Operating Instructions RDF302

The RDF302 thermostat allows users to adjust room temperature and fan speed, operating in Comfort, Economy, and Protection modes. It features a range of settings for temperature control, fan operation, and key locking, with options for manual or automatic adjustments. Users can also configure parameters for energy savings and frost protection, with settings adjustable via buttons or Modbus communication.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views2 pages

Operating Instructions RDF302

The RDF302 thermostat allows users to adjust room temperature and fan speed, operating in Comfort, Economy, and Protection modes. It features a range of settings for temperature control, fan operation, and key locking, with options for manual or automatic adjustments. Users can also configure parameters for energy savings and frost protection, with settings adjustable via buttons or Modbus communication.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

s Change room temperature

Press + or – to increase or decrease the current room temperature setpoint for


+/–
Comfort mode. The thermostat changes to Comfort .
Operating Instructions RDF302 The setting range is 5...40 °C, unless limited by parameters P09 and P10.

Adjust fan speed/fan mode


RDF302 – the room thermostat with RS 485 communications, using Modbus protocol, allows you to set the ideal room Press the button until you reach the desired fan mode.
temperature you want. In Auto mode, the thermostat automatically selects the fan speed based on
The thermostat provides Comfort, Economy, and Protection mode. setpoint and actual room temperature. The fan continues to run at low speed
The fan operates either in Auto mode or at a speed selected in Manual mode. (factory setting) after the room temperature reaches the setpoint.
You can either take advantage of the thermostat's factory settings or adjust it as needed.
In manual mode, the fan always runs at the speed that you select:
Low fan speed
Protection mode Condensation in the room *
Medium fan speed
Comfort mode Cooling demand/mode
High fan speed
Economy mode Heating demand/mode
For a single-speed fan, you can change the mode between and .
Electrical heater active
Measured room temperature, Change thermostat operating
setpoints and parameters
Display

Automatic fan Press operating mode button to change the operating mode display.
Current time of day or Low fan speed In protection mode, the plant stops operating. However, if the room
additional user information Medium fan speed temperature drops below 8 °C, heating is switched on to protect the room
High fan speed against frost.
Actual room temperature Your HVAC installer can change the frost protection limit and set a heat
Outdoor temperature protection limit as needed:
Changes made by installer: ! Frost protection: ........... ˚C
Buttons are locked Heat protection: ........... ˚C
Fault indicator * In Comfort mode, the thermostat maintains the room temperature on the
setpoint which can be readjusted using the + and – buttons.
In Economy mode, the room temperature is maintained at a lower or higher
setpoint, thus saving energy and money. Adjust parameters P11 and P12 to
change the preselected setpoints.
Operating mode button The thermostat can be set to Economy mode either by pressing the operating
Operation and settings

mode button if enabled (P02 = 2), or via an external signal (switch or Modbus
- Protection
command) such as window contact, keycard or presence detector.
- Comfort
- Economy ** Fan mode button
Change from heating to cooling mode
– Automatic fan ( )
– Manual fan ( ) Changeover between cooling and heating is either automatic using a
or in a system with manual heating/cooling changeover sensor or a remote changeover switch or via
changeover: / instruction from the central management station via Modbus, or manual by
- Protection pressing operating mode button . No changeover is possible if the thermostat
- Comfort heating is configured for cooling only or heating only (see parameter P01).
Colder / Warmer
- Comfort cooling Display for automatic changeover or heating only/cooling only:
Heating valve is open
Cooling valve is open
Display for manual changeover:
* Needs to be configured by your HVAC installer
** Needs to be enabled via parameter P02 Thermostat is in heating mode
Thermostat is in cooling mode

