Fire Alarm System Limitations Guide
Fire Alarm System Limitations Guide
ACS Series
Installation Manual
Document 15842
7/23/2002
PN 15842:K
Rev:
ECN 02-266
K
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion
smoke detectors, heat detectors, manual pull stations, and alarm only when heat on their sensors increases at
audible warning devices, and a fire alarm control with a predetermined rate or reaches a predetermined level.
remote notification capability—can provide early warning Rate-of-rise heat detectors may be subject to reduced
of a developing fire. Such a system, however, does not sensitivity over time. For this reason, the rate-of-rise fea-
assure protection against property damage or loss of life ture of each detector should be tested at least once per
resulting from a fire. year by a qualified fire protection specialist. Heat detec-
The Manufacturer recommends that smoke and/or heat tors are designed to protect property, not life.
detectors be located throughout a protected premise fol- IMPORTANT! Smoke detectors must be installed in the
lowing the recommendations of the current edition of the same room as the control panel and in rooms used by
National Fire Protection Association Standard 72 (NFPA the system for the connection of alarm transmission wir-
72), manufacturer's recommendations, State and local ing, communications, signaling, and/or power. If detec-
codes, and the recommendations contained in the Guide tors are not so located, a developing fire may damage
for Proper Use of System Smoke Detectors, which is the alarm system, crippling its ability to report a fire.
made available at no charge to all installing dealers. A Audible warning devices such as bells may not alert
study by the Federal Emergency Management Agency people if these devices are located on the other side of
(an agency of the United States government) indicated closed or partly open doors or are located on another
that smoke detectors may not go off in as many as 35% floor of a building. Any warning device may fail to alert
of all fires. While fire alarm systems are designed to pro- people with a disability or those who have recently con-
vide early warning against fire, they do not guarantee sumed drugs, alcohol or medication. Please note that:
warning or protection against fire. A fire alarm system • Strobes can, under certain circumstances, cause sei-
may not provide timely or adequate warning, or simply zures in people with conditions such as epilepsy.
may not function, for a variety of reasons: • Studies have shown that certain people, even when
Smoke detectors may not sense fire where smoke can- they hear a fire alarm signal, do not respond or com-
not reach the detectors such as in chimneys, in or behind prehend the meaning of the signal. It is the property
walls, on roofs, or on the other side of closed doors. owner's responsibility to conduct fire drills and other
Smoke detectors also may not sense a fire on another training exercise to make people aware of fire alarm
level or floor of a building. A second-floor detector, for signals and instruct them on the proper reaction to
example, may not sense a first-floor or basement fire. alarm signals.
Particles of combustion or “smoke” from a develop- • In rare instances, the sounding of a warning device
ing fire may not reach the sensing chambers of smoke can cause temporary or permanent hearing loss.
detectors because: A fire alarm system will not operate without any electri-
• Barriers such as closed or partially closed doors, cal power. If AC power fails, the system will operate from
walls, or chimneys may inhibit particle or smoke flow. standby batteries only for a specified time and only if the
• Smoke particles may become “cold,” stratify, and not batteries have been properly maintained and replaced
reach the ceiling or upper walls where detectors are regularly.
located. Equipment used in the system may not be technically
• Smoke particles may be blown away from detectors by compatible with the control. It is essential to use only
air outlets. equipment listed for service with your control panel.
• Smoke particles may be drawn into air returns before Telephone lines needed to transmit alarm signals from
reaching the detector. a premise to a central monitoring station may be out of
The amount of “smoke” present may be insufficient to service or temporarily disabled. For added protection
alarm smoke detectors. Smoke detectors are designed against telephone line failure, backup radio transmission
to alarm at various levels of smoke density. If such den- systems are recommended.
sity levels are not created by a developing fire at the The most common cause of fire alarm malfunction is
location of detectors, the detectors will not go into alarm. inadequate maintenance. To keep the entire fire alarm
Smoke detectors, even when working properly, have system in excellent working order, ongoing maintenance
sensing limitations. Detectors that have photoelectronic is required per the manufacturer's recommendations,
sensing chambers tend to detect smoldering fires better and UL and NFPA standards. At a minimum, the require-
than flaming fires, which have little visible smoke. Detec- ments of Chapter 7 of NFPA 72 shall be followed. Envi-
tors that have ionizing-type sensing chambers tend to ronments with large amounts of dust, dirt or high air
detect fast-flaming fires better than smoldering fires. velocity require more frequent maintenance. A mainte-
Because fires develop in different ways and are often nance agreement should be arranged through the local
unpredictable in their growth, neither type of detector is manufacturer's representative. Maintenance should be
necessarily best and a given type of detector may not scheduled monthly or as required by National and/or
provide adequate warning of a fire. local fire codes and should be performed by authorized
Smoke detectors cannot be expected to provide ade- professional fire alarm installers only. Adequate written
quate warning of fires caused by arson, children playing records of all inspections should be kept.
with matches (especially in bedrooms), smoking in bed,
and violent explosions (caused by escaping gas,
improper storage of flammable materials, etc.). [Link]
2 PN 15842:K 7/23/2002
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can Like all solid state electronic devices, this system
be connected to the fire alarm control panel. Discon- may operate erratically or can be damaged when sub-
nect all sources of power before servicing. Control unit jected to lightning-induced transients. Although no sys-
and associated equipment may be damaged by remov- tem is completely immune from lightning transients and
ing and/or inserting cards, modules, or interconnecting interferences, proper grounding will reduce susceptibility.
cables while the unit is energized. Do not attempt to Overhead or outside aerial wiring is not recommended,
install, service, or operate this unit until this manual is due to an increased susceptibility to nearby lightning
read and understood. strikes. Consult with the Technical Services Department
CAUTION - System Reacceptance Test after Soft- if any problems are anticipated or encountered.
ware Changes. To ensure proper system operation, this Disconnect AC power and batteries prior to removing
product must be tested in accordance with NFPA 72 or inserting circuit boards. Failure to do so can damage
Chapter 7 after any programming operation or change in circuits.
site-specific software. Reacceptance testing is required Remove all electronic assemblies prior to any drilling,
after any change, addition or deletion of system compo- filing, reaming, or punching of the enclosure. When pos-
nents, or after any modification, repair or adjustment to sible, make all cable entries from the sides or rear.
system hardware or wiring. Before making modifications, verify that they will not
All components, circuits, system operations, or software interfere with battery, transformer, and printed circuit
functions known to be affected by a change must be board location.
100% tested. In addition, to ensure that other operations Do not tighten screw terminals more than 9 in-lbs.
are not inadvertently affected, at least 10% of initiating Over-tightening may damage threads, resulting in
devices that are not directly affected by the change, up reduced terminal contact pressure and difficulty with
to a maximum of 50 devices, must also be tested and screw terminal removal.
proper system operation verified. Though designed to last many years, system compo-
This system meets NFPA requirements for operation at nents can fail at any time. This system contains static-
0-49° C/32-120° F and at a relative humidity of 85% RH - sensitive components. Always ground yourself with a
93% per ULC - (non-condensing) at 30° C/86° F. How- proper wrist strap before handling any circuits so that
ever, the useful life of the system's standby batteries and static charges are removed from the body. Use static-
the electronic components may be adversely affected by suppressive packaging to protect electronic assemblies
extreme temperature ranges and humidity. Therefore, it removed from the unit.
is recommended that this system and all peripherals be Follow the instructions in the installation, operating,
installed in an environment with a nominal room temper- and programming manuals. These instructions must be
ature of 15-27° C/60-80° F. followed to avoid damage to the control panel and asso-
Verify that wire sizes are adequate for all initiating and ciated equipment. FACP operation and reliability depend
indicating device loops. Most devices cannot tolerate upon proper installation by authorized personnel.
more than a 10% I.R. drop from the specified device volt-
age.
FCC Warning
WARNING: This equipment generates, uses, and Canadian Requirements
can radiate radio frequency energy and if not This digital apparatus does not exceed the Class A
installed and used in accordance with the instruc- limits for radiation noise emissions from digital
tion manual, may cause interference to radio com- apparatus set out in the Radio Interference Regu-
munications. It has been tested and found to lations of the Canadian Department of Communi-
comply with the limits for class A computing device cations.
pursuant to Subpart B of Part 15 of FCC Rules, Le present appareil numerique n'emet pas de
which is designed to provide reasonable protection bruits radioelectriques depassant les limites appli-
against such interference when operated in a com- cables aux appareils numeriques de la classe A
mercial environment. Operation of this equipment prescrites dans le Reglement sur le brouillage radi-
in a residential area is likely to cause interference, oelectrique edicte par le ministere des Communi-
in which case the user will be required to correct cations du Canada.
the interference at his own expense.
[Link]
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, ONYX™, and VeriFire™ are trademarks, and FlashScan®
and VIEW® are registered trademarks of NOTIFIER. NION™ and UniNet™ are trademarks of NIS. NIS™ and
Notifier Integrated Systems™ are trademarks and NOTIFIER® is a registered trademark of Fire•Lite Alarms, Inc.
Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a
registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the
Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric
Company.
