Vertiv VRC-S User Manual Overview
Vertiv VRC-S User Manual Overview
User Manual
Vertiv™ VRC-S User Manual
The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential
and proprietary information owned by Vertiv. Any copying, use or disclosure of
it without the written permission of Vertiv is strictly prohibited.
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
TABLE OF CONTENTS
iii
Vertiv™ VRC-S User Manual
6.2.3 Faults 37
6.2.4 Troubleshooting UPS Issues 38
7 Faults, Warnings and Events 39
8 Specifications 41
8.1 Vertiv™ VRC-S with VRC self-contained 120V NAM 41
8.2 Vertiv™ VRC-S with VRC self-contained 208V NAM 42
8.3 Vertiv™ VRC-S with VRC split lee temp 120 V NAM 44
8.4 Vertiv™ VRC-S with VRC split lee temp 208V NAM 46
8.5 Vertiv™ VRC-S with VRC self-contained 230V EMEA 48
8.6 Vertiv™ VRC-S with VRC split and VRC-S with VRC split lee temp 230V EMEA 49
8.7 Vertiv™ VRC-S with VRC self-contained 230V EMEA and Liebert® GXT5 52
8.8 Vertiv™ VRC-S with VRC split and VRC-S with VRC split lee temp 230V EMEA and Liebert® GXT5 55
9 Appendices 59
Appendix A: Startup Checklist Vertiv™ VRC-S 59
iv
Vertiv™| VRC-S User Manual
This manual contains important instructions that must be closely followed during installation of this unit to maintain
compliance with agency listings. Read this manual thoroughly and the safety and regulatory information, available at
[Link]
information/, before attempting to install, service, or operate this unit.
Retain this manual for the entire service life of the unit.
WARNING! Risk of handling heavy unit. Can cause equipment damage, injury or death. Read all
instructions before beginning.
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment
damage, injury or death. Only properly trained and qualified personnel wearing appropriate
OSHA-approved personal protection equipment (PPE) should attempt to move, lift, remove
packaging from or prepare this unit for installation. Read all instructions before attempting to
move, lift, remove packaging from or prepare the unit for installation.
Vertiv recommends installing equipment in the Vertiv VR from bottom to top, beginning with
the Vertiv™ VRC in the bottom of the rack. Heavier rack equipment should be installed in the
positions just above the Vertiv VRC, then installing lighter equipment in the upper positions.
This product is designed for commercial/industrial use only. This product is not intended for use with life support or other
U.S. FDA designated “critical” devices. Maximum loads must not exceed those specified in this manual. The maximum load
rating for the standard Vertiv™VR is 1360 kg (3000 lb.); static load rating is 1022 kg (2250 lb.); dynamic load rating is, 907
kg (2000 lb.). Do not exceed the static load rating. Additional information may be found in the user manual, SL-11425, which
shipped with the Vertiv™ VRC-S and is available at Vertiv's web site [Link].
Install and operate this unit in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.
The Vertiv VRC-S must be installed on a flat, level surface for proper assembly and operation.
Ensure that the rack has proper ventilation. Never block or insert objects into the ventilation holes or other openings.
Maintain minimum clearances as specified in this manual.
Provide at least the minimum space between the accessories /components and the housing. This spacing must be
maintained for safe operation of the equipment when installed in accordance with the National Electric Code, ANSI/NFPA
70. As appropriate, all wiring and equipment should be installed in accordance with NFPA 70, “National Electrical Code,”
and the applicable sections of ANSI C2, “National Electrical Safety Code."
WARNING! Risk of handling heavy unit and component parts. Can cause injury and equipment
damage. Use OSHA-recommended safe lifting techniques and/or lifting equipment rated for the
weight of the unit. Unit weights are specified in Specifications on page 41 .
WARNING! Risk of improper moving. Can cause equipment damage, injury or death. Use only
lifting equipment that is rated for the unit weight by an OSHA-certified rating organization. The
center of gravity varies depending on the unit size.
CAUTION: Risk of contact with sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate, OSHA-approved personal
protection equipment should attempt to move, lift, remove packaging from or prepare the unit
for installation.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep the forklift's tines level and at a height suitable to fit
below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Keep the unit upright, indoors and protected from dampness, freezing temperatures
and contact damage.
• The rack PDU is designed for information technology equipment in a Restricted Access Location. Only service
personnel should install and access the PDU. The rack PDU is not intended for use with life support or other
designated critical devices. If uncertain about its intended application, consult your local dealer or Vertiv
representative.
• Follow nameplate ratings when connecting equipment to the branch circuit. Maximum load must not exceed
the rating shown on the rack PDU nameplate. Take into consideration the effect that overloading of the circuits
might have on overcurrent protection and supplied wiring.
• The rated line voltage must not exceed the specifications on the rPDU's accompanying documentation..
• Operate the rack PDU in an indoor environment only in the appropriate ambient temperature range:
• Install the rack PDU in a clean environment, free of conductive contaminants, moisture, flammable liquids,
gases and corrosive substances.
• The rack PDU must be installed in a restricted-access location. A restricted-access location is an area where
access is possible only through the use of a tool or lock and key or other means of security, and is controlled by
the authority responsible for the location.
• The rack PDU has no user-serviceable parts, other than the field replaceable plastic carrier (not installed on all
models) that is designed to be field replaceable by qualified service personnel only. Under no circumstances
attempt to gain internal access due to the risk of electric shock or burn.
• Refer any unexpected behavior or unusual fault conditions to your local dealer or Vertiv representative.
• Vertiv recommends powering only devices with safety agency approval from the rack PDU.
• For permanently connected rack PDU’s (hard-wired versions), a readily accessible disconnect device must be
incorporated external to the equipment.
• For rack PDU’s with integral plugs, the socket/outlet or appliance coupler must be installed near the equipment
and must be easily accessible to disconnect for service.
For more information on this product, visit [Link] to download the user manual.
Safety Precautions
WARNING! Observe all cautions and warnings. Failure to do so may result in serious injury or
death. Rack PDU units contain no user-serviceable parts, other than the field replaceable
plastic carrier (not installed on all models) that is designed to be field replaceable by qualified
service personnel only. For service or technical support, contact your local Vertiv
representative. Do not attempt to service this product yourself.
CAUTION: Connecting a rack PDU to a power supply with an incorrect rating in voltage or
amperes may damage the connected equipment and your rack PDU. For questions about the
power supply connections, contact your Vertiv representative.
CAUTION: Ensure that the ratings of the electric circuit of each connected device meet the
specified rating at each branch and receptacle.
NOTE: For power management purposes, record the receptacle where each piece of equipment is
connected. Receptacles on the rack PDU have a numeric designation. The rack PDU identifies the
receptacles with numbers and are grouped by branch with a letter referring to the proper circuit
breaker.
CAUTION: All configuration steps must be completed before attempting to start equipment
connected to the PDU.
WARNING! Each rack must have its own protective-earth conductor. Do not daisy-chain the
protective-earth circuit using the multiple protective-earthing connection points. Protective-
earthing connections shall be such that disconnection of a protective earth at one point in a
unit or a system does not break the protective-earthing connection to other parts or units in a
system, unless the relevant hazard is removed at the same time.