CE1B3079en / 2014-10-16 Subject to change Siemens Building Technologies


Key lock Control parameters
Proceed as follows to change the most important control parameters (your HVAC installer can set additional parameters):
Press operating mode button for 5 seconds to lock or unlock the buttons
if manual key lock is configured (parameter P14 = 2). 1. Press the – and + buttons simultaneously at least 3 seconds.
The thermostat automatically locks the buttons 10 seconds after the last Release, and within 2 seconds, press + again for 3 seconds. "P01" is displayed.
adjustment if "Auto lock" is configured (P14 = 1). 2. Repeatedly press the + or – button to select the required parameter.
The key symbol indicates locked buttons. - - - - - -
Notes: The key lock cannot be released (unlocked) once the buttons were
locked by the master through the Modbus command. +/– 3. Press + and – simultaneously. The current value of the selected parameter begins to flash, allowing you to
change the value by repeatedly pressing + or –.
Reminder to clean filters and for external faults
4. The next parameter is displayed when you press + and – again simultaneously.
FIL * This message reminds you to clean your HVAC equipment filters.
5. Repeat steps 2 to 4 to display and change additional parameters.
It is displayed after !………… “fan operating hours” and disappears when
the thermostat is set to Protection ( ). 6. Press + or – until “End” is displayed, and then press + and – simultaneously to save the change and exit
parameter entry mode.
These messages inform you on external faults *:
AL1 * AL1 :! ...………………………………….
AL2 * AL2 :! ...…………………………………. Parameter Description Factory setting Setting range Adjustment !
2-pipe: [0…3] 0 = Heating only
Recalibrating the sensor 1 (Cooling only) 1 = Cooling only
P01 Control sequence 2 = Manual Heating or Cooling
If the room temperature displayed by the thermostat does not agree with 4-pipe: [2…4] 3 = Auto Changeover
the temperature effectively measured (after min 1 hour of operation), the 4 (Heating & Cooling) 4 = Heating & cooling
temperature sensor can be recalibrated through parameter P05. 1 = Comfort, Protection
P02 Mode selection by user via operating mode button 1 (Comfort, Protection) 2 = Comfort, Economy,
Note: Economy mode Protection
0 = °C
The energy saving setpoints are factory-set to 15 °C for heating and 30 °C P04 Selection of °C or °F °C
1 = °F
for cooling. Use parameters P11 and P12 to adjust the values.
P05 Sensor calibration 0.0 °C -3...3 °C
Important: You can set these setpoints to OFF; the thermostat then is
0 = Room temperature
inactive, i.e. no protective heating or cooling function. P06 Standard temperature display 0 (Room temperature)
1 = Setpoint
Risk of frost!
0 = No display
1 = Temperature in °C/°F
Commissioning 2 = Outside temperature
P07 Additional user information 0 (no display)
You can adjust a number of different control parameters to adapt the thermostat to your (via bus)
system and optimize control performance. You can do this during operation either via 3 = Time of day (12 h, via bus)
the buttons on the thermostat or using a commissioning tool via Modbus. 4 = Time of day (24 h, via bus)
P08 Comfort basic setpoint 21 °C 5...40 °C
Baud rate and parity
P09 Minimum setpoint limitation in Comfort (WminComf) 5 °C 5...40 °C
The Baud rate can be adjusted to 4800 bps, 9600 bps, 19200 bps (factory P10 Maximum setpoint limitation in Comfort (Wmax Comf) 35 °C 5...40 °C
setting) or 38400 bps. The Parity can be set to none, odd or even (factory P11 Setpoint of heating in Economy (WheatEco) 15 °C OFF, 5 °C…Wcool Eco
setting). Your HVAC installer can set them through the additional
P12 Setpoint of cooling in Economy (Wcool Eco) 30 °C OFF, WheatEco…40 °C
parameters.
OFF = disabled
Important: Once you made any changes on the baud rate or parity, you P13 *** Electrical heater in cooling mode ON
ON = enabled
must reset the power before the changes become effective. Key lock 0 = Disabled
* Needs to be configured by your HVAC installer P14 (Press operating mode button for 5 seconds to lock or 0 (Disabled) 1 = Auto lock
unlock the buttons) 2 = Manual lock

*** Parameter P13 is only displayed for application "2-pipe with electric heater". ! Please record all changes you make!
All temperature settings are in increments of 0.5 °C.

CE1B3079en / 2014-10-16 Subject to change Siemens Building Technologies