PN 15842:K 7/23/2002 3
Table of Contents
Table of Contents ........................................................................................... 4
1 Product Overview ......................................................................................8
General .....................................................................................................8
Panel Compatibility: .........................................................................9
ACM-24AT, ACM-48A, AEM-24AT, and AEM-48A ....................9
ACM-16AT, ACM-32A, Expanders, and Variations ....................10
Related Documentation ..........................................................................10
2 Product Overview ....................................................................................12
ACM-24AT and AEM-24AT ..................................................................12
ACM-48A and AEM-48A ......................................................................12
ACM-16AT Series ..................................................................................13
Control Modules ..............................................................................13
Expander Modules ..........................................................................13
ACM-32A Series ....................................................................................14
Control Modules ..............................................................................14
Expander Modules ..........................................................................14
Cabinet & Panel Hardware .....................................................................15
Surface-Mount Backboxes .............................................................15
Flush-mount Backboxes ..................................................................15
Semi-flush-mount Backboxes .........................................................16
Additional Hardware .......................................................................18
3 Design Considerations .............................................................................20
Limits .....................................................................................................20
Wire Runs ...............................................................................................20
EIA-485 Wiring Specifications ..............................................................20
Receive/Transmit and Receive Only Configuration ..............................21
Cabinet Mounting of Annunciators ........................................................22
Annunciator Power Requirements & Electrical Ratings ........................23
4 Installation, Configuration, and Programming ....................................25
Installation Checklist ..............................................................................25
Connections and Switches ......................................................................26
Mount the Cabinet or Backbox ..............................................................28
Mount Annunciators and Expanders ......................................................28
EIA-485 Circuit Connections .................................................................30
Shielding the EIA-485 Circuit ................................................................31
End of Line Resistor for EIA-485 Circuit ..............................................31
Earth Ground ..........................................................................................32
Main Power Supply Connections ...........................................................32
Labeling Annunciators & Expanders .....................................................34
Connecting Annunciator Key Switch and Phone Jack ...........................35
Setting Address and DIP Switches: ACM-24AT, ACM-48A ................36
DIP Switch Summary: ACM-24AT, ACM-48A ............................36
Addressing ACM-24AT and ACM-48A .........................................37
4 PN 15842:K 7/23/2002
Configuring Number of Expander Modules ...................................37
Speaker Control Mode ...................................................................38
Setting Address and DIP Switches: ACM-16AT, ACM-32A ................40
DIP Switch Summary: ACM-16AT, ACM-32A ............................40
Addressing ACM-16AT and ACM-32A .........................................40
Configuring Number of Expander Modules ...................................41
Supervising Devices with ACM-16AT, ACM-32A ...............................41
Programming the Control Panel and Annunciators ................................42
Selecting LED Colors: ACM-24AT and AEM-24AT ....................42
Selecting LED Colors: ACM-48A & AEM-48A ............................42
Testing the Annunciators ........................................................................42
5 LED and Keypad-Switch Functions ......................................................43
ACM-24AT, ACM-48A, and Expanders ...............................................43
Acknowledge/Lamp Test Switch ....................................................43
On-line LED ....................................................................................43
System Trouble LED ......................................................................44
Control Switch ................................................................................44
Point-Active LED ...........................................................................44
Trouble LED ...................................................................................44
ACM-16AT, ACM-32A, and Expanders ................................................45
ACM-16AT .....................................................................................45
AEM-16AT .....................................................................................46
ACM-32A .......................................................................................47
AEM-32A ........................................................................................48
Appendix A: AFP-100 Systems .................................................................. 49
Capabilities ............................................................................................. 49
Connecting the EIA-485 Circuit ............................................................ 49
Providing Power to Annunciators .......................................................... 49
Configuring Annunciators for AFP-100 ................................................ 50
Appendix B: AFP-200 Systems .................................................................. 51
Capabilities ............................................................................................. 51
Connecting the EIA-485 Circuit ............................................................ 51
Providing Power to Annunciators .......................................................... 51
Configuring Annunciators for the AFP-200 ........................................... 52
Appendix C: AFP-300/AFP-400 ................................................................. 53
Capabilities ............................................................................................. 53
Connecting the EIA-485 Circuit ............................................................ 53
Providing Power to Annunciators .......................................................... 53
Configuring Annunciators for the AFP-300/AFP-400 ........................... 54
System and Point Annunciation ............................................................. 55
Appendix D: AFC-600 Systems .................................................................. 56
Capabilities ............................................................................................. 56
Connecting the EIA-485 Circuit ............................................................ 56
Providing Power to Annunciators .......................................................... 56
PN 15842:K 7/23/2002 5
Configuring Annunciators for the AFC-600 .......................................... 57
System and Point Annunciation ............................................................. 57
Appendix E: AM2020/AFP1010 Systems .................................................. 59
Capabilities ............................................................................................. 59
Connecting the EIA-485 Circuit ............................................................ 59
Providing Power to Annunciators .......................................................... 60
Programming the AM2020/AFP1010 for Remote Annunciation .......... 61
Configuring Annunciators for AM2020/AFP1010 ................................ 62
Configurations for Specific Applications ............................................... 63
Common System Annunciation ...................................................... 63
Speaker and Telephone Mode ......................................................... 64
Manual Override ............................................................................. 64
ACS Program Mapping .......................................................................... 66
Appendix F: NFS-640 Systems ................................................................... 67
Capabilities ............................................................................................. 67
Connecting the EIA-485 Circuit ............................................................ 67
Providing Power to Annunciators .......................................................... 68
Configuring Annunciators for the NFS-640 ........................................... 69
System and Point Annunciation ............................................................. 70
Appendix G: System 500 Systems: ACM-16AT and ACM-32A Only .... 71
Capabilities ............................................................................................. 71
Connecting EIA-485 Circuit .................................................................. 71
Providing Power to Annunciators .......................................................... 72
Configuring the ACS for System 500 .................................................... 73
ACS Program Mapping .......................................................................... 74
Appendix H: System 5000 Systems: ACM-16AT and ACM-32A Only .. 76
Capabilities ............................................................................................. 76
Connecting the EIA-485 Circuit ............................................................ 76
Providing Power to Annunciators .......................................................... 77
Installing Modules in the System ........................................................... 78
Configuring the ACS for System 5000 .................................................. 79
ACS Program Mapping .......................................................................... 80
AIM-200 Point Annunciation ................................................................. 81
Appendix I: Combination Fire Alarm/Burglary Systems ....................... 83
Appendix J: NCA Systems ......................................................................... 84
Capabilities ............................................................................................ 84
Connecting the EIA-485 Circuit ............................................................ 84
Providing Power to Annunciators .......................................................... 84
Programming the NCA for Remote Annunciation ................................. 85
Configuring Annunciators for the NCA ................................................. 86
Appendix K: NFS-3030 Systems ............................................................... 87
Capabilities ............................................................................................. 87
Connecting the EIA-485 Circuit ........................................................... 87
6 PN 15842:K 7/23/2002
Providing Power to Annunciators ......................................................... 88
Programming the NFS-3030 for Remote Annunciation ........................ 88
Configuring Annunciators for NFS-3030 .............................................. 89
Configurations for Specific Applications ............................................... 90
Common System Annunciation ...................................................... 90
Speaker and Telephone Mode ......................................................... 91
Manual Override ............................................................................. 91
ACS Program Mapping ......................................................................... 93
Index ............................................................................................................. 95
PN 15842:K 7/23/2002 7
Product Overview
1.1 General
ACS annunciators provide Notifier fire alarm control panels or network displays
with remote serially connected annunciators. Arrays of LEDs indicate, at a
remote location, the status of circuits within the system. Individual fire alarm
control panels offer different methods of identifying annunciator points.
Common system functions such as signal silence, system reset, and local
annunciation controls (local acknowledge and lamp test) are controlled through
switches on the annunciator’s keypad.
Communication between the control panels or network displays and these
annunciators is accomplished over a power-limited, two-wire serial interface
employing an EIA-485 communication standard. Power for these annunciators
is provided via a separate power-limited power loop from the control panel
which is inherently supervised by these annunciators (loss of power results in an
annunciator communication failure at the control panel). These annunciators can
also be powered from a power-limited and regulated remote power supply listed
for fire-protective signalling use.
The National Standard of Canada (CAN/ULC-S527) requires that a dedicated
display use yellow visual indicators to indicate the status of supervisory inputs.
The annunciators listed below are intended to be used for Canadian
Supervisory Service in conjunction with AFP-200, AFP-400, S500, S2500,
and S5000 control units (subject to annunciator-panel compatibility):
• ACM-24AT/ACM-48A and expanders: These modules provide
programmable colors (red/green/yellow).
• ACM-16AT/ACM-32A and expanders: Modules in the -16/-32 “Y”
series have been designed with yellow LEDs; other colors are also
available (see Section 2.3 and Section 2.4).
8 PN 15842:K 7/23/2002
Product Overview
* Section 1.2 “Related Documentation” lists part numbers for manuals of compatible
equipment such as control panels.
PN 15842:K 7/23/2002 9
Product Overview
* Section 1.2 “Related Documentation” lists part numbers for manuals of compatible
equipment such as control panels.
10 PN 15842:K 7/23/2002
Product Overview
PN 15842:K 7/23/2002 11
Product Overview
[Link]
alarm and trouble conditions at each annunciator.
