Supervised Single Interlock Preaction System
Supervised Single Interlock Preaction System
TE
Supervised Single Interlock Preaction (100) (590,6) (88,9) (220,7) (304,8) (369,8) (347,7) (59,4) (192,0)
System (Ref. Figure 1) utilizes the 6 26.25 3.00 8.69 12.00 15.44 14.50 2.34 8.44
Model DV-1 External Resetting Deluge (150) (666,8) (76,2) (220,7) (304,8) (392,2) (368,3) (59,4) (214,4)
Valve described in Technical Data NOTES:
Sheet TFP1330. Actuation of the sys- (1) Minimum clearance, additional 2" (500 mm) is recommended.
tem can be initiated by wet pilot, dry
pilot, or electric detection as described
LE
(2) Refer to Technical Data Sheet TFP1330 for additional installation dimensions.
piping will not cause the DV-1 Valve to ate sooner than the automatic sprin-
open — the air pressure is for supervi- Technical klers on the sprinkler piping.
sion only.
Typically, the system designer selects Data In planning the installation, considera-
tion must also be given to the disposal
the detection components for a preac- Approvals of the relatively large quantities of
tion system which will respond to a fire UL and C-UL Listed. water that may be associated with
sooner than the automatic sprinklers. FM Approved (electric actuation only). draining the system or performing a
In these cases, the system will experi- flow test.
ence only a minimal delay in water Deluge Valve
delivery over that for a wet pipe sprin- Model DV-1. NOTES
kler system, since the system will have Riser Check Valve Approval by Factory Mutual is contin-
begun to fill with water before a sprin- Model CV-2. gent on the use of an FM Approved
kler operates. 24VDC Solenoid Valve (P/N 52-287-1-
Working Pressure Range 024). FM only approves solenoid
In addition to being used for detecting 20 to 175 psi (1,4 to 12,1 bar). valves for use in non-hazardous loca-
a break in the system piping that might
Valve Trim tions.
impair water delivery in the event of a
fire, supervised single interlock preac- The trim for the Supervised Single In- Consult with the Authority Having Ju-
tion systems are also used to protect terlock Preaction System (TFP1330 risdiction regarding installation criteria
areas where there is danger of serious plus Fig. 2) forms a part of the labora- pertaining to electric actuation cir-
water damage which might result from tory listings and approvals. The trim is cuitry.
damaged automatic sprinklers or pip- necessary for proper operation of the
DV-1 Valve. System Air Pressure Requirements
ing. Typically, such areas include com-
TE
The supervisory air (nitrogen) pres-
puter rooms, storage areas for valu- Each package of trim includes the fol- sure is to be 10 plus or minus 2 psi
able artifacts, libraries, archives, and lowing items: (0,69 plus or minus 0,07 bar). The use
areas subject to freezing.
of a higher supervisory pressure is
Also, preaction systems are effectively • Water Supply Pressure Gauge subject to approval by the Authority
used to protect properties where a pre- Having Jurisdiction, and it should be
• Diaphragm Chamber
alarm of a possible fire condition may
allow time for fire extinguishment by
LE
Pressure Gauge
understood that the use of a higher
supervisory pressure may increase
alternate suppression means, prior to • Diaphragm Chamber Connections water delivery time. The use of a lower
the need for a sprinkler discharge. In supervisory pressure may prevent
the event the fire cannot otherwise be • Manual Control Station clearing the alarm of the Supervisory
extinguished, the preaction sprinkler • Main Drain Valve Low Pressure Alarm Switch (Item 16 -
O
system will then perform as the pri- Fig. 2), which is factory set to alarm at
mary fire protection system. • System Drain Valve 5 plus or minus 1 psi (0,34 plus or
• Alarm Test Valve minus 0,07 bar) on decreasing pres-
WARNING sure. The supervisory air supply pres-
• Automatic Drain Valve
BS
The Model DV-1 Supervised Single In- sure of 10 plus or minus 2 psi (0,69
terlock Preaction System described • System Air Pressure Gauge plus or minus 0,07 bar) can be pro-
herein must be installed and main- vided by any of the following methods.
tained in compliance with this docu- • Air Supply Connections Refer to the applicable data sheet for
ment, as well as with the applicable • Low Air Pressure Supervisory laboratory approval information.
standards of the National Fire Protec- Switch
tion Association, in addition to the
• Model G16AC812 (self contained)
O
4 2
When the 4 and 6 inch (DN100 and
TE
14 13
DN150) Supervised Single Interlock 5
Preaction System is set for service
there is no water in the system piping.
