Supervised Single Interlock Preaction System

The document details the specifications and operational guidelines for the Supervised Single Interlock Preaction System using the Model DV-1 Deluge Valve, including installation dimensions, system components, and pressure requirements. It emphasizes the importance of maintaining the system in compliance with National Fire Protection Association standards and outlines the necessary components for proper operation. The system is designed to provide fire protection while minimizing water damage risks in sensitive areas.

Uploaded by

Mohamed Eid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views8 pages

Supervised Single Interlock Preaction System

The document details the specifications and operational guidelines for the Supervised Single Interlock Preaction System using the Model DV-1 Deluge Valve, including installation dimensions, system components, and pressure requirements. It emphasizes the importance of maintaining the system in compliance with National Fire Protection Association standards and outlines the necessary components for proper operation. The system is designed to provide fire protection while minimizing water damage risks in sensitive areas.

Uploaded by

Mohamed Eid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Preaction System with Model DV-1 Deluge Valve


Single Interlock, Supervised
4 and 6 Inch (DN100 and DN150)
General
Nominal Installation Dimensions in Inches and (mm)
Description Valve
Size A B C D E F G H
The 4 and 6 inch (DN100 and DN150) 4 23.25 3.50 8.69 12.00 14.56 13.69 2.34 7.56

TE
Supervised Single Interlock Preaction (100) (590,6) (88,9) (220,7) (304,8) (369,8) (347,7) (59,4) (192,0)
System (Ref. Figure 1) utilizes the 6 26.25 3.00 8.69 12.00 15.44 14.50 2.34 8.44
Model DV-1 External Resetting Deluge (150) (666,8) (76,2) (220,7) (304,8) (392,2) (368,3) (59,4) (214,4)
Valve described in Technical Data NOTES:
Sheet TFP1330. Actuation of the sys- (1) Minimum clearance, additional 2" (500 mm) is recommended.
tem can be initiated by wet pilot, dry
pilot, or electric detection as described
LE
(2) Refer to Technical Data Sheet TFP1330 for additional installation dimensions.

in TFP1330, and supervision of the E


sprinkler piping is provided with the
Preaction Trim (Ref. Figure 2) that is
used in conjunction with the Model
CV-2 Swing Check Valve described in G
D (1)
O
TFP1560. No priming water is required
for use with this Preaction Trim.
The Supervised Single Interlock Pre-
action System utilizes automatic sprin-
BS

klers and a supplemental heat detec- C


tion system (Ref. Figures 3A, 3B, and
3C). Actuation of the detection system
automatically operates (releases) the
DV-1 Deluge Valve, which in turn per- E (1) F (1)
mits water to flow into the sprinkler
O

piping system and to be discharged


from any sprinklers that may be open. B (1)
MODEL CV-2
In accordance with the requirements CHECK VALVE
of the National Fire Protection Asso-
ciation, a preaction system employing
more than 20 automatic sprinklers is to
have the sprinkler piping automatically
supervised to monitor the overall pres-
MODEL DV-1 A
sure retention integrity of the system.
In the case of the 4 and 6 inch (DN100 DELUGE VALVE
and DN150) Supervised Single Inter-
lock Preaction System, the Model
CV-2 Swing Check Valve provides an
air check so that the system can be
automatically pressurized with a nomi-
nal supervisory air or nitrogen pres-
sure of 10 psi (0,69 bar). A supervi-
sory low pressure alarm switch which
is set to transfer its contacts at nomi-
nally 5 psi (0,34 bar), on decreasing
FIGURE 1
pressure, is then utilized to indicate
whether there are any abnormal leaks 4 and 6 INCH (DN100 and DN150) SUPERVISED SINGLE INTERLOCK
in the sprinkler system piping. Loss of PREACTION SYSTEM RISER ARRANGEMENT
air pressure from the system as a re-
sult of a damaged sprinkler or broken