The UPS contains no user-serviceable parts except the battery pack. Do not remove the cover. Removing the cover may
result in electric shock and will invalidate any implied warranty. The UPS has an internal battery, so the output receptacles
of the UPS may carry live voltage even if the UPS is not connected to mains input power.
Before moving or rewiring the UPS, disconnect mains input power and the battery and make sure that the UPS is
completely shut down. Otherwise, the output terminal may carry live voltage, presenting an electric shock hazard. To ensure
human safety and normal UPS operation, the UPS must be properly grounded before use. When the UPS is connected to an
IT power distribution system, the short-circuit protection device must be installed on the neutral line. Install and use the
UPS in the following environments:
Keep the air inlet and outlet of the UPS unobstructed. Poor ventilation will increase the UPS internal temperature and can
shorten the life of the UPS and its batteries. Keep liquid and other foreign objects away from the UPS. In case of fire, use a
dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher may cause electric shock. This UPS is not
intended for use with life support and other designated critical devices. Maximum load must not exceed that shown on the
UPS rating label. This UPS is designed for data processing equipment. If uncertain, consult your local dealer or company
representative.
Electromagnetic Compatibility
This UPS complies with the limits for a Class A digital device. Operating this device in a residential area is likely to cause
harmful interference that users must correct at their own expense. This UPS complies with the requirements of EMC
Directive 2014/30/ EU and the published technical standards. Continued compliance requires installation in accordance
with these instructions anduse of accessories approved by Vertiv™.
BATTERY SAFETY
CAUTION: Do not dispose of the battery in a fire. The battery may explode. Do not open or
damage the battery. Released electrolyte is harmful to skin and eyes. If electrolyte comes into
contact with the skin, wash the affected area immediately with plenty of clean water and get
medical attention.
CAUTION: A battery can present a risk of electrical shock and high short-circuit current. The
following precautions should be observed when working on batteries:
2 Introduction
The Vertiv™ VRC-S product line is an IT rack-cooling solution equipped with a network-enabled rPDU and is designed for
critical equipment in small server rooms, network closets and edge computing spaces.
The Vertiv VRC-S is available in these series with either 120 V, 208 V, or 230 V:
The Vertiv VRC-S is based on the Vertiv™ VR rack. The cabinet is equipped with a Vertiv™ VRC 3.5 kW cooling unit, a
Vertiv™ Geist™ rPDU, optional with Liebert® GXT5™ UPS and sensors, as well as venting to convey heat from the cabinet
into an adjacent space or out of the area. SNMP and Modbus-RTU connectivity permit connection to a building
management system for remote monitoring. See Specifications on page 41 for more information.
A backup fan on the rear door is actuated when the temperature at the top front of the cabinet exceeds 32°C (86°F). The fan
shuts off when the temperature sensor, installed at the top front of the cabinet, senses that the temperature has dropped
below 32°C (86°F).
Operating the Vertiv VRC-S in extreme environments may cause condensation inside the cabinet. The VRC-S is not
environmental neutral. The user is encouraged to try to correct this condition by these measures:
• Increasing the supply air operating temperature of the Vertiv™ VRC module. Refer to Operation on page 31 for
details.
• Reducing the relative humidity in the operating environment. This can be accomplished through passive
means by adding louvers to doors or walls for more ventilation; or by cooling the room through the building's
cooling system.
For the Vertiv™ VRC-S, the rack also has a factory-installed backup fan on the rear door. The backup fan is connected to the
Geist™ rPDU for backup power and network connectivity. A sensor at the front of the cabinet automatically senses any rise
in cabinet temperature and, in emergency situations, signals the fan to exhaust the warmer air from the rack. The backup fan
is actuated when the temperature at the top front of the rack exceeds 32°C (86°F). It switches Off when the temperature
drops below that threshold.
2 Introduction 7
Vertiv™ VRC-S User Manual
The Vertiv VRC-S, painted RAL 7021 as are its main components, may be controlled through the Geist rPDU, which is
network-enabled and permits remote monitoring and management over a network. A display that may be installed on the
rack's back door, provides local monitoring and control of the Vertiv™ VRC.
The Vertiv™ VRC-S easily accepts either the Vertiv™ Liebert® PSI5 or Vertiv™ Liebert® GXT5 UPS and the Geist rPDU
family of products to provide conditioned and backup power to the rack equipment.
IMPORTANT! If a UPS is installed, it should be installed immediately above the Vertiv VRC. Installing
the UPS higher in the rack could result in a tipping hazard.
The Vertiv™ VRC-S must be installed indoors in an environment with a temperature range of 18°C-30°C (64.4°F-86°F) and
less than 80% relative humidity (non-condensing).
For VRC-S with VRC split the outdoor temperature range is -15°C (5°F) to 45°C (113°F).
For VRC-S with VRC split lee temp the outdoor temperature range is -34°C (-29.2°F) to 45°C (113°F).
8 2 Introduction
Vertiv™| VRC-S User Manual
5 Vertiv VRC return air intake, hot air from inside cabinet
Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject to voltage sags,
spikes, and complete failure that may interrupt computer operations, cause data loss, and damage equipment.
The Liebert GXT5 protects equipment from these disturbances. The Liebert GXT5 continuously charges its batteries from
the mains, enabling it to supply power to connected loads, even when the mains fail.
2 Introduction 9
Vertiv™ VRC-S User Manual
10 2 Introduction
Vertiv™| VRC-S User Manual
Figure 2.3 One-Line Diagram of Vertiv™ VRC-S self-contained Connection - EMEA (without Liebert®
GXT5)
2 Introduction 11
Vertiv™ VRC-S User Manual
Figure 2.4 One-Line Diagram of Vertiv™ VRC-S self-contained Connection - EMEA (with Liebert®
GXT5)
12 2 Introduction
Vertiv™| VRC-S User Manual
Figure 2.5 One-Line Diagram of Vertiv™ VRC-S split Connection - EMEA (without Liebert® GXT5)
2 Introduction 13
Vertiv™ VRC-S User Manual
Figure 2.6 One-Line Diagram of Vertiv™ VRC-S Split Connection - EMEA (with Liebert® GXT5)
14 2 Introduction
Vertiv™| VRC-S User Manual
Figure 2.7 One-Line Diagram of Vertiv™ VRC-S Split Connection - NAM (without Liebert® GXT5)
2 Introduction 15
Vertiv™ VRC-S User Manual
16 2 Introduction
Vertiv™| VRC-S User Manual
Store the unit in the original packaging indoors in an area protected from excessive dirt, debris, and contact damage until
final installation. Observe the following requirements and the conditions listed in Storage Conditions below .
IMPORTANT! If the combined time for shipment and storage exceeds 6 months, the Vertiv™ VRC
requires recalibration for proper performance. If the shipment includes a UPS, refer to that UPS's
manual for battery recharging information.
The manuals shipped with the Vertiv™ VRC-S. They can be found attached to the interior of the Vertiv™ VR rack. Cut the
plastic wrapping from the rack, using a knife along the corrugated padding to prevent damaging the rack's paint.
IMPORTANT! Uncrate the components according to the instructions in the documents that were
shipped inside the Vertiv VR rack.
The Vertiv VR, a 19-in. EIA server rack, will have these components factory-installed:
• Thermal separation
• Rack closing kit
• Sensors for temperature and door contact
• Backup fan
• Geist™ rPDU (factory-programmed)
• Liebert® GXT5 (in some EMEA versions)
4 Installation
NOTE: EMEA version: all parts are factory installed.
