INDEX
TLY 29 1
1.1
1.2
2
2.1
INSTRUMENT DESCRIPTION
GENERAL DESCRIPTION
FRONT PANEL DESCRIPTION
PROGRAMMING
PROGRAMMING OF SET POINT
2.2 PARAMETERS PROGRAMMING
2.3 PARAMETER PROTECTION USING THE PASSWORD
2.4 PARAMETERS PROGRAMMING LEVEL
MICROPROCESSOR-BASED 2.5
2.6
ACTIVE SET POINT SELECTION
ON / STAND-BY FUNCTION
DIGITAL ELECTRONIC FREEZER 2.7
3
CLOCK PROGRAMMING
INFORMATION ON INSTALLATION AND USE
CONTROLLER 3.1 PERMITTED USE
3.2 MECHANICAL MOUNTING
3.3 ELECTRICAL CONNECTIONS
3.4 ELECTRICAL WIRING DIAGRAM
4 FUNCTIONS
4.1 MEASURING AND VISUALIZATION
4.2 OUTPUTS CONFIGURATION
4.3 TEMPERATURE CONTROL
4.4 CONTINUOUS CYCLE FUNCTION
4.5 COMPRESSOR PROTECTION FUNCTION AND AND
DELAY AT POWER-ON
4.6 DEFROST CONTROL
4.7 MANUAL DEFROST
4.8 EVAPORATOR FANS CONTROL
4.9 ALARM FUNCTIONS
4.9.1 TEMPERATURE ALARMS
4.9.2 EXTERNAL ALARM
4.9.3 OPEN DOOR ALARM
4.9.4 ALARM MEMORY
4.10 DIGITAL INPUT
4.11 AUXILIARY OUTPUT
4.12 FUNCTION OF KEYS “U” AND “DOWN/AUX”
4.13 PARAMETERS CONFIGURATION BY KEY01
5 PROGRAMMABLE PARAMETERS TABLE
6 PROBLEMS , MAINTENANCE AND GUARANTEE
6.1 SIGNALLING
6.2 CLEANING
OPERATING INSTRUCTIONS 6.3 GUARANTEE AND REPAIRS
Vr. 01 (ENG) - cod.: ISTR 06408 7 TECHNICAL DATA
7.1 ELECTRICAL DATA
7.2 MECHANICAL DATA
TECNOLOGIC S.p.A. 7.3 MECHANICAL DIMENSIONS, PANEL CUT-OUT AND
MOUNTING
7.4 FUNCTIONAL DATA
VIA INDIPENDENZA 56 7.5 INSTRUMENT ORDERING CODE
27029 VIGEVANO (PV) ITALY
TEL.: +39 0381 69871 1 - INSTRUMENT DESCRIPTION
FAX: +39 0381 698730 1.1 - GENERAL DESCRIPTION
internet : http:\\www.tecnologic.it The model TLY 29 is a digital controller with microprocessor that is
e-mail: [email protected] typically used in cooling applications that have temperature control
with ON/OFF regulation and defrosting control with set time and
hours intervals (Real Time Clock Defrosting) by means of electrical
FOREWORD heating or hot gas/cycle inversion.
This manual contains the information necessary for the product to The instrument has 3 relay outputs, two inputs for PTC or NTC
be installed correctly and also instructions for its maintenance and temperature probes and a digital input, that can all be configured.
use; we therefore recommend that the utmost attention is paid to The 3 outputs can be used for controlling the compressor or the
the following instructions. temperature control device (OUT), the defrosting device (DEF), the
Though this manual has been issued with the greatest care, evaporation fan (FAN) or, alternatively any of the previous
TECNOLOGIC S.p.A. will not take any responsibility deriving from functions, using an auxiliary device (AUX) or an alarm (AL).
its use. The two inputs for the PTC and NTC temperature probes (which
The same applies to each person or Company involved in the can be selected by parameter) can be used to measure the cell
issuing of this manual. temperature (Pr1) and the evaporator temperature (Pr2) while the
This document is the exclusive property of TECNOLOGIC S.p.A. digital input (DIG) can be programmed to carry out various
which forbids any reproduction and divulgation , even in part, of the functions such as defrosting commands, selecting a different set of
document, unless expressly authorized. temperature regulations, external alarm signals, activating a
TECNOLOGIC S.p.A. reserves the right to make any formal or continuous cycle, and activating an auxiliary output etc.
functional changes at any moment and without any notice. The instrument is equipped with 4 programme keys, a 4-digit
display and 9 LED signals, in addition to an internal buzzer that is
the sound system for alarms.
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 1
Other important characteristics of the instrument are: programme 2.2 - PARAMETERS PROGRAMMING
parameters protection using personalised password, switching on To access the instrument’s function parameters, press the key P
and off (stand-by) of the instrument using the front keys or the and keep it pressed for about 5 seconds, after which the SET led
digital input, configuration of parameters via the KEY 01 device, will light up, the display will visualised the code that identifies the
memorising of two sets of temperature regulations that can be first group of parameters (“]SP “) and the group of parameters that
switched and the possibility of power supply in the range 100 ... are to be edited are selected by pressing the UP and DOWN keys.
240 VAC. Once the group of parameters has been selected, press the P and
the code that identifies the first parameter in the selected group will
1.2 - FRONT PANEL DESCRIPTION be visualised.
Again using the UP and DOWN keys, the desired parameter can
9 TLY 29 4 be selected and pressing the P key, the display will alternately
AL show the parameter code and its setting that can be changed with
3 the UP and DOWN keys.
Once the desired value has been set, press the key P again: the
2 new value will be memorised and the display will show only the
Aux
abbreviation of the selected parameter.
1 Pressing the UP and DOWN keys, it is possible to select another
Out Def - OK + Fan Aux
parameter (if present) and change it as described.
10 To return to select another group of parameters, keep the UP or
5 6 11 12 13 7 8 the DOWN key pressed for about 1 second, after which the display
will return to showing the code of the parameter group.
Release the pressed key and using the UP and DOWN keys it will
1 - Key P : Used for setting the Set point and for programming the
be possible to select another group (if present).
function parameters
To exit the programming mode, do not press any key for about 20
2 - Key DOWN/Aux : Used for decreasing the values to be set and
seconds, or keep the UP or DOWN key pressed until it exits the
for selecting the parameters. It can also be programmed via the programming mode.
parameter “Fbd” to carry out other functions such as activating the
Aux output, starting up the continuous cycle, selecting the active
set point or turning on and off (stand-by) the device (see par. 4.12). Hold for
3 - Key UP/DEFROST : Used for increasing the value to be set, for 5 sec.
selecting the parameters and for activating manual defrosting.
4 - Key U : Used for visualising the temperatures taken by the cell Hold for
2 sec.
probes and evaporator (Pr1 and Pr2) and the internal clock (if
present). It can also be programmed via the parameter “USrb” to Hold for
2 sec.
Hold
Longer
carry out other functions, just like the key DOWN/AUX (see par.
4.12).