Page 1 of 8 JANUARY, 2005 TFP1424


Page 2 of 8 TFP1424

piping will not cause the DV-1 Valve to ate sooner than the automatic sprin-
open — the air pressure is for supervi- Technical klers on the sprinkler piping.
sion only.
Typically, the system designer selects Data In planning the installation, considera-
tion must also be given to the disposal
the detection components for a preac- Approvals of the relatively large quantities of
tion system which will respond to a fire UL and C-UL Listed. water that may be associated with
sooner than the automatic sprinklers. FM Approved (electric actuation only). draining the system or performing a
In these cases, the system will experi- flow test.
ence only a minimal delay in water Deluge Valve
delivery over that for a wet pipe sprin- Model DV-1. NOTES
kler system, since the system will have Riser Check Valve Approval by Factory Mutual is contin-
begun to fill with water before a sprin- Model CV-2. gent on the use of an FM Approved
kler operates. 24VDC Solenoid Valve (P/N 52-287-1-
Working Pressure Range 024). FM only approves solenoid
In addition to being used for detecting 20 to 175 psi (1,4 to 12,1 bar). valves for use in non-hazardous loca-
a break in the system piping that might
Valve Trim tions.
impair water delivery in the event of a
fire, supervised single interlock preac- The trim for the Supervised Single In- Consult with the Authority Having Ju-
tion systems are also used to protect terlock Preaction System (TFP1330 risdiction regarding installation criteria
areas where there is danger of serious plus Fig. 2) forms a part of the labora- pertaining to electric actuation cir-
water damage which might result from tory listings and approvals. The trim is cuitry.
damaged automatic sprinklers or pip- necessary for proper operation of the
DV-1 Valve. System Air Pressure Requirements
ing. Typically, such areas include com-

TE
The supervisory air (nitrogen) pres-
puter rooms, storage areas for valu- Each package of trim includes the fol- sure is to be 10 plus or minus 2 psi
able artifacts, libraries, archives, and lowing items: (0,69 plus or minus 0,07 bar). The use
areas subject to freezing.
of a higher supervisory pressure is
Also, preaction systems are effectively • Water Supply Pressure Gauge subject to approval by the Authority
used to protect properties where a pre- Having Jurisdiction, and it should be
• Diaphragm Chamber
alarm of a possible fire condition may
allow time for fire extinguishment by
LE
Pressure Gauge
understood that the use of a higher
supervisory pressure may increase
alternate suppression means, prior to • Diaphragm Chamber Connections water delivery time. The use of a lower
the need for a sprinkler discharge. In supervisory pressure may prevent
the event the fire cannot otherwise be • Manual Control Station clearing the alarm of the Supervisory
extinguished, the preaction sprinkler • Main Drain Valve Low Pressure Alarm Switch (Item 16 -
O
system will then perform as the pri- Fig. 2), which is factory set to alarm at
mary fire protection system. • System Drain Valve 5 plus or minus 1 psi (0,34 plus or
• Alarm Test Valve minus 0,07 bar) on decreasing pres-
WARNING sure. The supervisory air supply pres-
• Automatic Drain Valve
BS

The Model DV-1 Supervised Single In- sure of 10 plus or minus 2 psi (0,69
terlock Preaction System described • System Air Pressure Gauge plus or minus 0,07 bar) can be pro-
herein must be installed and main- vided by any of the following methods.
tained in compliance with this docu- • Air Supply Connections Refer to the applicable data sheet for
ment, as well as with the applicable • Low Air Pressure Supervisory laboratory approval information.
standards of the National Fire Protec- Switch
tion Association, in addition to the
• Model G16AC812 (self contained)
O

standards of any other authorities hav- • Waterflow Pressure Alarm Switch


Automatic Supervisory Air Supply
ing jurisdiction. Failure to do so may
described in Technical Data Sheet
impair the performance of the re- The Preaction Trim (Ref. Fig. 2) is pro- TFP1620.
lated devices. vided with galvanized or black nipples
and fittings. The galvanized trim is in- • A maximum 200 psi (13,8 bar) plant
The owner is responsible for maintain-
tended for non-corrosive or corrosive air supply in combination with the
ing their fire protection system and de-
conditions, whereas the black trim is Model AMD-1 Air Maintenance De-
vices in proper operating condition.
principally intended for use with AFFF vice described in Technical Data
The installing contractor or manufac-
systems. Sheet TFP1221.
turer should be contacted with any
questions. System Design Considerations • A maximum 3000 psi (206,9 bar)
The automatic sprinklers, as well as nitrogen cylinder in combination with
the electric fire control panel (automat- the Model AMD-3 Nitrogen Mainte-
ic control unit), fire detection devices, nance Device described in Techni-
manual pull stations, and signaling de- cal Data Sheet TFP1241.
vices, as applicable, which are utilized
with the Supervised Single Interlock NOTE
Preaction System must be UL Listed, The dew point of the air or nitrogen
ULC or C-UL Listed, or FM Approved, supply, for a system exposed to freez-
as applicable. ing conditions, must be maintained be-
low the lowest ambient temperature to
In order for a single interlock preaction which the system piping will be ex-
system to be hydraulically calculated posed. Introduction of moisture into
as a wet pipe system, as opposed to a the system piping can create ice build
dry pipe sprinkler system, the detec-
tion system must be designed to oper-
TFP1424 Page 3 of 8