Assemble the Vertiv™ VRC-S as detailed in documentation for the Vertiv™ VR solution and Vertiv™ VRC. This
documentation shipped inside the rack. However, assembly will be eased by performing these steps before sliding the
cooling unit into the rack:
• Attach the condensate pump and the transition piece to the Vertiv VRC (perform Section 4.3 in the Vertiv VRC
manual before Section 4.1). The pump installation includes attaching the 25-foot (7.5 m) drain tubing if the
shorter, factory-attached piece is not adequate. The drain tube used should be checked for kinks before
attachment. After attaching the tubing, push about half an inch through the outlet hole in the pump shroud.
IMPORTANT! When installing the brass condensate fitting, do not use a wrench. Using a wrench may
cause overtightening and damage internal components. Hand-tighten the fitting only. The tube is a
gravity drain only and is not pressurized.
• For Vertiv VRC Self-Containted, attach the transition piece to the cooling unit (perform Section 4.2 in the Vertiv
VRC manual before Section 4.1). The transition piece is attached to the rear of the cooling unit with six screws.
The lower screws will be easier to manipulate before the cooling unit is inside the rack.
• Attach the condensate pump and bracket (perform Section 4.3 in the Vertiv VRC manual before Section 4.1).
• Install the filter in the Vertiv VRC. The cooling unit has a filter on the top rear that collects particulates from the
return air going back into the Vertiv VRC. The brackets holding the filter in place may need to be loosened
before the filter can be inserted. This is done more easily before the Vertiv VRC is inserted into the cabinet.
Note that the filter has an arrow to indicate the airflow direction.
NOTE: Do not discard the handles removed from the Vertiv VRC cooling unit after sliding it into the
Vertiv VR. Retain the handles and the bolts for use in handling the cooling unit should it need to be
removed from the cabinet.
The cage nuts are used to attach the rack cooling unit to the rack's rails and to attach air baffles in the front of the rack even
with the top of the Vertiv VRC. Cage nuts are supplied with the rack. They may be found in the bag attached with the
manuals inside the rack.
Install cage nuts at these positions, except the 10U positions, on each of the cabinet's four rails. Insert cage nuts at the 10U
positions, 6U for split in the front rails only.
4 Installation 21
Vertiv™ VRC-S User Manual
Cage Nut
Cage Nut Purpose Install On
Location
4.2 Install the Vertiv™ VRC (Vertiv™ VRC-S with Vertiv VRC
Self-Contained)
Prepare the rack to receive the Rack Cooling Unit (self contained) and install the Vertiv VRC in the rack as described in the
unit's manual, which shipped with the Vertiv™ VRC-S. For the M6x12 T30 screws, used to secure the Vertiv VRC to the EIA-
rails, use 5.6 Nm (4.13 ft-lb.) tightening torque.
Air barrier placement on the Vertiv VRC-S uprights varies according to the size of your rack. Depending on the cabinet
model, there is a tab on the air barrier that is bent up (600 mm (23.62 in.) cabinet) or bent down (800 mm (31.5 in.) cabinet).
• 600 mm (23.62 in.): The air barriers should be mounted so the top of the air barrier tab is even with the top of
the Vertiv VRC.
• 800 mm (31.5 in.): The air barriers should be mounted so that the flat part of the air barrier (not the tab) is even
with the top of the Vertiv VRC.
1. Refer to the 800 mm (31.5 in.) air barriers image, below, and identify the left air barrier; hold it in position and
fasten it to the upright using one M6x12 T30 screw and M6 cage nut (4.13 ft-lb /5.6 Nm torque).
2. Repeat for the right air barrier.
22 4 Installation
Vertiv™| VRC-S User Manual
4 Installation 23
Vertiv™ VRC-S User Manual
4.5 Install the Vertiv (Vertiv VRC-S with Vertiv VRC Split)
Prepare the rack to receive the Rack Cooling Unit (split) and install the Vertiv VRC in the rack as described in the unit's
manual, which shipped with the Vertiv VRC-S. For the M6x12 T30 screws, used to secure the Vertiv VRC to the EIA-rails, use
5.6 Nm (4.13 ft-lb.) tightening torque.
For VRC split there is need to interconnect the indoor and outdoor unit, for more details see VRC manual.
NOTE: Piping between the indoor and outdoor units must be routed so that it does not block the IT
space above and does not extend into the space between the EIA rails.
1. Take the power cord attached to the backup fan and cut the zip tie.
2. Connect the power cord to the Geist rPDU as shown in Figure 4.4 on the facing page .
3. Route the power cord to the Geist rPDU.
4. Locate the proper receptacle on the Geist rPDU and plug the power cord into it. The receptacle is marked with
a sticker showing a small fan (see Figure 4.4 on the facing page ).
24 4 Installation
Vertiv™| VRC-S User Manual
2 Backup fan
1. Connect the power cord to the condensate pump as shown in Figure 4.5 below .
2. Route the power cord over top of the transition piece to the Geist rPDU.
3. Locate the proper receptacle and plug the power cord into the Geist rPDU receptacle. The receptacle is
marked with a sticker to indicate where the condensate plug should go.
4 Installation 25
Vertiv™ VRC-S User Manual
The local display may be installed on either the door or laid on the Vertiv VRC. If the display is to be placed on the cooling
unit, simply attach the 20in. (50cm) communication cable to the rack and to the rear of the cooling unit as shown Figure 4.6
below .
IMPORTANT! Vertiv recommends installing the display in the opening fabricated in the rear door.
1. Remove the magnetic case from the display by extracting the four screws holding the assembly together.
2. Insert the display into the cutout on the rear door of the Vertiv™ VR and secure it with the four screws removed
in Step 1 .
3. Connect the 32 ft. (10m) display cable to the display and route it around the top of the exhaust fan and to the
Vertiv VRC.
4. Plug the cable into the Vertiv VRC as shown in Figure 4.6 below .
26 4 Installation
Vertiv™| VRC-S User Manual
1 Local Display
WARNING! Risk of electric shock. Can cause property damage, injury and death. The backup
fan input power cable is a live wire when connected. Pulling it loose from the connector or
abrading it on the rack may expose personnel to hazardous voltage. When routing the cable, be
sure to leave enough slack in the cables to permit the door to open fully without straining the
cables' connections.
To route the cables for the local display and the fan:
IMPORTANT! The cables must be properly placed in the cable tie so they can be positioned under the
lip of the door for protection against pinching.
b. Slip the longer end around the cables and through the ratcheted end of the cable tie.
c. Pull the cable tie until it is snug around the cables.
d. Snip off the excess cable to ease attachment to the door.
4. Leaving adequate slack in the cables, press the clip onto the top inner edge of the rear door as shown in Figure
4.7 on the next page . The cables should be under the door's lip to prevent pinching.
5. Repeat 3 to attach at least one more cable tied bundle near the hinged edge of the door.
6. Leaving adequate slack in the cables for the door to open, secure the cables to the rack rail near the Geist™
rPDU.
