Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
R120 ( For 1 and 3 Phase)
R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121
A. Product Affected:-
Alternators with AVR R120 and R121
B. Issue
Voltage Issues and Fuse Failure.
Post receipt of failed part at HO (AVR), it has been observed in majority cases the replaced AVR has
been found OK.
C. Service Information
Before replacement of AVR at field, kindly ensure to follow the check points provided in the SOP. This
SOP will be helpful in identifying the failure of AVR and avoid unnecessary replacement at field.
Procedure
For R120 and R121
Ensure the Fuse healthiness before
check.
Remove the green cover.
Check the fuse and replace if
blown or missing.
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
R120 ( For 1 and 3 Phase)
R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121
AVR Model:- R120
Y Phase (V terminal)
R Phase (U terminal)
Field winding (F1, F2)
Neutral (N1 and N)
Description
Model: - R 120.
Part No:-2H.[Link]
This AVR is used in 1-Phase and 3-Phase alternators from the range of 15 to 160KVA.
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
R120 ( For 1 and 3 Phase)
R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121
Step 1. Diode Check
(Note :- Keep Multi meter in diode test mode)
a) Check the -ve Probe (Black Wire) to F1 and +ve Probe (Red Wire) to F2 meter read should be 0.3 to 0.5
V.
F2 F1
b) Check the +ve Probe (Red Wire) to F1 and -ve Probe (Black Wire) to F2 meter read should be 0L.
F1 F2
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
R120 ( For 1 and 3 Phase)
R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121
Step 2. Continuity Check
(Note :- Keep the multi meter in Continuity Mode)
a) Connect the multi meter probes to F1 and N terminal. The continuity to be observed with the beep
sound
N F1
b) Connect the multi meter probes to U and fuse terminal (as shown in the picture). The continuity to be
observed with the beep sound
Fuse
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
R120 ( For 1 and 3 Phase)
R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121
Step 3. Resistance Check (Only for R120)
(Note :- Keep the multi meter in Resistance Mode)
a) Connect the multi meter probe to V and N1 terminal, the meter should read >200 Kohms.
V N1
b) Connect the multi meter probe to U and N1 terminal, the meter should read >0.99 Mohms.
N1 U
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
R120 ( For 1 and 3 Phase)
R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121
AVR Model:- R121
R Phase(U Terminal)
Neutral(N)
Field Winding(F1,F2)
External V-Trim Port
Description:-
Model:- R 121.
Part No: 2H.1025.10.0.00.
This AVR is Used in 1-Phase alternators from the range of 7.5 to 62.5KVA
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
R120 ( For 1 and 3 Phase)
R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121
Step 1. Diode Check
(Note :- Keep the multi meter in Diode Mode)
a) Check the -ve Probe (Black Wire) to F1 and +ve Probe (Red Wire) to F2 meter read should be 0.3 to 0.5 V.
F2 F1
b) Check the +ve Probe (Red Wire) to F1 and -ve Probe (Black Wire) to F2 meter read should be 0L.
F1
F2
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
R120 ( For 1 and 3 Phase)
R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121
Step 2. Continuity Check
(Note :- Keep the multi meter in Continuity Mode)
a) Connect the multi meter probes to F1 and N terminal. The continuity to be observed with the beep
sound
N F1
F1
b) Connect the multi meter probes to U and fuse terminal (as shown in the picture). The continuity to be
observed with the beep sound
Fuse
Technical Service Bulletin
Reference DABU-TSB-PG-011
Date 18-Jul-2024
Model AVR
R120 ( For 1 and 3 Phase)
R121 ( For 1 Phase only)
Subject SOP to check the AVR R120 and R121
Check list for AVR
[Link] Fault Cause Rectification
Incorrect excitation, circuit Check proper connection,
1 No voltage from generator connection, Blown or missing Fuses, replace the fuse or replace the
AVR failed. AVR.
Adjust the voltage by V-Trim
2 Low voltage build up V-Trim pot incorrectly set
pot in AVR
[Link] or No connection to U
[Link] the Connection
Terminal of AVR
3 Voltage High [Link] Voltage V-Trim Pot in
[Link] voltage setting, AVR
AVR Replace AVR
defective – Resistor damaged
No Output after flashing of
4 AVR Faulty Replace AVR
AVR
Conclusion
By following the procedure outlined in SOP, Engineers can identify and address potential issues before they
escalate, Minimizing the down time and operational efficiency.
Adhere to these guidelines helps to ensure a reliable operational efficiency.
D. Document History
Date Details
18-July-2024 SOP to check the AVR R120 and R121