5 - Led OUT : Indicates the compressor output status (or the
temperature control device) on (on), off (off) or inhibited (flashing)
6 - Led DEF : Indicates defrosting in progress (on) or dripping
(flashing). 2.3 - PARAMETER PROTECTION USING THE PASSWORD
7 - Led FAN : Indicates fan output status on (on), off (off) or The instrument has a parameter protection function using a
delayed after defrosting (flashing) password that can be personalised, through the “PASS”
8 - Led AUX : Indicates AUX output status on (on), off (off) or parameter in the “]PAn” set.
inhibited (flashing) If one wishes to have this protection, set the password number
9 - Led AL : Indicates the alarm status (on), off (off) and silenced desired in the parameter “PASS”.
or memorized (flashing) When the protection is working, press the P key to access the
10 - Led SET : Indicates the input in programming mode and the parameters and keep it press for about 5 seconds, after which the
programming level of the parameters. It also serves to indicate the LED SET will flash and the display will show “0” .
Stand-by status. At this point, using the UP and DOWN keys, set the password
11 - Led - : Indicates that a low temperature alarm is in progress number programmed and press the key "P".
(lit) or that a low temperature alarm has been memorised (flashing). If the password is correct, the display will visualise the code that
12 - Led OK : Indicates that no alarms are in progress identifies the first group of parameters(“]SP “) and it will be possible
13 - Led + : Indicates that a high temperature alarm is in progress to programme the instrument in the same ways described in the
(lit) or that a high temperature alarm has been memorised previous section.
(flashing). Protection using a password can be disabled by setting the
parameter “PASS” = OFF.
2 - PROGRAMMING
2.4 - PARAMETERS PROGRAMMING LEVELS
2.1 - PROGRAMMING OF THE SET POINT The instrument has two parameter programming levels.
Press the key P then release it and the display will show SP 1 (or The first level (“visible” parameters) is accessed according to the
SP 2 if the second set is active at that time) alternating with the set procedure described above (with or without password request)
value (see selection of the active set point). while the second level (“hidden” password) can be accessed
To change it press the UP key to increase the value or DOWN to according to the following procedure.
decrease it. Remove the power supply to the instrument, press the key P and
These keys increase or decrease the value one digit at a time, but return power to the instrument, keeping the key pressed.
if the button is pressed for more than one second the value After about 5 sec. the SET led will light up, the display ]
will show the
increase or decreases rapidly, and after two seconds pressed, the code that identifies the first group of parameters(“ SP “) and it will
speed increases even more to all the desired valued to be reached be possible to set the parameters of the instrument using the same
rapidly. programming procedure described previously.
Exiting the Set mode is achieved by pressing the P key or Once the parameter has been selected and the SET is on, it means
automatically if no key is pressed for 15 seconds. After that time that the parameter can be programmed even on the first level
the display returns to the normal function mode. ("visible”).
If the LED is off it means that the parameter can only be
programmed on this level (i.e. “hidden”).
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 2
To change the visibility of the parameter, press the key U: the led 3.2 - MECHANICAL MOUNTING
SET will change status, indicating the accessibility level of the The instrument, in case 33 x 75 mm, is designed for flush-in panel
parameter (on = parameter “visible”; off = parameter “hidden”). mounting.
The access procedure for “hidden” parameters allows the “PASS” Make a hole 29 x 71 mm and insert the instrument, fixing it with the
parameter to be checked and changed, and is useful therefore if provided special bracket.
the password set has been forgotten. We recommend that the gasket is mounted in order to obtain the
front protection degree as declared. Avoid placing the instrument in
2.5 - ACTIVE SET POINT SELECTION environments with very high humidity levels or dirt that may create
The instrument allows up to 2 different regulation Set points to be condensation or introduction of conductive substances into the
pre-set (“SP 1” and “SP 2”) and then to choose which one to instrument.
make active. Ensure adequate ventilation to the instrument and avoid installation
This function can be used if it is necessary to switch two different in containers that house devices which may overheat or which may
function temperatures (e.g. day and night or positive and negative cause the instrument to function at a higher temperature than the
etc). one permitted and declared.
The active set point can be selected: Connect the instrument as far away as possible from sources of
- Using the parameter “SPAt” electromagnetic disturbances such as motors, power relays, relays,
- using the key U if the parameter "USrb" = 3. solenoid valves, etc.
- Using the key DOWN/AUX if the parameter "Fbd" = 3.
- Using the digital input if the parameter. “diF” = 8 3.3 - ELECTRICAL CONNECTION
(see par. 4.10 e 4.12) Carry out the electrical wiring by connecting only one wire to each
The Set points "SP1" and "SP2" can be set with a value between terminal, according to the following diagram, checking that the
the programmed value in parameter. “SPLL” and the programmed power supply is the same as that indicated on the instrument and
value in parameter “SPHL”. that the load current absorption is no higher than the maximum
Nota: in the examples that follow, the Set point is generally electricity current permitted.
indicated as "SP", how when operating the instrument will work As the instrument is built-in equipment with permanent connection
according to the Set point selected as active. inside housing, it is not equipped with either switches or internal
devices to protect against overload of current: the installation will
2.6 - ON / STAND-BY FUNCTION include an overload protection and a two-phase circuit-breaker,
The instrument, once powered up, can assume 2 different placed as near as possible to the instrument, and located in a
conditions: position that can easily be reached by the user and marked as
- ON : means that the controller uses the control functions. instrument disconnecting device which interrupts the power supply
- STAND-BY : means that the controller does not use any control to the equipment.
function and the display is turned off except for the green SET led. It is also recommended that the supply of all the electrical circuits
If there is no power, and then power returns, the system always connected to the instrument must be protect properly, using
sets itself in the condition it was in before the black-out. devices (ex. fuses) proportionate to the circulating currents.
It is strongly recommended that cables with proper insulation,
The ON/Stand-by function can be selected:
according to the working voltages and temperatures, be used.
- Using the key U if the parameter "USrb" = 4.
Furthermore, the input cable of the probe has to be kept separate
- Using the key DOWN/AUX if the parameter "Fbd" = 4.
from line voltage wiring. If the input cable of the probe is screened,
- using the digital input if the parameter “diF” = 10
it has to be connected to the ground with only one side.
(see par. 4.10 e 4.12)
Whether the instrument is 12 V version it’s recommended to use an
external transformer TCTR, or with equivalent features, and to use
2.7 - TIME SETTING only one transformer for each instrument because there is no
When the instrument has an internal clock it is necessary to insulation between supply and input.
programme it on the current time by using the parameter “StCL” We recommend that a check should be made that the parameters
contained in the group “]CLO“. are those desired and that the application functions correctly before
The instrument has an internal quartz for the clock, however, connecting the outputs to the actuators so as to avoid
should the clock become inaccurate (especially over a long period) malfunctioning that may cause irregularities in the plant that could
it can be adjusted daily using the parameter “CLOF” contained in cause damage to people, things or animals.
the same group.