7. Secure the cables to the rack rail as needed for good cable management.
4 Installation 27
Vertiv™ VRC-S User Manual
Item Description
4 Fan cable
1. Take the communication cable out of the packaging and straighten the coils, removing any kinks.
2. Plug the RJ-45 connector into either of the two ports on the rear of the Vertiv VRC.
3. Route the cable to the Geist rPDU and connect it as shown in Figure 4.8 on the facing page .
28 4 Installation
Vertiv™| VRC-S User Manual
Item Description
1 RJ-45 port on the rear of the Vertiv VRC (either port may be used)
2 Monitoring cable connected to an RJ-45 port on the rear of the Vertiv VRC (either port may be used)
The Vertiv VRC-S includes a flexible duct and two ceiling tiles, one to move warm air from the Vertiv VRC-C into the ceiling
or and adjacent area through the duct. The second tile is for make-up air to deliver enough fresh air to the room.
WARNING! The two air traces (warm air and make-up air) must be separated.
The factory-supplied ducting attaches to the transition piece on the rear of the Vertiv VRC with a large hose clamp (factory-
supplied) that tightens around the two pieces. The ceiling grille may be used where a conventional dropped ceiling with
frames is used. The flexible ducting connects to the ceiling tile with the second hose clamp supplied by the factory.
4 Installation 29
Vertiv™ VRC-S User Manual
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment
damage, injury or death. Only properly trained and qualified personnel wearing appropriate
OSHA-approved personal protection equipment (PPE) should attempt to move, lift, remove
packaging from or prepare this unit for installation. Read all instructions before attempting to
move, lift, remove packaging from or prepare the unit for installation.
Vertiv recommends installing equipment in the Vertiv VR from bottom to top, to promote a
lower center of gravity.
All equipment must be installed using the rails or a support shelf. No equipment should be
installed directly on the Vertiv VRC or Liebert®GXT5. This arrangement is necessary to permit
replacing the Vertiv VRC's filter and to permit the unit's removal for service.
IMPORTANT! As a best practice, all unused rack space should be covered with the optional blanking
panels to promote the most effective airflow patterns and prevent short cycling of cooling airflow.
30 4 Installation
Vertiv™| VRC-S User Manual
5 Operation
5.1 Initial Startup—Vertiv™ Services
Startup services are available from Vertiv Services Services. If startup services are included with your unit, Vertiv personnel
will start the Vertiv™ VRC-S and make all settings required for proper operation.
NOTE: Vertiv recommends installing and preparing rack equipment before starting the Vertiv VRC-S so
that the cooling unit will have a heat load to operate with. Starting up the Vertiv™ VRC with the
maximum heat load can cause erratic operation and may damage the cooling unit.
Refer to the Vertiv VRC user manual, which shipped with the Vertiv VRC-S, for instructions on starting the unit.
After connecting the rPDU to your network, log in as detailed in the rPDU user manual. You must create an account and
password. Open the Sensors page and scroll to the Vertiv VRC panel at the bottom of the page.
Check the settings for the cooling unit and adjust as required. The Vertiv VRC must be operated as specified in
Specifications on page 41 .
The Geist rPDU interface, shown in Figure 5.1 on the next page , permits monitoring and managing the Vertiv VRC-S. The
interface recognizes the Vertiv VRC as a sensor. The Sensors page shows the status of the component or function, a wrench
symbol permits changing the configuration if logged in with proper access, the name of the component or function, current
readings and an arrow reveals additional information in a drop-down menu.
For details on changing the settings, refer to the Geist rPDU manual that shipped with the unit.
5 Operation 31
Vertiv™ VRC-S User Manual
Figure 5.1 Geist rPDU Sensor Page > Vertiv VRC Settings
Table 5.1 Geist rPDU Sensor Page > Vertiv VRC Settings Descriptions
Item Description
3 Component Name
4 Current Readings
5 Additional Information
32 5 Operation
Vertiv™| VRC-S User Manual
5 Operation 33
Vertiv™ VRC-S User Manual
34 5 Operation
Vertiv™| VRC-S User Manual
6 Troubleshooting
6.1 Troubleshooting the Vertiv™ VRC
Table 6.1 Troubleshooting the Vertiv VRC
Message or Problem Possible Cause Suggested Action
Loss of Check the input cord and ensure that it is connected to the specified power source.
power
Reset building input circuit breaker.
Confirm that blanking panels are installed in any unused rack space to prevent short-
cycling of Vertiv VRC airflow.
Poor Confirm there are no obstructions such as cable bundles or equipment chassis blocking
Internal the internal supply and return airflow paths.
Airflow Review and follow Preventive Maintenance procedures in the Vertiv VRC user manual.
High
Temperature
Check the front and rear filters. Replace them if they are dirty as described in the Vertiv
VRC user manual.
Confirm that the rack has unobstructed front and rear clearances of at least 12 in. (305
mm).
Poor External Airflow Verify that the heat rejection duct at the rear of the rack is free of debris and airflow
obstructions.
The warm ambient air influences the indoor temp because the system is not sealed.
Alarm temperature setpoint is Adjust the setpoint temperature that triggers the alarm. Refer to the Vertiv VRC user
too low. manual.
Make sure that the actual heat load is not above the maximum rated value. The Vertiv
Thermal overload VRC's maximum load at 30°C (86°F) is 3,3 kW; the Vertiv VRC's cooling module is rated
to remove 3.5 kW worth of heat.
Equipment or blanking panels should be added to prevent this. The equipment should
Air mixing in the rack due to
cover the whole width of 19 in. profile, with adapters. Add additional blanking panels or
gaps between front and rear of
equipment. Airflow should not be able to mix from front to rear; this will inhibit the cool
rack.
airflow up the front of the rack.
Internal drain line clogged or Check the condensate drain line for obstructions and verify it is not kinked and runs
kinked freely.
Water Leaking from or into Cabinet not level Confirm that the leveling feet are adjusted to the make the cabinet level.
the Cabinet
Confirm that the condensate drain line is properly connected to the condensate pump
Drain line is not connected to
outlet. Loosen the O-ring clamp if necessary and press the line onto the outlet nozzle,
condensate pump.
tighten clamp.
6 Troubleshooting 35
Vertiv™ VRC-S User Manual
High Pressure Vertiv VRC Fan malfunction Contact Vertiv Technical Support.
Condenser malfunction or
Contact Vertiv Technical Support.
refrigerant leak
Confirm the power plug from the fan is plugged into outlet
marked with the symbol for the fan.
36 6 Troubleshooting
Vertiv™| VRC-S User Manual
• The alarm indicator illuminates, indicating the UPS has detected a problem.
• An alarm buzzer sounds, alerting the user that the UPS requires attention.
Continuous beep Generated when a UPS fault appears, such as a fuse or hardware failure.
One beep every 0.5 seconds Generated when a UPS critical alarm appears, such as on inverter overload.
One beep every 1 second. Generated when a UPS critical alarm appears, such as on battery low voltage
One beep every 3.3 seconds Generated when a UPS general alarm appears
NOTE: When an alarm is indicated, an alarm message is logged. See Liebert® GTX5 User Manual that
describes the alarm messages. When a fault is indicated, front-panel display list the fault, which are
described in Table 6.4 below .
6.2.3 Faults
When the fault indicator is illuminated, the LCD displays the fault. The faults are described in Table 6.4 below .
Battery test fail The battery is bad or weak. Contact technical support.
Inverter overload,
The UPS is overloaded, Bypass is over current. Reduce the load and contact technical support.