Height = 8.375" (21.27 cm), Width = 4.37" (11.10
cm).
Expander
The AEM-24AT is an expander board for the ACM-24AT with an additional 24
switched and controlled annunciator points. An ACM-24AT can support one,
two, or three expanders at the same address, to a maximum of 96 system points.
Note: The AEM-24AT cannot be used to expand the ACM-48A, ACM-16AT
series, or ACM-32A series.
* Check local regulations when programming colors; some jurisdictions restrict color
choice. For example, in Canada red indicates active alarm inputs; yellow indicates
supervisory, burglary or trouble signals; green indicates the presence of power, or an
activated output.
12 PN 15842:K 7/23/2002
Product Overview
[Link]
Height = 8.375" (21.27 cm), Width = 4.375" (11.11
cm). In Canada this module must be used to
annunciate the fire alarm input points/zones only.
ACM-16ATY*. Same as the ACM-16AT, except that all LEDs are yellow
(yellow On/Alarm and yellow Trouble). In Canada this module must be used to
annunciate supervisory and burglary signals from associated points/zones.
* In Canada the color red must be used to indicate active alarm inputs. Yellow indicates
supervisory, burglary or trouble signals. Green indicates the presence of power, or an
activated output.
PN 15842:K 7/23/2002 13
Product Overview
24AT, ACM-48A, or ACM-32A series. Expander LED colors need not match
the control module LED colors for the expander to operate.
AEM-16ATY*. Same as the AEM-16AT but all LEDs are yellow (yellow On/
Alarm and yellow Trouble).
AEM-16ATG*. Same as the AEM-16AT, but On/Alarm LEDs are green (green
On/Alarm and yellow Trouble).
[Link]
this module must be used to annunciate the fire
alarm input points/zones only.
ACM-32AY*. Same as the ACM-32A but with all LEDs yellow (yellow On/
Alarm and yellow Trouble). In Canada this module must be used to annunciate
supervisory and burglary signals from associated points/zones.
AEM-32Y*. Same as the AEM-32A but with all LEDs yellow (yellow
On/Alarm and yellow Trouble).
AEM-32G*. Same as the AEM-32A, but On/Alarm LEDs are green (green
On/Alarm and yellow Trouble).
* In Canada the color red must be used to indicate active alarm inputs. Yellow indicates
supervisory, burglary or trouble signals. Green indicates the presence of power, or an
activated output.
14 PN 15842:K 7/23/2002
Product Overview
[Link]
ABS-2B, ABS-2. Mounts two annunciators
directly to the ABS-2/2B without a dress plate.
ABS-2 only fits ACM-16AT/ACM-32A series; the
“B” version is black and is slightly deeper to fit either
series. Note: This backbox will not support the ABS-1B, ABS-1
installation of the Annunciator Key Switch or the
Annunciator Phone Jack.
ABS-4D, ABS-4R. Mounts four annunciators, or two annunciators to the right
of an NCA. This surface box can also be mounted semi-flush. Note: This
backbox will not support the installation of the Annunciator Key Switch or the
Annunciator Phone Jack for Firefighters' Telephone.
ABS-1TB, ABS-1T. Mounts one
annunciator. Unlike the ABS-1/1B and
ABS-2/2B, the ABS-1T/1TB has an
increased depth that allows mounting of
the Annunciator Phone Jack for
Firefighters' Telephone and Annunciator
Key Switch. ABS-1T only fits
ACM-16AT/ACM-32A series; the “B”
version is black and is slightly deeper to fit
either series.
[Link]
2.5.2 Flush-mount
Backboxes
These backboxes provide a flush-mount
enclosure for remote mounting of
annunciators. Knockouts are provided for ABF-1B, ABF-1
use with 1/2" conduit. Dimensions are
listed in Table 2-1. Backboxes include a trim plate and an adhesive-backed
annunciator label for the dress plate (15824).
ABF-1B, ABF-1. Mounts one annunciator. ABF-1 only fits ACM-16AT/
ACM-32A series; the “B” version is black and is slightly deeper to fit either
series.
PN 15842:K 7/23/2002 15
Product Overview
2.5.3 Semi-flush-mount
Backboxes
[Link]
These backboxes provide a semi-flush-
mount enclosure for remote mounting of
annunciators. Knockouts are provided for
use with 1/2" conduit. Dimensions are
listed in Table 2-1.
ABF-4B, ABF-4
ABF-1DB, ABF-1D.
Mounts one
annunciator behind an
attractive smoked glass
[Link], [Link]
door with keylock.
ABF-1D only fits
ACM-16AT/ACM-32A
series; the “B” version
is black and is slightly
deeper to fit either
series.
ABF-2DB, ABF-2B.
Mounts two
annunciators or an
NCA; otherwise the
same as ABF-1D/1DB.
ABS-4D, ABS-4R. ABF-1DB, ABF-1D
These backboxes can
be surface-mounted or semi-flush mounted; see description in Section 2.5.1.
16 PN 15842:K 7/23/2002
Product Overview
Part
Number Height Width Depth Color
ABS-1 1.375" (3.49 cm) Gray
8.5" (21.59 cm) 4.5" (11.43 cm)
ABS-1B 2.0" (5.08 cm) Black
ABS-2 1.375" (3.49 cm) Gray
8.5" (21.59 cm) 8.920" (22.66 cm)
ABS-2B 2.0" (5.08 cm) Black
Black
ABS-4D, Box: 11.97" (30.40 cm) Box: 19.87" (50.47 cm) Box: 3.5" (8.89 cm)
or
ABS-4DR Door: 11.97" (30.40 cm) Door: 19.87" (50.47 cm) Door: 1.25" (3.18 cm)
Red
ABS-1T 2.5" (6.35 cm) Gray
9.938" (25.24 cm) 4.625" (11.75 cm)
ABS-1TB 2.5" (6.35 cm) Black
Box: 9.938" (25.24 cm) Box: 4.625" (11.75 cm)
ABF-1, Gray,
Trim plate: Trim plate: 2.5" (6.35 cm)
ABF-1B Black
11" (27.94 cm) 6.25" (15.875 cm)
ABF-2 Box: 9.188" (23.34 cm) 1.375" (3.49 cm) Gray
Box: 9.938" (25.24 cm)
Trim plate:
ABF-2B Trim plate: 11" (27.94 cm) 3.75" (9.525 cm) Black
10.625" (26.99 cm)
ABF-4 Box: 9.938" (25.24 cm) Box: 17.750" (45.09 cm) Gray
Trim plate: Trim plate: 2.5" (6.35 cm)
ABF-4B 11.0" (27.94 cm) 19.375" (49.21 cm) Black
ABF-1D, Box: 9.938" (25.24 cm) Box: 4.625" (11.75 cm) Box: 2.5" (6.35 cm) Gray,
ABF-1DB Door: 11.0" (27.94 cm) Door: 6" (15.24 cm) Door: 0.75" (1.9 cm) Black
Box: 2.5" (6.35 cm)
ABF-2D Gray
Box: 9.938" (25.24 cm) Box: 9.188" (20.80 cm) Door: 0.75" (1.9 cm)
Door: 11.0" (27.94 cm) Door: 10.375" (26.35 cm) Box: 3.750" (9.53 cm)
ABF-2DB Black
Door: 0.75" (1.9 cm)
PN 15842:K 7/23/2002 17
Product Overview
[Link]
ADP-4/4B (Shown with ACM-24AT Modules)
DP-DISP. Dress Panel Display provides for the cabinet mounting of one to four
annunciators, including applications where two annunciators are mounted to the
right of an NCA or control panel keypad. The DP-DISP hinge-mounts to a
CAB-4 series backbox; chassis CHS-4L can be mounted behind it.
Annunciators and expanders mount directly to threaded studs on the dress panel.
dp-disp
18 PN 15842:K 7/23/2002
Product Overview
gap between the ADP-4/4B and the top of the cabinet. It secures to the cabinet
with two screws. The “B” version is black.
vp-2revc
AKS-1B, AKS-1. The Annunciator Key Switch provides access security for
the control switches on the ACM-24AT and ACM-16AT. The key switch kit
includes a key and hardware for mounting to the trim plate of a flush-mount
type annunciator enclosure. Also included is an adhesive-backed Annunciator
Label for use with the key switch/dress plate assembly. The “B” version is black
for use with ACM-24AT/ACM-48A.
Note: The key switch can only be employed with a flush-mount type backbox or
ABS-1T/1TB.
APJ-1B, APJ-1. The Annunciator Phone Jack
provides a single phone jack input for
annunciators used in telephone applications. The
phone jack kit includes hardware for mounting to
the trim plate of one of the flush-mount type
annunciator enclosures. Also included is an
adhesive-backed Annunciator Label for use with
the key switch/dress plate assembly. The “B”
[Link]
version is for use with black equipment.
Note: The phone jack can only be employed with
a flush-mount type backbox or ABS-1T/1TB.
PN 15842:K 7/23/2002 19
Design Considerations
PN 15842:K 7/23/2002 21
Design Considerations
[Link], [Link]
Two-wire
EIA-485 Circuit
“Receive only”
Annunciator set to
address “X” and
installed upstream.
