Simplex Fire Alarm Troubles Report

The document details trouble reports for a fire alarm panel, including issues with the RS232 interface, Loop A short circuit, and an extra modem card. Each section outlines the description of the problem, possible causes, and recommended actions for resolution. It emphasizes checking connections, verifying device functionality, and consulting a technician if issues persist.

Uploaded by

ubaid_45
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
486 views3 pages

Simplex Fire Alarm Troubles Report

The document details trouble reports for a fire alarm panel, including issues with the RS232 interface, Loop A short circuit, and an extra modem card. Each section outlines the description of the problem, possible causes, and recommended actions for resolution. It emphasizes checking connections, verifying device functionality, and consulting a technician if issues persist.

Uploaded by

ubaid_45
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

Fire Alarm Panel Trouble Reports

RS232 Interface Trouble

CARD 8. 2120/RS232 INTERFACE - RS232 Interface PORT B ABNORMAL

Description:
This message indicates a problem with the RS232 communication interface on Card 8, Port
B. The system is reporting an 'Abnormal' condition, which may affect communication with
connected external devices such as a printer, PC, or SMS module.

Possible Causes:
- RS232 cable disconnected or damaged.
- Connected device (printer, PC) is turned off or malfunctioning.
- Incorrect RS232 settings (baud rate, parity, etc.)
- Hardware fault in the RS232 card.

Recommended Actions:
- Check RS232 cable connections.
- Verify that the connected device is powered and functioning.
- Confirm RS232 configuration settings in the panel match the device.
- If issue persists, consult Simplex technician for card replacement or diagnostics.
Loop A Short Circuit Trouble

CARD 2 LOOP A ISOLATOR - SHORT CKT TROUBLE

Description:
This error indicates that a short circuit has been detected on Loop A of Card 2. The isolator
has activated to protect the rest of the loop from the fault.

Possible Causes:
- Conductors touching or shorted within junction boxes or wiring.
- Damaged device or faulty wiring on Loop A.
- Moisture or burn damage on loop cable.

Recommended Actions:
- Use panel navigation to identify the address closest to the fault.
- Inspect field wiring and junction boxes for shorts.
- Disconnect devices one by one to isolate the fault.
- After resolving the issue, perform a system reset.
Extra Modem Card Trouble

EXTRA MODEM CARD TROUBLE - TROUBLE POINT ABNORMAL

Description:
The panel reports an abnormal condition with the Extra Modem Card. This card is typically
used for communication with remote monitoring or for sending alerts.

Possible Causes:
- Modem device is not connected or powered off.
- Cable between the modem and the card is loose or damaged.
- Modem card not configured correctly in the panel software.
- The card may be physically faulty.

Recommended Actions:
- Check physical connections and power to the modem device.
- Verify card settings in system configuration.
- If the modem is not used, disable the configuration or remove the card.
- Reset the system after correction. If issue persists, consult a qualified technician.