Bypass overcurrent
Output short The output connection is short-circuited. Shut-down the equipment and contact technical support.
6 Troubleshooting 37
Vertiv™ VRC-S User Manual
When reporting a UPS issue to Vertiv, include the UPS model and serial number. These are located in several places for
your ease of location:
Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles.
UPS is short- circuited or overloaded.
Ensure loads are not defective or shorted internally.
UPS fails to start
Check to ensure the internal battery is connected. If it is not, fully remove and reinstall the
Batteries are not charge denough or
battery, and try to start the unit. If the battery is connected, leave the UPS connected to
not connected.
input power for 24 hours to recharge batteries, then try to start the unit.
Batteries are not fully charged. Keep UPS plugged in continuously at least 24 hours to recharge batteries.
UPS has reduced
UPS is overloaded. Check load level indicator and reduce the load on the UPS.
battery backup
time Batteries may not be able to hold a Replace batteries. Contact your Vertiv representative or Vertiv Technical Support for
full charge due to age. replacement battery kit.
38 6 Troubleshooting
Vertiv™| VRC-S User Manual
IMD-01
The IMD discovered either none or more than one input boards. This may be caused by internal cabling issues or
Err1 (Metered
an unresponsive input board. This is also displayed if there is a measurement error reported by the input board.
only)
IMD-02,
IMD is booting and has yet to discover the simple display and shows boot on it. If this is displayed for more than a
8888 IMD-03,
few seconds there is a problem with the display board or with internal cabling.
IMD-3
“ --”
IMD-02,
(Two dashes on the The IMD cannot communicate with the input board. This may also be shown intermittently for individual
IMD-03,
rightmost display measurements. There is a problem with the input board or with internal cabling.
IMD-3
position)
IMD-02,
boot IMD-03, Firmware is initializing. This will be displayed while firmware is being updated in slave boards.
IMD-3
IMD-02,
updt IMD-03, Firmware update in progress.
IMD-3
IMD-02,
Following user action, rset (Reset) will appear during a parameter reset sequence. During a parameter reset, dflt
rset dflt IMD-03,
(Default) will appear briefly.
IMD-3
IMD-02,
bcup IMD-03, bcup (Backup) will appear during a configuration backup.
IMD-3
IMD-02,
rest conf IMD-03, rest (Restore) and Conf (Configuration) will appear during a configuration restore.
IMD-3
Alarm temperature setpoint too low. Adjust the setpoint temperature that triggers the alarm.
Overload condition. Make sure that the actual head load is not above the maximum rated value.
High Temperature
Fan malfunction. Contact Vertiv Technical Support.
Alarm temperature setpoint too high. Adjust the setpoint temperature that triggers the alarm.
8 Specifications
8.1 Vertiv™ VRC-S with VRC self-contained 120V NAM
VRC-S SKUs VRCS3350-120V VRCS3300-120V VRCS3307-120V VRCS3357-120V
Configured system weight 319 kg (704 lb.) 274 kg (605 lb.) 310 kg (684 lb.) 337 kg (743 lb.)
Shipping weight 419 kg (924 lb.) 361 kg (796 lb.) 397 kg (876 lb.) 437 kg (964 lb.)
Sound (at 60% fan speed and 40% compressor speed) 52.5 dBA @ 1 m 52.5 dBA @ 1 m 52.5 dBA @ 1 m 52.5 dBA @ 1 m
42U; 2000 mm, 800 42U; 2000 mm, 600 48U; 2200 mm, 600 48U; 2200 mm, 800
Rack dimensions U; H, W, D mm, 1200 mm (78.6 mm, 1200 mm (78.6 mm, 1200 mm (86.6 mm, 1200 mm (86.6
in., 31.5 in., 47.8 in.) in., 23.6 in., 47.8 in.) in., 23.6 in., 47.8 in.) in., 31.5 in., 47.8 in.)
2134 mm, 826 mm, 2134 mm, 626 mm, 2396 mm, 626 mm, 2396 mm, 826 mm,
Shipping dimensions of rack H, W, D 1385 mm(84 in., 32.5 1385 mm(84 in., 24.6 1385 mm (94.3 in., 1385 mm (94.3 in.,
in., 54.5 in.) in., 54.5 in.) 24.6 in., 54.5 in.) 32.5 in., 54.5 in.)
Voltage 120 V
Input current 30 A
Horizontal/Vertical Vertical
Cord length 3m
ARP, IPv4, IPv6, ICMP, ICMPv6, NDP, TCP, UDP, RSTP, STP, DNS, HTTP, HTTPS (TLSv1.2),
Geist Upgradable 2.0 protocols supported
SMTP, SMTPS, DHCP, SNMP (v1/v2c/v3), LDAP, NTP, SSH, and Syslog
Certifications/Agency approvals UL & c-UL Listed 60950, RoHS Compliant, FCC Part 15 Class A Conformance
8 Specifications 41
Vertiv™ VRC-S User Manual
10U
VRC form factor NOTE: Do not block any U spaces with equipment past the rear EIA mounting
rails
Shipping dimensions H, D, W 1194 mm, 737 mm, 889 mm (47 in., 29 in., 35 in.)
Certifications UL 484
Configured system weight 319 kg (704 lb.) 274 kg (605 lb.) 310 kg (684 lb.) 337 kg (743 lb.)
Shipping weight 419 kg (924 lb.) 361 kg (796 lb.) 397 kg (876 lb.) 437 kg (964 lb.)
42U; 2000 mm, 800 42U; 2000 mm, 600 48U; 2200 mm, 600 48U; 2200 mm, 800
Rack dimensions U; H, W, D mm, 1200 mm (78.6 in., mm, 1200 mm (78.6 in., mm, 1200 mm (86.6 in., mm, 1200 mm (86.6 in.
31.5 in., 47.8 in.) 23.6 in., 47.8 in.) 23.6 in., 47.8 in.) 31.5 in., 47.8 in.)
2134 mm, 826 mm, 1385 2134 mm, 626 mm, 1385 2396 mm, 626 mm, 2396 mm, 826 mm,
Shipping dimensions of rack H, W, D mm (84 in., 32.5 in., 54.5 mm (84 in., 24.6 in., 54.5 1385 mm (94.3 in., 24.6 1385 mm (94.3 in., 32.5
in.) in.) in., 54.5 in.) in., 54.5 in.)
Input current 30 A 30 A
42 8 Specifications
Vertiv™| VRC-S User Manual
Cord length 3m 3m
(20) U-Lock IEC C13 (4) U-Lock IEC C19 (30) U-Lock IEC C13 (6) U-Lock IEC C19
Outlets NOTE: (2) U-Lock IEC C13 outlets will be NOTE: (2) U-Lock IEC C13 outlets will be
required and preprogrammed for the required and preprogrammed for the
backup fan and condensate pump backup fan and condensate pump
ARP, IPv4, IPv6, ICMP, ICMPv6, NDP, TCP, UDP, ARP, IPv4, IPv6, ICMP, ICMPv6, NDP, TCP, UDP,
RSTP, STP, DNS, HTTP, HTTPS (TLSv1.2), SMTP, RSTP, STP, DNS, HTTP, HTTPS (TLSv1.2), SMTP,
Geist Upgradable 2.0 protocols supported
SMTPS, DHCP, SNMP (v1/v2c/v3), LDAP, NTP, SMTPS, DHCP, SNMP (v1/v2c/v3), LDAP, NTP,
SSH, and Syslog SSH, and Syslog
UL & c-UL Listed 60950, RoHS Compliant, FCC Part UL & c-UL Listed 60950, RoHS Compliant, FCC
Certifications/Agency approvals
15 Class A Conformance Part 15 Class A Conformance
10U
VRC form factor
NOTE: Do not block any U spaces with equipment past the rear EIA mounting rails
Shipping dimensions H, D, W 1194 mm, 737 mm, 889 mm (47 in., 29 in., 35 in.)
