFFICERS TOILET-01 0.50 1 0.50 50 0.25


HAND DRIER @ LADIES TOILET & ORS
9R 20 2x4 4.0 0.50 2 1.00 50 0.50
TOILET-1
9Y 32 2x4 4.0 HAND DRIER @ OFFICERS TOILET-02 0.50 1 0.50 50 0.25
HAND DRIER @ LADIES TOILET & ORS
9B 20 2x4 4.0 0.50 2 1.00 50 0.50
TOILET-2
UNSWITCHED SPUR OUTLETS FOR SLIDING
10R 20 2x4 4.0 0.20 1 0.20 50 0.10
DOOR @ ENTRANCE
10Y 32 SPARE

10B 32 2x4 4.0 SPARE 0.20 8 1.60 75 1.20

11R 32 SPARE

11Y 32 SPARE

11B 32 SPARE

12R 32 SPARE

12Y 32 SPARE

12B 32 SPARE

TOTAL LOAD (KW) = 48.30 15.70 15.30 17.30 32.58 kW

Page 2 of 2
DB REF : DB-13A03 FED FROM :SMDB-13A01 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + RCD

LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RCD

CIRCUIT BREAKER LOAD (KW)


WIRE SIZE EARTH TOTAL CIRCUIT
BUSBAR

LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
(KW) LOAD (KW)
MCB N) (mm2)(E) POINTS FACTOR (%)
CIRCUIT NO R Y B
RATING (A)

1R 20 2X4 4.0 13A S.SOCKET FOR VAV-1 0.50 1 0.50 90 0.45

1Y 20 2x4 4.0 13A S.SOCKET FOR VAV-2 0.50 1 0.50 90 0.45

1B 20 2x4 4.0 13A S.SOCKET FOR VAV-3 0.50 1 0.50 90 0.45

2R 20 2X4 4.0 13A S.SOCKET FOR VAV-4 0.50 1 0.50 90 0.45

2Y 20 2x4 4.0 13A S.SOCKET FOR VAV-5 0.50 1 0.50 90 0.45

2B 20 2x4 4.0 13A S.SOCKET FOR VAV-6 0.50 1 0.50 90 0.45

3R 20 2X4 4.0 13A S.SOCKET FOR VAV-7 0.50 1 0.50 90 0.45

3Y 20 2x4 4.0 13A S.SOCKET FOR VAV-8 0.50 1 0.50 90 0.45

3B 20 2x4 4.0 13A S.SOCKET FOR VAV-9 0.50 1 0.50 90 0.45

4R 20 2X4 4.0 13A S.SOCKET FOR VAV-10 0.50 1 0.50 90 0.45

4Y 20 2x4 4.0 13A S.SOCKET FOR VAV-11 0.50 1 0.50 90 0.45

4B 20 2x4 4.0 13A S.SOCKET FOR VAV-12 0.50 1 0.50 90 0.45

5R 20 2X4 4.0 13A S.SOCKET FOR VAV-13 0.50 1 0.50 90 0.45

5Y 20 2x4 4.0 13A S.SOCKET FOR VAV-14 0.50 1 0.50 90 0.45

5B 20 2x4 4.0 13A S.SOCKET FOR VAV-15 0.50 1 0.50 90 0.45

6R 20 2X4 4.0 13A S.SOCKET FOR VAV-16 0.50 1 0.50 90 0.45


40A, TPN (100mA RCD)

6Y 20 2x4 4.0 13A S.SOCKET FOR VAV-17 0.50 1 0.50 90 0.45

6B 20 2x4 4.0 13A S.SOCKET FOR VAV-18 0.50 1 0.50 90 0.45

7R 20 2X4 4.0 13A S.SOCKET FOR VAV-19 0.50 1 0.50 90 0.45

7Y 20 2x4 4.0 13A S.SOCKET FOR VAV-20 0.50 1 0.50 90 0.45

7B 20 2x4 4.0 13A S.SOCKET FOR VAV-21 0.50 1 0.50 90 0.45

Page 1 of 2
DB REF : DB-13A03 FED FROM :SMDB-13A01 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + RCD

LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RCD

CIRCUIT BREAKER LOAD (KW)


WIRE SIZE EARTH TOTAL CIRCUIT
BUSBAR

LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
(KW) LOAD (KW)
MCB N) (mm2)(E) POINTS FACTOR (%)
CIRCUIT NO R Y B
RATING (A)

8R 20 2X4 4.0 13A S.SOCKET FOR VAV-22 0.50 1 0.50 90 0.45

8Y 20 2x4 4.0 13A S.SOCKET FOR VAV-23 0.50 1 0.50 90 0.45

8B 20 2x4 4.0 13A S.SOCKET FOR VAV-24 0.50 1 0.50 90 0.45

9R 20 2X4 4.0 13A S.SOCKET FOR VAV-25 0.50 1 0.50 90 0.45

9Y 20 2x4 4.0 13A S.SOCKET FOR CAV-1 0.50 1 0.50 90 0.45

9B 20 2x4 4.0 13A S.SOCKET FOR CAV-2 0.50 1 0.50 90 0.45

10R 20 2X4 4.0 13A S.SOCKET FOR CAV-3 0.50 1 0.50 90 0.45

10Y 20 2x4 4.0 13A S.SOCKET FOR CAV-4 0.50 1 0.50 90 0.45

10B 20 2x4 4.0 13A S.SOCKET FOR CAV-5 0.50 1 0.50 90 0.45

11R 20 2X4 4.0 13A S.SOCKET FOR CAV-6 0.50 1 0.50 90 0.45

11Y 20 2x4 4.0 13A S.SOCKET FOR AIR CURTAIN 0.22 2 0.45 90 0.40

11B 20 SPARE

12R 20 SPARE

12Y 20 SPARE

12B 20 SPARE

TOTAL LOAD (KW) = 15.95 5.50 5.45 5.00 14.35 kW

Page 2 of 2
SMDB REF : SMDB-13A01/E FED FROM : ATS-13A01 INCOMING BREAKER SIZE : 200 A MCCB MAIN

LOC. GROUND FLOOR ELEC.ROOM-02 SMDB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 95mm2 CU XLPE/SWA/PVC+ 1C, 50mm2 CU.PVC

CIRCUIT BREAKER PHASE LOAD (KW)


DB's
MCCB DIVERSITY DIVERSIFIED
CABLE SIZE (mm2) DESCRIPTION LOAD (KW) DIVERSIFIED REMARKS
CIRCUIT NO RATING (A) R Y B FACTOR (%) LOAD (KW)
LOAD (KW)
25KA

1RYB 125 4C, 50mm2 CU XLPE/SWA/PVC+1C, 25mm2 CU.PVC DB-13A0B/UPS 37.00 13.00 10.80 13.20 27.75 90 24.98

2RYB 16 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC TPN ISOLATOR FOR LIFT 3.70 1.23 1.23 1.23 3.70 90 3.33

3RYB 63 4C, 16mm2 CU XLPE/SWA/PVC+ 1C, 16mm2 CU.PVC TPN ISOLATOR FOR CCU-B1 (DUTY) AT BASEMENT 10.80 3.60 3.60 3.60 9.72 90 8.75

4R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR SEF-1 AT ROOF 1.10 1.10 1.10 90 0.99

4Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-1 AT ROOF (DUTY) FOR CCU BASEMENT 1.10 1.10 1.10 90 0.99

4B 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B1 AT ROOF(STAND BY) FOR BF OPER.RM 4.00 4.00 4.00 90 3.60

5RYB 32 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC TPN ISOLATOR FOR AHU-B1 AT ROOF 4.00 1.33 1.33 1.33 3.60 90 3.24

6R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B1(STAND BY) AT ROOF FOR BF OPER.RM 4.00 4.00 4.00 90 3.60

6Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B1 (STAND BY) AT ROOF FOR BF OPER.RM 4.00 4.00 4.00 90 3.60

6B 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B1 AT ROOF(STAND BY) FOR BF OPER.RM 4.00 4.00 4.00 90 3.60

