This Technical Service Bulletin provides a Standard Operating Procedure (SOP) for checking the AVR models R120 and R121, which are used in alternators. It outlines common issues such as voltage problems and fuse failures, and emphasizes the importance of following the SOP to avoid unnecessary replacements. The document includes detailed steps for diode, continuity, and resistance checks, as well as a checklist for troubleshooting various faults.

Uploaded by

Ganesh M
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
151 views9 pages

AVR R120 and R121

This Technical Service Bulletin provides a Standard Operating Procedure (SOP) for checking the AVR models R120 and R121, which are used in alternators. It outlines common issues such as voltage problems and fuse failures, and emphasizes the importance of following the SOP to avoid unnecessary replacements. The document includes detailed steps for diode, continuity, and resistance checks, as well as a checklist for troubleshooting various faults.

Uploaded by

Ganesh M
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Technical Service Bulletin

Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
 R120 ( For 1 and 3 Phase)
 R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121

A. Product Affected:-
 Alternators with AVR R120 and R121

B. Issue

 Voltage Issues and Fuse Failure.


 Post receipt of failed part at HO (AVR), it has been observed in majority cases the replaced AVR has
been found OK.

C. Service Information

 Before replacement of AVR at field, kindly ensure to follow the check points provided in the SOP. This
SOP will be helpful in identifying the failure of AVR and avoid unnecessary replacement at field.

Procedure

For R120 and R121

Ensure the Fuse healthiness before


check.
 Remove the green cover.
 Check the fuse and replace if
blown or missing.
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
 R120 ( For 1 and 3 Phase)
 R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121

AVR Model:- R120

Y Phase (V terminal)
R Phase (U terminal)

Field winding (F1, F2)

Neutral (N1 and N)

Description
 Model: - R 120.
 Part No:-2H.[Link]
 This AVR is used in 1-Phase and 3-Phase alternators from the range of 15 to 160KVA.
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
 R120 ( For 1 and 3 Phase)
 R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121

Step 1. Diode Check


(Note :- Keep Multi meter in diode test mode)

a) Check the -ve Probe (Black Wire) to F1 and +ve Probe (Red Wire) to F2 meter read should be 0.3 to 0.5
V.

F2 F1

b) Check the +ve Probe (Red Wire) to F1 and -ve Probe (Black Wire) to F2 meter read should be 0L.

F1 F2
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
 R120 ( For 1 and 3 Phase)
 R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121

Step 2. Continuity Check


(Note :- Keep the multi meter in Continuity Mode)

a) Connect the multi meter probes to F1 and N terminal. The continuity to be observed with the beep
sound

N F1

b) Connect the multi meter probes to U and fuse terminal (as shown in the picture). The continuity to be
observed with the beep sound

Fuse
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
 R120 ( For 1 and 3 Phase)
 R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121

Step 3. Resistance Check (Only for R120)


(Note :- Keep the multi meter in Resistance Mode)

a) Connect the multi meter probe to V and N1 terminal, the meter should read >200 Kohms.

V N1

b) Connect the multi meter probe to U and N1 terminal, the meter should read >0.99 Mohms.

N1 U
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
 R120 ( For 1 and 3 Phase)
 R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121

AVR Model:- R121

R Phase(U Terminal)
Neutral(N)

Field Winding(F1,F2)

External V-Trim Port

Description:-
 Model:- R 121.
 Part No: 2H.1025.10.0.00.
 This AVR is Used in 1-Phase alternators from the range of 7.5 to 62.5KVA
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
 R120 ( For 1 and 3 Phase)
 R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121

Step 1. Diode Check


(Note :- Keep the multi meter in Diode Mode)

a) Check the -ve Probe (Black Wire) to F1 and +ve Probe (Red Wire) to F2 meter read should be 0.3 to 0.5 V.

F2 F1

b) Check the +ve Probe (Red Wire) to F1 and -ve Probe (Black Wire) to F2 meter read should be 0L.

F1
F2
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
 R120 ( For 1 and 3 Phase)
 R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121

Step 2. Continuity Check


(Note :- Keep the multi meter in Continuity Mode)

a) Connect the multi meter probes to F1 and N terminal. The continuity to be observed with the beep
sound

N F1

F1

b) Connect the multi meter probes to U and fuse terminal (as shown in the picture). The continuity to be
observed with the beep sound

Fuse
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
 R120 ( For 1 and 3 Phase)
 R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121

Check list for AVR


[Link] Fault Cause Rectification

Incorrect excitation, circuit Check proper connection,


1 No voltage from generator connection, Blown or missing Fuses, replace the fuse or replace the
AVR failed. AVR.

Adjust the voltage by V-Trim


2 Low voltage build up V-Trim pot incorrectly set
pot in AVR

[Link] or No connection to U
[Link] the Connection
Terminal of AVR
3 Voltage High [Link] Voltage V-Trim Pot in
[Link] voltage setting, AVR
AVR Replace AVR
defective – Resistor damaged

No Output after flashing of


4 AVR Faulty Replace AVR
AVR

Conclusion

By following the procedure outlined in SOP, Engineers can identify and address potential issues before they
escalate, Minimizing the down time and operational efficiency.

Adhere to these guidelines helps to ensure a reliable operational efficiency.


D. Document History

Date Details

18-July-2024 SOP to check the AVR R120 and R121

Prepared By Verified By

Pratiba Alur Prashant Prasanna and Kadhirval M