Full Function
“Receive/Transmit”
Annunciator set to
Address “X”
Annunciator Expander
22 PN 15842:K 7/23/2002
Design Considerations
Annunciators in a backbox,
Fire Alarm powered from control panel
Control Panel
Power Loop
EIA-485 Reference
[Link]
EIA-485 Circuit
Annunciators in a cabinet,
powered from remote supply
[Link]
Figure 3-2 Using Multiple Power Supplies With the EIA-485 Circuit
PN 15842:K 7/23/2002 23
Design Considerations
Non-Fire Alarm Status A: On-line LED is flashing; all other LEDs are off
Number of ACM-24AT/ACM-48A modules [_____] X 0.016 = [__________] amps
Number of AEM-24AT/AEM-48A modules [_____] X 0.002 = [__________] amps
Number of ACM-16AT/ACM-32A modules [_____] X 0.040 = [__________] amps
Note: The 0.040 amps can be reduced to 0.030 for ACM-16AT/ACM-32A modules
with Piezo Disable or Flash Inhibit modes selected.
Number of AEM-16AT/AEM-32A modules [_____] X 0.002 = [__________] amps
Non-Fire Alarm Status B: On-line LED is on; other LEDs are also on
Number of ACM-24AT/ACM-48A modules
assumed to have points active simultaneously[_____] X 0.070 = [__________] amps
Number of AEM-24AT/AEM-48A modules
assumed to have points active simultaneously[_____] X 0.056 = [__________] amps
Number of ACM-16AT/ACM-32A or
AEM-16AT/AEM-32A modules
assumed to have points active simultaneously[_____] X 0.018 = [__________] amps
Total Annunciator Standby Current = [__________] amp
24 PN 15842:K 7/23/2002
Installation, Configuration, and Programming
PN 15842:K 7/23/2002 25
Installation, Configuration, and Programming
SW26 ONES
5 6 5 6
4 4
KEYLOCK
3
3
7
SW32
SW28
2
2
8
9 9
0 1 0 1
J3 J3 J4
Expander
Connectors:
J3
J1
[Link], [Link]
PWR SUPPLY
REF TB2 +24V
J1 J2
Power Supply
ACS+
Connectors TB2
ACS-
EGND REF
J1
EIA485 INTFC
TB1
EIA-485
Connectors TB1
RXB TXB
SW29
DISABLE ENABLE
ELR TERMINATE
SW26 ONES
5 6 5 6
4 4
KEYLOCK
3
3
7
SW32
SW28
2
2
8
9 9
0 1 0 1
SW25
Expander J3 J3 J4
SW31
Color Color
SW26
SW30
Connectors:
Selection Selection
J3
Switches: Switches:
J1
SW30 SW26
SW31 SW25
[Link], [Link]
PWR SUPPLY
+24V
J2
TB2
Power Supply
REF
ACS+
Connectors TB2
ACS-
EGND REF
J1 J1
EIA-485
EIA485 INTFC
TB1
Connectors TB1
RXB TXB SW29
SW29
DISABLE ENABLE RXB TXB DISABLE ENABLE
ELR TERMINATE ELR T ERMINAT E
End of Line
ACM-48A AEM-48A
Resistor Switch
SW29
26 PN 15842:K 7/23/2002
Installation, Configuration, and Programming
Addressing
Switches
Configuration
Annunciator DIP Switches
Key Switch
Connector
Expander EIA-485
Connector J1 Connectors TB2
Power Supply
Connectors TB1
Annunciator
Key Switch
Connector
PN 15842:K 7/23/2002 27
Installation, Configuration, and Programming
AnWir_in.tif
metallic ground, such as a grounded cold
water pipe. Pull all annunciator wiring into the
enclosure as illustrated in Figure 4-5. Connect
annunciator wiring to the removable terminal
blocks at this time as specified in Section 4.5
“EIA-485 Circuit Connections”.
Figure 4-5 Pull Wiring
into Enclosure
28 PN 15842:K 7/23/2002
Installation, Configuration, and Programming
J3 J4 J3 J4 J3 J4 J3 J4 J3
[Link]
[Link]
+2 4V
TB2 P WR SUP PLY
+24V
REF
REF
J2 J1 J2
RS48 5+
J1 J2 J1 J2 J1 J2 J1
RS 485 +
RS4 85-
RS485-
REF
REF
EGND
E GND
RS485 INTFC
TB1
RS485 INTFC
TB1
[Link]
J2 J2 J2 J2 J2
P3 P3 P3 P3
PN 15842:K 7/23/2002 29
Installation, Configuration, and Programming
+ IN
+ OUT
1
2
+
+ - In
- OUT
- IN
3
4
-
- - Out
Ref Out
Ref In
5
6 + Out
EGnd 7 +In
TB2 on Last
+ IN
1 + Annunciator
+ OUT +
- OUT
2
3 -
- IN In
Ref Out
4
5
-
- Out
Ref In
EGnd
6
7 -
Out
+ In
+ IN
+ OUT
1
2
+
+
+
TB2 on Middle
- OUT 3 -
- IN 4 - Annunciators
Ref Out 5
Ref In 6
EGnd 7
REF
- In
- Out
[Link]
+ Out
- + + In
EIA-485
TB2 on First
Annunciator
Note: See Section 4.7 “End of Line
Resistor for EIA-485 Circuit” to set on-
board ELR for ACM-24AT/ACM-48A. - +
acs_eia.cdr
30 PN 15842:K 7/23/2002
Installation, Configuration, and Programming
[Link]
Enclosure Annunciator
PN 15842:K 7/23/2002 31
Installation, Configuration, and Programming
32 PN 15842:K 7/23/2002
Installation, Configuration, and Programming
Reference Out
+ Common In -
Section 4.14)
Reference Out
+ N.C. Trouble Inputs
N.C. Trouble Inputs
Reference In
Common In -
Common Out -
TB2 PWR SUPPLY Power In +
+24 VDC In
+ Power Out +
+24 VDC Out
Reference Out
+ Earth Ground
Reference In TB1
N.C. Trouble Inputs
N.C. Trouble Inputs
Common In
-
Common Out -
[Link]
- + Power In +
24 VDC Power Power Out +
Earth Ground
PN 15842:K 7/23/2002 33
Installation, Configuration, and Programming
[Link]
Note: ACM-24AT, ACM-48A, and expanders provide
a plastic protector sheet to insert with the slide-in
labels. Labels should be slightly narrower than the
protector sheet to allow easier insertion.
Figure 4-15
Notifier’s Magni•Fire CD contains LabelEase—a Slide-in Labels
program for customizing professional slide-in labels.
Apply adhesive label onto flush-mount dress plate
If mounting the annunciator onto a
flush-mount dress plate, remove
backing from the adhesive-backed
Annunciator Label and stick the
label to the bottom of the dress plate
[Link], [Link]
34 PN 15842:K 7/23/2002
Installation, Configuration, and Programming
[Link], [Link]
model; see Table 4-1:
ACM-24AT, J2
ACM-48A Resistor (for
Red
ACM-16AT, J4 last jack on
ACM-32A telephone
circuit)
Table 4-1
Black
Wire phone jack into Red
telephone circuit as + Telephone
Black -
shown in Figure 4-17. Circuit
PN 15842:K 7/23/2002 35
Installation, Configuration, and Programming
DIP
Switch Function
SW32-1 Turn “ON” for Program mode. Used to cycle LED colors for
annunciator points on the ACM-24AT and all AEM-24ATs
connected to it. While in this mode, communication with panel is
broken and interrupt routines are disabled.
Turn “OFF” for normal operating mode.
SW32-2, Configures Speaker Control Mode; see Section 4.12.4 “Speaker
SW32-3, Control Mode” for more details.
SW32-4
SW28-1 Turn “ON” for Manual override of control relays: When manual
override button is pressed, CBE or CCBE will be inhibited. (Not
supported by all control panels; see appendix section)
Turn “OFF” for normal operating mode
SW28-2, Specifies the number of expanders installed; see Section 4.12.3
SW28-3 “Configuring Number of Expander Modules”.
SW28-4 Not used; set to OFF
SW28-5 Turn “ON” to set annunciator as Receive Only: Duplicates
another annunciator operating at the same address; see Section
3.4 “Receive/Transmit and Receive Only Configuration”
Turn “OFF” for normal operating mode (receive/transmit)
SW28-6 Turn “ON” to disable piezo.
Turn “OFF” to leave piezo in normal operating mode.
SW28-7 Turn “ON” to enable Switch inhibit: Point-control switches
cannot execute system control functions.
Turn “OFF” for normal operating mode.
SW28-8 Turn “ON” for Flash inhibit: Disables flashing LEDs and prohibits
piezo from sounding.
Turn “OFF” for normal operating mode.
SW30, Sets LED colors on ACM-48A; see Section 4.15.2 “Selecting
SW31 LED Colors: ACM-48A & AEM-48A”
SW25, Sets LED colors on AEM-48A; see Section 4.15.2 “Selecting
SW26 LED Colors: ACM-48A & AEM-48A”
36 PN 15842:K 7/23/2002
Installation, Configuration, and Programming
[Link]
switches SW27 and SW26 on the
back of the annunciator. Turn the J2
SW27 TENS
SW26 ONES
5 6 5 6
4 4
KEYLOCK
2 3
2 3
7 8
7 8
it points to the correct digit. 0 1
9
0 1
9
PN 15842:K 7/23/2002 37
Installation, Configuration, and Programming
38 PN 15842:K 7/23/2002
Installation, Configuration, and Programming
*Note: If adding an expander or expanders, the second unit starts at P25 and goes up, to a maximum of P96.