7RYB 63 4C, 16mm2 CU XLPE/SWA/PVC+ 1C, 16mm2 CU.PVC TPN ISOLATOR FOR CCU-B1 (ASSIST) AT BASEMENT 10.80 3.60 3.60 3.60 9.72 90 8.75

8R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR LIFT LIGHTING 0.50 0.50 0.50 90 0.45

8Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-1 AT ROOF (STAND BY) FOR CCU BASEMENT 1.00 1.00 1.00 90 0.90

8B 20 SPARE

9RYB 40 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC DB-13A0B 10.45 2.35 4.10 4.00 7.86 90 7.07

10R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B2 AT GF ROOF(DUTY) FOR BF TUNNEL 2.45 2.45 2.45 90 2.21

10Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B2 AT GF ROOF(DUTY) FOR BF TUNNEL 2.45 2.45 2.45 90 2.21

10B 20 SPARE

11R 20 SPARE

11Y 20 SPARE

11B 20 SPARE

12RYB 40 SPARE

TOTAL LOAD(KW) = 101.35 33.17 33.22 34.97 78.25


DB REF : DB-13A0B/UPS FED FROM :SMDB-13A01/E INCOMING BREAKER SIZE : 125 A,TPN ISO.+ RCD

LOCATION: BASEMENT FLOOR ELECTRICAL ROOM-01 DB SIZE : 14 WAYS INCOMING CABLE SIZE : 4C, 50mm2 CU XLPE/SWA/PVC+1C, 25mm2 CU.PVC
SECTION/RC

CIRCUIT BREAKER LOAD (KW)


WIRE SIZE EARTH TOTAL CIRCUIT
BUSBAR

LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
D

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)
16A INDUSTRIAL SOCKETS IN OPERATION
1R 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
1Y 32 SPARE

1B 20 2x4 4.0 UNSWITCHED SPUR OUTLETS FOR FM200 0.20 2 0.40 75 0.30
16A INDUSTRIAL SOCKETS IN OPERATION
2R 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
16A INDUSTRIAL SOCKETS IN OPERATION
2Y 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
16A INDUSTRIAL SOCKETS IN OPERATION
2B 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
3R 20 SPARE 75 0.00

3Y 32 SPARE

3B 32 SPARE

4R 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30

4Y 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30

4B 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30

5R 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30

5Y 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30

5B 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30


16A INDUSTRIAL SOCKETS IN TELECOM
6R 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM-01
16A INDUSTRIAL SOCKETS IN TELECOM
6Y 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM-01
16A INDUSTRIAL SOCKETS IN TELECOM
6B 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM-01
16A INDUSTRIAL SOCKETS IN TELECOM
7R 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM-01
125A, TPN (30mA RCD)

16A INDUSTRIAL SOCKETS IN OPERATION


7Y 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
7B 32 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 8 1.60 75 1.20
16A INDUSTRIAL SOCKETS IN OPERATION
8R 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
8Y 32 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 8 1.60 75 1.20

8B 32 2x4 4.0 13A SOCKETS IN TELECOM ROOM -01 0.20 6 1.20 75 0.90

9R 32 2x4 4.0 13A SOCKETS IN OFFICE-01 ROOM 0.20 5 1.00 75 0.75


16A INDUSTRIAL SOCKETS IN OPERATION
9Y 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
16A INDUSTRIAL SOCKETS IN OPERATION
9B 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
10R 32 2x4 4.0 13A SOCKETS IN TELECOM-02 0.20 8 1.60 75 1.20
16A INDUSTRIAL SOCKETS IN TELECOM
10Y 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM-02
16A INDUSTRIAL SOCKETS IN TELECOM
10B 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM-02
11R 32 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 8 1.60 75 1.20
16A INDUSTRIAL SOCKETS IN TELECOM
11Y 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM-1
16A INDUSTRIAL SOCKETS IN TELECOM
11B 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM-1
16A INDUSTRIAL SOCKETS IN SECURITY
12R 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
12Y 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30
16A INDUSTRIAL SOCKETS IN SECURITY
12B 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
13R 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30