The working of the clock is guaranteed by an internal condenser for Tecnologic S.p.A. and its legal representatives do not assume
a period of about 4 hours without any power to the instrument. any responsibility for any damage to people, things or animals
If the instrument should remain without power for a long period, deriving from violation, wrong or improper use or in any case
remember to check and if necessary re-programme the exact time. not in compliance with the instrument’s features.
3 - INFORMATION ON INSTALLATION AND USE 3.4 - ELECTRICAL WIRING DIAGRAM
3.1 - PERMITTED USE OUT1: 16A-AC1(6A-AC3) / 250 VAC
OUT2: 8A-AC1(3A-AC3) / 250 VAC
The instrument has been projected and
OUT3: 5A-AC1(2A-AC3) / 250 VAC
manufactured as a measuring and control device to
be used according to EN61010-1 for the altitudes OUT2 OUT1OUT3
operation until 2000 ms. INTERNAL
The use of the instrument for applications not BUZZER TLY29
expressly permitted by the above mentioned rule must adopt all the C NO NC NO NO INPUTS
necessary protective measures.
The instrument CANNOT be used in dangerous environments 1 2 3 4 5 6 7 8 9 10 11 12
(flammable or explosive) without adequate protection.
The installer must ensure that EMC rules are respected, also after SUPPLY
the instrument installation, if necessary using proper filters.
Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, thing or animals, please Pr1 Pr2 Dig
remember that the plant has to be equipped with additional devices
which will guarantee safety.
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 3
4 - FUNCTIONS “Func” the differential is automatically considered by the regulator
with positive values for a Refrigeration control (“Func”=CooL) or
4.1 - MEASURING AND VISUALIZATION with negative values for a heating control (“Func”=HEAt).
All the parameters concerning measuring are contained in the Temp. Temp.
Pr1 Pr1
group “]InP”.
SP
Via the parameter “SEnS” it is possible to select the type of probes HSEt
that one wishes to use and which can be: thermistores PTC HSEt
SP
KTY81-121 (Ptc) or NTC 103AT-2 (ntc).
Once the type of probe used has been selected, through the time time
parameter “Unit”, it is possible to select the temperature unit of ON ON ON ON ON ON
measurement (°C or °F) and, through the parameter “dP”, the
resolution of the desired measurement (OFF=1°; On =0,1°).
Out off off Out off off
The instrument allows the measuring to be calibrated, that can be
used for re-calibrating the instrument according to application CooL HEAt
needs, through the parameters “OFS1” (for the probe Pr1) and In the event of cell probe error (Pr1), it is possible to set the
“OFS2” (for the probe Pr2). instrument so that that the output “Out” continues to work in cycles
If probe Pr2 (evaporator) is not used, set the parameter “Pr 2” = according to the times programmed in the parameter “tonE”
OFF. (activation time) and “toFE” (deactivation time).
Using the parameter “FiL”, it is possible to set the time constant If an error occurs on the probe Pr1 the instrument activates the
for the software filter for measuring the input values to be able to output for the time “tonE”, then deactivates it for the time “toFE”
reduce the sensitivity to measurement disturbances (increasing the and so on whilst the error remains.
time). Programming “tonE” = OFF lthe output in probe error condition will
Through the paragraph “diSP”, it is possible to fix the normal remain switched off.
visualisation on the display that can be the measurement of the cell Programming instead “tonE” to any value and “toFE” = OFF the
probe (Pr 1), the measurement of the evaporator probe (Pr 2), the output in probe error condition will remain switched on.
set point of active regulation (SP), the current hour if the instrument Remember that the temperature regulation function can be
has a clock (CLo) or it can have the numerical display switched off conditioned by the “Continuous Cycle”, “Compressor Protection”,
(OFF). “Minimum compressor function time”, “Delay compressor start up
Regardless of what is set in the parameter “diSP”, it is possible to after defrosting” and “inhibition of compressor close to defrosting”
visualise all the variables in rotation by pressing the key U, the functions described below.
display will alternately show the code that identifies the variable (Pr
1, Pr 2 and, if present the clock, CLo) and its value. 4.4 - CONTINUOUS CYCLE FUNCTION
The exit of this visualisation mode occurs automatically 15 seconds The instrument has a continuous cycle function by which it is
after the last pressing on the key U. possible to maintain the configured output configured as “out”
Please remember that visualisation of the probe Pr1 can be always active for the time set in parameter “tCC” (in the group
changed by the display block in defrosting function too, by using “]rEG”) regardless of the temperature control command.
the parameter “dLo” (see par. 4.6). The function can be used for example, when rapid lowering of the
product temperature is required after the refrigerator loading phase.
4.2 - OUTPUTS CONFIGURATION During the continuous cycle, the defrosting is inhibited and the
The instrument outputs can be configured in the parameters group temperature alarms are disabled during the entire cycle and also
“]Out” where the relative parameters “O1F” , “O2F” “O3F” are later for the time set in parameter “dALc” (see par. 4.9).
found and also the parameter “buF” that allows configuration of Starting up a continuous cycle can only be done by a manual
the internal buzzer (if present). command using the U or DOWN/AUX (“UrSb” or “Fbd” = 2) keys or
The outputs can be configured for the following functions via the digital input (“diF”=3) if suitably programmed (see par. 4.10
= Out - to control the compressor or however, the temperature and 4.12).
control device The continuous cycle in progress is shown on the display with the
= dEF - to control the defrosting device indication CC and can be stopped by a further action on the key or
= FAn - to control the fans digital input (as for activation).
= AuS - to control the auxiliary device (see par. 4.11) The continuous cycle function cannot be activated during defrosting
= ALt - to control a silenceable alarm device through a contact that and with "tCC" = OFF.
is normally open, and then closed when the alarm sounds
= AL - to control an alarm that cannot be silenced through a 4.5 - COMPRESSOR PROTECTION FUNCTION AND DELAY AT
contact that is normally open and closed when the alarm sounds. POWER-ON
= ALL - to control an alarm with a memory function through a All the parameters concerning the compressor protection functions
contact that is normally open and closed when the alarm sounds. and the delay at power on are contained in the group “]PrC”.
= -ALt - to control a silenceable alarm device through a contact The function “Compressor Protection” carried out by the machine
that is normally closed, and then open when the alarm sounds. aims to avoid close start ups of the compressor controlled by the
= -AL - control an alarm that cannot be silenced through a contact instrument in cooling applications.
that is normally closed and open when the alarm sounds. This function foresees a time control on the switching on of the
= -ALL - to control an alarm with a memory function through a “Out” output associated with the temperature regulation request.
contact that is normally closed and open when the alarm sounds The protection consists of preventing the output being switched on
(see alarm memory). during the time set in the parameter “PtC” and counted depending
= OFF - Disabled output on what has been programmed in the parameter “PSC”, and
therefore that any activation occurs only after the “PtC” time has
4.3 - TEMPERATURE CONTROL finished.