Certifications UL 484
8 Specifications 43
Vertiv™ VRC-S User Manual
8.3 Vertiv™ VRC-S with VRC split lee temp 120 V NAM
VRC-S SKUs VRCS3350-120VSL VRCS3300-120VSL VRCS3307-120VSL VRCS3357-120VSL
Configured system weight 270 kg (595 lb.) 225 kg (496 lb.) 261 kg (575 lb.) 288 kg (635 lb.)
Shipping weight 336 kg (741 lb.) 278 kg (613 lb.) 314 kg (692 lb.) 354 kg (781 lb.)
42U; 2000 mm, 800 mm, 42U; 2000 mm, 600 mm, 48U; 2200 mm, 600 mm, 48U; 2200 mm, 800 mm,
Rack dimensions U; H, W,
1200 mm (78.6 in., 31.5 in., 1200 mm (78.6 in., 23.6 in., 1200 mm (86.6 in., 23.6 in., 1200 mm (86.6 in., 31.5 in.,
D
47.8 in.) 47.8 in.) 47.8 in.) 47.8 in.)
Shipping dimensions of 2134 mm, 826 mm, 1385 mm 2134 mm, 626 mm, 1385 mm 2396 mm, 626 mm, 1385 mm 2396 mm, 826 mm, 1385 mm
rack H, W, D (84 in., 32.5 in., 54.5 in.) (84 in., 24.6 in., 54.5 in.) (94.3 in., 24.6 in., 54.5 in.) (94.3 in., 32.5 in., 54.5 in.)
rPDU (Pre-installed in
NU30021
rack)
Voltage 120 V
Input current 30 A
Horizontal/Vertical Vertical
Cord length 3m
Vertive Intelligence
YES
Director enabled
Geist Upgradable 2.0 ARP, IPv4, IPv6, ICMP, ICMPv6, NDP, TCP, UDP, RSTP, STP, DNS, HTTP, HTTPS (TLSv1.2), SMTP, SMTPS, DHCP, SNMP
protocols supported (v1/v2c/v3), LDAP, NTP, SSH, and Syslog
Certifications/Agency
UL & c-UL Listed 60950, RoHS Compliant, FCC Part 15 Class A Conformance
approvals
44 8 Specifications
Vertiv™| VRC-S User Manual
6U
VRC Form Factor
NOTE: Do not block any U spaces with equipment past the rear EIA mounting rails.
VRC-S operating
18°C-30°C (65°F-86°F)
temperature
Condensate pump
Yes, powered via rPDU
integrated
Dimensions H, W, D 527 mm, 282 mm, 1158 mm ( 20.75 in., 11.10 in., 45.60 in.)
Shipping dimensions H, W, D 755 mm, 480 mm, 1350 mm (29.72 in., 18.90 in., 53.20 in.)
8 Specifications 45
Vertiv™ VRC-S User Manual
8.4 Vertiv™ VRC-S with VRC split lee temp 208V NAM
VRC-S SKUs VRCS3350-208VSL VRCS3300-208VSL VRCS3307-208VSL VRCS3357-208VSL
Configured system
270 kg (595 lb.) 225 kg (496 lb.) 261 kg (575 lb.) 288 kg (635 lb.)
weight
Shipping weight 336 kg (741 lb.) 278 kg (613 lb.) 314 kg (692 lb.) 354 kg (781 lb.)
42U; 2000 mm, 800 mm, 42U; 2000 mm, 600 mm, 48U; 2200 mm, 600 mm, 48U; 2200 mm, 800 mm,
Rack dimensions U; H,
1200 mm (78.6 in., 31.5 in., 1200 mm (78.6 in., 23.6 in., 1200 mm (86.6 in., 23.6 in., 1200 mm (86.6 in., 31.5 in.,
W, D
47.8 in.) 47.8 in.) 47.8 in.) 47.8 in.)
Shipping dimensions of 2134 mm, 826 mm, 1385 mm 2134 mm, 626 mm, 1385 mm 2396 mm, 626 mm, 1385 mm 2396 mm, 826 mm, 1385 mm
rack H, W, D (84 in., 32.5 in., 54.5 in.) (84 in., 24.6 in., 54.5 in.) (94.3 in., 24.6 in. 54.5 in.) (94.3 in., 32.5 in., 54.5 in.)
rPDU (Pre-installed in
VP8641 VP5870V
rack)
Input current 30 A 30 A
Regularoty derated
input current (North 24 A 24 A
America)
Cord length 3m 3m
(20) U-Lock IEC C13 (4) U-Lock IEC C19 (30) U-Lock IEC C13 (6) U-Lock IEC C19
Outlets NOTE: (2) U-Lock IEC C13 outlets will be required NOTE: (2) U-Lock IEC C13 outlets will be required
and preprogrammed for the backup fan and and preprogrammed for the backup fan and
condensate pump condensate pump
Vertive Intelligence
YES YES
Director enabled
ARP, IPv4, IPv6, ICMP, ICMPv6, NDP, TCP, UDP, RSTP, STP, ARP, IPv4, IPv6, ICMP, ICMPv6, NDP, TCP, UDP, RSTP, STP,
Geist Upgradable 2.0
DNS, HTTP, HTTPS (TLSv1.2), SMTP, SMTPS, DHCP, SNMP DNS, HTTP, HTTPS (TLSv1.2), SMTP, SMTPS, DHCP, SNMP
protocols supported
(v1/v2c/v3), LDAP, NTP, SSH, and Syslog (v1/v2c/v3), LDAP, NTP, SSH, and Syslog
Certifications/Agency UL & c-UL Listed 60950, RoHS Compliant, FCC Part 15 Class A UL & c-UL Listed 60950, RoHS Compliant, FCC Part 15 Class
approvals Conformance A Conformance
46 8 Specifications
Vertiv™| VRC-S User Manual
6U
VRC form factor
NOTE: Do not block any U spaces with equipment past the rear EIA mounting rails
VRC-S operating
18°C-30°C (65°F-86°F)
temperature
VRC-S operating
8%-80% (non-condensing)
humidity
Condensate pump
Yes, powered via rPDU
integrated
Dimensions H, W, D 527 mm, 282 mm, 1158 mm ( 20.75 in., 11.10 in., 45.60 in.)
Shipping dimensions H, W, D 755 mm, 480 mm, 1350 mm (29.72 in., 18.90 in., 53.20 in.)
8 Specifications 47
Vertiv™ VRC-S User Manual
Configured system weight 321 kg (708 lb.) 276 kg (609 lb.) 312 kg (688 lb.) 339 kg (747 lb.)
Shipping weight 421 kg (928 lb.) 363 kg (800 lb.) 399 kg (880 lb.) 439 kg (968 lb.)
