Hydrostatic Test Report for Fire Extinguishers

The hydrostatic test report for fire extinguishers conducted by Haseen Habib Corporation on June 27, 2022, indicates that out of 34 extinguishers tested, 24 failed while 10 passed. The tests were performed at a pressure of 35 bar for DCP 6Kg and 250 bar for CO2 5Kg, with visual inspections confirming no leaks or pressure drops for the passing units. The report was prepared by Engr. Umair Zafar Khan, Maintenance Engineer.

Uploaded by

King Khan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
874 views2 pages

Hydrostatic Test Report for Fire Extinguishers

The hydrostatic test report for fire extinguishers conducted by Haseen Habib Corporation on June 27, 2022, indicates that out of 34 extinguishers tested, 24 failed while 10 passed. The tests were performed at a pressure of 35 bar for DCP 6Kg and 250 bar for CO2 5Kg, with visual inspections confirming no leaks or pressure drops for the passing units. The report was prepared by Engr. Umair Zafar Khan, Maintenance Engineer.

Uploaded by

King Khan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

HYDROSTATIC TEST REPORT FOR FIRE EXTINGUISHERS

Customer Name: Exalo Drilling Date:27-06-2022

Test Performed By: Haseen Habib Corporation – Lahore Plant

Equipment: Fire Extinguishers

[Link] Type of Fire Extinguishers Test Pressure Pressure Result


(bar) Maintained for
(Min)
1 DCP 6Kg 35 2.5 Pass
2 DCP 6Kg 35 2.5 Pass
3 DCP 6Kg 35 2.5 Pass
4 DCP 6Kg 35 2.5 Pass
5 DCP 6Kg 35 2.5 Pass
6 DCP 6Kg 35 2.5 Pass
7 DCP 6Kg 35 2.5 Pass
8 DCP 6Kg 35 2.5 Pass
9 DCP 6Kg 35 2.5 Pass
10 DCP 6Kg 35 2.5 Pass
11 DCP 6Kg 35 2.5 Pass
12 DCP 6Kg 35 2.5 Pass
13 DCP 6Kg 35 2.5 Pass
14 DCP 6Kg 35 2.5 Pass
15 DCP 6Kg 35 2.5 Pass
16 DCP 6Kg 35 2.5 Pass
17 DCP 6Kg 35 2.5 Pass
18 DCP 6Kg 35 2.5 Pass
19 DCP 6Kg 35 2.5 Pass
20 DCP 6Kg 35 2.5 Pass
21 DCP 6Kg 35 2.5 Fail /Rejected
22 DCP 6Kg 35 2.5 Fail /Rejected
23 DCP 6Kg 35 2.5 Fail /Rejected
24 DCP 6Kg 35 2.5 Fail /Rejected
25 DCP 6Kg 35 2.5 Fail /Rejected
26 DCP 6Kg 35 2.5 Fail /Rejected
27 DCP 6Kg 35 2.5 Fail /Rejected
28 DCP 6Kg 35 2.5 Fail /Rejected
29 DCP 6Kg 35 2.5 Fail /Rejected
30 DCP 6Kg 35 2.5 Fail /Rejected
31 DCP 2Kg 35 2.5 Pass
32 DCP 2Kg 35 2.5 Pass
33 CO2 5Kg 250 2.5 Pass
34 Co2 5Kg 250 2.5 Pass

Hydrotest of above S.N 1 to 20 and 31 to 34 are also visually inspected under BS EN ISO 9001:2000
Quality Control System, no leakage and pressure drop observed during holding period.

Hydrotest of above S.N 21 to 30 are also visually inspected under BS EN ISO 9001:2000 Quality Control
System, Pressure drops, and leakage observed during holding period.

Prepared By:

Engr. Umair Zafar Khan


Maintenance Engineer