All the parameters concerning temperature regulation are If during the power on delay phase, the regulator request should
contained in the group “]rEG”. disappear, due to an inhibition caused by the compressor
The regulation of the instrument is ON/OFF and acts on the output protection function, the foreseen start up of the output is naturally
cancelled.
configured as “Out” depending on the measuring of probe Pr1, of
Using the parameter "PSC", it is possible to set the type of
the active Set Point “SP” (1 or 2), the intervention differential
compressor protection and therefore from when the inhibition time
“HSEt” and the function mode “Func” .
“PtC” must start.
Depending on the function mode programmed on the parameter
The parameter “PSC” can be set as:
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 4
= 1 : Power on delay To use this mode, it is necessary to set the parameter "dint"=OFF
so that the defrosting at intervals is disabled and to set the
Tem p.
P r1
"P S C " = 1 parameters “dF 1”, “dF 2”, “dF 3”, “dF 4”, “dF 5”, “dF 6” with
the times when the defrosting must be carried out.
SP
HSEt The automatic defrosting cycle can be at time intervals or, if an
evaporator probe is used (Pr2), when a temperature is reached.
ON ON ON t im e If the evaporator probe is not used (par. “Pr 2” = OFF) the duration
cycle is set by the parameter “dEFE”.
O ut o ff o ff o ff o ff
If instead the evaporator probe is used (parameter “Pr 2” = on) the
P tC P tC P tC defrosting takes place when the temperature measured by the
probe exceeds the temperature set in the parameter “tEdF”.
= 2 : Delay after power off If this temperature is not reached in the time set in the parameter
“dEFE”, defrosting is interrupted.
T em p.
"P S C " = 2 In order to avoid pointless defrosting the parameter. “tSdF” is
P r1
foreseen that sets the enablement temperature for defrosting
SP
HSEt If the temperature measured by the probe is higher than the one
set in the parameter “tSdF” and in the parameter "tEFE" the
ON ON ON t im e
defrosting is inhibited.
Temp.
O ut o ff o ff o ff Pr2
P tC P tC P tC
tEdF
tSdF
= 3 : Delay between power on phases.
ON ON time
Tem p.
P r1 "P S C " = 3 dEF 1 2 3
off off off
HSEt dEFE (NO def.)
SP
dint dint dint dint
(defrost) (defrost)
ON ON ON t im e
Out o ff o ff o ff
Examples: defrosting 1 ends due to reaching of temperature
P tC P tC P tC “tEdF”, defrosting 2 ends at the end of the “dEFE” time as the
temperature “tEdF” is not reached, defrosting 3 does not take place
as the temperature is higher than “tSdF”.
The function is disabled by programming “PtC” = 0.
At the end of defrosting, it is possible to delay the new start up of
Through the parameter “LCt” it is also possible to set the minimum
the compressor (output “Out”) at the time set in parameter “tdCO”
activation time of the output to avoid switching on of the
to allow the evaporator to drain.
compressor that is too short.
During this delay, the led Def flashes to indicate the draining state.
During the power on delay phases of the OUT output by inhibiting
It is also possible to prevent start up of the compressor near to
the function “Compressor Protection” or delay of power off caused
defrosting, to avoid waste of energy.
by the minimum function time “LCt”, the led OUT flashes.
If inside the time set in the parameter “COFd” (counted in advance
It is also possible to prevent activation of all the outputs after the
compared to the start up of automatic defrosting both at intervals
instrument is turned on, for the time set in the parameter “od”.
and by clock), an activation request for the output “Out” should take
The function is disabled by “od” = OFF.
place, this does not take place and it is signalled by the flashing of
During the power on delay phase, the display shows the indication
the Out led.
od, alternating with the normal programmed visualisation. If one wishes to set a defrosting cycle every time the instrument is
switched on (as long as the conditions set in the parameters “tSdF”
4.6 - DEFROST CONTROL and "tEFE" apply) programme the parameter “SdEF” = yES.
All the parameters concerning the defrosting control that acts on This allows the evaporator to be permanently defrosted, even when
the outputs configured as “Out” and “dEF”, are container in the frequent interruptions to power supply occur that may cause the
group “]dEF”. cancellation of the various defrosting cycles.
The type of defrosting that the instrument must carry out is set by During the defrosting, it may occur that the temperature measured
the parameter “dtyP” that can be programmed: by the cell probe (Pr1) increases excessively (this obviously
= EL - WITH ELECTRICAL HEATING or BY STOPPING depends on the position of the probe Pr1 compared to the
COMPRESSOR (during defrosting, the output “Out” is deactivated evaporator).
while the output “dEF” is enabled) In the event that one does not wish this increase to be visualised
= in - WITH HOT GAS or INVERSION OF CYCLE (during by the instrument, it is possible to use the functions in the
defrosting the outputs “Out” and “dEF” are enabled) parameter “dLo” (Block display during defrosting) and “Etdu”
The automatic defrosting can take place at intervals or if the (Differential unblocking of display after defrosting).
instrument has an internal clock, at set hours. The parameter “dLo” = On allows the temperature Pr1 visualisation
Defrosting at intervals is possible by setting the time that runs to be blocked on the last reading during a whole defrosting cycle
between the two next automatic defrostings in the parameter and until the temperature does not return under the value [”SP” +
“dint”. “Etdu”] after defrosting has finished (or the time set in the
Counting this interval is set through the parameter "dCt" that can parameter "dALd" contained in the block “]AL”).
be programmed: With “dLo” = Lb, this allows visualisation of the writing dEF during
= rt - counts the total function time (instrument on) defrosting and at the end of defrosting the writing PdEF up to when
= ct - counts only the compressor function time (output OUT the temperature Pr1 does not return below the value [”SP” + “Etdu”]
switched on) (or the time set on the parameter "dALd" contained in the block
= cS - the instrument carries out a defrosting cycle at each “]AL”).
compressor stop (i.e. at each deactivation of the output OUT). If Alternatively with the “dLo” = OFF, during defrosting, the instrument
this option is used, set “dint”=OFF. will continue to visualise the temperature measured by the probe
if the instrument has an internal clock, it is possible to carry out up Pr1.
to 6 defrostings per day at set times. Note that during defrosting, the temperature alarms are disabled
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 5
during the whole cycle and also afterwards for the time set in the = -ALt - when one wants the function described as ALt but with an
parameter “dALd” (see par. 4.9). inverse function (buzzer or output activated in normal condition and
disabled in alarm status).
4.7 - MANUAL DEFROST = -AL - when one wants the function described as AL but with
To start up a manual defrosting cycle, press the key UP/DEFROST inverse logic (buzzer or output activated in normal conditions and
when it is not in programming mode and keep it pressed for about disabled in alarm status).
5 seconds after which, if the conditions are correct, the led DEF will = -ALL - when one wants the function described as ALL but with
light up and the instrument will carry out a defrosting cycle. inverse working logic (buzzer or output activated in normal
The start up or switch off commands of a defrosting cycle can also conditions and disabled in alarm status).
be given by the digital input that are correctly programmed (see When no alarms are present, the green LED OK is lit.
par. 4.10). Any active alarm is shown on the instrument display with the
lighting up of the AL led and the switching off of the led OK.