up which could prevent proper opera-


tion of the system. NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 250 psi/ 1750 kPa
The Supervisory Low Pressure Alarm Air Pressure Gauge . . . . . 1 92-343-1-012 9 1/2" 45° Elbow . . . . . . . . . 1 CH
Switch (Item 16 - Fig. 2) is factory set 2 1/4" Gauge Test Valve . . 1 46-005-1-002 10 1/2" 90° Elbow . . . . . . . . . 1 CH
at 5 plus or minus 1 psi (0,34 plus or 3 1/4" Pressure Relief 11 1/2" Tee . . . . . . . . . . . . . . 1 CH
minus 0,07 bar) on decreasing pres- Valve . . . . . . . . . . . . . . . . 1 92-343-1-019 12 1/2" x 1/2" x 1/4" Tee . . . . 1 CH
sure. The Pressure Relief Valve (Item 4 1/2" Globe Valve . . . . . . . 1 46-047-1-004 13 1/4" x 4" Nipple . . . . . . . . 1 CH
5 1/2" Swing Check Valve .1 46-049-1-004 14 1/2" x 1-1/2" Nipple . . . . . 7 CH
3- Fig. 2) is factory set to fully open at 6 2" Angle Valve . . . . . . . . . 1 46-048-1-009 15 2" x 3" Nipple . . . . . . . . . . 1 CH
25 plus or minus 2 psi (1,72 plus or 7 1/4" Plug . . . . . . . . . . . . . 1 CH 16 Low Pressure Alarm
minus 0,14 bar) and it begins to crack 8 1/2" Union . . . . . . . . . . . . 1 CH Switch (PS10-2A) . . . . . . . 1 2571
open at a pressure of about 18 psi
(1,24 bar). RELIEF
VALVE SUPERVISORY
Friction Loss SUPERVISORY
1/2" NPT AIR PRESSURE
AIR SUPPLY
The nominal pressure loss versus flow CONTROL VALVE
CONNECTION GAUGE
data for the DV-1 and CV-2 Valves are 3 FOR AUTOMATIC
(NORMALLY OPEN)
given in TFP1330 and TFP1560, re- SUPERVISORY
SUPERVISORY AIR SUPPLY
spectively. LOW PRESSURE
ALARM SWITCH
12
Operation 16
14
TO SYSTEM
1 7

4 2
When the 4 and 6 inch (DN100 and

TE
14 13
DN150) Supervised Single Interlock 5
Preaction System is set for service
there is no water in the system piping.
The system piping is automatically
11
pressurized with air (nitrogen) at nomi-
14 14
nally 10 psi (0,69 bar), and a Supervi-
sory Low Pressure Alarm Switch is 10
LE 8
14
used to supervise for a low pressure
condition. Substantial loss of pressure, 9
14
at a rate that cannot be maintained by
an automatic pressure maintenance
15
device, to below nominally 5 psi (0,34
O
6
bar), due to a damaged sprinkler or
piping, will result in a supervisory MODEL CV-2
alarm condition indicating that the CHECK VALVE
sprinkler system piping and/or sprin- (ORDERED
FROM
BS

SEPARATELY)
klers are in need of repair. The DV-1 MODEL DV-1
Valve will not open due to loss of su- DELUGE
pervisory air. MAIN VALVE
DRAIN VALVE
Typically, in the event of a fire, the (NORMALLY
detection system (i.e., wet pilot, dry CLOSED)
pilot, or electric) will first permit the
O

DV-1 Valve to open, which will also


allow the waterflow alarms to be initi-
ated. Subsequently, water will be dis- FIGURE 2
charged from any sprinklers which op- 4 and 6 INCH (DN100 and DN150) PREACTION TRIM
erate.
Details with respect to operation of the
DV-1 Deluge Valve are provided in
Technical Data Sheet TFP1330.
Page 4 of 8 TFP1424

SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY


AUTOMATIC
SUPERVISORY
AIR/NITROGEN
SUPPLY
8 TO 12 PSI
DRY PILOT SPRINKLER
REMOTE DIAPHRAGM SYSTEM MAIN
DETECTION SYSTEM SUPERVISORY
MANUAL CHAMBER DRAIN VALVE
(MINIMUM 1/2" PIPE LOW AIR
CONTROL PRESSURE (NORMALLY
AND AUTOMATIC PRESSURE
STATION DRAIN GAUGE CLOSED)
SPRINKLERS) ALARM SWITCH
(WHEN
SPECIFIED) MODEL CV-2
CHECK VALVE

WATERFLOW
INSPECTOR'S LOCAL DRAIN
PRESSURE
TEST CONNECTION MANUAL
ALARM SWITCH
(AT THE MOST CONTROL
HYDRAULICALLY STATION
RESTRICTION MODEL DV-1
DRAIN DEMANDING DRAIN
DELUGE VALVE
LOCATION OF THE
WET PILOT LINE) MAIN DRAIN VALVE WATER SUPPLY
(NORMALLY CLOSED) PRESSURE

TE
DRAIN GAUGE
DIAPHRAGM CHAMBER MAIN
SUPPLY CONNECTION CONTROL VALVE
DIAPHRAGM
NOTE: CHAMBER SUPPLY (NORMALLY
REFER TO TFP1330 FOR CONTROL VALVE OPEN)
WET PILOT DETECTION (NORMALLY WATER
DESIGN CRITERIA OPEN)
LE SUPPLY

FIGURE 3A
SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM ARRANGEMENT
— WET PILOT ACTUATION —
O
SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY
AUTOMATIC
BS

SUPERVISORY
AIR/NITROGEN
SUPPLY
8 TO 12 PSI
DRY PILOT SPRINKLER DIAPHRAGM
DETECTION SYSTEM CHAMBER SYSTEM MAIN
REMOTE SUPERVISORY
(MINIMUM 1/2" PIPE AND PRESSURE DRAIN VALVE
MANUAL LOW AIR
AUTOMATIC SPRINKLERS) GAUGE (NORMALLY
CONTROL
O

PRESSURE
STATION DRAIN DRY PILOT CLOSED)
ALARM SWITCH
(WHEN LOW PRESSURE ACTUATOR
SPECIFIED) ALARM SWITCH MODEL CV-2
DRAIN CHECK VALVE
INSPECTOR'S
TEST CONNECTION WATERFLOW
LOCAL DRAIN
(AT THE MOST PRESSURE
MANUAL
REMOTE LOCATION ALARM SWITCH
CONTROL
FROM THE DV-1
STATION
VALVE) RESTRICTION MODEL DV-1
DRAIN DRAIN
DELUGE VALVE
AUTOMATIC MAIN DRAIN VALVE WATER SUPPLY
AIR/NITROGEN (NORMALLY CLOSED) PRESSURE
MAINTENANCE DRAIN GAUGE
DEVICE
DIAPHRAGM CHAMBER MAIN
SUPPLY CONNECTION CONTROL VALVE
DIAPHRAGM
NOTE: CHAMBER SUPPLY (NORMALLY
REFER TO TFP1330 FOR CONTROL VALVE OPEN)
DRY PILOT DETECTION (NORMALLY WATER
DESIGN CRITERIA OPEN) SUPPLY

FIGURE 3B
SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM ARRANGEMENT
— DRY PILOT ACTUATION —
TFP1424 Page 5 of 8

SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY


AUTOMATIC
SUPERVISORY
DIAPHRAGM AIR/NITROGEN
CHAMBER SUPPLY
ELECTRIC DETECTION SYSTEM
PRESSURE 8 TO 12 PSI
(TYPICALLY 24 VOLTS DC)
GAUGE
HEAT DETECTORS, SMOKE DETECTORS,
MANUAL PULL STATIONS, ETC. SYSTEM MAIN
SUPERVISORY
DRAIN VALVE
LOW AIR
(NORMALLY
DELUGE VALVE SOLENOID VALVE PRESSURE
CLOSED)
RELEASING PANEL (TYPICALLY 24 VOLTS DC) ALARM SWITCH
(AUTOMATIC
CONTROL UNIT) MODEL CV-2
DRAIN CHECK VALVE