40 PN 15842:K 7/23/2002
Installation, Configuration, and Programming
TB1 on TB1 on
ACM-16AT, ACM-16AT,
Supervised Device Trouble
ACM-32A ACM-32A
Input
5 VDC @ 0.5 mA
Normally
closed
trouble When not using the trouble
contacts input, jumper terminals [Link]
TB1-6 and TB1-7 together.
If an electrical short circuit
(jumper) does not exist
between terminals TB1-6 and
TB1-7, the control panel will
register a trouble condition.
PN 15842:K 7/23/2002 41
Installation, Configuration, and Programming
ACM-48A AEM-48A
To locate these switches on the back of the annunciator, refer to Figure 4-1 and
Figure 4-2. To set a DIP switch “ON”, push it towards the green circuit board.
42 PN 15842:K 7/23/2002
LED and Keypad-Switch Functions
Annunciator Points
Annunciator Points
Slide-in Labels Annunciator Points
Slide-in Labels
[Link]
Point-Active LED
ACM-48A, AEM-48A
Annunciator Points
PN 15842:K 7/23/2002 43
LED and Keypad-Switch Functions
44 PN 15842:K 7/23/2002
LED and Keypad-Switch Functions
annunciator/expanders.
Note: In AM2020/AFP1010 systems, this LED may also
indicate manual override mode.
Model ACM-
Number ACM-16AT ACM-16ATG ACM-16ATY ACM-16CS4 16ATCS
Color of
12 Red, 8 Red,
Point-active Red Green Yellow
4 Yellow 8 Yellow
LED
Color of
Trouble Yellow Yellow Yellow Yellow Yellow
LED
PN 15842:K 7/23/2002 45
LED and Keypad-Switch Functions
5.2.2 AEM-16AT
[Link]
Control Switch
Functions as a local Lamp Test for the two LEDs
dedicated to this point. Control switches can be used to
execute such system functions as ACKNOWLEDGE,
SIGNAL SILENCE, and SYSTEM RESET. Switches
can also be used to control the states of various output
circuits.
46 PN 15842:K 7/23/2002
LED and Keypad-Switch Functions
5.2.3 ACM-32A
Local Silence/Acknowledge Switch. Performs
multiple functions:
• When pressed, it first lights all the LEDs on the
ACM-32A Series control module (except the
On-line LED) and then each expander. Piezo
sounds for as long as the switch is held down.
• It acknowledges all status changes for both the
annunciator and the expanders. Flashing LEDs will
latch on solid and the piezo will be silenced.
[Link]
with the control panel.
Note: Loss of communication with the control panel is monitored & reported by
the ACM-32A. If connection between ACM-32A & AEM-32A fails, the ACM-32A
will show a trouble condition and the main control panel will show annunciator-
point trouble.
PN 15842:K 7/23/2002 47
LED and Keypad-Switch Functions
5.2.4 AEM-32A
[Link]
Note: Loss of communication with the control panel is monitored & reported by
the ACM-32A. If connection between ACM-32A & AEM-32A fails, the ACM-32A
will show a trouble condition and the main control panel will show annunciator-
point trouble.
48 PN 15842:K 7/23/2002
AFP-100 Systems
[Link]
shown in the accompanying illustration.
See Section 3.3 “EIA-485 Wiring Specifications” for
details and notes about EIA-485 requirements.
TB5 on the
AFP-100
PN 15842:K 7/23/2002 49
AFP-100 Systems
Switch
# ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function
1 Not used: This switch must be set “OFF”
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Set switch “ON” to shift
the control panel functions from the first
eight annunciator positions to expander
positions 57-64. This shift can only be set
on an annunciator set for address “1”.
5 Receive Only: Set this switch “ON” for each annunciator that will provide the same
information as another annunciator in a different location. (When two or more
annunciators hold the same address, all but one must be configured as “Receive Only”
annunciators.)
6 Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event.
(The piezo will also be disabled if Flash Inhibit is “ON”.)
7 Switch Inhibit: Set this switch “ON” to disable the point control switches on the
annunciator and prevent them from executing system control functions. When
inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by
the system.
NOTE: Only the first four switches control the AFP-100. Their functions are:
1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill.
8 Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with
unacknowledged events. Flash Inhibit also disables the piezo from sounding.
Note: For ACM-24AT and ACM-48A with AFP-100, set all pins on SW32 to
“OFF”.
50 PN 15842:K 7/23/2002
AFP-200 Systems
[Link]
Note:
TB5 TB6
• Set SW2 on AFP-200 to “ACS”
position.
TB5 on the
• EIA-485 circuit rated 5.5 VDC AFP-200
max., 60 mA max.
See Section 3.3 “EIA-485 Wiring Specifications” for details and notes about
EIA-485 requirements.
PN 15842:K 7/23/2002 51
AFP-200 Systems
Switch
# ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function
1 Not used: This switch must be set “OFF”
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Set switch “ON” to shift
the control panel functions from the first
eight annunciator positions to expander
positions 57-64. This shift can only be set
on an annunciator set for address “1”.
5 Receive Only: Set this switch “ON” for each annunciator that will provide the same
information as another annunciator in a different location. (When two or more
annunciators hold the same address, all but one must be configured as “Receive Only”
annunciators.)
6 Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event.
(The piezo will also be disabled if Flash Inhibit is “ON”.)
7 Switch Inhibit: Set this switch “ON” to disable the point control switches on the
annunciator and prevent them from executing system control functions. When
inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by
the system.
NOTE: Only the first four switches control the AFP-200. Their functions are:
1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill.
8 Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with
unacknowledged events. Flash Inhibit also disables the piezo from sounding.
Note: For ACM-24AT and ACM-48A with AFP-200, set all pins on SW32 to
“OFF”.
52 PN 15842:K 7/23/2002
AFP-300/AFP-400
APPENDIX N AFP-300/AFP-400
N.1 Capabilities
When installed with an AFP-300/AFP-400, ACS annunciators can be used to
annunciate control panel status, addressable devices, panel modules, and
software zones. The fire alarm control panel uses ACS Annunciator addresses 1
through 19 (1 through 10 when employing a UDACT). Up to 32 devices can be
driven by the EIA-485 communications output, all addresses combined, with up
to 64 points to an address. Two-way communications can occur with only one
annunciator per address; other devices on the same address must be configured
as “Receive Only”.
The panel annunciation points are divided into nine groups of 64
! points. Each group can be assigned to one or more of the 19
annunciator addresses supported by the AFP-300/AFP-400. See the
AFP-300/AFP-400 Programming Manual for assignment details.
[Link]
See Section 3.3 “EIA-485 Wiring Specifications” for details
and notes about EIA-485 requirements. + -
TB4 on
AFP-300/
AFP-400
N.3 Providing Power to Annunciators
AFP-300/AFP-400 panels use Main Power Supply
24 VDC
MPS-400. The annunciator’s power supply is
A B
connected to either of the MPS-400’s two non-
resettable power supplies: TB2 Terminals 1(+) and 2 + - + -
(-) or TB2 Terminals 3 (+) and 4(-), as shown in the
[Link]
PN 15842:K 7/23/2002 53
AFP-300/AFP-400
Switch
# ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function
1 Not used: This switch must be set “OFF”
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Set switch “ON” to shift
the control panel functions from the first
eight annunciator positions to expander
positions 57-64. This shift can only be set
on an annunciator set for address “1”.
5 Receive Only: Set this switch “ON” for each annunciator that will provide the same
information as another annunciator in a different location. (When two or more
annunciators hold the same address, all but one must be configured as “Receive Only”
annunciators.)
6 Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event.
(The piezo will also be disabled if Flash Inhibit is “ON”.)
7 Switch Inhibit: Set this switch “ON” to disable the point control switches on the
annunciator and prevent them from executing system control functions. When
inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by
the system.
NOTE: Only the first four switches control the AFP-300/AFP-400. Their functions are:
1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill.
8 Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with
unacknowledged events. Flash Inhibit also disables the piezo from sounding.
Note: See Section 4.12.1 “DIP Switch Summary: ACM-24AT, ACM-48A” and
Section 4.12.4 “Speaker Control Mode” for details about SW32 on ACM-24AT
and ACM-48A.
54 PN 15842:K 7/23/2002
AFP-300/AFP-400
ACS
Selection
Group Annunciator Display
PN 15842:K 7/23/2002 55
AFC-600 Systems
56 PN 15842:K 7/23/2002
AFC-600 Systems
Switch
# ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function
1 Not used: This switch must be set “OFF”
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Set switch “ON” to shift
the control panel functions from the first
eight annunciator positions to expander
positions 57-64. This shift can only be set
on an annunciator set for address “1”.
5 Receive Only: Set this switch “ON” for each annunciator that will provide the same
information as another annunciator in a different location. (When two or more
annunciators hold the same address, all but one must be configured as “Receive Only”
annunciators.)
6 Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event.
(The piezo will also be disabled if Flash Inhibit is “ON”.)