The system piping is automatically
11
pressurized with air (nitrogen) at nomi-
14 14
nally 10 psi (0,69 bar), and a Supervi-
sory Low Pressure Alarm Switch is 10
LE 8
14
used to supervise for a low pressure
condition. Substantial loss of pressure, 9
14
at a rate that cannot be maintained by
an automatic pressure maintenance
15
device, to below nominally 5 psi (0,34
O
6
bar), due to a damaged sprinkler or
piping, will result in a supervisory MODEL CV-2
alarm condition indicating that the CHECK VALVE
sprinkler system piping and/or sprin- (ORDERED
FROM
BS
SEPARATELY)
klers are in need of repair. The DV-1 MODEL DV-1
Valve will not open due to loss of su- DELUGE
pervisory air. MAIN VALVE
DRAIN VALVE
Typically, in the event of a fire, the (NORMALLY
detection system (i.e., wet pilot, dry CLOSED)
pilot, or electric) will first permit the
O
WATERFLOW
INSPECTOR'S LOCAL DRAIN
PRESSURE
TEST CONNECTION MANUAL
ALARM SWITCH
(AT THE MOST CONTROL
HYDRAULICALLY STATION
RESTRICTION MODEL DV-1
DRAIN DEMANDING DRAIN
DELUGE VALVE
LOCATION OF THE
WET PILOT LINE) MAIN DRAIN VALVE WATER SUPPLY
(NORMALLY CLOSED) PRESSURE
TE
DRAIN GAUGE
DIAPHRAGM CHAMBER MAIN
SUPPLY CONNECTION CONTROL VALVE
DIAPHRAGM
NOTE: CHAMBER SUPPLY (NORMALLY
REFER TO TFP1330 FOR CONTROL VALVE OPEN)
WET PILOT DETECTION (NORMALLY WATER
DESIGN CRITERIA OPEN)
LE SUPPLY
FIGURE 3A
SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM ARRANGEMENT
— WET PILOT ACTUATION —
O
SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY
AUTOMATIC
BS
SUPERVISORY
AIR/NITROGEN
SUPPLY
8 TO 12 PSI
DRY PILOT SPRINKLER DIAPHRAGM
DETECTION SYSTEM CHAMBER SYSTEM MAIN
REMOTE SUPERVISORY
(MINIMUM 1/2" PIPE AND PRESSURE DRAIN VALVE
MANUAL LOW AIR
AUTOMATIC SPRINKLERS) GAUGE (NORMALLY
CONTROL
O
PRESSURE
STATION DRAIN DRY PILOT CLOSED)
ALARM SWITCH
(WHEN LOW PRESSURE ACTUATOR
SPECIFIED) ALARM SWITCH MODEL CV-2
DRAIN CHECK VALVE
INSPECTOR'S
TEST CONNECTION WATERFLOW
LOCAL DRAIN
(AT THE MOST PRESSURE
MANUAL
REMOTE LOCATION ALARM SWITCH
CONTROL
FROM THE DV-1
STATION
VALVE) RESTRICTION MODEL DV-1
DRAIN DRAIN
DELUGE VALVE
AUTOMATIC MAIN DRAIN VALVE WATER SUPPLY
AIR/NITROGEN (NORMALLY CLOSED) PRESSURE
MAINTENANCE DRAIN GAUGE
DEVICE
DIAPHRAGM CHAMBER MAIN
SUPPLY CONNECTION CONTROL VALVE
DIAPHRAGM
NOTE: CHAMBER SUPPLY (NORMALLY
REFER TO TFP1330 FOR CONTROL VALVE OPEN)
DRY PILOT DETECTION (NORMALLY WATER
DESIGN CRITERIA OPEN) SUPPLY
FIGURE 3B
SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM ARRANGEMENT
— DRY PILOT ACTUATION —
TFP1424 Page 5 of 8
WATERFLOW
LOCAL DRAIN
PRESSURE
POWER SUPPLY MANUAL
ALARM SWITCH
(TYPICALLY CONTROL
120 VOLTS AC) STATION
RESTRICTION MODEL DV-1
DRAIN
DELUGE VALVE
TE
DRAIN GAUGE
DIAPHRAGM CHAMBER MAIN
SUPPLY CONNECTION CONTROL VALVE
DIAPHRAGM
NOTE: CHAMBER SUPPLY (NORMALLY
REFER TO TFP1330 FOR CONTROL VALVE OPEN)
ELECTRIC DETECTION (NORMALLY WATER
DESIGN CRITERIA OPEN)
LE SUPPLY
FIGURE 3C
SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM ARRANGEMENT
— ELECTRIC PILOT ACTUATION —
O
thread sealant sparingly on male pipe Step 6. A desiccant dryer, when re-
Installation threads only. quired for the supervisory air supply, is
BS
TE
any questions.