42U; 2000 mm, 800 mm, 42U; 2000 mm, 600 mm, 48U; 2200 mm, 600 mm, 48U; 2200 mm, 800 mm,
Rack dimensions U; H, W,
1200 mm (78.6 in., 31.5 in., 1200 mm (78.6 in., 23.6 in., 1200 mm (86.6 in., 23.6 in., 1200 mm (86.6 in., 31.5 in.,
D
47.8 in.) 47.8 in.) 47.8 in.) 47.8 in.)
Shipping dimensions of 2134 mm, 826 mm, 1385 mm 2134 mm, 626 mm, 1385 mm 2396 mm, 626 mm, 1385 mm 2396 mm, 826 mm, 1385 mm
rack H, W, D (84 in., 32.5 in., 54.5 in.) (84 in., 24.6 in., 54.5 in.) (94.3 in., 24.6 in., 54.5 in.) (94.3 in., 32.5 in., 54.5 in.)
rPDU (Pre-installed in
GU30017L
rack)
Category Switched
Current 32 A
Frequency 50/60 Hz
Over Current Protection (2) 16A Single Pole Magnetic Breakers (5kAIC Rated)
Horizontal/Vertical Vertical
Outlets (20) Locking IEC 320 C13, (4) Locking IEC 320 C19
Vertive Intelligence
Yes
Director enabled
Certifications/Agency CE Marked, Complies with EN 55032 and EN 55024, Complies with IEC 60950-1 (CB Certificate Available), RoHS Compliant,
Approvals RCM Mark (EMC Only), China RoHS, C مMark
VRC Input plug IEC 320 C20 Inlet + Interconnection Cable IEC 320 C19 to C20
48 8 Specifications
Vertiv™| VRC-S User Manual
10U
VRC form factor
NOTE: Do not block any U spaces with equipment past the rear EIA mounting rails
Shipping dimensions
1194 mm, 737 mm, 889 mm(47 in.,29 in., 35 in.)
H,D,W; (Inches)
VRC-S Operating
18°C-30°C (65°F-86°F)
Temperature
VRC-S Operating
8-80 % (non-condensing)
Humidity
Condensate Pump
Yes, powered via rPDU
integrated
CE Marked, Complies with EN 60335-1, EN 60335-2-40, EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3, RoHS
Certifications
Compliant
8.6 Vertiv™ VRC-S with VRC split and VRC-S with VRC split
lee temp 230V EMEA
VRCS3350-230VS / VRCS3300-230VS / VRCS3307-230VS / VRCS3357-230VS /
VRC-S SKUs
VRCS3350-230VSL VRCS3300-230VSL VRCS3307-230VSL VRCS3357-230VSL
Configured system weight 270 kg (595 lb.) 225 kg (496 lb.) 261 kg (575 lb.) 288 kg (635 lb.)
Shipping weight 336 kg (741 lb.) 278 kg (613 lb.) 314 kg (692 lb.) 354 kg (781 lb.)
42U; 2000 mm, 800 mm, 42U; 2000 mm, 600 mm, 48U; 2200 mm, 600 mm, 48U; 2200 mm, 800 mm,
Rack dimensions U; H, W,
1200 mm (78.6 in., 31.5 in., 1200 mm (78.6 in., 23.6 in., 1200 mm (86.6 in., 23.6 in., 1200 mm (86.6 in., 31.5 in.,
D
47.8 in.) 47.8 in.) 47.8 in.) 47.8 in.)
Shipping dimensions of 2134 mm, 826 mm, 1385 mm 2134 mm, 626 mm, 1385 mm 2396 mm, 626 mm, 1385 mm 2396 mm, 826 mm, 1385 mm
rack H, W, D (84 in., 32.5 in., 54.5 in.) (84 in., 24.6 in., 54.5 in.) (94.3 in., 24.6 in., 54.5 in.) (94.3 in., 32.5 in., 54.5 in.)
Certifications CE Marked
rPDU (Pre-installed in
GU30017L
rack)
8 Specifications 49
Vertiv™ VRC-S User Manual
Frequency 50/60 Hz
Over current protection (2) 16 A Single Pole Magnetic Breakers (5 kAIC Rated)
Horizontal/Vertical Vertical
Outlets (20) Locking IEC 320 C13, (4) Locking IEC 320 C19
Vertive Intelligence
Yes
Director enabled
Certifications/Agency CE Marked, Complies with EN 55032 and EN 55024, Complies with IEC 60950-1 (CB Certificate Available), RoHS Compliant,
approvals RCM Mark (EMC Only), China RoHS, C مMark
VRC-S operating
18°C-30°C (65°F-86 °F)
temperature
Condensate pump
Yes, powered via rPDU
integrated
CE Marked, Complies with EN 60335-1; EN 60335-2-40, EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3, RoHS
Certifications
Compliant (EN 50581)
50 8 Specifications
Vertiv™| VRC-S User Manual
Dimensions H, W, D 527 mm, 282 mm, 1158 mm ( 20.75 in., 11.10 in., 45.60 in.)
Shipping dimensions H,W,D 755 mm, 480 mm, 1350 mm (29.72 in., 18.90 in., 53.20 in.)
CE Marked, Complies with EN 60335-1; EN 60335-2-40, EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3, RoHS
Certifications
Compliant (EN 50581)
Dimensions H, W, D 527 mm, 282 mm, 786 mm ( 20.75 in., 11.10 in., 30.94 in.)
Shipping dimensions H,W,D 750 mm, 480 mm, 970 mm (29.53 in., 18.90 in., 38.19 in.)
CE Marked, Complies with EN 60335-1; EN 60335-2-40, EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3, RoHS
Certifications
Compliant (EN 50581)
8 Specifications 51
Vertiv™ VRC-S User Manual
Configured system weight 392 kg (864 lbs) 347 kg (765 lbs) 383 kg (844 lbs) 410 kg (903 lbs)
Shipping Weight 492 kg (1084 lbs) 434 kg (956 lbs) 470 kg (1036 lbs) 510 kg (1124 lbs)
Rack dimensions U; 42U; 2000 mm, 800 mm, 42U; 2000 mm,600 mm, 48U; 2200 mm,600 mm, 48U; 2200 mm, 800 mm,
HxWxD; (Inches) 1200 mm (78.6", 31.5", 47.8") 1200 mm (78.6", 23.6", 47.8") 1200 mm (86.6", 23.6", 47.8") 1200 mm (86.6", 31.5", 47.8")
Shipping dimensions of 2134mm, 826mm, 1385mm 2134mm, 626mm, 1385mm 2396mm, 626mm, 1385mm 2396mm, 826mm, 1385mm
rack HxWxD; (Inches): (84", 32.5", 54.5") (84", 24.6", 54.5") (94.3", 24.6", 54.5") (94.3", 32.5", 54.5")
Certifications CE Marked
Category Switched
Current 32 A
Frequency 50/60 Hz
Over Current Protection (2) 16 A Single Pole Magnetic Breakers (5 kAIC Rated)
Outlets (20) Locking IEC 320 C13, (4) Locking IEC 320 C19
Geist™ Upgradable 2.0 protocols DHCP, HTTP, HTTPS, IPv4, IPv6, LDAP, NTP, RADIUS, RSTP, SSH, SMTP, SNMP (v1/v2c/v3), Syslog,
supported TACACS+
CE Marked, Complies with EN 55032 and EN 55024, Complies with IEC 60950-1 (CB Certificate Available), RoHS
Certifications /Agency Approvals
Compliant, RCM Mark (EMC Only), China RoHS, C مMark
VRC Input plug IEC 320 C20 Inlet + Interconnection Cable IEC 320 C19 to C20
52 8 Specifications
Vertiv™| VRC-S User Manual
Shipping dimensions H,D,W; (Inches) 1194mm, 737mm, 889mm (47", 29", 35")
UPS (Pre-installed
GXT5-6000IRT5UXLE
in rack):
Form factor 5U
Unit dimensions
217 mm x 630 mm x 430 mm (8.5" x 24.8" x 16.9")
HxDxW; (Inches)
Input AC Parameters
Operating Frequency,
50 or 60 Hz (factory-default is 50 Hz)
Nom.