7 Switch Inhibit: Set this switch “ON” to disable the point control switches on the
annunciator and prevent them from executing system control functions. When
inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by
the system.
NOTE: Only the first four switches control the AFC-600. Their functions are:
1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill.
8 Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with
unacknowledged events. Flash Inhibit also disables the piezo from sounding.
Note: See Section 4.12.1 “DIP Switch Summary: ACM-24AT, ACM-48A” and
Section 4.12.4 “Speaker Control Mode” for details about SW32 on ACM-24AT
and ACM-48A.
PN 15842:K 7/23/2002 57
AFC-600 Systems
58 PN 15842:K 7/23/2002
AM2020/AFP1010 Systems
PN 15842:K 7/23/2002 59
AM2020/AFP1010 Systems
Central Processing Unit (CPU-2020) 73123 and higher or M2.7 and higher
Display Interface Assembly (DIA-1) 73132 and higher or M2.7 and higher
Loop Interface Board (LIB-200) 73117 and higher or M2.7 and higher
Loop Interface Board M2.7 and higher
(LIB-200A/LIB-400)
[Link]
power; use the middle two pins on TB3 of the
TB2 TB3
MPS-24A as shown in the accompanying
illustration. Do not cut jumper JP5! No more
POWER LIMITED
than 3A can be drawn from these power- +24R COMMON +24 COMMON
60 PN 15842:K 7/23/2002
AM2020/AFP1010 Systems
ACM-32A, AEM-32A,
Points 1-32 Points 33-64
PN 15842:K 7/23/2002 61
AM2020/AFP1010 Systems
Switch
# ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function
1 Manual override: Set “ON” when the annunciator is used for manual override of control
relays.
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Always set this switch
“OFF” in AM2020/AFP1010 systems.
5 Receive Only: Set this switch “ON” for each annunciator that will provide the same
information as another annunciator in a different location. (When two or more
annunciators hold the same address, all but one must be configured as “Receive Only”
annunciators.)
6 Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event.
(The piezo will also be disabled if Flash Inhibit is “ON”.)
7 Switch Inhibit: Set this switch “ON” to disable the point control switches on the
annunciator and prevent them from executing system control functions. When
inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by
the system.
8 Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with
unacknowledged events. Flash Inhibit also disables the piezo from sounding.
Note: See Section 4.12.1 “DIP Switch Summary: ACM-24AT, ACM-48A” and
Section 4.12.4 “Speaker Control Mode” for details about SW32 on ACM-24AT
and ACM-48A.
62 PN 15842:K 7/23/2002
AM2020/AFP1010 Systems
Switch
# ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function
1 Manual override: Set switch “OFF” for this application.
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Always set this switch
“OFF” in AM2020/AFP1010 systems.
5 Receive Only: Set switch accordingly
6 Piezo Disable: When the annunciator and AMG-1 are not located adjacent to the
AM2020/AFP1010, as in this application, the piezo must sound and the switch must be
set to “OFF”.
7 Switch Inhibit: Set this switch “ON” to disable the point control switches on the
annunciator and prevent them from executing system control functions. When
inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by
the system.
8 Flash Inhibit: Set switch to the OFF position for this application.
64 PN 15842:K 7/23/2002
AM2020/AFP1010 Systems
Switch
# ACM-24AT Function ACM-16AT Function
1 Manual override: Set “ON” for this application.
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Always set this switch
“OFF” in AM2020/AFP1010 systems.
5 Receive Only: Set this switch “OFF” for this application.
6 Piezo Disable: Set this switch “ON” for this application unless the annunciator and
AMG-1 are not located adjacent to the AM2020/AFP1010. In that case, the piezo must
sound and the switch must be set to “OFF”.
7 Switch Inhibit: Set this switch “OFF” for this application.
8 Flash Inhibit: Set this switch “OFF” for this application.
PN 15842:K 7/23/2002 65
AM2020/AFP1010 Systems
ACM-48A or
ACM-32A Module &
AEM-48A or
AEM-32A Expander
Control Module Indicates on/off status Indicates trouble Turns module on/off
XPC Circuit of module or circuit status of module or
XPR Circuit circuit
XPIQ Speaker and
Telephone/Strobe Circuits
Note: Control Switches marked “not used” will still function as local LAMP TEST
switches for their respective LEDs.
1. In older systems, if the monitor module or XPM-8 circuit is programmed as a
supervisory point (SPSU), illumination of the trouble LED will occur for both
trouble and supervisory conditions. The exact status of the point (trouble versus
supervisory condition) can be read at the AM2020/AFP1010 control panel.
Prior to software release M2.8, supervisory points do not activate the point active
LEDs of an annunciator.
2. With the AM2020/AFP1010, the functions of ACK/STEP, SIGNAL SILENCE,
SYSTEM RESET and LAMP TEST may be assigned (mapped) to multiple
annunciator points.
66 PN 15842:K 7/23/2002
NFS-640 Systems
[Link]
and notes about EIA-485 requirements.
+ -
TB13 on
NFS-640
PN 15842:K 7/23/2002 67
NFS-640 Systems
[Link]
panel as shown in the
TB7
accompanying illustration. No
more than 1.25A can be drawn + - + -
from these power-limited
terminals in standby or alarm. TB7 on NFS-640
The power run to the annunciator does not require a Power Supervision Relay.
Loss of power is inherently supervised through a Communications loss. This
24 VDC output is supervised, power-limited, filtered, and non-resettable.
68 PN 15842:K 7/23/2002
NFS-640 Systems
Switch
# ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function
1 Not used: This switch must be set “OFF”
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Set switch “ON” to shift
the control panel functions from the first
eight annunciator positions to expander
positions 57-64. This shift can only be set
on an annunciator set for address “1”.
5 Receive Only: Set this switch “ON” for each annunciator that will provide the same
information as another annunciator in a different location. (When two or more
annunciators hold the same address, all but one must be configured as “Receive Only”
annunciators.)
6 Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event.
(The piezo will also be disabled if Flash Inhibit is “ON”.)
7 Switch Inhibit: Set this switch “ON” to disable the point control switches on the
annunciator and prevent them from executing system control functions. When
inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by
the system.
NOTE: Only the first four switches control the NFS-640. Their functions are:
1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill.
8 Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with
unacknowledged events. Flash Inhibit also disables the piezo from sounding.
Note: See Section 4.12.1 “DIP Switch Summary: ACM-24AT, ACM-48A” and
Section 4.12.4 “Speaker Control Mode” for details about SW32 on ACM-24AT
and ACM-48A.
PN 15842:K 7/23/2002 69
NFS-640 Systems
70 PN 15842:K 7/23/2002
System 500 Systems: ACM-16AT and ACM-32A Only
PN 15842:K 7/23/2002 71
System 500 Systems: ACM-16AT and ACM-32A Only
WARNING: Cut JP1 to make this circuit non-resettable. Do not use this
! connection to simultaneously power four-wire detectors and annunciators.
See the System 500 Manual for location of JP1.
No more than 200 mA current can be drawn from these power-limited terminals
in standby or alarm.
The power run to the annunciator does not require a Power Supervision Relay
because loss of power is inherently supervised through a Communications loss.
This 24 VDC output is filtered, regulated, power-limited, and non-resettable.
When not using the trouble input on annunciator or expander, jumper terminals
TB1-6 and TB1- 7 together.
Mps24b_Inver.cdr
P3 2 1 4 3 2 1 TB2 4 3 2 CB1
P2
TB3
B ATT -
R55 1 2 3 4 6 7 8 AC HO T EARTH AC NEUT TB1
BATT + CO MM ON +24 VP OW ER CO MM O N + 24 VRES ET
72 PN 15842:K 7/23/2002
System 500 Systems: ACM-16AT and ACM-32A Only
PN 15842:K 7/23/2002 73
System 500 Systems: ACM-16AT and ACM-32A Only
ACM-32A &
AEM-32A
IZ-4, IZ-4A, IZ-8, IZ- Indicates alarm status Indicates Not used
8CS, IZ-8CS4 circuit of circuit3 trouble status of
circuit
IC-4/ICE-4, ICR-4L Indicates Activation Indicates Controls
circuit trouble status of Notification Circuit
circuit
CR-4/CRE-4, CR-4L Indicates Activation Indicates Controls Relays
circuit trouble status of relay
TC-2, TC-4 circuit Indicates Activation Indicates Remote Switch
trouble status of relay Functions
Annunciator Point #1 Indicates Indicates ACKNOWLEDGE
System Alarm System Trouble
Annunciator Point #2 Not used Indicates that signals SIGNAL SILENCE
have been silenced
Annunciator Point #3 Not used Not used SYSTEM RESET
Annunciator Point #4 Not used Indicates Supervisory Not used
condition
Annunciator Point #5 Indicates that Indicates trouble Controls
Notification Circuit #1 status of circuit Notification Circuit #1
has been activated
Annunciator Point #6 Indicates that Indicates Controls
Notification Circuit #2 trouble status of Notification Circuit #2
has been activated circuit
Annunciator Point #7 Indicates that Remote Indicates trouble Controls Remote
Signalling Municipal status of circuit 5 Signalling Municipal
Tie has been Tie
activated
Annunciator Point #8 Indicates that Alarm Indicates AC Fail Controls Alarm Relay
Relay has been
activated
Note: Control Switches marked “not used” will still function as local LAMP
TEST or local ACKNOWLEDGE switches for their respective points.