4.8 - EVAPORATOR FANS CONTROL Any silenced or memorised alarm status is shown by the AL led
All the parameters concerning fan control are contained in the flashing .
group “]FAn”. The alarm conditions of the instrument are:
The control of the fans on the output configured as “FAn” - Probe errors “E1”, “-E1”, “E2, “-E2”
depending on determined control statuses of the instrument and - temperature alarms “HI” and “LO”
the temperature measured by the probe Pr2. - External alarms “AL”
In the case that the probe Pr2 is not used (parameter “Pr 2” = OFF) - Open door alarm “AP”
or in error (E2 o -E2) , the output FAN is activated only depending
on the parameters “FCOF” and “FEdF”. 4.9.1 - TEMPERATURE ALARMS
The parameter “FCOF” decides whether the fans must always be The temperature alarms work according to the probe Pr1
switched on independently of the compressor status (“FCOF”=On) measurements, the type of alarm set in the parameter “Aty” the
or be switched off together with the compressor (“FCOF”=OFF). alarm thresholds set in parameters “HAL” (maximum alarm) and
The parameter “FEdF” instead decides whether the fans must “LAL” (minimum alarm) and the relative differential “dAL”.
always be switched on independently of the defrosting status Through the parameter “Aty” it is possible to set the alarm
(“FEdF”=On) or switched off during defrosting (“FEdF”=OFF). thresholds “HAL” and “LAL” which must be considered as absolute
In this latter case, it is possible to delay the start up of the fans (“Aty”=Ab) or relative to the active Set Point (“Aty”=dE).
even after the end of the defrosting of the time set in the parameter Using some parameters it is also possible to delay the
“Fd”. enablement and the intervention of these alarms.
When the probe Pr2 is used (par. “Pr 2” = on) the fans, as well as These parameters are:
being conditioned by the parameters “FCOF” and “FEdF”, are also “PAL” - is the temperature alarm exclusion time on switching on
conditioned by the temperature control. the instrument if the instrument is in alarm status when it is
It is possible to set the disablement of the fans when the switched on.
temperature measured by the probe Pr2 is higher than the one set “dALd” - is the temperature alarm exclusion time at the end of
in the parameter “FLt” (temperature too hot) or when it is lower defrosting (and , if programmed, at the end of draining)
than the one set in the parameter “Fct” (temperature too cold). "dALc" - is the temperature alarm exclusion time at the end of a
The relative differential that can be set in parameter “dF” is also continuous cycle.
associated with these parameters. “ALd” - is the temperature alarm delay activation time
Te m p. The temperature alarm is enabled at the end of exclusion time and
P r2 is enabled after the “ALd” time when the temperature measured by
F Lt the probe Pr1 exceeds or goes below the respective maximum and
dF
minimum alarm thresholds.
The alarm thresholds will be the same as those set on the
parameters “HAL” and LAL” if the alarms are absolute (“Aty”=Ab)
dF T em p.
F ct
P r1
ON ON HAL
tim e dAL
FAn o ff o ff o ff
dAL
LA L
4.9 - ALARM FUNCTIONS ON ON tim e
All the parameters concerning the alarm functions are contained in
AL o ff HI o ff LO o ff
group “]AL”.
The alarm functions of the instrument work on the internal buzzer, if
present and configured via the parameter “buF”, and on the output Or will be the values [”SP”+”HAL”] and [”SP”-”LAL”] if the alarms
desired, if configured by the parameters “O1F”, “O2F” or “O3F”, are relative (“Aty”=dE).
depending on what is set on the said parameters. Tem p.
The possible selections of these parameters for the alarm P r1
signalling function are: dA L
= ALt - when one wants the buzzer or output to be activated in HAL
alarm and can be disabled (alarm silencing) manually by pressing SP
any key of the instrument (typical application for sound signal). LAL
dA L
= AL - when one wants the buzzer or output to be activated in
alarm status but cannot be disabled manually and are therefore
ON ON
only disabled when the alarm status ceases (typical application for t im e
a light signal). AL o ff HI o ff LO o ff
= ALL - when one wants the buzzer or output to be activated in
alarm status and that they remain activated even when the alarm
has ceased (see par.4.9.4) Disablement (recognition of memorised The maximum and minimum temperature alarms can be disabled
alarm) can only be carried out manually by pressing any key when by setting the relative parameters "HAL" and "LAL" = OFF.
the alarm has ended (typical application for light signal). At the same time as the signalling of the configured alarm (buzzer
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 6
and/or output), the instrument signals the alarm by turning on the = 6 - Cell door opening with compressor and fan block with contact
led light AL, switching off the LED OK, turning on the led - in case normally open: similar to “diF” = 5 but with fan and compressor
of minimum alarm or the led + for maximum alarm, and visualises block.
on the display: = 7 - Remote control of auxiliary output AUX with contact normally
- Alternately HI and the set variable in parameter “diSP” for open: on closing the input (and after the “did” time) the auxiliary
maximum alarm output is activated as described in the "FOA" = 2 function mode of
- Alternately LO and the set variable in parameter “diSP” for the the auxiliary output.
minimum alarm = 8 - Selecting the active set point with contact normally open: on
closing the input (and after the “did” time) the temperature
4.9.2 - EXTERNAL ALARM regulation set point “SP 2” is activated. When instead the input is
The instrument can signal an external alarm by activating the digital open the set point “SP 1” is active (see selecting active set point)
input with the function programmed as “din” = 4 or 9 (see par. = 9 - Signalling of external alarm with disablement of all the control
4.10). outputs with contact normally open: on closing the input (and after
At the same time as the signalling of the configured alarm (buzzer the “did” time) all the control outputs are disabled, the alarm is
and/or output), the instrument signals the alarm by turning on the activated and the instrument visualises AL and the variable set in
led AL, turning off the led OK and visualising AL and the variable parameter “diSP” alternately on the display.
set in parameter “diSP” alternately on the display. = 10 - Switching on/switching off (Stand-by) of instrument with
contact normally open: on closing the input (and after the “did”
4.9.3 - OPEN DOOR ALARM time) the instrument is switched on while it is placed in Stand-by
The instrument can signal an open door alarm by activating the when opened.
digital input with the function programmed as “din” = 5 or 6 (see = -1 - defrosting commencement command with contact normally
par. 4.10). closed : similar to “diF”=1 but with function logic reversed.
When the digital input is activated and after the delay programmed = -2 - defrosting end command with contact normally closed :
in parameter “oAd”, the instrument signals the alarm via the similar to “diF”=2 but with function logic reversed.
activation of the configured devices (buzzer and/or output), the = -3 - continuous cycle start-up command with contact normally
turning on of the led AL, the turning off of the led OK and AP and closed : similar to “diF”=3 but with function logic reversed.
the variable set in parameter “diSP” are visualised alternately on = -4 - External alarm signal with contact normally closed : similar to
the display. “diF”=4 but with function logic reversed.
= -5 - Cell door opening with fan block with contact normally closed
4.9.4 - ALARM MEMORY : similar to “diF”=5 but with function logic reversed
The instrument offers the possibility of arranging the alarm memory = -6 - Cell door opening with compressor and fan block with contact
function via the parameter “tAL”. normally closed : similar to “diF”=6 but with function logic reversed.