13Y 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30

13B 32 2x6 6.0 13A SOCKETS IN SECURITY ROOM 0.20 8 1.60 75 1.20

14R 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30

14Y 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30

14B 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30

TOTAL LOAD (KW) = 37.00 13.00 10.80 13.20 27.75

Page 1 of 1
DB REF : DB-13A0B FED FROM :SMDB-13A01/E INCOMING BREAKER SIZE : 40 A,TPN ISO. + 2RCD

LOCATION: BASEMENT FLOOR ELECTRICAL ROOM-01 DB SIZE : 10 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC

CIRCUIT BREAKER LOAD (KW)


WIRE SIZE EARTH TOTAL CIRCUIT
BUSBAR

LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
D

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)

1R 10 2 x 2.5 2.5 LIGHTS IN OPERATION ROOM 0.05 12 0.60 75 0.45

1Y 10 2 x 2.5 2.5 LIGHTS IN OPERATION ROOM 0.05 6 0.30 75 0.23

1B 10 2 x 2.5 2.5 LIGHTS IN OPERATION ROOM 0.05 12 0.60 75 0.45

2R 10 SPARE

2Y 10 2 x 2.5 2.5 LIGHTS IN OPERATION ROOM 1.00 1 1.00 75 0.75

2B 10 2x4 4.0 LIGHTS IN STAIR CASE + 1 EM LIGHT 0.05 5 0.25 75 0.19

3R 10 2x4 4.0 LIGHTS IN OFFICE-01 & ELEC. ROOM + 2 EM LIGHTS 0.05 6 0.30 75 0.23
32A, TPN (100mA RCD)

3Y 10 2x4 4.0 LIGHTS IN TELECOM & SUMP PIT + 1 EM LIGHT 0.05 4 0.20 75 0.15

3B 10 2x4 4.0 LIGHTS IN CORRIDOR + 7 EM LIGHTS 0.05 11 0.55 75 0.41

4R 10 2x4 4.0 LIGHTS IN TUNNEL + 6 EM LIGHTS 0.05 15 0.75 75 0.56

4Y 20 2x4 4.0 13A SOCKET FOR CAV-1 0.30 1 0.30 90 0.27

4B 20 2x4 4.0 13A SOCKET FOR VAV-1 0.30 2 0.60 90 0.54

5R 20 2x4 4.0 13A SOCKET FOR VAV-2 0.30 1 0.30 90 0.27

5Y 20 2x4 4.0 13A SOCKET FOR VAV-3 0.30 2 0.60 90 0.54

5B 10 2 x 2.5 2.5 LIGHTS IN STAIR CASE-1 + 2 EM LIGHTS 0.10 12 1.20 75 0.90

6RYB 20 3C X 6 CU BOOSTER PUMP CONTROL PANEL 1.20 1 0.40 0.40 0.40 75 0.90

7R 32 SPARE

7Y 20 2x4 4.0 13A SOCKETS IN LOBBY & ELEC.-01 0.20 3 0.60 50 0.30

7B 32 2x4 4.0 13A SOCKETS IN LOBBY 0.20 2 0.40 50 0.20

Page 1 of 2
DB REF : DB-13A0B FED FROM :SMDB-13A01/E INCOMING BREAKER SIZE : 40 A,TPN ISO. + 2RCD

LOCATION: BASEMENT FLOOR ELECTRICAL ROOM-01 DB SIZE : 10 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC

CIRCUIT BREAKER LOAD (KW)


WIRE SIZE EARTH TOTAL CIRCUIT
BUSBAR

LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
D

MCB (KW) LOAD (KW)


CIRCUIT NO N) (mm2)(E) POINTS R Y B FACTOR (%)
RATING (A)

8R SPARE
40A, TPN (30mA RCD)

8Y 20 3C X 6 CU SPN ISOLATOR FOR SUMP PUMP 0.70 1 0.70 75 0.53

8B SPARE

9R 32 SPARE

9Y 32 SPARE

9B 32 SPARE

10R 32 SPARE

10Y 32 SPARE

10B 32 SPARE

TOTAL LOAD (KW) = 10.45 2.35 4.10 4.00 7.86

Page 2 of 2