Structural Data

The document outlines the structural design specifications for a three-storey frame building using SAP 2000 V18 software, including material specifications, occupancy loads, wind and seismic design parameters, and fire safety considerations. It details the design unit weights for RCC and brick masonry, as well as the seismic design approach based on IS 1893 (Part 1): 2002. Additionally, it confirms compliance with safety measures and provides specific structural data for beams, columns, and foundations.

Uploaded by

Kishor Bohaju
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views3 pages

Structural Data

The document outlines the structural design specifications for a three-storey frame building using SAP 2000 V18 software, including material specifications, occupancy loads, wind and seismic design parameters, and fire safety considerations. It details the design unit weights for RCC and brick masonry, as well as the seismic design approach based on IS 1893 (Part 1): 2002. Additionally, it confirms compliance with safety measures and provides specific structural data for beams, columns, and foundations.

Uploaded by

Kishor Bohaju
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

STRUCTURAL DESIGN ( TYPE B) ( IS Code)

BUILDING ELEMENTS As Per Submitted Design Remark


General
Building Structure Type Frame Structure
No. of Storeys applied for permit ( in Nos) 3
Number of Storeys Considered in Structural design ( in Nos) 3
If Computer Aided Design(CAD) is used, please state the name of the software
SAP 2000 V18
package
Number of storeys considered in the design provision for further extension no
Total height (h) of the structure with extension ( in m) 8.535

NBC 101-1994 MATERIALS SPECIFICATIONS

Materials to be used in Structure ( tick the listed materials that will be used in Brick Masonry
structure element )
RCC

NBC 102-1994 Unit weight of Materials


Specify the Design unit weight of materials: RCC ( in KN/m 3) 25
Specify the Design unit Weight of materials: Brick Masonary( in KN/m 3) 19.2

NBC 103-1994 occupancy Load ( Imposed Load)


For Residential Buildings
Occupancy Load ( Uniformly Distributed Load in KN/m 2) for Rooms and
2
Kitchen
Occupancy Load ( Uniformly Distributed Load in KN/m 2) for corridors
3
staircase and store
Occupancy Load ( Uniformly Distributed Load in KN/m 2) for Balconies 3

NBC 104-1994 WIND LOAD


Wind Zone 1
Basic wind speed (m/s) 47

NBC 105-1994 Seismic Design of Building in nepal


Method adopted for earthquake resistant design seismic coefficient approach
Adopted code for seismic design IS 1893 (Part 1): 2002
Subsoil Category Type II Medium
Seismic Weight (W) in KN 2389.27
Fundamental Time Period of the building along X Tx in seconds 0.375
Fundamental Time Period of the building along Y Ty in seconds 0.375
Seismic Zoning Factor (Z) 0.36
Importance Factor (I) 1
Response Reductio factor ( R) 5
Spectral acceleration coefficient ( S a/g) along X 2.5
Spectral acceleration coefficient ( S a/g) along Y 2.5
Design Horizontal Seismic Coefficient Along X ( A h) 0.09
Design Horizontal Seismic Coefficient Along Y( A h) 0.09
Base Shear ( Vb) for Seismic Coefficient Along X 215.03
Base Shear ( Vb) for Seismic Coefficient Along Y 215.03
Base Shear Generated through dynamic Analysis Along X ( if response
-
spectrum method is used)
Base Shear Generated through dynamic Analysis Along Y ( if response
-
spectrum method is used)

Adopted Base Shear multification Factor Along X ( if response method used) -

Adopted Base Shear multification Factor Along Y ( if response method used) -

Maximum Inter-storey Drift(mm) 4.26


Corresponding Storey height for Maximum inter-Storey Drift (h)mm 2845
Maximum Inter-storey Drift Ratio 0.0015

NBC 106-1994 snow load


snow fall type or condition No snowfall

NBC 107-1994 PROVISIONAL RECOMMENDATION ON FIRE SAFETY

Have you considered fire safety requirement? yes

NBC 108-1994 SITE SITE CONSIDERATION FOR SIESMIC HAZARDS

whether Distance of construction site from toe/ beginning of downward slope


no
withinn 50m?
whether Distance of construction site from river bank is within 50m no
availability of soil test report no

NBC 114-1994 Construction Safety


Are you sure that all safety measures will be fulfilled in the construction site as
yes
per this code?
safety hard hat
safety googles
safety wares used safety boots
safety belts
first aid facility

STRUCTURAL DATA FOR FRAMED RCC STRUCTURE


NBC 110-1994 PLAIN AND REINFORCED CONCRETE
Concrete grade in Structure M20
Reinforcement Steel Grade Fe-500
Slab Design
Boundary Condition of Slab one long edges discontinous
Effective Thickness of Slab ( d) in mm 106
short span of critical slab panel ( L ) in mm 4030

Calculated short span to effective depth ratio (L/D) for the corresponding slab 38.02

Basic ( L/D) ratio 23


Required modification factor for tension reinforcement 1.65
Required Tension reinforcement Ast percentage for short span bottom
0.08
reinforcement
Provided Tension reinforcement Ast percentage for short span bottom
0.31
reinforcement
Actual modification factor for tension reinforcement 2
CHECK FOR CRITICAL BEAM
Effective depth of beam ( d) in mm 396
Critical span ( L) in mm 5182
support condition one side continuous
Basic L/D ratio 26
calculated critical span to effective depth ratio L/D for corresponding slab 13.09
Check for Critical Column
Critical column height 2845
Minimum size of the column (mm x mm) 305 x 305
Short colum effect considered or not no
Minimum area of longitudinal reinforcement provided 1.72%
Design Philosophy Limit State Method
Load Combination
1 DL 1.5
1 LL 1.5
2 DL 1.2
2 LL 1.2
2 EQ 1.2
3 DL 1.5
3 EQ 1.5
4 DL 0.9
4 EQ 1.5
Whether the sample design calculations of foundations columns, beams and
yes
slabs, are submitted
Types of foundation isolated/strap
Depth of foundation from the ground level to the bottom of footing ( in m) 1.52