If "tAL" = no, the instrument cancels the alarm signal when the = -7 - Remote control of auxiliary output AUX with contact normally
alarm status ends, if instead it is programmed as "yES" , the led AL closed : similar to “diF”=7 but with function logic reversed.
flashes even when the alarm status has ended to indicate that = -8 - Selecting the active set point with contact normally closed :
there has been an alarm. similar to “diF”=8 but with function logic reversed.
If the memorised alarm is for temperature, it also keeps the led - = -9 - - Signalling of external alarm with disablement of all the
flashing to show a minimum alarm and + to show a maximum outputs with contact normally closed : similar to “diF”=9 but with
alarm. function logic reversed
To cancel the alarm memory signal, press any key. = -10 - Switching on/off (Stand-by) of instrument: similar to “diF”=10
It must be remembered that if an output function is desired (or the but with function logic reversed.
buzzer) with an alarm memory (=ALL or =-ALL) it is necessary to
set the parameter “tAL” = yES.
4.11 - AUXILIARY OUTPUT
All the parameters concerning the auxiliary output functions are
4.10 - DIGITAL INPUT
contained in the group “]AuS”.
All the parameters concerning the digital input functions are
The auxiliary outpurt can be configured to operate on any of the
contained in the group “]din”. outputs by programming the parameter of the desired output =
The digital input present on the instrument accepts contacts free of AuS.
voltage, the function carried out is defined by the parameter “diF” The function carried out is defined by the parameter “FOA” and
and the action can be delayed for the time set in parameter “did”. the function is conditioned by the time set in parameter “tuA”.
The parameter “diF” can be configured for the following functions: The parameter “FOA” can be configured for the following functions:
= 0 - Digital input not active = 0 - Auxiliary output not active
= 1 - defrosting commencement command with contact normally = 1 - Regulation output delayed with contact normally open: the
open: on closing the input (and after the “did” time) a defrosting auxiliary output is activated with delay that can be set on the
cycle is activated. parameter "tuA" compared to the output configured as Out. The
= 2 - defrosting end command with contact normally open: on output is then turned off at the same time as the OUT output is
closing the input (and after the “did” time) a defrosting cycle is disabled. This function mode can be used as a command for a
ended if in progress or defrosting is inhibited. second compressor or for all other working utilities according to the
= 3 - continuous cycle activation command with contact normally same OUT output conditions, but which must be delayed after the
open: on closing the input (and after the “did” time) a continuous start up of the compressor to avoid excess electricity absorption.
cycle is started up as described in the paragraph on the continuous = 2 - Activation by front key (U or DOWN/AUX) or by digital input
cycle function. with contact normally open: the output is activated by pressing the
= 4 - External alarm signal with contact normally open: on closing keys U or DOWN/AUX suitably configured (“USrb” or “Fbd” = 1) or
the input (and after the “did” time) the alarm is activated and the via activation of the digital input if suitably configured (“diF”=7).
instrument visualises AL and the variable set in parameter “diSP” These commands have a bi-stable function, Which means that
alternately on the display. when first pressed, the output key is activated while the second is
= 5 -Cell door opening with fan block with contact normally open: disabled. In this mode, the AUX output can be turned off
on closing the input (and after the “did” time) the fans are stopped automatically after a certain time that can be set on the parameter
and the instrument visualises AP and the variable set in parameter "tuA". With "tuA" = OFF the output is activated and deactivated
“diSP” alternately on the display. With this function mode, the only manually, using the front key (U or DOWN/AUX) or via the
action of the digital input also activates the time that can be set in digital input. Differently, the output, once activated, is turned off
parameter "oAd" after which the alarm is activated to signal that the automatically after the set time. This function can be used, for
door has been left open. example, as a cell light command, for non-misting resistance or
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 7
other utilities . 6) observe the indication led : after having pressed the button, the
= -1 - Delayed regulation output with contact normally closed: led becomes red and therefore, at the end of the data transfer, it
similar to “FOA”=1 but with function logic reversed. becomes green.
= -2 - Activation by front key (U or DOWN/AUX) or by digital input 7) now it is possible to disconnect the device.
with contact normally closed: similar to “FOA”=2 but with function To transfer the configuration loaded on the device onto an
logic reversed. instrument of the same family (DOWNLOAD), it is necessary to
proceed in the following way:
4.12 FUNCTIONING OF KEYS “U” AND “DOWN/AUX” 1) position both dip switch of KEY 01 in the ON mode.
Two of the instrument keys, in addition to their normal functions, 2) connect the device to an instrument TLY having the same
can be configured to operate other commands. features of the one from which has been downloaded the desired
The U key function can be defined by the parameter “USrb” while configuration, plugging the special connector.
the DOWN/AUX key function can be defined by the parameter 3) verify that the instrument or the device are supplied
“Fbd” both contained in the group “]PAn”. 4) observe the indication led on the device KEY 01: it has to result
Both the parameters have the same possibilities and can be green, because if the led results green blinking or red blinking, this
configured for the following functions: means that on the device it has not been downloaded any valid
= 0 - The key carries out no function. configuration and therefore it’s useless to continue.
= 1 - Pressing the key for at least 1 second, it is possible to 5) if the les results green, press the button placed on the device.
enable/disable the auxiliary output if configured (“FOA”=2). 6) observe the indication led : after having pressed the button, the
= 2 - Pressing the key for at least 1 second, it is possible to led becomes red and therefore, at the end of the data transfer, it
enable/disable a continuous cycle (see continuous cycle function). becomes green.
7) now it is possible to disconnect the device.
= 3 - Pressing the key for at least 1 second, it is possible to select
For additional info, please have a look at the KEY01 instruction
one of the 2 memorised set point in rotation. Once selection has
been made, the display will flash the active set point code for aboutmanual.
1 sec. (SP 1or SP 2).
= 4 - Pressing the key for at least 1 second, it is possible to switch 5 - PROGRAMMABLE PARAMETERS TABLE
the instrument from the ON status to Stand-by status and vice
versa. Here below is a description of all the parameters available on the
instrument. Some of them may not be present, either due to the
4.13 - PARAMETERS CONFIGURATION BY “KEY01” fact they depend on the type of instrument or because they are
The instrument is equipped with a connector that allows the automatically disabled as unnecessary.
transfer from and toward the instrument of the functioning
]
parameters through the device TECNOLOGIC KEY01 with 5 poles Group SP (parameters relative to Set Point)
connector. Par. Description Range Def. Note
This device it’s mainly useable for the serial programming of the 1 SPAt Active Set point 1÷2 1
instruments which need to have the same parameters configuration 2 SP1 Set Point 1 SPLL ÷ SPHL 0.0
or to keep a copy of the programming of an instrument and allow its 3 SP2 Set Point 2 SPLL ÷ SPHL 0.0
rapid retransmission. 4 SPLL Minimum Set Point -58 ÷ SPHL -50.0
To use the device KEY01 it’s necessary that the device or
5 SPHL Maximum Set Point SPLL ÷ 302 100.0
instrument are being supplied.