1. If the Eight-Point Shift (DIP switch # 4) is set “ON,” the eight control
74 PN 15842:K 7/23/2002
System 500 Systems: ACM-16AT and ACM-32A Only
PN 15842:K 7/23/2002 75
System 5000 Systems: ACM-16AT and ACM-32A Only
76 PN 15842:K 7/23/2002
System 5000 Systems: ACM-16AT and ACM-32A Only
Note: “System Trouble” and “Module Failure” will also occur if the normally
closed supervisory path between TB1 Terminals 6 and 7 on the annunciator is
opened (or the jumper has not been installed).
The EIA-485 circuit that drives the ACS must be connected to the control panel
as in the accompanying illustration.
• Power-limited and supervised.
• 6,000 feet maximum distance (@16 AWG) between the control panel
and the furthest annunciator.
• Use twisted pair cable with a characteristic impedance of approximately
120 ohms.
• EIA-485 circuit rated 5.5 VDC max., 60 mA max.
POWER LIMITED
+24R COMMON +24 COMMON
24 VDC
MPS-24B Main Power Supply. Cut JP1 on
MPS-24B to make the circuit non-resettable
+ -
and connect the power run for the ACS to
[Link]
MPS-24B TB2 Terminals 1 (+) and 2 (-) as TB2 TB3
shown in the accompanying illustration
(filtered, power-limited, 200 milliamps POWER LIMITED
max). +24RST COMMON +24 COMMON
PN 15842:K 7/23/2002 77
System 5000 Systems: ACM-16AT and ACM-32A Only
[Link]
second and third expanders of the second
ACM-16AT, or by an AEM-32A.
CPU-5000
Note: Without invoking the Eight-Point-
Shift, the first eight points would be dedicated to control panel functions, not
circuits of the first module. (See “Configuring the ACS for This Control
Panel.”)
78 PN 15842:K 7/23/2002
System 5000 Systems: ACM-16AT and ACM-32A Only
PN 15842:K 7/23/2002 79
System 5000 Systems: ACM-16AT and ACM-32A Only
ACM-32A &
AEM-32A
2. These control switches are active only if all of the following conditions are
set:
• Receive Only (DIP Switch #5) is set to “OFF”.
• Switch Inhibit (DIP Switch #7) is set to “OFF”.
3. These status LEDs are active only when the system is programmed for
“Output Status”.
4. These control switches require that the system be programmed for “Output
Control”.
5. The ACS annunciates the eight AIM-200 software zones only, except as
described below.
6. With Software P/N#S5000R7.0 or higher installed in the System 5000, the
manner in which IZM-8 circuits programmed as supervisory are
annunciated depends upon whether Mode 1 or Mode 2 is selected.
7. Annunciator Point #7 yellow LED indicates Municipal Tie Trouble if no
UDACT is installed. It will annunciate Low Battery/Ground Fault if a
UDACT is installed in the system.
up to 192 intelligent
devices mapped by an
AIM-200. The AIM-200
must be installed
directly to the right of
the control panel.
This option provides
annunciation of up to
256 points for the
System 5000; one
possible configuration is
shown in the
accompanying
illustration.
Note that an annunciator
[Link]
controls standard
System zones; it cannot
be used to execute
manual ON/OFF control
of intelligent AIM-200 8 control 48 points mapped to modules in
points. panel points positions 3, 4, 5, 6, 7 and 8
8 unusable
Annunciator
AIM-200 points
Address 1:
• 8 control panel points (control panel point shift not an option).
• 8 unusable points (redundant AIM-200 points).
PN 15842:K 7/23/2002 81
System 5000 Systems: ACM-16AT and ACM-32A Only
• 48 points mapped to the next six modules installed in the System (which
can also be AIM-200s for annunciation of their eight software zones).
Annunciator Address 2:
• Intelligent Detectors, addressed 1-64, on the AIM-200 installed next to
the control panel.
Annunciator Address 3:
• Addressable Modules, addressed 1-64, on the AIM-200 installed next to
the control panel.
Annunciator Address 4:
• Intelligent Detectors, addressed 65-96, followed by Addressable
Modules, addressed 65-96, on the AIM-200 installed next to the control
panel. The control panel’s programming manual provides programming
instructions for this option. Refer to program choice “AIM(256)”.
Note: AIM-200 detector and module addresses 97, 98, and 99 may be used, but
cannot be point-annunciated.
82 PN 15842:K 7/23/2002
Combination Fire Alarm/Burglary Systems
PN 15842:K 7/23/2002 83
NCA Systems
[Link]
Mode interface) as shown in the accompanying +
illustration. See Section 3.3 “EIA-485 Wiring -
Specifications” for details and notes about EIA-485
requirements. TB3 on NCA
illustration. +
+
The current which can be drawn from these power-
EARTH
84 PN 15842:K 7/23/2002
NCA Systems
*Note: Points 65-96 are not used unless ACS device is programmed for 96 points.
Second
ACM-16AT, First AEM-16AT, Third AEM-16AT,
AEM-16AT,
Points 1-16 Points 17-32 Points 49-64
Points 33-48
ACM-32A, AEM-32A,
Points 1-32 Points 33-64
Note: To program the annunciators into NCA memory, and to map system
points and software zones to annunciator points, refer to the NCA Manual.
Note: When using the NCA to annunciate points on the AM2020/AFP1010 over
the network, enable state reporting in the AM2020/AFP1010 panel for control
module points and “NONA”/”NOA” module points; refer to the NCA Manual
for instructions.
PN 15842:K 7/23/2002 85
NCA Systems
Switch
# ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function
1 Manual override: Set “ON” when the annunciator is used for manual override of control
relays.
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF
5 Receive Only: Set this switch “ON” for each annunciator that will provide the same
information as another annunciator in a different location. (When two or more
annunciators hold the same address, all but one must be configured as “Receive Only”
annunciators.)
6 Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event.
(The piezo will also be disabled if Flash Inhibit is “ON”.)
7 Switch Inhibit: Set this switch “ON” to disable the point control switches on the
annunciator and prevent them from executing system control functions. When
inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by
the system.
NOTE: Only the first four switches control the NCA. Their functions are:
1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill.
8 Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with
unacknowledged events. Flash Inhibit also disables the piezo from sounding.
Note: See Section 4.12.1 “DIP Switch Summary: ACM-24AT, ACM-48A” and
Section 4.12.4 “Speaker Control Mode” for details about SW32 on ACM-24AT
and ACM-48A.
86 PN 15842:K 7/23/2002
NFS-3030 Systems
System Controls
• Acknowledge
• Signal Silence
• System Reset
• Lamp Test
• Drill
• Disable
• Monitor
• Control
• Telephone
XP Series Transponder System
• Power and Audio Supply Supervision
• XP Series Form-C Alarm and Trouble Relays
• Control, Monitor, and Relay Module Circuits
PN 15842:K 7/23/2002 87
NFS-3030 Systems
TB6 on AMPS-24/E
[Link]
ACM-32A, AEM-32A,
Points 1-32 Points 33-64
Note: To program the annunciators into NFS-3030 memory, and to map system
points and logic zones to annunciator points, refer to the NFS-3030 Manual.
88 PN 15842:K 7/23/2002
NFS-3030 Systems
Switch
# ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function
1 Manual override: Set “ON” when the annunciator is used for manual override of control
relays.
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Always set this switch
“OFF” in NFS-3030 systems.
5 Receive Only: Set this switch “ON” for each annunciator that will provide the same
information as another annunciator in a different location. (When two or more
annunciators hold the same address, all but one must be configured as “Receive Only”
annunciators.)
6 Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event.
(The piezo will also be disabled if Flash Inhibit is “ON”.)
7 Switch Inhibit: Set this switch “ON” to disable the point control switches on the
annunciator and prevent them from executing system control functions. When
inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by
the system.
8 Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with
unacknowledged events. Flash Inhibit also disables the piezo from sounding.
Note: See Section 4.12.1 “DIP Switch Summary: ACM-24AT, ACM-48A” and
Section 4.12.4 “Speaker Control Mode” for details about SW32 on ACM-24AT
and ACM-48A.
PN 15842:K 7/23/2002 89
NFS-3030 Systems
Switch
# ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function
1 Manual override: Set switch “OFF” for this application.
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Always set this switch
“OFF” in NFS-3030 systems.
5 Receive Only: Set switch accordingly
6 Piezo Disable: The piezo must sound - this switch must be set to the “OFF position.
7 Switch Inhibit: Set this switch “ON” to disable the point control switches on the
annunciator and prevent them from executing system control functions. When
inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by
the system.
8 Flash Inhibit: Set switch to the OFF position for this application.
90 PN 15842:K 7/23/2002
NFS-3030 Systems
PN 15842:K 7/23/2002 91
NFS-3030 Systems
Switch
# ACM-24AT Function ACM-16AT Function
1 Manual override: Set “ON” for this application.
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Always set this switch
“OFF” in NFS-3030 systems.