WATERFLOW
LOCAL DRAIN
PRESSURE
POWER SUPPLY MANUAL
ALARM SWITCH
(TYPICALLY CONTROL
120 VOLTS AC) STATION
RESTRICTION MODEL DV-1
DRAIN
DELUGE VALVE

MAIN DRAIN VALVE WATER SUPPLY


(NORMALLY CLOSED) PRESSURE

TE
DRAIN GAUGE
DIAPHRAGM CHAMBER MAIN
SUPPLY CONNECTION CONTROL VALVE
DIAPHRAGM
NOTE: CHAMBER SUPPLY (NORMALLY
REFER TO TFP1330 FOR CONTROL VALVE OPEN)
ELECTRIC DETECTION (NORMALLY WATER
DESIGN CRITERIA OPEN)
LE SUPPLY

FIGURE 3C
SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM ARRANGEMENT
— ELECTRIC PILOT ACTUATION —
O

thread sealant sparingly on male pipe Step 6. A desiccant dryer, when re-
Installation threads only. quired for the supervisory air supply, is
BS

to be installed between a drip leg and


Step 2. The DV-1 Valve must be
NOTES the Model AMD-1 Air Maintenance De-
trimmed in accordance with Technical
Proper operation of the Model DV-1 vice or between the Model G16AC812
Data Sheet TFP1330.
Deluge Valves depends upon their trim Automatic Supervisory Air Supply and
being installed in accordance with the Step 3. The Preaction Trim must be the Preaction Trim.
instructions given in this Technical installed in accordance with Figure 2.
Step 7. The Supervisory Low Pressure
O

Data Sheet, as well as TFP1330. Fail-


The grooved end elbow fitting and cou- Alarm Switch is to be wired to the su-
ure to follow the appropriate trim dia-
plings are to be installed in accordance pervisory alarm initiating circuit of an
gram may prevent the DV-1 Valve from
with standard Grinnell installation alarm panel.
functioning properly, as well as void
practices.
listings, approvals, and the manufac- Step 8. All conduit and electrical con-
turer’s warranties. Care must be taken to ensure that nections are to be made in accordance
check valves, strainers, globe valves, with the requirements of the authority
The DV-1 Valve must be installed in a
etc. are installed with the flow arrows having jurisdiction and/or the National
readily visible and accessible location.
in the proper direction. Electric Code.
The DV-1 Valve and associated trim
Drain tubing to the drip funnel must be
must be maintained at a minimum tem-
installed with smooth bends that will
perature of 40°F/4°C.
not restrict flow.
Heat tracing of the DV-1 Valve or its
Step 4. Suitable provision must be
associated trim is not permitted. Heat
made for disposal of drain water.
tracing can result in the formation of
Drainage water must be directed such
hardened mineral deposits that are ca-
that it will not cause accidental dam-
pable of preventing proper operation.
age to property or danger to persons.
The Model DV-1 Deluge Valve is to be
Step 5. A suitable automatic supervi-
installed in accordance with the follow-
sory air (nitrogen) supply, as described
ing criteria:
in the Technical Data Section, is to be
Step 1. All nipples, fittings, and de- installed in accordance with the appli-
vices must be clean and free of scale cable Technical Data Sheet and set for
and burrs before installation. Use pipe 10 plus or minus 2 psi (0,69 plus or
minus 0,14 bar).
Page 6 of 8 TFP1424

System In Case Of Low Care and


Setting Supervisory Maintenance
Procedure Pressure Alarm The following procedures, inspections,
and maintenance must be performed
Steps 1 through 6 are to be performed NOTE as indicated, in addition to any specific
when initially setting the system; after Before closing a fire protection system requirements of the NFPA, and any
an operational test of the system; or, main control valve for maintenance impairment must be immediately cor-
after system operation due to a fire. work on the fire protection system rected.
Refer to Technical Data Sheet which it controls, permission to shut The owner is responsible for the in-
TFP1330 as necessary. down the affected fire protection sys- spection, testing, and maintenance of
Step 1. Close the Diaphragm Cham- tems must first be obtained from the their fire protection system and de-
ber Supply Control Valve in the Dia- proper authorities and all personnel vices in compliance with this docu-
phragm Chamber Supply Connection who may be affected by this decision ment, as well as with the applicable
to the DV-1 Valve. must be notified. standards of the National Fire Protec-
Step 1. Close the Diaphragm Cham- tion Association (e.g., NFPA 25), in
Step 2. Close the Main Control Valve,
ber Supply Control Valve in the Dia- addition to the standards of any
and close the Supervisory Air Supply
phragm Chamber Supply Connection authority having jurisdiction. The in-
Control Valve. If the system is
to the DV-1 Valve. stalling contractor or product manufac-
equipped with dry pilot actuation,
turer should be contacted relative to
close the Air Supply Control Valve to Step 2. Close the Main Control Valve,