Instrument supplied and device not supplied
Group ]InP (parameters relative to measuring inputs)
SUPPLY
Par. Description Range Def. Note
6 SEnS Probes Type Ptc - ntc Ptc
7 OFS1 Pr1 Probe (cell) Cali- -30 ÷ 30 0.0
bration °C/°F
8 OFS2 Pr2 Probe (evaporator) -30 ÷ 30 0.0
Calibration °C/°F
9 Pr 2 Pr2 Probe Presence On - OFF On
(evaporator)
10 Unit Unit of measurement °C - °F °C
11 dP Decimal point On - OFF On
Instrument supplied from the device 12 FiL Measurement filter OFF ÷ 20.0 2.0
sec
13 diSP Variable visualized nor- OFF - Pr1 - Pr1
mally on display: Pr2 - SP - CL
OFF=Display off
Pr1= measurement
probe Pr1
SUPPLY ADAPTER Pr2= measurement
probe Pr2
12 VDC AC SUPPLY SP= Active Set Point
CL= Clock time
To transfer the configuration of an instrument into the device
(UPLOAD) it is necessary to proceed in the following way: Group ]rEG (parameters relative to temperature control)
1) position both dip switch of KEY 01 in the OFF mode. Par. Description Range Def. Note
2) connect the device to the instrument TLY plugging the special 14 HSEt Differential 0 ÷ 30 2.0
connector. °C/°F
3) verify that the instrument or the device are supplied 15 tonE Activation time output OFF ÷ 99.59 OFF
4) observe the indication led on the device KEY 01: if it results OUT for probe Pr1 bro- min.sec
green this means that a configuration is already loaded on the ken
device while if it results green blinking or red blinking this means
that it has not been loaded any valid configuration on the device .
5) press the button placed on the device.
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 8
16 toFE Deactivation time out- OFF ÷ 99.59 OFF Group ]PrC (parameters relative to compressor protection and
put OUT for probe Pr1 min.sec power on delay)
broken Par. Description Range Def. Note
17 Func Function mode output HEAt - CooL CooL 42 PSC Type of compressor 1-2-3 1
OUT protection:
18 tCC Continuous cycle Time OFF ÷ 99.59 OFF 1= delay at switch on
hrs.min 2= delay after switch off
3= delay between starts
Group ]dEF (parameters relative to defrosting control) 43 PtC Compressor protection OFF ÷ 99.59 OFF
Par. Description Range Def. Note time min.sec
19 dtyP Defrosting Type: EL - in EL 44 LtC Minimum compressor OFF ÷ 99.59 OFF
EL = electrical function time min.sec
in = hot gas/reverse 45 od Delay at power on OFF ÷ 99.59 OFF
cycle min.sec
20 dint Defrosting interval OFF ÷ 99.59 6.00
hrs.min Group ]AL (parameters relative to alarms)
21 dF 1 Time start defrost 1 OFF - 00.00 ÷ OFF Par. Description Range Def. Note
23.59 hrs.min 46 Aty Temperature alarms Ab - dE Ab
22 dF 2 Time start defrost 2 OFF - 00.00 ÷ OFF Type:
23.59 hrs.min Ab = Absolute
23 dF 3 Time start defrost 3 OFF - 00.00 ÷ OFF dE =Relative to Set
23.59 hrs.min 47 HAL High temperature Alarm OFF / - 58 ÷ OFF
24 dF 4 Time start defrost 4 OFF - 00.00 ÷ OFF threshold 302 °C/°F
23.59 hrs.min 48 LAL Low temperature Alarm OFF / - 58 ÷ OFF
25 dF 5 Time start defrost 5 OFF - 00.00 ÷ OFF threshold 302 °C/°F
23.59 hrs.min 49 dAL Temperature Alarms 0 ÷ 30 2.0
26 dF 6 Time start defrost 6 OFF - 00.00 ÷ OFF Differential °C/°F
23.59 hrs.min 50 ALd Temperature Alarms OFF ÷ 99.59 OFF
27 dEFE Max. lenght of defrost 0.01 ÷ 99.59 30.00 delay min.sec
cycle min.sec 51 tAL Alarm memory no - yES no
28 tEdF Defrost stop - 58 ÷ 302 8.0
52 PAL Temperature Alarms OFF ÷ 99.59 2.00
temperature °C/°F
delay at power on hrs.min
29 tSdF Defrost enable - 58 ÷ 302 2.0
53 dALd Temperature Alarms OFF ÷ 99.59 1.00
temperature °C/°F
delay and unlock hrs.min
30 dCt Defrosting intervals rt - ct - cS rt display delay after
Counting mode
defrost
31 tdCO Compressor delay after OFF ÷ 99.59 OFF 54 dALc Temperature alarms OFF ÷ 99.59 OFF
defrost (drainage time) min.sec
delay after continuous hrs.min
32 SdEF Defrost at power on no - yES no cycle
33 dLo Defrost display Lock On - OFF - Lb OFF 55 oAd Alarm delay with open OFF ÷ 99.59 OFF
OFF= display free door min.sec
On= Lock on
temperature Pr1 before
defrost Group ]din (parameters relative to digital input)
Lb= Lock on label “dEF” Par. Description Range Def. Note
(during defrosting) and 56 diF Function and function -10 / -9 / -8 / 0
“PdEF” (during logic of digital input: -7 / -6 / -5 / -4
post-defrosting) 0 = No function / -3 / -2 / -1 /
34 Etdu Differential display 0 ÷ 30 2.0 1= Start defrost 0/1/2/3/4
unlock after defrost °C/°F 2= End defrost /5/6/7/8/
35 COFd Time compressor off OFF ÷ 99.59 OFF 3= Continuous cycle 9 / 10
before defrost min.sec 4= External alarm
5= Door open with fan
block
Group ]FAn (parameters relative to evaporator fan control)
6= Door open with fan
Par. Description Range Def. Note and compressor block
36 FCOF Fan status with On - OFF On 7= Auxiliary output
compressor off command
37 FEdF Fan status during On - OFF OFF 8= Selection of active
defrost Set Point
38 FLt High temperature fan - 58 ÷ 302 2.0 9= External alarm with
off °C/°F deactivation of control
39 Fct Low temperature fan off - 58 ÷ 302 -50.0 outputs
°C/°F 10= Switch on/Switch
40 dF Differential fan control 0 ÷ 30 2.0 off (Stand-by)
°C/°F 57 did Delay in acquiring OFF ÷ 99.59 OFF
41 Fd Fan delay after defrost OFF ÷ 99.59 OFF digital input min.sec
min.sec
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 9
Group ]AuS (parameters relative to auxiliary output) 6 - PROBLEMS, MAINTENANCE AND GUARANTEE
Par. Description Range Def. Note
58 FOA Function mode auxiliary 0 / 1 / 2 / -1 / 0 6.1 - SIGNALLING
output: -2 Error Signalling:
0= No Function Error Reason Action
1= regulation output de- E1 The probe Pr1 may be Check the correct
layed -E1 interrupted or in short circuit, connection of the
2= manual activation by or may measure a value probe with the
key or digital input. outside the range allowed instrument and check
59 tuA Time relative to auxil- OFF ÷ 99.59 OFF E2 The probe Pr2 may be the probe works
iary output min.sec -E2 interrupted or in short circuit, correctly
or may measure a value
Group ]Out (parameters relative to configuration of outputs) outside the range allowed
Par. Description Range Def. Note EEPr Internal memory error Check and if
60 Out1 Configuration of output OFF/Out/dEF/ Out necessary
function OUT1: FAn/AuS/ALt/ re-programme the
OFF= No function AL/ALL/ -ALt/ parameters function.