the dry pilot line. open the Main Drain Valve for the DV-1
Valve, and close the Supervisory Air It is recommended that automatic
Step 3. Open the Main Drain Valve for
Supply Control Valve. sprinkler systems be inspected,
the DV-1 Valve, the Main Drain Valve
tested, and maintained by a qualified
for the CV-2 Check Valve, and all aux- Step 3. Determine/correct the cause Inspection Service in accordance with
iliary drains. Close the auxiliary drain for the loss of supervisory pressure. local requirements and/or national
valves after water ceases to dis-
charge.
LE
Step 4. Reset the system in accord- codes.
ance with the System Setting Proce-
Step 4. Reset the DV-1 Valve and open dure section. NOTES
the Main Control Valve in accordance Some of the procedures outlined in
with Technical Data Sheet TFP1330. this section will result in operation of
the associated alarms. Consequently,
Step 5. Close the Main Drain Valve for
O
notification must first be given to the
the CV-2 Check Valve.
owner and the fire department, central
Step 6. Open the Supervisory Air Sup- station, or other signal station to which
ply Control Valve and allow the system the alarms are connected.
BS
TE
ing with air will result in the opening of the National Fire Protection Associa-
the Pressure Relief Valve (Item 3, Fig. tion, and/or the standards of any other
2). If the Relief Valve continues to Authorities Having Jurisdiction. Mate-
bleed air after the system pressure has rials found by Tyco Fire Products to be
been reduced to its normal supervi- defective shall be either repaired or
sory pressure range of 10 plus or mi- replaced, at Tyco Fire Products’ sole
nus 2 psi (0,69 plus or minus 0,07 bar),
most likely debris became lodged in
LE
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
the seating area. To help clean the assume for it, any other obligation in
seating area, slowly pull up on the ring connection with the sale of products or
at the top of the Relief Valve to allow a parts of products. Tyco Fire Products
full flow of air through the Relief Valve, shall not be responsible for sprinkler
O
and then release the ring to allow the system design errors or inaccurate or
Relief Valve to snap closed. Repeat the incomplete information supplied by
cleaning procedure as necessary. Buyer or Buyer’s representatives.
BS
CHECK VALVE
• Deluge Valve P/N’s are for American Standard Flange, Grooved Connections, and Threaded Ports. For
• Check Valve other configurations refer to Technical Data Sheet TFP1560 for the Model CV-2 Check
Valve. Specify: (size, Model CV-2 (specify end connection) Check Valve, P/N (specify).
• Actuation Trim
4 Inch, Flange x Flange. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-013
• Preaction Trim 4 Inch, Flange x Groove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-413
4 Inch, Groove x Groove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-113
• Supervisory Air Supply 6 Inch, Flange x Flange. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-015
6 Inch, Flange x Groove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-615
• Solenoid Valve, as applicable 4 Inch, Groove x Groove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-115
• Accessories ACTUATION TRIM (SELECT ONE)
Specify: (Description and finish — galvanized is standard) for use with 4 or 6 inch DV-1
Replacement Trim Parts: Deluge Valve P/N (specify).
Specify: (description) for use with Wet Pilot Actuation Trim Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-2-101
TE
Model DV-1 Deluge Valve, P/N (see Dry Pilot Actuation Trim Galvanized. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-2-102
Figure 2). Electric Actuation Trim Galvanized. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-2-103
Wet Pilot Actuation Trim Black . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-1-101
Dry Pilot Actuation Trim Black . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-1-102
Electric Actuation Trim Black . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-1-103
OTHER ACCESSORIES
See TFP1330 as applicable for type of actuation.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446