TE
any questions.
the dry pilot line. open the Main Drain Valve for the DV-1
Valve, and close the Supervisory Air It is recommended that automatic
Step 3. Open the Main Drain Valve for
Supply Control Valve. sprinkler systems be inspected,
the DV-1 Valve, the Main Drain Valve
tested, and maintained by a qualified
for the CV-2 Check Valve, and all aux- Step 3. Determine/correct the cause Inspection Service in accordance with
iliary drains. Close the auxiliary drain for the loss of supervisory pressure. local requirements and/or national
valves after water ceases to dis-
charge.
LE
Step 4. Reset the system in accord- codes.
ance with the System Setting Proce-
Step 4. Reset the DV-1 Valve and open dure section. NOTES
the Main Control Valve in accordance Some of the procedures outlined in
with Technical Data Sheet TFP1330. this section will result in operation of
the associated alarms. Consequently,
Step 5. Close the Main Drain Valve for
O
notification must first be given to the
the CV-2 Check Valve.
owner and the fire department, central
Step 6. Open the Supervisory Air Sup- station, or other signal station to which
ply Control Valve and allow the system the alarms are connected.
BS

supervisory pressure of 10 plus or mi-


Before closing a fire protection system
nus 2 psi (0,69 plus or minus 0,07 bar)
main control valve for maintenance
to be established at which point the
work on the fire protection system that
Super visory Low Pressure Alarm
it controls, permission to shut down the
Switch should return to its “normal”
affected fire protection systems must
condition.
first be obtained from the proper
O

authorities and all personnel who may


NOTE
be affected by this action must be no-
After setting a fire protection system,
tified.
notify the proper authorities and ad-
vise those responsible for monitoring Quarterly Supervisory Low Pres-
proprietary and/or central station sure Alarm Test Procedure
alarms. Proper operation of the Supervisory
Low Pressure Alarm Switch should be
performed quarterly as follows:
Step 1. Crack open the Main Drain
Valve for the CV-2 Check Valve (Item
6, Figure 2) to slowly relieve supervi-
sory air pressure from the system. Ver-
ify that the Supervisory Low Pressure
Alarm Switch is operational and that
the low pressure set point is approxi-
mately 5 psi (0,34 bar).
Step 2. Close the Main Drain Valve
(Item 6, Figure 2) and allow the system
supervisory pressure of nominally 10
plus or minus 2 psi (0,69 0,14 bar) be
automatically re-established. The Su-
pervisory Low Pressure Alarm Switch
should return to its “normal” condition.
TFP1424 Page 7 of 8

Model DV-1 Deluge Valve Test


Procedures Limited
The following list of test procedures as
outlined in Technical Data Sheet Warranty
TFP1330 should be performed at the
indicated intervals: Products manufactured by Tyco Fire
Products are warranted solely to the
• Annual Operation Test Procedure original Buyer for ten (10) years
• Five Year Internal Valve Inspection against defects in material and work-
manship when paid for and properly
• Quarterly Waterflow Alarm Test Pro- installed and maintained under normal
cedure use and service. This warranty will ex-
• Quarterly Solenoid Valve Test Pro- pire ten (10) years from date of ship-
cedure For Electric Actuation ment by Tyco Fire Products. No war-
ranty is given for products or
• Quarterly Dry Pilot Actuator Test components manufactured by compa-
Procedure For Dry Pilot Actuation nies not affiliated by ownership with
• Quarterly Low Pressure Alarm Test Tyco Fire Products or for products and
Procedure And Condensate Drain components which have been subject
Procedure For Dry Pilot Actuation to misuse, improper installation, corro-
sion, or which have not been installed,
Pressure Relief Valve Maintenance maintained, modified or repaired in ac-
Over pressurization of the system pip- cordance with applicable Standards of

