s
Datasheet for
SITRANS LUT400 Series Ultrasonic level controller: continuous, non-contact, 60 m (197 ft) range. Monitors level, volume, and volume
flow in liquids, slurries, and solids. With high accuracy volume flow and built in data logging.
Ordering data: 7ML50500AA121DA0
General
Manufacturer Siemens
Supplier Siemens
Product designation Ultrasonic transducer
Brand name SITRANS LUT420
Type designation SITRANS LUT400 Series Ultrasonic level controller: continuous,
non-contact, 60 m (197 ft) range. Monitors level, volume, and volume flow in
liquids, slurries, and solids. With high accuracy volume flow and built in data
logging.
Net weight 3 kg
Slogan High accuracy level monitor/controller/open channel flow
Mode of operation and application
Measuring principle ultrasonic
Operating frequency of the transmitter 10 kHz...52 kHz
Input
Measurand Level
Digital input
Input voltage, DC 0 V...50 V
Input voltage signal 0, DC (minimum) 9.9 V
Input voltage signal 1, DC (minimum) 10 V
Input voltage signal 1, DC (maximum) 50 V
Input current (maximum) 3 mA
Measuring range
Measuring range 0.3 m...60 m
Output
Current output
Signal range 4 ... 20 mA
Load, at active output (maximum) 600 Ohm
Load, at passive output (maximum) 750 Ohm
Digital output
Type relais
...Relay output
Number 3
Type 1 Change-over (NO/NC)
Number of outputs 1 1
Switching capacity voltage, AC (maximum) 1 250 V
Switching capacity current, AC (maximum) 1 1A
Switching capacity voltage, DC (maximum) 1 30 V
Switching capacity current, DC (maximum) 1 3A
Type 2 Normally Open (NO)
Number of outputs 2 2
Switching capacity voltage, AC (maximum) 2 250 V
Switching capacity current, AC (maximum) 2 5A
Switching capacity voltage, DC (maximum) 2 30 V
Switching capacity current, DC (maximum) 2 3A
This is only an extract from the technical data. For more details, see the FI 01 catalog or the Industry Mall.
Creation date: 09/26/2024 Page 1 of 3
s
Datasheet for
SITRANS LUT400 Series Ultrasonic level controller: continuous, non-contact, 60 m (197 ft) range. Monitors level, volume, and volume
flow in liquids, slurries, and solids. With high accuracy volume flow and built in data logging.
Ordering data: 7ML50500AA121DA0
Accuracy
Resolution of the A/D converter (percental) 0.1 %
Operating conditions
Degree of pollution Pollution degree 4
Overvoltage class 2
Environmental conditions
Ambient temperature during operation -20 °C...+50 °C
Degree of protection
IP rating IP65
NEMA Enclosure Type NEMA 4X
Structural Design
Mechanical design
...Material
....Enclosure
Material Polycarbonate (PC)
...Mounting
Location Indoor area, Outdoor area
Electrical connections
Connection technology 4-wire technology
Potential insulation to all outputs
Number of cable entries 3
Design of the cable gland M8 x 1
Display and operating controls
Design of the display LCD
Resolution 240 x 160
Operating controls 4 membrane keys
Power supply
Electrical
Voltage type AC
Nominal frequency 50 Hz, 60 Hz
Communication
Protocol HART
Protocol version Version 7
Certificates and approvals
Reliability (MTBF)
MTBF 146 a
Standard for MTBF SN 29500
Determination procedure calculation with component load
Reference temperature 40 °C
Applicability Measuring device
This is only an extract from the technical data. For more details, see the FI 01 catalog or the Industry Mall.
Creation date: 09/26/2024 Page 2 of 3
s
The information provided in this data sheet contains descriptions or characteristics of performance which in case of actual use do not
always apply as described or which may change as a result of further development of the products. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject
to change without notice.
This is only an extract from the technical data. For more details, see the FI 01 catalog or the Industry Mall.
Creation date: 09/26/2024 Page 3 of 3