Out= Temperature -AL/ -ALL In Cell probe error status, the output OUT behaves as set by the
control (compressor) parameters “tonE” and “toFE”.
dEF= defrosting Other Signalling:
FAn= fans Message Reason
AuS= Auxiliary od Delay in switching on in progress
ALt= Silenceable alarm dEF Defrosting in progress with “dLo”=Lb
AL= Alarm not PdEF Post-defrosting in progress with “dLo”=Lb
silenceable CC Continuous cycle in progress
ALL= memorised alarm
HI Maximum temperature alarm in progress
61 Out2 Configuration of output OFF/Out/dEF/ dEF
LO Minimum temperature alarm in progress
function OUT2: FAn/AuS/ALt/
see “Out1” AL/ALL/ -ALt/ AL Digital input alarm in progress
-AL/ -ALL AP Door open
62 Out3 Configuration of output OFF/Out/dEF/ FAn
function OUT3: FAn/AuS/ALt/ 6.2 - CLEANING
see “Out1” AL/ALL/ -ALt/ We recommend cleaning of the instrument with a slightly wet cloth
-AL/ -ALL using water and not abrasive cleaners or solvents which may
63 buF Configuration Buzzer OFF/Out/dEF/ ALt damage the instrument.
function: FAn/AuS/ALt/
see “Out1” AL/ALL/ -ALt/ 6.3 - GUARANTEE AND REPAIRS
-AL/ -ALL The instrument is under warranty against manufacturing flaws or
faulty material, that are found within 12 months from delivery date.
Group ]PAn (parameters relative to configuration of the keyboard) The guarantee is limited to repairs or to the replacement of the
Par. Description Range Def. Note instrument.
The eventual opening of the housing, the violation of the instrument
64 Fbd Function mode key OFF / 1 / 2 / 3 OFF
or the improper use and installation of the product will bring about
DOWN/AUX: /4
the immediate withdrawal of the warranty’s effects.
OFF= No function
In the event of a faulty instrument, either within the period of
1= Auxiliary output
warranty, or further to its expiry, please contact our sales
command
department to obtain authorisation for sending the instrument to
2= Continuous cycle
our company.
command
The faulty product must be shipped to TECNOLOGIC with a
3= Selection of active
detailed description of the faults found, without any fees or charge
Set Point
for Tecnologic, except in the event of alternative agreements.
4= Switch on/Switch off
(Stand-by)
7 - TECHNICAL DATA
65 USrb Function mode key U: OFF / 1 / 2 / 3 OFF
see “Fbd” /4
66 PASS Access Password to OFF ÷ 9999 OFF 7.1 - ELECTRICAL DATA
parameter functions Power supply: 12 VAC/VDC, 24 VAC/VDC, 100..240 VAC +/- 10%
Frequency AC: 50/60 Hz
Power consumption: 3 VA approx.
Group ]CLO (parameters relative to the internal clock)
Input/s: 2 inputs for temperature probes: PTC (KTY 81-121, 990 Ω
Par. Description Range Def. Note @ 25 °C) or NTC (103AT-2, 10KΩ @ 25 °C); 1 digital input for free
67 StCL Current time 0.00 ÷ 23.59 0.00 voltage contacts
hrs.min Output/s: 3 relay outputs: OUT1 SPST-NO (16A-AC1, 6A-AC3 250
68 CLOF Daily calibration of -20 ÷ 20 0 VAC), OUT2 SPDT (8A-AC1, 3A-AC3 250 VAC), and OUT3 SPST-
clock sec NO (5A-AC1, 2A-AC3 250 VAC). 16 A Max. for common (pin. 1)
Electrical life for relay outputs: 100000 operat. (VDE om.)
Installation category: II
Measurement category: I
Protection class against electric shock: Class II for Front panel
Insulation: Reinforced insulation between the low voltage part
(supply H type and relay outputs) and front panel; Reinforced
insulation between the low voltage section (supply type H and relay
outputs) and the extra low voltage section (inputs); Reinforced
between supply and relay outputs; No insulation between supply F
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 10
type and inputs. Display resolution: 1 ° or 0,1°
Overall accuracy: +/- 0,5 % fs
7.2 - MECHANICAL DATA Sampling rate: 130 ms.
Housing: Self-extinguishing plastic, UL 94 V0 Display: 4 Digit Red h 12 mm
Dimensions: 33 x 75 mm, depth 64 mm Endurance time of the internal clock without power supply: 4 hours
Weight: 115 g approx. approx. by internal condenser
Mounting: Flush in panel in 29 x 71 mm hole Compliance: ECC directive EMC 89/336 (EN 61326), ECC directive
Connections: 2,5 mm 2 screw terminals block LV 73/23 and 93/68 (EN 61010-1)
Degree of front panel protection : IP 65 mounted in panel with
gasket 7.6 - INSTRUMENT ORDERING CODE
Pollution situation: 2
Operating temperature: 0 ... 50 °C TLY 29 - a b c dd
Operating humidity: 30 ... 95 RH% without condensation
Storage temperature: -10 ... +60 °C a : POWER SUPPLY
H = 100...240 VAC
7.3 – MECHANICAL DIMENSIONS, PANEL CUT-OUT AND L = 24 VAC/VDC
MOUNTING [mm] F = 12 VAC/VDC
75 5
TLY 29
b : INTERNAL BUZZER
AL B = Yes
- = No
33
28
Aux
Out Def - OK + Fan Aux
c : REAL TIME CLOCK DEFROSTING
64 C = Yes
- = No
min. 15 mm
dd : SPECIAL CODES
71
29
min. 12 mm
RECOMMENDED
PANEL CUTOUT
BRACKETS
TYPE 2
86 34
74
31
43
BRACKET
TYPE 1
PANEL + GASKET
TYPE 1
PANEL + GASKET
MAX 12 mm
TYPE 2
MAX 29 mm
7.4 – FUNCTIONAL FEATURES
Temperature Control: ON/OFF mode
Defrost control: interval cycles or at programmed times (Real Time
Clock Defrosting) by Electric Heating or hot-gas / reverse cycle
Measurement range: PTC: -50...150 °C / -58 ... 302 °F;
NTC: -50...109 °C / -58...228 °F
TECNOLOGIC - TLY29 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06408 - PAG. 11