User-configurable
200/208/220/230/240 VAC [Adjustable using operation/display configuration options] (Factory-default is 230 VAC)
VAC
Output AC
Parameters
Factory-default VAC,
230 VAC, 50 Hz
Frequency
Waveform Sinewave
Battery Parameters
8 Specifications 53
Vertiv™ VRC-S User Manual
UPS (Pre-installed
GXT5-6000IRT5UXLE
in rack):
Quantity x Voltage x
16 x 12V x 9.0AH
Rating
Back-up time:
LOAD 6 kVA 5,4 kVA 4,8 kVA 4,2 kVA 3,6 kVA 3 kVA 2,4 kVA 1,8 kVA 1,2 kVA 0,6 kVA
BACKUP TIME 5,5 min 6,0 min 7,5 min 9,0 min 11,0 min 14,5 min 19,5 min 29,0 min 48,0 min 100,0 min
Environmental
Operating
0°C to 40°C (32°F to 104°F) (no derating)
Temperature
Audible Noise <55 dBA,at 1 meter from the front, <50 dBA, at 1 meter from rear or sides
Agency
EMI/EMC/C-Tick
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
EMC
Radiated
IEC/EN EN61000-4-3, Level 3, Criteria A
Susceptibility
Electrical Fast
IEC/EN EN61000-4-4, Level 4, Criteria A
Transient
54 8 Specifications
Vertiv™| VRC-S User Manual
8.8 Vertiv™ VRC-S with VRC split and VRC-S with VRC split
lee temp 230V EMEA and Liebert® GXT5
VRCS3350-230VSU/ VRCS3300-230VSU/ VRCS3307-230VSU/ VRCS3357-230VSU/
VRC-S SKUs:
VRCS3350-230VSLU VRCS3300-230VSLU VRCS3307-230VSLU VRCS3357-230VSLU
Configured system
341 kg (751 lbs) 296 kg (652 lbs) 332 kg (731 lbs) 359 kg (791 lbs)
weight
Shipping Weight 407 kg (897 lbs) 349 kg (769 lbs) 385 kg (848 lbs) 425 kg (937 lbs)
Rack dimensions U; 42U; 2000 mm, 800 mm, 42U; 2000 mm,600 mm, 48U; 2200 mm,600 mm, 48U; 2200 mm, 800 mm,
HxWxD; (Inches) 1200 mm (78.6", 31.5", 47.8") 1200 mm (78.6", 23.6", 47.8") 1200 mm (86.6", 23.6", 47.8") 1200 mm (86.6", 31.5", 47.8")
Shipping dimensions of 2134mm, 826mm, 1385mm 2134mm, 626mm, 1385mm 2396mm, 626mm, 1385mm 2396mm, 826mm, 1385mm
rack HxWxD; (Inches) (84", 32.5", 54.5") (84", 24.6", 54.5") (94.3", 24.6", 54.5") (94.3", 32.5", 54.5")
Frequency 50/60 Hz
Over Current Protection (2) 16 A Single Pole Magnetic Breakers (5 kAIC Rated)
Horizontal/Vertical Vertical
Outlets (20) Locking IEC 320 C13, (4) Locking IEC 320 C19
CE Marked, Complies with EN 55032 and EN 55024, Complies with IEC 60950-1 (CB Certificate Available), RoHS
Certifications/Agency Approvals
Compliant, RCM Mark (EMC Only), China RoHS, C مMark
8 Specifications 55
Vertiv™ VRC-S User Manual
Dimensions H, W, D; (Inches) 527 mm, 282 mm, 786 mm ( 20.75", 11.10", 30.94")
Shipping dimensions H,W,D; (Inches) 750 mm, 480 mm, 970 mm (29.53", 18.90", 38.19")
56 8 Specifications
Vertiv™| VRC-S User Manual
Dimensions H, W, D; (Inches) 527 mm, 282 mm, 1158 mm ( 20.75", 11.10", 45.60")
CE Marked, Complies with EN 60335-1; EN 60335-2-40, EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3, RoHS
Certifications
Compliant (EN 50581)
UPS (Pre-installed in
GXT5-6000IRT5UXLE
rack):
Form factor 5U
Input AC Parameters
User-configurable VAC 200/208/220/230/240 VAC [Adjustable using operation/display configuration options] (Factory-default is 230 VAC)
Output AC Parameters
Factory-default VAC,
230 VAC, 50 Hz
Frequency
Waveform Sinewave
Battery Parameters
Back-up time:
LOAD 6 kVA 5,4 kVA 4,8 kVA 4,2 kVA 3,6 kVA 3 kVA 2,4 kVA 1,8 kVA 1,2 kVA 0,6 kVA
BACKUP TIME 5,5 min 6,0 min 7,5 min 9,0 min 11,0 min 14,5 min 19,5 min 29,0 min 48,0 min 100,0 min
8 Specifications 57
Vertiv™ VRC-S User Manual
UPS (Pre-installed in
GXT5-6000IRT5UXLE
rack):
Environmental
Audible Noise <55 dBA,at 1 meter from the front, <50 dBA, at 1 meter from rear or sides
Agency
58 8 Specifications
Vertiv™| VRC-S User Manual
9 Appendices
Appendix A: Startup Checklist Vertiv™ VRC-S
Completed Item
There is front, rear and overhead clearance of 3 ft. (0.9 m) for unit access and maintenance.
Unit is level.
Heaviest equipment is installed nearest the bottom of the cabinet, but not sitting on the Vertiv™ VRC
Vertiv VRC is oriented correctly in the rack cabinet: cool, supply air is at the front and hot, return air is at the back.
Foreign materials are removed from the rack (shipping material, packaging, tools, etc.)
Condensate-drain line is properly connected to the pump and to a drain or receptacle and has no kinks.
External ventilation is adequate to supply makeup air for the Vertiv VRC. (System is not closed.)
External air is within a temperature range of 64.4°F-86°F (18°C-30°C), condensing and less than 90% relative humidity (non-
condensing).
Exhaust air duct is connected securely to the Vertiv VRC and to either an external area or other space for cooling.
9 Appendices 59
Vertiv™ VRC-S User Manual
60 9 Appendices
Vertiv™| VRC-S User Manual
[Link] | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2021 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All
other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has
been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages
resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional offers are subject to change at
Vertiv’s sole discretion upon notice.
SL-07003_REVC_02-21