5 Receive Only: Set this switch “OFF” for this application.
6 Piezo Disable: Set this switch accordingly.
7 Switch Inhibit: Set this switch “OFF” for this application.
8 Flash Inhibit: Set this switch “OFF” for this application.
92 PN 15842:K 7/23/2002
NFS-3030 Systems
ACM-48A or
ACM-32A Module &
AEM-48A or
AEM-32A Expander
Control Module Indicates on/off status Indicates trouble Turns module on/off
XPC Circuit of module or circuit status of module or
XPR Circuit circuit
XPIQ Speaker and
Telephone/Strobe Circuits
XP5-C Circuit
Monitor Module Indicates alarm status Indicates trouble Not used
XPM Circuit of module or circuit status of module or
circuit
Note: Control Switches marked “not used” will still function as local LAMP TEST
switches for their respective LEDs.
*With the NFS-3030, the functions of ACKNOWLEDGE, SIGNAL SILENCE, SYSTEM
RESET and LAMP TEST may be assigned (mapped) to multiple annunciator points.
PN 15842:K 7/23/2002 93
NFS-3030 Systems
Notes
94 PN 15842:K 7/23/2002
Index
A Point annunciation 57
ABF, ABS see Backboxes Power connections 56
ABM-1 18 Selection groups 57
ACM-16AT 10, 26, 27, 41 Speaker Control Mode 38
Addressing 40 AFP-100 9
Color variations 13 DIP switches 50
DIP switches 40, 41 Power connections 49
Expanders 28, 29 AFP1010, see AM2020/AFP1010
Keypad switches 45 AFP-200 9
LEDs 45 DIP switches 52, 54
Supervising devices 41 Power connections 51
ACM-24AT 9, 12, 26 UDACT 40
Addressing 36, 37 AFP-300/AFP-400 9
DIP switches 36, 38, 42 DIP switches 54
Expanders 28, 29 Power connections 53
Keypad switches Speaker Control Mode 38
LEDs 42 AFP-400 see AFP-300/AFP-400
Speaker Control Mode 38 AIM-200 81
ACM-32A 10, 14, 26, 27, 41 AKS-1(B), see Key switch
Addressing 40 AM2020 software requirements 60
DIP switches 40, 41 AM2020/AFP1010 9, 20
Expanders 28, 29 Applications 63
Keypad switches 47, 48 Cabinet mounting 22
LEDs 47 Common system annunciation 63
Supervising devices 41 DIP switches 62, 63, 64, 65, 91
ACM-48A 9, 12, 26 Manual override 64, 91
Addressing 36, 37 Power connections 60
DIP switches 36, 42 Speaker and Telephone Mode 64
Expanders 28, 29 Speaker Control Mode 38
Keypad switches Annunciator key switch, see Key
LEDs 42 switch
Addressing Annunciator phone jack see Phone
ACM-16AT, ACM-32A 40 jack
ACM-24AT 37 Audio functions with AM2020/
ACM-48A 37 AFP1010 64
Switch locations 26 Audio functions with NFS-3030 91
System 5000 78
Adhesive label 34 B
ADP-4, ADP-4B 18 Backboxes 15, 16, 22, 28
AEM-16AT 10, 13 Battery calculations 23, 24
Keypad switches 46 BMP-1 18
LEDs 46 Burglary systems 83
AEM-24AT 9, 12
DIP switches 42 C
LEDs 42 Cabinet mounting 22, 28
AEM-32A 10, 14 Cabinets see Backboxes, or Doors
LEDs 48 Canada, National Standard of 8
AEM-48A 9, 12 Common system annunciation
DIP switches 42 AM2020/AFP1010 63
LEDs 42 NFS-3030 90
AFC-600 9 Compatible panels 9
DIP switches 57 Configuring the ACS
PN 15842:K 7/23/2002 95
AFC-600 57 32A only) 71
AFP-100 50 System 5000 (ACM-16AT, ACM-
AFP-200 52, 54 32A only) 76
AFP-300/AFP-400 54 Eight-point shift 40
AM2020/AFP1010 62, 63 System 500 73, 74
DIP switch locations 26 System 5000 78, 79, 80
NCA 86 Electrical ratings 23
NFS-3030 89, 90 End of line resistor 31, 35
NFS-640 69 Expanders 28, 29
System 500 73
System 5000 79 F
Connecting Expanders 28, 29 Fire/burglary systems 83
Control switch 80
Functions 44, 45, 46 G
System 5000 80 Ground 32
Control switches
System 500 74 I
Current draw calculations 24 Installation Checklist 25
Custom display labels 34 Installation procedures 25
Installing Modules in System
D 5000 78
DIP switches Installing modules in System
ACM-16AT, ACM-32A 27, 40 5000 78
ACM-24AT 38, 42
ACM-48A, AEM-48A 42 K
AEM-24AT 42 Key switch 34, 35
AFC-600 57 Key switch connector 27
AFP-100 50 keylock connector 35
AFP-200 52, 54 Keypad switches
AFP-300/AFP-400 54 AM2020/AFP1010 66
AM2020/AFP1010 62, 64, 65, 91 NFS-3030 93
Configuring number of expander
modules 37, 41 L
NCA 86 Labeling 34
NFS-3030 89, 91, 92 Lamp test switch 46, 48
NFS-640 69 LEDs 42
System 500 73 AM2020/AFP1010 66
System 5000 79 Color-programmable 42
with AM2020/AFP1010 63 Inactive 46, 48
with NFS-3030 90 NFS-3030 93
DP-DISP 18 Point-active 44, 45, 46, 47, 48
Dress plates 18, 29, 34 System 500 74
System 5000 80
E System Trouble 43, 44, 45, 47
Earth ground 32 Trouble 44, 45, 46
EIA-485 20, 30, 31 Local silence/acknowledge
AFC-600 56 switch 45, 47
AFP-100 49 see also Acknowledge/Lamp Test
AFP-200 51 switch
AFP-300/AFP-400 53
AM2020/AFP1010 59 M
NFS-3030 87 Manual override 43, 45, 63, 64, 90,
NFS-640 67, 84 91
Shielding the circuit 31 Mounting 28
System 500 (ACM-16AT, ACM- multiple power supplies 22, 23
96 PN 15842:K 7/23/2002
multi-speakers 38 Program mapping
AM2020/AFP1010 66
N NFS-3030 93
NCA 38, 84 System 500 74
DIP switches 86 System 5000 80
NFS-3030 9, 10, 38, 87
Applications 90 R
Common system annunciation 90 Receive Only Annunciators 21, 22
DIP switches 89, 90, 92 Receive/transmit annunciators 21
Power connections 88 Related Documentation 11
Speaker and Telephone Mode 91 Remote annunciation, AM2020/
NFS-640 9, 67 AFP1010 61
DIP switches 69 Remote annunciation, NCA 85
Selection groups 70 Remote annunciation, NFS-3030 88
Speaker Control Mode 38
S
O Selection groups
On-line LED 43, 45, 47 AFC-600 57
Overview AFP-300/AFP-400 55
ACM-16AT 10 NFS-640 70
ACM-24AT, AEM-24AT 9, 12 Semi-flush-mount Backboxes 16
ACM-32A 10, 14 SIB, AM2020/AFP1010 59
ACM-48A, AEM-48A 9, 12 Slide-in labels 34
AEM-16AT 10, 13 Slide-in labels, see also center pages
AEM-32A 10, 14 Software requirements, AM2020 60
Backboxes 15, 16 Speaker and telephone mode
Color variations 13 AM2020/AFP1010 63
Dress panels 18 NFS-3030 90
installation procedures 25 Speaker Control Mode 38
Key switch Specifications 20
Phone jack Communication 20
Electrical Ratings 23
P Power 23
Phone jack 34, 35 Supervising devices with ACM-
Point annunciation 57 16AT, ACM-32A 41
AIM-200 81 Surface-Mount Backboxes 15
AM2020/AFP1010 61 Switch locations 26
NCA 85 System 500
NFS-3030 88 ACS program mapping 74
NFS-640 70 Control switches 74
System 5000 81 DIP switches 73
Point mapping 39 LEDs 74
AFP-300/AFP-400 55 Power connections 72
Point-active LEDs see LEDs System 5000 80
Power connections 32, 33 ACS program mapping 80
AFC-600 56 Control switches 80
AFP-100 49 DIP switches 79
AFP-200 51 EIA-485 76
AFP-300/AFP-400 53 LEDs 80
AM2020/AFP1010 60 Power connections 77
NFS-3030 88 System annunciation 57
NFS-640 68, 84 System Trouble LEDs see LEDs
System 500 72
System 5000 77 T
Power Requirements 23 Testing 42
PN 15842:K 7/23/2002 97
Trouble LEDs see LEDs
U
UDACT
ACM-16AT, ACM-32A 40
ACM-24AT, ACM-48A 37
AFC-600 56
AFP-200 40
AFP-300/AFP-400 53
NFS-640 67
System 500 75
System 5000 81
V
VeriFire™ 9, 10, 56
Voice applications, AM2020/
AFP1010 63
Voice applications, NFS-3030 90
VP-2, VP-2B 18
W
Wiring 28, 30, 33, 35
X
XPIQ 38
Z
Zone mapping, AFP-300/AFP-
400 55
98 PN 15842:K 7/23/2002
Limited Warranty
[Link]