TE
ing with air will result in the opening of the National Fire Protection Associa-
the Pressure Relief Valve (Item 3, Fig. tion, and/or the standards of any other
2). If the Relief Valve continues to Authorities Having Jurisdiction. Mate-
bleed air after the system pressure has rials found by Tyco Fire Products to be
been reduced to its normal supervi- defective shall be either repaired or
sory pressure range of 10 plus or mi- replaced, at Tyco Fire Products’ sole
nus 2 psi (0,69 plus or minus 0,07 bar),
most likely debris became lodged in
LE
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
the seating area. To help clean the assume for it, any other obligation in
seating area, slowly pull up on the ring connection with the sale of products or
at the top of the Relief Valve to allow a parts of products. Tyco Fire Products
full flow of air through the Relief Valve, shall not be responsible for sprinkler
O
and then release the ring to allow the system design errors or inaccurate or
Relief Valve to snap closed. Repeat the incomplete information supplied by
cleaning procedure as necessary. Buyer or Buyer’s representatives.
BS

IN NO EVENT SHALL TYCO FIRE


PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
O

LIMITED TO LABOR CHARGES, RE-


GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Page 8 of 8 TFP1424

Ordering DELUGE VALVE (SELECT ONE


P/N’s are for American Standard Flange, Grooved Connections, and Threaded Ports, For
other configurations refer to Technical Data Sheet TFP1330. Specify: (size), Model DV-1
Procedure (specify end connection) Deluge Valve, P/N (specify).
4 Inch, Flange x Flange. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-1-013
4 Inch, Flange x Groove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-4-613
With reference to Table A, the following 6 Inch, Flange x Flange. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-1-015
items must be ordered separately: 6 Inch, Flange x Groove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-4-615

CHECK VALVE
• Deluge Valve P/N’s are for American Standard Flange, Grooved Connections, and Threaded Ports. For
• Check Valve other configurations refer to Technical Data Sheet TFP1560 for the Model CV-2 Check
Valve. Specify: (size, Model CV-2 (specify end connection) Check Valve, P/N (specify).
• Actuation Trim
4 Inch, Flange x Flange. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-013
• Preaction Trim 4 Inch, Flange x Groove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-413
4 Inch, Groove x Groove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-113
• Supervisory Air Supply 6 Inch, Flange x Flange. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-015
6 Inch, Flange x Groove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-615
• Solenoid Valve, as applicable 4 Inch, Groove x Groove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-520-1-115
• Accessories ACTUATION TRIM (SELECT ONE)
Specify: (Description and finish — galvanized is standard) for use with 4 or 6 inch DV-1
Replacement Trim Parts: Deluge Valve P/N (specify).
Specify: (description) for use with Wet Pilot Actuation Trim Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-2-101

TE
Model DV-1 Deluge Valve, P/N (see Dry Pilot Actuation Trim Galvanized. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-2-102
Figure 2). Electric Actuation Trim Galvanized. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-2-103
Wet Pilot Actuation Trim Black . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-1-101
Dry Pilot Actuation Trim Black . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-1-102
Electric Actuation Trim Black . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-1-103

PREACTION TRIM (SELECT ONE)


LE
Specify: (specify finish — galvanized is standard) Preaction Trim for 4 or 6 inch Model
DV-1 Deluge Valves, P/N (specify).
Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-2-104
Black. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-470-1-104

SUPERVISORY AIR SUPPLY (SELECT ONE)


A device capable of maintaining a nominal system air or nitrogen pressure of nominal 10
O
psi (0,69 bar) must be separately ordered. Specify: (Specify model and description), P/N
(specify).
Model AMD-1 Air Maintenance Device (TFP1221) . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-324-2-002
BS

Model AMD-3 Nitrogen Maintenance Device (TFP1241) . . . . . . . . . . . . . . . . . . . . . P/N 52-328-2-001


Model G16AC812 Automatic Supervisory Air Supply (TFP1620) . . . . . . . . . . . . . . . P/N 52-150-1-001

SOLENOID VALVE (SELECT FOR ELECTRIC ACTUATION ONLY)


Specify: 24 VDC, NEMA 2, 4, and 4X, 175 psi, Solenoid Valve, P/N (specify).
175 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-287-1-024
O

OTHER ACCESSORIES
See TFP1330 as applicable for type of actuation.

TABLE A — ORDERING LIST